SIST EN 15001-2:2023
(Main)Gas supply systems - Gas installation pipework with an operating pressure greater than 0,5 bar for industrial installations and greater than 5 bar for industrial and non-industrial installations - Part 2: Detailed functional requirements for commissioning, operation and maintenance
Gas supply systems - Gas installation pipework with an operating pressure greater than 0,5 bar for industrial installations and greater than 5 bar for industrial and non-industrial installations - Part 2: Detailed functional requirements for commissioning, operation and maintenance
This European Standard specifies detailed functional requirements for the commissioning, operation and maintenance of
• industrial gas installations and assemblies with an operating pressure greater than 0,5 bar and of
• non-industrial installations (residential and commercial) with an operating pressure greater than 5 bar,
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas appliance; normally the inlet isolation valve. This European Standard also covers the inlet connection to the gas appliance comprising of the pipework that does not fall within the scope of the appliance standard.
This standard applies to gas installations operating at ambient temperatures between –20 °C and 40 °C and operating pressures up to and including 60 bar. For operating conditions outside these limitations, reference should additionally be made to EN 13480 for metallic pipework.
For industrial gas installations up to and including 0,5 bar and for non-industrial (residential and commercial) gas installations up to and including 5 bar EN 1775 applies.
For gas installations that do not fall within the scope of EN 1775 or other European Standards, this European Standard applies.
In this European Standard, the term “gas“ refers to combustible gases, which are gaseous at 15 °C and 1 013 mbar absolute atmospheric pressure. These gases are commonly referred to as manufactured gas, natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family gases (see table 1 of EN 437:2003).
LPG storage vessels (including all ancillaries fitted directly to storage vessels) are excluded. Also excluded are LPG installations and sections of LPG installations operating at vapour pressure (e.g. between the storage vessel and its pressure regulator).
In this European Standard, all pressures are gauge pressures unless otherwise stated.
For gas installations within the scope of this standard, national legisl
Gasversorgungssysteme - Gasleitungsanlagen mit einem Betriebsdruck größer 0,5 bar für industrielle Installationen und größer 5 bar für industrielle und nicht-industrielle Installationen - Teil 2: Detaillierte funktionale Anforderungen an Inbetriebnahme, Betrieb und Instandhaltung
Dieses Dokument legt detailliert die funktionalen Anforderungen hinsichtlich Inbetriebnahme, Betrieb und Instandhaltung von:
— industriellen Gasleitungsanlagen und Baugruppen mit einem Betriebsdruck größer 0,5 bar; und
— nicht-industriellen Gasleitungsanlagen (Haushalte und Gewerbebetriebe) mit einem Betriebsdruck größer 5 bar,
beginnend am Ausgangsanschluss der Übergabestelle des Netzbetreibers bis zum Eingangsanschluss der Gasgeräte, d. h. in der Regel der Absperrarmatur vor dem Gerät, fest. Dieses Dokument gilt auch für die Rohrleitungen zum Eingangsanschluss der Gasgeräte, die nicht in den Anwendungsbereich der Gasgerätenorm fallen.
Abgesehen von den nachstehend angegebenen Ausnahmen gilt dieses Dokument für den Betrieb von Gasleitungsanlagen bei Umgebungstemperaturen zwischen –20 °C und 40 °C mit Betriebsdrücken bis einschließlich 60 bar. Bei Betriebszuständen außerhalb dieser Grenzen wird zusätzlich auf EN 13480 für metallische Rohrleitungen Bezug genommen.
Für industrielle Gasleitungsanlagen mit Betriebsdrücken bis einschließlich 0,5 bar und für nicht-industrielle Gasleitungsanlagen (Haushalte und Gewerbebetriebe) mit Betriebsdrücken bis einschließlich 5 bar gilt EN 1775.
Diese Europäische Norm gilt für Gasleitungsanlagen, die nicht in den Anwendungsbereich der EN 1775 oder anderer Europäischer Normen fallen.
