Static transfer systems (STS) - Part 1: General and safety requirements

applies to free standing a.c. static transfer systems (STS) intended to ensure the continuity of power to load by automatically or manually controlled transfer, with or without interruption, from two or several a.c. independent sources. includes requirements for the switching elements, their control and protective elements, where applicable. This part of IEC 62310 also includes information for the overall integration of the STS and its accessories into the a.c. power distribution system

Systèmes de transfert statique (STS) - Partie 1: Exigences générales et règles de sécurité

aux systèmes de transfert statique (STS) à courant alternatif autonomes destinés à assurer la continuité de l'alimentation d'une charge par un transfert manuel ou automatique, avec ou sans coupure, à partir d'au moins deux sources indépendantes à courant alternatif.contient des exigences concernant les éléments de commutation et leur commande ainsi que les éléments de protection, le cas échéant. La présente partie de la CEI 62310 contient également des informations relatives à l'intégration globale d'un STS et de ses accessoires dans un réseau de distribution de courant alternatif

General Information

Status
Published
Publication Date
07-Mar-2005
Current Stage
PPUB - Publication issued
Start Date
08-Mar-2005
Completion Date
30-Jun-2005
Ref Project
Standard
IEC 62310-1:2005 - Static transfer systems (STS) - Part 1: General and safety requirements
English and French language
119 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NORME CEI
INTERNATIONALE IEC
62310-1
INTERNATIONAL
Première édition
STANDARD
First edition
2005-03
Systèmes de transfert statique (STS) –
Partie 1:
Exigences générales et règles de sécurité

Static transfer systems (STS) –
Part 1:
General and safety requirements
Numéro de référence
Reference number
CEI/IEC 62310-1:2005
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE IEC
62310-1
INTERNATIONAL
Première édition
STANDARD
First edition
2005-03
Systèmes de transfert statique (STS) –
Partie 1:
Exigences générales et règles de sécurité

Static transfer systems (STS) –
Part 1:
General and safety requirements
 IEC 2005 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale PRICE CODE XA
International Electrotechnical Commission
Международная Электротехническая Комиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 62310-1  CEI:2005
SOMMAIRE
AVANT-PROPOS.6

1 Domaine d’application .10
2 Références normatives .12
3 Termes et définitions .14
3.1 Définitions générales .14
3.2 Valeurs spécifiées .24
3.3 Valeurs d'entrée .30
4 Exigences de sécurité.32
4.1 Marquage et instructions.32
4.2 Exigences fondamentales de conception .44
4.3 Exigences physiques .98
4.4 Exigences thermiques, protection contre le feu et risques de feu .104
5 Exigences électriques et simulation de conditions anormales.108
5.1 Généralités.108
5.2 Rigidité diélectrique .110
5.3 Fonctionnement anormal et conditions de défaut .110

Annexe A (normative) Méthode de calcul de la section des conducteurs de protection
en fonction des contraintes thermiques dues aux courants de courte durée (des
informations plus détaillées sont données dans la CEI 60364-5-54) .114
Annexe B (normative) Sections minimales et maximales des conducteurs en cuivre
adaptés pour le raccordement .116

Bibliographie .118

Figure 1 – Doigt d’épreuve (voir CEI 60529) .46
Figure 2 – Broche d’essai .48
Figure 3 – Sonde d’essai .48
Figure 4 – Détermination de l’isolation à l’intérieur d’un circuit .68
Figure 5 – Détermination de l’isolation entre parties actives et surfaces accessibles .70
Figure 6– Détermination de l’isolation a) entre circuits et environnement, et b) entre
circuits .72
Figure 7– Détermination de l’isolation fonctionnelle .74
Figure 8 Détermination de l’isolation principale.76
Figure 9 – Détermination de l’isolation double ou renforcée .78

Tableau 1 – Distance à travers l’isolation du câblage interne .50
Tableau 2 – Section des conducteurs de protection (PE et PEN).60
Tableau 3 –Définitions des degrés de pollution.80
Tableau 4 – Distances d’isolement entre les circuits primaires et leur environnement
(tension de tenue aux chocs relative à la catégorie de surtension III) .84

