Electromagnetic compatibility (EMC) -- Part 6-2: Generic standards - Immunity for industrial environments

This part of IEC 61000 for EMC immunity requirements applies to electrical and electronic apparatus intended for use in industrial environments, as described below. Immunity requirements in the frequency range 0 Hz to 400 GHz are covered. No tests need to be performed at frequencies where no requirements are specified. This generic EMC immunity standard is applicable if no relevant dedicated product or product-family EMC immunity standard exists. This standard applies to apparatus intended to be connected to a power network supplied from a high or medium voltage transformer dedicated to the supply of an installation feeding manufacturing or similar plant, and intended to operate in or in proximity to industrial locations, as described below. This standard applies also to apparatus which is battery operated and intended to be used in industrial locations. The environments encompassed by this standard are industrial, both indoor and outdoor. Industrial locations are in addition characterised by the existence of one or more of the following: - industrial, scientific and medical (ISM) apparatus (as defined in CISPR 11); - heavy inductive or capacitive loads are frequently switched; - currents and associated magnetic fields are high. The object of this standard is to define immunity test requirements for apparatus defined in the scope in relation to continuous and transient, conducted and radiated disturbances, including electrostatic discharges. The immunity requirements have been selected to ensure an adequate level of immunity for apparatus at industrial locations. The levels do not, however, cover extreme cases, which may occur at any location, but with an extremely low probability of occurrence. Not all disturbance phenomena have been included for testing purposes in this standard, but only those considered as relevant for the equipment covered by this standard. These test requirements represent essential electromagnetic compatibility immunity requirements.

Elektromagnetische Verträglichkeit (EMV) -- Teil 6-2: Fachgrundnormen - Störfestigkeit - Industriebereich

Compatibilité électromagnétique (CEM) -- Partie 6-2: Normes génériques - Immunité pour les environnements industriels

S'applique aux appareils électriques et électroniques destinés à être utilisés dans les environnements industriels, pour lesquels aucune norme d'immunité spécifique à un produit ou à une famille de produits n'existe. Cette norme couvre les exigences d'immunité dans la gamme de fréquences de 0 Hz à 400 GHz, en rapport avec les perturbations continues et transitoires, conduites et rayonnées, y compris les décharges électrostatiques. Les prescriptions d'essais sont spécifiées pour chaque accès considéré. Les appareils destinés à être utilisés dans des sites industriels sont caractérisés par l'existence d'une ou plusieurs des conditions suivantes: - existence d'une installation de puissance alimentée par un transformateur de puissance haute ou moyenne tension, réservé à l'alimentation d'une installation alimentant un site industriel ou analogue; - présence d'appareils industriels, scientifiques et médicaux (ISM); - commutations fréquentes de charges inductives ou capacitives importantes; - valeurs élevées des courants et des champs magnétiques associés.

Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments (IEC 61000-6-2:1999, modified)

General Information

Status
Withdrawn
Publication Date
30-Apr-2002
Withdrawal Date
27-Apr-2008
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
14-Apr-2008
Due Date
07-May-2008
Completion Date
28-Apr-2008

Relations

Buy Standard

Standard
EN 61000-6-2:2002
English language
18 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI SIST EN 61000-6-2:2002
prva izdaja
STANDARD
maj 2002
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for
industrial environments (IEC 61000-6-2:1999, modified)
ICS 5HIHUHQþQDãWHYLOND
33.100.20
SIST EN 61000-6-2:2002(en)
! "#$%!&!%’()*#+’

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD EN 61000-6-2
NORME EUROPÉENNE
EUROPÄISCHE NORM October 2001
ICS 33.100.20 Supersedes EN 61000-6-2:1999
English version
Electromagnetic compatibility (EMC)
Part 6-2: Generic standards -
Immunity for industrial environments
(IEC 61000-6-2:1999, modified)
Compatibilité électromagnétique (CEM) Elektromagnetische Verträglichkeit (EMV)
Partie 6-2: Normes génériques - Teil 6-2: Fachgrundnormen -
Immunité pour les environnements Störfestigkeit - Industriebereich
industriels (IEC 61000-6-2:1999, modifiziert)
(CEI 61000-6-2:1999, modifiée)
This European Standard was approved by CENELEC on 2001-07-03. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands,
Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2001 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61000-6-2:2001 E

---------------------- Page: 2 ----------------------

EN 61000-6-2:2001 - 2 -
Foreword
The text of the International Standard IEC 61000-6-2:1999, prepared by IEC TC 77,
Electromagnetic compatibility, together with the common modifications prepared by the
Technical Committee CENELEC TC 210, Electromagnetic compatibility (EMC), was submitted to
the formal vote and was approved by CENELEC as EN 61000-6-2 on 2001-07-03.
This European Standard supersedes EN 61000-6-2:1999.
The following dates were fixed:
- latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2002-04-01
- latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2004-07-01
Annexes designated "normative" are part of the body of the standard.
In this standard, annex ZA is normative.
Annex ZA has been added by CENELEC.
__________

---------------------- Page: 3 ----------------------

- 3 - EN 61000-6-2:2001
Endorsement notice
The text of the International Standard IEC 61000-6-2:1999 was approved by CENELEC as a
European Standard with agreed common modifications as given below.
COMMON MODIFICATIONS
2 Normative references
Replace the text of clause 2 by:
NOTE  Normative references to international publications are listed in anne
...