Infrastructures gazières - Canalisations d'installation de gaz avec une pression de service supérieure à 0,5 bar pour les installations industrielles et supérieure à 5 bar pour les installations industrielles et non industrielles - Partie 2 : Exigences fonctionnelles détaillées pour la mise en service, l'exploitation et la maintenance
l’exploitation et à la maintenance :
- des installations et ensembles de gaz industriels fonctionnant à une pression supérieure à 0,5 bar et aux ;
- installations de gaz non industrielles (résidentielles et commerciales) fonctionnant à une pression supérieure à 5 bar ;
allant de la sortie du point de livraison de l’opérateur de réseau jusqu’à la connexion d’entrée de l’appareil à gaz, normalement le robinet de sectionnement d’entrée. Cette norme couvre aussi la tuyauterie de la connexion d’entrée d’un appareil à gaz qui n’est pas couverte par la norme de l’appareil.
NOTE 1 Les termes « installation » et « tuyauterie » sont interchangeables.
Outre les exceptions énoncées ci-après, la présente norme s’applique aux installations de gaz fonctionnant à des températures ambiantes comprises entre - 20 °C et 40 °C et des pressions de service inférieures ou égales à 60 bar. Pour des conditions d’exploitation à l’extérieur de ces limites, il convient qu’il soit fait référence à la norme EN 13480 concernant les tuyauteries métalliques.
Pour les installations de gaz industrielles inférieures ou égales à 0,5 bar et pour les installations de gaz non industrielles (résidentielles et commerciales) fonctionnant à une pression inférieure ou égale à 5 bar, c’est l’EN 1775 qui s’applique.
La présente norme s’applique aux installations de gaz qui n’entrent pas dans le domaine d’application de la norme EN 1775 ou d’autres normes européennes.
Dans la présente Norme, le terme « gaz » se rapporte à des gaz combustibles se présentant sous forme gazeuse à 15 °C et à 1 013 mbar de pression atmosphérique absolue. Ces gaz sont couramment appelés gaz manufacturés, gaz naturel ou gaz de pétrole liquéfié (GPL). Ils sont aussi dénommés gaz de la 1ère, 2e ou 3e famille respectivement selon le classement de l’EN 437:2003+A1:2009, Tableau 1. Les valeurs données sont considérées aux conditions normales pour tous les volumes donnés dans cette norme.
La présente Norme européenne s’applique aux canalisations d'installations pour le transport du :
- gaz traité, non toxique et non corrosif, naturel, conformément à l’EN 437:2003+A1:2009 et à l’EN 16726, « Infrastructures gazières - Qualité du gaz - Groupe H » ;
- GNL vaporisé ;
- biométhane, conforme à l’EN 16723-1 ;
- GNL vaporisé.
NOTE 2 La spécification du GNL vaporisé équivaut à celle du gaz naturel classé dans l’EN 437:2003+A1:2009.
La présente Norme européenne ne couvre pas la tuyauterie pour les gaz riches en hydrogène ne relevant pas de la définition figurant dans l’EN 437:2003+A1:2009. Les réservoirs de stockage de GPL (y compris tous les accessoires fixés directement sur les réservoirs) sont exclus. Il en est de même pour les installations de GPL et les parties d'installations de GPL exploitées à la pression de vapeur (par exemple entre le réservoir de stockage et son régulateur de pression).
Infrastruktura za plin - Plinske napeljave z delovnim tlakom nad 0,5 bar za industrijsko uporabo in delovnim tlakom nad 5 bar za industrijsko in neindustrijsko uporabo - 2. del: Podrobne funkcionalne zahteve za začetek obratovanja, obratovanje in vzdrževanje
Ta evropski standard določa podrobne funkcionalne zahteve za zagon, delovanje in vzdrževanje
• industrijskih plinskih naprav in sestavov z obratovalnim tlakom, višjim od 0,5 bara, in
• neindustrijskih naprav (stanovanjskih in poslovnih) z obratovalnim tlakom, višjim od 5 barov,
od izhoda iz dobavnega mesta upravljavca omrežja do dovodnega priključka plinske naprave: običajno do dovodnega izolirnega ventila. Ta evropski standard zajema tudi dovodni priključek plinske naprave, ki obsega cevovode, ki ne spadajo na področje uporabe standarda za naprave.