62310-1  IEC:2005 – 3 –
CONTENTS
FOREWORD.7

1 Scope .11
2 Normative references .13
3 Terms and definitions .15
3.1 General definitions .15
3.2 Specified values .25
3.3 Input values.31
4 Safety requirements .33
4.1 Marking and instructions .33
4.2 Fundamental design requirements .45
4.3 Physical requirements .99
4.4 Thermal requirements, fire protection and fire risks .105
5 Electrical requirements and simulated abnormal conditions .109
5.1 General .109
5.2 Electric strength .111
5.3 Abnormal operating and fault conditions.111

Annex A (normative) Method of calculating the cross-sectional area of protective
conductors with regard to thermal stresses due to currents of short duration (more
detailed information is to be found in IEC 60364-5-54).115
Annex B (normative) Minimum and maximum cross-sections of copper conductors
suitable for connection.117

Bibliography .119

Figure 1 – Test finger (see IEC 60529).47
Figure 2 – Test pin.49
Figure 3 – Test probe.49
Figure 4 – Determination of insulation within a circuit .69
Figure 5 – Determination of insulation between live parts and accessible – surfaces .71
Figure 6 – Determination of insulation a) between circuits and the environment, and b)
between circuits .73
Figure 7 – Determination of functional insulation .75
Figure 8 – Determination of basic insulation .77
Figure 9 – Determination of double or reinforced insulation.79

Table 1 – Distance through insulation of internal wiring .51
Table 2 – Cross-sectional area of protective conductors (PE, PEN).61
Table 3 – Definitions of pollution degrees .81
Table 4 – Clearances between primary circuits and their environment (impulse
withstand voltages according to overvoltage category III).85

– 4 – 62310-1  CEI:2005
b)
Tableau 5 – Distances d’isolement entre les circuits secondaires et leur environnement
(Tensions de tenue aux chocs relatives à la catégorie de surtension II).86
Tableau 6 – Distances d’isolement internes à un circuit (tension de tenue aux chocs
relative à la catégorie de surtension I).88
Tableau 7 – Lignes de fuite minimales.92
Tableau 8 – Limites des sources de puissance limitées par construction .94
Tableau 9 – Limites des sources de puissance limitées par construction (dispositif de
protection contre les surintensités requis) .96
Tableau 10 –Limites d’échauffements: Partie 1.106
Tableau 11 – Limites d’échauffements: Partie 2.108
Tableau A.1 – Valeurs de k pour les conducteurs de protection isolés non incorporés
dans des câbles, ou pour les conducteurs de protection nus en contact avec le
revêtement des câbles .114
Tableau B.1 – Sections minimales et maximales des conducteurs en cuivre adaptés
pour le raccordement .116

62310-1  IEC:2005 – 5 –
b)
Table 5 – Clearances between secondary circuits and their environment (impulse
withstand voltages according to overvoltage category II).87
Table 6 –Clearances within a circuit (impulse withstand voltage according to
overvoltage category I) .89
Table 7 – Minimum creepage distances.93
Table 8 – Limits for inherently limited power sources .95
Table 9 – Limits for power sources not inherently limited (overcurrent protective device
required) .97
Table 10 – Temperature rise limits: Part 1 .107
Table 11 – Temperature rise limits: Part 2 .109
Table A.1 – Values of k for insulated protective conductors not incorporated in cables,
or bare protective conductors in contact with cable covering .115
Table B.1 − Minimum and maximum cross-sections of copper conductors suitable for
connection.117

– 6 – 62310-1  CEI:2005
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
SYSTÈMES DE TRANSFERT STATIQUE (STS) –

Partie 1: Exigences générales et règles de sécurité

AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 62310-1 a été établie par le sous-comité 22H: Alimentations
sans interruption (ASI), du comité d'études 22 de la CEI: Systèmes et équipements
électroniques de puissance.
Le texte anglais de cette norme est basé sur les documents 22H/66/FDIS et 22H/67/RVD. Le
rapport de vote 22H/67/RVD donne toute l’information sur le vote ayant abouti à l’approbation
de cette norme.
La version française de cette norme n’a pas été soumise au vote.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.