Ta standard se uporablja za plinske naprave, ki delujejo pri temperaturah okolice med −20 °C in 40 °C ter pri obratovalnih tlakih do vključno 60 barov. Za obratovalne pogoje zunaj teh omejitev se je treba dodatno sklicevati na standard EN 13480 za kovinske cevovode.
Za industrijske plinske napeljave do vključno 0,5 bara in za neindustrijske (stanovanjske in poslovne) plinske napeljave do vključno 5 barov v stavbah se uporablja standard EN 1775.
Za plinske napeljave, ki ne spadajo na področje uporabe standarda EN 1775 ali drugih evropskih standardov, velja ta evropski standard.
V tem standardu se izraz »plin« nanaša na gorljive pline, ki so plinasti pri 15 °C in absolutnem atmosferskem tlaku 1013 mbar (normalni pogoji). Ti plini se običajno imenujejo industrijski plin, zemeljski plin ali utekočinjeni naftni plin (LPG). Imenujemo jih tudi plini prve, druge ali tretje plinske družine (glej preglednico 1 standarda EN 437:2003).
Posode za shranjevanje utekočinjenega naftnega plina (LPG) (vključno z vsemi pomožnimi napravami, nameščenimi neposredno na posode za shranjevanje) so izključene. Prav tako so izključene naprave za LPG in deli naprav za LPG, ki delujejo pri parnem tlaku (npr. med posodo za shranjevanje in regulatorjem tlaka).
V tem evropskem standardu so vsi tlaki merilni tlaki, razen če ni drugače navedeno.
Za plinske naprave, ki spadajo v področje uporabe tega standarda, se uporablja nacionalna zakonodaja.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 15001-2:2023
01-april-2023
Nadomešča:
SIST EN 15001-2:2009
Infrastruktura za plin - Plinske napeljave z delovnim tlakom nad 0,5 bar za
industrijsko uporabo in delovnim tlakom nad 5 bar za industrijsko in
neindustrijsko uporabo - 2. del: Podrobne funkcionalne zahteve za začetek
obratovanja, obratovanje in vzdrževanje
Gas supply systems - Gas installation pipework with an operating pressure greater than
0,5 bar for industrial installations and greater than 5 bar for industrial and non-industrial
installations - Part 2: Detailed functional requirements for commissioning, operation and
maintenance
Gasversorgungssysteme - Gasleitungsanlagen mit einem Betriebsdruck größer 0,5 bar
für industrielle Installationen und größer 5 bar für industrielle und nicht-industrielle
Installationen - Teil 2: Detaillierte funktionale Anforderungen an Inbetriebnahme, Betrieb
und Instandhaltung
Infrastructures gazières - Canalisations d'installation de gaz avec une pression de
service supérieure à 0,5 bar pour les installations industrielles et supérieure à 5 bar pour
les installations industrielles et non industrielles - Partie 2 : Exigences fonctionnelles
détaillées pour la mise en service, l'exploitation et la maintenance
Ta slovenski standard je istoveten z: EN 15001-2:2023
ICS:
91.140.40 Sistemi za oskrbo s plinom Gas supply systems
SIST EN 15001-2:2023 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 15001-2:2023
---------------------- Page: 2 ----------------------
SIST EN 15001-2:2023
EN 15001-2
EUROPEAN STANDARD
NORME EUROPÉENNE
February 2023
EUROPÄISCHE NORM
ICS 23.040.01 Supersedes EN 15001-2:2008
English Version
Gas supply systems - Gas installation pipework with an
operating pressure greater than 0,5 bar for industrial
installations and greater than 5 bar for industrial and non-
industrial installations - Part 2: Detailed functional
requirements for commissioning, operation and
maintenance
Infrastructures gazières - Canalisations d'installation Gasversorgungssysteme - Gas-Leitungsanlagen mit
de gaz avec une pression de service supérieure à 0,5 einem Betriebsdruck größer 0,5 bar für industrielle
bar pour les installations industrielles et supérieure à 5 Installationen und größer 5 bar für industrielle und
bar pour les installations industrielles et non nicht-industrielle Installationen - Teil 2: Detaillierte
industrielles - Partie 2 : Exigences fonctionnelles funktionale Anforderungen an Inbetriebnahme, Betrieb
détaillées pour la mise en service, l'exploitation et la und Instandhaltung
maintenance
This European Standard was approved by CEN on 1 July 2019.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2023 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15001-2:2023 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
Contents Page
European foreword . 4
1 Scope . 6
2 Normative references . 7
3 Terms and definitions . 7
3.1 Definitions relating to pressure . 7
3.2 Definitions relating to the gas installation . 8
3.3 Definitions relating to means of isolation . 9
3.4 Definitions relating to components . 9
3.5 Definitions relating to tests . 9
3.6 Definitions relating to commissioning, operation and maintenance . 10
3.7 Definitions relating to pressure regulating and metering . 11
4 General . 11
4.1 Installation drawings and technical file. 11
4.2 Changes affecting an existing installation pipework . 11
4.3 Quality system . 12
4.4 Protection against hazards . 12
4.4.1 Electrical installation in hazardous area . 12
4.4.2 Gas detection systems . 12
4.4.3 Non-odorized gas. 12
4.5 Protection against adverse influences . 13
5 Commissioning . 13
5.1 General . 13
5.2 Purging . 13
5.2.1 General . 13
5.2.2 Setting and checking regulators and safety devices . 14
5.2.3 Inspection of gas pressure boosters/compressors . 14
6 Operation and maintenance . 14
6.1 Requirements involving operation and maintenance . 14
6.1.1 Identification of buried services . 14
6.1.2 Depth of cover . 14
6.1.3 External hazards . 15
6.1.4 Supporting structures . 15
6.2 Operation . 15
6.2.1 General . 15
6.2.2 Properties of fuel gas . 15
6.2.3 Condensation and design temperature effect in pressure control systems . 16
6.2.4 Effects of construction and other activities on the installation. 16
6.2.5 Prevention of migration of gas into buildings . 16
6.2.6 Trees and plants . 16
6.2.7 Emergencies . 16
6.3 Maintenance . 17
6.3.1 General . 17
6.3.2 Safety engineering . 17
2
---------------------- Page: 4 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
6.3.3 Appliance isolating valves . 18
6.3.4 Identification of above-ground gas pipework . 18
6.3.5 Detail engineering . 18
6.3.6 Work on pipework . 19
6.3.7 Inspections . 19
6.3.8 Operability check on valves . 21
6.3.9 Pressure control systems. 21
6.3.10 Pressure settings . 21
6.3.11 Installation of pressure regulating systems . 21
6.3.12 Filters and liquid separators . 21
6.3.13 Corrosion protection . 21
6.3.14 Hazardous areas. 22
6.3.15 Hot working in hazardous areas . 22
6.3.16 Hot tapping. 23
Annex A (informative) Significant technical changes between this European standard and
the previous version EN 15001-2:2008 . 24
Bibliography . 26
3
---------------------- Page: 5 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
European foreword
This document (EN 15001-2:2023) has been prepared by Technical Committee CEN/TC 234 “Gas
supply”, the secretariat of which is held by DIN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by August 2023, and conflicting national standards shall
be withdrawn at the latest by August 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 15001-2:2008.
A list of the significant changes compared to EN 15001-2:2008 can be found in Annex A, Table A.1.
The scope of this revised standard is extended with biomethane and vaporized LNG gases. This
standard is not designed for various mixtures of natural gas and hydrogen which may be allowed in the
different member states.
With respect to hydrogen there are proposals to inject hydrogen (H2) from renewable sources into the
natural gas network. Investigations have been conducted to evaluate the impact. According to EN 16726
at present it is not possible to specify a limiting hydrogen value which would generally be valid for all
parts of the European gas infrastructure.
There is a complete suite of functional standards prepared by CEN/TC 234 “Gas infrastructure” to cover
all parts of the gas supply system from the input of gas to the transmission system up to the inlet
connection of the gas appliances, whether for domestic, commercial or industrial purposes.