62310-1  IEC:2005 – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
STATIC TRANSFER SYSTEMS (STS) –

Part 1: General and safety requirements

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62310-1 has been prepared by subcommittee 22H: Uninterruptible
Power Systems (UPS), of IEC technical committee 22: Power electronic systems and
equipment.
The text of this standard is based on the following documents:
FDIS Report on voting
22H/66/FDIS 22H/67/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
The French version of this standard has not been voted upon.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

– 8 – 62310-1  CEI:2005
La CEI 62310 comprend les parties suivantes, présentées sous le titre général Systèmes de transfert
statique (STS):
Partie 1: Exigences générales et règles de sécurité
Partie 2: Electromagnetic Compatibility (EMC) requirements

Partie 3: Method of specifying the performance and test requirements
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous "http://webstore.iec.ch" dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.
___________
A publier.
A l’étude.
62310-1  IEC:2005 – 9 –
IEC 62310 consists of the following parts, under the general title Static transfer systems
(STS):
Part 1: General and safety requirements
Part 2: Electromagnetic Compatibility (EMC) requirements

Part 3: Method of specifying the performance and test requirements
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
___________
To be published.
Under consideration.
– 10 – 62310-1  CEI:2005
SYSTÈMES DE TRANSFERT STATIQUE (STS) –

Partie 1: Exigences générales et règles de sécurité

1 Domaine d’application
La CEI 62310 est constituée de trois parties et s'applique aux systèmes de transfert statique
(STS) à courant alternatif autonomes destinés à assurer la continuité de l'alimentation d'une
charge par un transfert manuel ou automatique, avec ou sans coupure, à partir d'au moins
deux sources indépendantes à courant alternatif.
La présente partie de la CEI 62310 concerne les exigences générales et les règles de
sécurité. Se reporter à la future CEI 62310-2 pour la compatibilité électromagnétique (CEM)
et à la future CEI 62310-3 pour la méthode de spécification des exigences de performance et
d'essais.
La présente partie de la CEI 62310 est destinée à réduire le risque de feu, de choc électrique
ou de blessure de personnes dû à des équipements installés, sous réserve que l'installation,
l'exploitation et la maintenance de ces équipements suivent les exigences du fabricant.
La présente partie de la CEI 62310 contient des exigences concernant les éléments de
commutation et leur commande ainsi que les éléments de protection, le cas échéant. La
présente partie de la CEI 62310 contient également des informations relatives à l'intégration
globale d'un STS et de ses accessoires dans un réseau de distribution de courant alternatif.
Il convient que les composants ou les dispositifs nécessaires à l'exploitation/à la commande/à
la protection/à l'isolation (par exemple disjoncteurs, fusibles, transformateurs, etc.) d'un STS
soient conformes aux exigences des normes CEI qui leur sont applicables et ne sont pas
couverts par la présente norme.
Cette norme s'applique aux réseaux jusqu'à 1 000 V en courant alternatif qui sont destinés à
être utilisés dans des applications monophasées, biphasées ou triphasées.
Cette norme ne s’applique pas:
− aux dispositifs pour la commutation de sources à courant continu;
− aux systèmes de transfert statique utilisant uniquement des dispositifs de commutation
électromécaniques destinés à être utilisés dans les systèmes d'alimentation de secours
avec coupure de l'alimentation de la charge pendant le transfert. Ces équipements sont
couverts par la CEI 60947-6-1;
− aux dispositifs de commutation automatiques intégrés aux ASI couvertes par la série
CEI 62040.
NOTE Pour les STS destinés à être utilisés dans des véhicules, à bord de navires ou d'aéronefs, dans des pays
tropicaux, pour les systèmes d'alimentation de secours (comme ceux utilisés dans les établissements de santé,
pour la lutte contre les incendies, les secours d'urgence, etc.), ou à des altitudes supérieures à 1 000 m, des
exigences différentes peuvent être nécessaires.