In preparing this document, a basic understanding of gas supply by the user has been assumed.
In the event of conflicts in terms of more restrictive requirements in national legislation/regulation
with the requirements of this standard, national legislation/regulation takes precedence as illustrated
in CEN/TR 13737.
NOTE CEN/TR 13737 contains:
— clarification of relevant legislation/regulations applicable in a country;
— if appropriate, more restrictive national requirements;
— national contact point for the latest information.
Gas supply systems are complex and the importance on safety of their construction and use has led to
the development of very detailed codes of practice and operating manuals in the member countries.
These detailed statements embrace recognized standards of gas engineering and the specific
requirements imposed by the legal structures of the member countries.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
4
---------------------- Page: 6 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the
United Kingdom.
5
---------------------- Page: 7 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
1 Scope
This document specifies detailed functional requirements for the commissioning, operation and
maintenance of
— industrial gas installation pipework and assemblies with an operating pressure greater than
0,5 bar; and
— non-industrial gas installation pipework (residential and commercial) with an operating pressure
greater than 5 bar in buildings,
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas
appliance; normally the inlet isolation valve. This document also covers the pipework to the inlet
connection of a gas appliance that is not included within the scope of the appliance standard.
Apart from the exceptions stated below, this document applies to gas installation pipework operating at
ambient temperatures between –20 °C and 40 °C and operating pressures up to and including 60 bar.
For operating conditions outside these limitations, reference is additionally be made to EN 13480 for
metallic pipework.
For industrial gas installation pipework up to and including 0,5 bar and for non-industrial (residential
and commercial) gas installation pipework up to and including 5 bar EN 1775 applies.
For gas installation pipework that do not fall within the scope of EN 1775 or other European Standards,
this European Standard applies.
In this document, the term “gas“ refers to combustible gases, which are gaseous at 15 °C and
1 013 mbar absolute atmospheric pressure. These gases are commonly referred to as manufactured gas,
natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family
gases as classified in EN 437:2021, Table 1 The given values are considered as normal conditions for all
volumes given in this document.
This document is applicable to gas installation pipework for the carriage of:
— processed, non-toxic and non-corrosive natural gas according to EN 437:2021 and EN 16726 “Gas
infrastructure — Quality of gas — Group H”;
— biomethane, complying with EN 16723-1;
— vaporized LNG.
NOTE The specification of vaporized LNG is equal to that of natural gas as classified in EN 437:2021.
This document does not cover pipework for hydrogen rich gases that fall outside the definitions within
EN 437:2021.
LPG storage vessels (including all ancillaries fitted directly to storage vessels) are excluded. Also
excluded are LPG installations and sections of LPG installations operating at vapour pressure or in the
liquid state.
In this document, all pressures are gauge pressures unless otherwise stated.
This document specifies common basic principles for gas supply systems. Users of this document should
be aware that more detailed national standards and/or code of practice may exist in the CEN member
countries.
This document is intended to be applied in association with these national standards and/or codes of
practice setting out the above-mentioned basic principles.
6
---------------------- Page: 8 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
For gas installation pipework within the scope of this document, national legislation and regulations are
meant to be taken into account.
Functional requirements for design, selection of materials, construction, inspection and testing of
industrial gas installation- pipework with an operating pressure greater than 0,5 bar and of gas
installation pipework greater than 5 bar in buildings and areas intended for non-industrial installation
pipework are described in EN 15001-1:2023.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12954, General principles of cathodic protection of buried or immersed onshore metallic structures
EN 15001-1:2023, Gas Infrastructure — Gas installation pipework with an operating pressure greater
than 0,5 bar for industrial installations and greater than 5 bar for industrial and non-industrial
installations — Part 1: Detailed functional requirements for design, materials, construction, inspection and
testing erection
EN 60079-17, Explosive atmospheres - Part 17: Electrical installations inspection and maintenance
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at http://www.iso.org/obp
3.1 Definitions relating to pressure
3.1.1
pressure
gauge pressure of the fluid inside the system, measured in static conditions
3.1.2
maximum allowable pressure
PS
maximum pressure for which pipework is designed in accordance with the strength requirements in
this document
Note 1 to entry: For this standard, PS is equivalent to the design pressure (DP).