62310-1  IEC:2005 – 11 –
STATIC TRANSFER SYSTEMS (STS) –

Part 1: General and safety requirements

1 Scope
IEC 62310 consists of three parts and applies to free standing a.c. static transfer systems
(STS) intended to ensure the continuity of power to load by automatically or manually
controlled transfer, with or without interruption, from two or several a.c. independent sources.
This part of IEC 62310 concerns general and safety requirements. See future IEC 62310-2 for
electromagnetic compatibility (EMC) and futureIEC 62310-3 for the method of specifying
performance and test requirements.
This part of IEC 62310 is intended to reduce the risk of fire, electric shock, or injury to
persons from installed equipment subject to installing, operating, and maintaining the
equipment in the manner prescribed by the manufacturer.
This part of IEC 62310 includes requirements for the switching elements, their control and
protective elements, where applicable. This part of IEC 62310 also includes information for
the overall integration of the STS and its accessories into the a.c. power distribution system.
Components or devices necessary for the operation/control/protection/isolation (e.g. circuit-
breakers, fuses, transformers, etc.) of a STS should comply with the requirements of the
relevant IEC standards and are not covered by this part of IEC 62310.
This standard applies to systems up to 1 000 V (a.c. value) which are intended to be used in
single phase or phase-phase or three phase applications.
This standard does not apply to:
− devices for d.c. source switching;
− static transfer system using only electromechanical switching devices intended to be used
in emergency power systems with interruption of the supply to the load during transfer.
This equipment is covered by IEC 60947-6-1;
− the automatic switching devices integrated into UPS covered by IEC 62040 series.
NOTE For STS intended to be used in vehicles, onboard ships or aircraft, in tropical countries, for emergency
power systems (such as those used for health care facilities, fire fighting, emergency rescue, etc.), or on elevations
greater than 1 000 m, different requirements may be necessary.

– 12 – 62310-1  CEI:2005
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références
non datées, la dernière édition du document de référence s'applique (y compris les éventuels
amendements).
CEI 60060-1:1989, Techniques des essais à haute tension – Première partie: Définitions et
prescriptions générales relatives aux essais
CEI 60073, Principes fondamentaux et de sécurité pour l’interface homme-machine, le
marquage et l’identification − Principes de codage pour les indicateurs et les organes de
commande
CEI 60083, Prises de courant pour usages domestiques et analogues normalisées par les
pays membres de la CEI
CEI 60085, Isolation électrique − Classification thermique
CEI 60112, Méthode de détermination des indices de résistance et de tenue au cheminement
des matériaux isolants solides
CEI 60364-5-54, Installations électriques des bâtiments – Partie 5-54: Choix et mise en
œuvre des matériels électriques –Mises à la terre, conducteurs de protection et conducteurs
d'équipotentialité de protection
CEI 60364-7-707, Installations électriques des bâtiments – Septième partie: Règles pour les
installations et emplacements spéciaux – Section 707: Mise à la terre des installations de
matériel de traitement de l’information
CEI 60417-DB:2002 , Symboles graphiques utilisables sur le matériel
CEI 60529, Degrés de protection procurés par les enveloppes (code IP)
CEI 60664-1:1992, Coordination de l’isolement des matériels dans les systèmes (réseaux) à
basse tension – Partie 1: Principes, prescriptions et essais
Amendement 1 (2000)
Amendement 2 (2002)
CEI 60664-3:2003: Coordination de l’isolement des matériels dans les systèmes (réseaux) à
basse tension – Partie 3: Utilisation de revêtement, d'empotage ou de moulage pour la
protection contre la pollution
CEI 60730-1 :1999, Dispositifs de commande électrique automatiques à usage domestique et
analogue – Partie 1: Règles générales
Amendement 1 (2003)
CEI 60755, Règles générales pour les dispositifs de protection à courant différentiel résiduel

___________
« DB » se réfère à la base données « on-line » de la CEI.
Il existe une édition consolidée 1.2 comprenant la CEI 60664-1:1992 et ses Amendements 1 (2000) et 2 (2002).
Il existe une édition consolidée 3.1 comprenant la CEI 60730-1:1999 et son Amendement 1 (2003).

62310-1  IEC:2005 – 13 –
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60060-1:1989, High-voltage test techniques – Part 1: General definitions and test
requirements
IEC 60073, Basic and safety principles for man-machine interface, marking and identification
– Coding principles for indicators and actuators
IEC 60083, Plugs and socket-outlets for domestic and similar general use, standardised in
member countries of IEC
IEC 60085, Electrical insulation – Thermal classification
IEC 60112, Method for the determination of the proof and the comparative tracking indices of
solid insulating materials
IEC 60364-5-54, Electrical installations of buildings – Part 5-54: Selection and erection of
electrical equipment – Earthing arrangements, protective conductors and protective bonding
conductors
IEC 60364-7-707, Electrical installations of building – Part 7: Requirements for special
installations or locations – Section 707: Earthing requirements for the installation of data
processing equipment
IEC 60417-DB:2002 , Graphical symbols for use on equipment
IEC 60529, Degrees of protection provided by enclosures (IP Code)
IEC 60664-1:1992, Insulation co-ordination for equipment within low-voltage systems – Part 1:
Principles, requirements and tests
Amendment 1 (2000)
Amendment 2 (2002)
IEC 60664-3:2003, Insulation coordination for equipment within low-voltage systems – Part 3:
Use of coating, potting or moulding for protection against pollution
IEC 60730-1:1999, Automatic electrical controls for household and similar use – Part 1:
General requirements
Amendment 1 (2003)
IEC 60755, General requirements for residual current operated protective devices

___________
“DB” refers to the IEC on-line database.
A consolidated edition 1.2 exists including IEC 60664-1:1992 and its Amendments 1 (2000) and 2 (2002).
A consolidated edition 3.1 exists including IEC 60730-1:1999 and its Amendment 1 (2003).

– 14 – 62310-1  CEI:2005
CEI 60950-1:2001, Matériels de traitement de l’information – Sécurité – Partie 1:
Prescriptions générales
CEI 61008-1, Interrupteurs automatiques à courant différentiel résiduel pour usages
domestiques et analogues sans dispositif de protection contre les surintensités incorporé (ID)
– Partie 1: Règles générales
CEI 61009-1, Interrupteurs automatiques à courant différentiel résiduel avec protection contre
les surintensités incorporée pour installations domestiques et analogues (DD) –
Partie 1: Règles générales
CEI 62103:2003, Equipements électroniques utilisés dans les installations de puissance
CEI 62310-2,___ Static transfer systems (STS) – Part 2: Electromagnetic Compatibility
(EMC) requirements
ISO 3864-1:2002, Symboles graphiques – Couleurs de sécurité et signaux de sécurité –
Partie 1: Principes de conception pour les signaux de sécurité sur les lieux de travail et dans
les lieux publics
ISO 7000:2004, Symboles graphiques utilisables sur le matériel – Index et tableau synoptique
3 Termes et définitions
Pour les besoins du présent document, les termes et définitions suivants s’appliquent.
3.1 Définitions générales
3.1.1
commutateur de transfert
équipement de commutation constitué d’un ou de plusieurs interrupteurs utilisés pour
transférer la puissance d’une source à une autre
3.1.2
système de transfert statique
STS
système qui utilise des dispositifs statiques pour transférer une charge, entre une source
préférentielle et une source alternative
NOTE 1 Le transfert peut être automatique et/ou manuel.
NOTE 2 Le transfert peut s'effectuer avec ou sans coupure.
3.1.3
interrupteur électronique (de puissance)
ensemble fonctionnel comprenant au moins une valve électronique commandable, assurant la
commande (ouverture et fermeture) électronique d'un circuit de puissance
[VEI 551-13-01]
3.1.4
commutateur électronique alimenté par le réseau
interrupteur électronique dans lequel la tension de commutation est fournie par le réseau
___________
A publier.
62310-1  IEC:2005 – 15 –
IEC 60950-1:2001, Information technology equipment – Safety – Part 1: General requirements
IEC 61008-1, Residual current operated circuit-breakers without integral overcurrent
protection for household and similar uses (RCCBs) – Part 1: General rules
IEC 61009-1, Residual current operated circuit-breakers without integral overcurrent
protection for household and similar uses (RCBOs) – Part 1: General rules
IEC 62103:2003, Electronic equipment for use in power installations
IEC 62310-2, ___ Static transfer systems (STS) – Part 2: Electromagnetic Compatibility
(EMC) requirements
ISO 3864-1:2002, Graphical symbols – Safety colours and safety signs – Part 1: Design
principles for safety signs in workplaces and public areas
ISO 7000:2004, Graphical symbols for use on equipment – Index and synopsis
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 General definitions
3.1.1
transfer switch
switching equipment consisting of one or more switches used to transfer power from one
source to another
3.1.2
static transfer system
STS
system that transfers a load, by static means, between a preferred source and an alternate
source
NOTE 1 The transfer may be automatic and/or manual.
NOTE 2 The transfer may be with or without interruption.
3.1.3
electronic (power) switch
operative unit for electronic power switching comprising at least one controllable valve device
[IEV 551-13-01]
3.1.4
line commutated electronic switch
electronic switch where the commutating voltage is supplied by the line
___________
To be published.
– 16 – 62310-1  CEI:2005
3.1.5
dérivation de maintenance
circuit de dérivation conçu pour permettre l'isolation d'une ou plusieurs sections appropriées
d'un STS pour assurer la sécurité pendant la maintenance et/ou pour maintenir la continuité
de l'alimentation d'une charge
3.1.6
système redondant
ajout d'ensembles fonctionnels ou groupes d'ensembles fonctionnels dans un système pour
accroître la continuité de l'alimentation d'une charge
3.1.7
puissance d'entrée de STS
puissance fournie au STS et à la dérivation, le cas échéant, qui peut être soit une source
préférentielle soit une source alternative
3.1.8
source alternative
source utilisée comme alimentation alternative de la charge lorsque la source préférentielle
subit une défaillance ou sort des tolérances admises ou est coupée pour la maintenance
3.1.9
source préférentielle
source utilisée comme alimentation normale de la charge, généralement réglée par
l'opérateur
3.1.10
charge linéaire
charge dont le courant issu de l’alimentation est défini par la relation:
I = U/Z