MIP
Note 2 to entry: PS ≥
1,1
3.1.3
maximum incidental pressure
MIP
maximum pressure which pipework can experience during a short time, limited by the safety devices
7
---------------------- Page: 9 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
3.1.4
operating pressure
OP
pressure which occurs within pipework under normal operating conditions
3.2 Definitions relating to the gas installation
3.2.1
pipework
assembly of pipes and fittings
3.2.2
component
item from which a gas supply system or installation is constructed and for which a distinction is drawn
between the following groups of components:
— ancillaries (for example pressure regulators, valves, safety devices, expansion joints, and insulating
joints);
— pipes, including bends made from pipe;
— instrumentation pipework;
— fittings (for example reducers, tees, factory-made elbows, flanges, dome ends, welding stubs, and
mechanical joints)
3.2.3
point of delivery
point where the gas is transferred to the user
Note 1 to entry: This can be at a means of isolation or at the meter outlet connection and is normally at the
point of transfer of ownership.
3.2.4
user
person responsible for the safety of the gas installation and associated risks on a site
Note 1 to entry: Normally the user will be the site occupier, operator or owner. It should be assumed that every
user has a responsibility for work performed on their site, whether or not the work is performed directly for the
user or not. This does not mean that they cannot take advice from an independent specialist.
3.2.5
installation pipework
pipework including components and stations downstream of the point of delivery terminating at the
appliance inlet connection
Note 1 to entry: This pipework is normally the property of the customer rather than the supplier.
3.2.6
ventilated space
space where the air is continuously changed by natural or mechanical means
3.2.7
ventilation duct
duct forming part of the structure of the building and intended exclusively for ventilation purposes
8
---------------------- Page: 10 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
3.3 Definitions relating to means of isolation
3.3.1
means of isolation
device that is intended to interrupt the gas flow in pipework
EXAMPLE A manually operable valve
3.4 Definitions relating to components
3.4.1
regulator
device which reduces the gas pressure to a set value and maintains it within prescribed limits
3.4.2
insulating joint
fitting installed to insulate electrically one section of pipework from another
3.4.3
sleeve
protective pipe through which a gas pipe passes
3.4.4
vent pipe
pipework connected to a safety or control device to release gas at a safe location
3.4.5
creep relief valve
device designed to release a limited flow of gas in the event of an unacceptable pressure being detected
within the system it protects
3.4.6
instrumentation pipework
pipework required for the proper functioning of the ancillaries installed within the pressure regulating
installation
EXAMPLE Sensing, measuring, auxiliary and sampling lines
3.5 Definitions relating to tests
3.5.1
strength test
specific procedure intended to verify that the pipework meets the requirements for mechanical
strength
3.5.2
tightness test
specific procedure intended to verify that the pipework meets the requirements for tightness
3.5.3
leak detection fluid
specially formulated fluid and foaming product that gives a clear indication that a leak exists when
applied to an element of pipework
9
---------------------- Page: 11 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
3.6 Definitions relating to commissioning, operation and maintenance
3.6.1
admission of gas
operation of replacing the air or inert gas contained in pipework with distributed gas
3.6.2
purging from gas
operation of replacing the distributed gas in pipework with air or inert gas
3.6.3
purging
process for safety removing air or inert gas from pipework and/or pipeline components and replacing it
with gas, or the reverse process
3.6.3.1
direct purging
displacement of air by gas or vice versa;
3.6.3.2
indirect purging
displacement of air by inert gas followed by the displacement by gas or vice versa: alternatively by
means of a barrier (a slug of inert gas or a pig) between the air and the gas or vice versa
3.6.4
commissioning
activities required to fill and to pressurize pipework, stations, equipment and assemblies with gas and
to put them into operation
3.6.5
decommissioning
activities required to take out of service any pipework, stations, equipment and assemblies filled with
gas and to disconnect them from the rest of the system
3.6.6
competent person
person who is trained, experienced and approved to perform activities relating to gas pipework
Note 1 to entry: Means of approval are determined within each country.