I est le courant de charge;
U est la tension d’alimentation;
Z est l’impédance constante de charge.
3.1.11
charge non linéaire
charge où le paramètre Z (impédance de charge) n’est plus une constante mais une variable
dépendant d’autres paramètres, comme la tension ou le temps
3.1.12
défaillance réseau
toute variation de la source d'alimentation estimée pouvoir provoquer des performances
inacceptables de l’équipement à alimenter
3.1.13
mode de fonctionnement normal du STS
situation dans laquelle la charge est alimentée par la source préférentielle ou la source
alternative via les interrupteurs électroniques (de puissance)
3.1.14
mode dérivation
situation dans laquelle la charge est alimentée via l'interrupteur d'isolation de dérivation de
maintenance
62310-1  IEC:2005 – 17 –
3.1.5
maintenance by-pass
power path designed to allow isolation of an appropriate section or sections of a STS for
safety during maintenance and/or to maintain continuity of load power
3.1.6
redundant system
addition of functional units or groups of functional units in a system to enhance the continuity
of power to the load
3.1.7
STS input power
power supplied to STS and bypass, if any, which can be either the preferred source or the
alternate source
3.1.8
alternate source
source used as alternate power supply of the load when the preferred source fails or is out of
tolerance or is switched off for maintenance
3.1.9
preferred source
source used as normal power supply to the load, usually set by the operator
3.1.10
linear load
load where the current drawn from the supply is defined by the relationship:
I = U/Z
where
I is the load current;
U is the supply voltage;
Z is the constant load impedance.
3.1.11
non linear load
load where the parameter Z (load impedance) is no longer a constant but is a variable
dependent on other parameters, such as voltage or time
3.1.12
power failure
any variation in power source deemed to cause unacceptable performance of the load
equipment
3.1.13
normal mode of STS operation
when the load is supplied by the preferred source or the alternate source via the electronic
(power) switches
3.1.14
by-pass mode
when the load is supplied via the maintenance by-pass isolation switch

– 18 – 62310-1  CEI:2005
3.1.15
commande manuelle
commande d'une manœuvre, effectuée par intervention humaine
[VEI 441-16-04]
3.1.16
transfert manuel
manœ
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...