3.6.7
hot tapping
procedure involving the safe use of heat, e.g. welding or fusion, to affix an attachment to a section of
pipework containing gas at pressure
3.6.8
hot work
work that can provide an ignition source
10
---------------------- Page: 12 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
3.7 Definitions relating to pressure regulating and metering
3.7.1
gas pressure control and metering system
system comprising all equipment, together with inlet and outlet piping up to and including the isolating
valves, which together performs the functions of pressure regulation, pressure safety and/or
quantitative gas measurement, whether or not including pressure boosting and/or gas mixing facilities
4 General
4.1 Installation drawings and technical file
Any change to the installation pipework shall be recorded in the technical file and on the installation
drawings required in EN 15001-1.
Special attention shall be given to ensure that, after completion of commissioning, the technical file is
correctly updated to record any changes made in respect of the following:
1) diagram of the installation pipework and pressure regulation installations;
2) details of design standards used, evidence of testing of materials and components along with any
Certificates issued by the test bodies/manufacturers;
3) maximum allowable pressures and temperatures, maximum and minimum;
4) flow rates and discharge capacities;
5) function and duty of protective controls;
6) corrosion allowances;
7) material wall thickness of pipes;
8) materials specified;
9) welding standards and test procedures;
10) commissioning procedure;
11) testing and re-testing procedures;
12) purging procedures or methodology;
13) setting of pressure regulators and safety devices;
14) operating manual including decommissioning and maintenance procedures including in-service
inspections;
15) changes made during the commissioning procedure.
4.2 Changes affecting an existing installation pipework
Alterations or modifications to the installation including electrical equipment that changes its original
characteristics, purpose and/or type, shall be carried out in accordance with EN 15001-1.
11
---------------------- Page: 13 ----------------------
SIST EN 15001-2:2023
EN 15001-2:2023 (E)
4.3 Quality system
The life of a gas installation pipework can be divided into four phases:
— design (see EN 15001-1);
— construction and testing (see EN 15001-1);
— commissioning, as covered in this standard;
— operation and maintenance, as covered in this standard.
A quality system shall be applied to the operation
...
SLOVENSKI STANDARD
oSIST prEN 15001-2:2017
01-julij-2017
6LVWHPLRVNUEHVSOLQRP3OLQVNHQDSHOMDYH]GHORYQLPWODNRPQDGEDU]D
LQGXVWULMVNRXSRUDERLQGHORYQLPWODNRPQDGEDU]DLQGXVWULMVNRLQ
QHLQGXVWULMVNRXSRUDERGHO3RGUREQHIXQNFLRQDOQH]DKWHYH]D]DþHWHN
REUDWRYDQMDREUDWRYDQMHLQY]GUåHYDQMH
Gas supply systems - Gas installation pipework with an operating pressure greater than
0,5 bar for industrial installations and greater than 5 bar for industrial and non-industrial
installations - Part 2: Detailed functional requirements for commissioning, operation and
maintenance
Gasversorgungssysteme - Gas-Leitungsanlagen mit einem Betriebsdruck größer 0.5 bar
für industrielle Installationen und größer 5 bar für industrielle und nicht-industrielle
Installationen - Teil 2: Detaillierte funktionale Anforderungen an Inbetriebnahme, Betrieb
und Instandhaltung
Alimentation en gaz - Installation intérieure de pression de service plus de 0.5 bar pour
les installations industrielles et plus de 5 bar pour les installations industrielles et non-
industrielles - Partie 2 : Prescriptions fonctionelles et détaillées pour la mise en service,
l'exploitation et la maintenance
Ta slovenski standard je istoveten z: prEN 15001-2
ICS:
91.140.40 Sistemi za oskrbo s plinom Gas supply systems
oSIST prEN 15001-2:2017 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
oSIST prEN 15001-2:2017
---------------------- Page: 2 ----------------------
oSIST prEN 15001-2:2017
DRAFT
EUROPEAN STANDARD
prEN 15001-2
NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2017
ICS 91.140.40; 23.040.01 Will supersede EN 15001-2:2008
English Version
Gas supply systems - Gas installation pipework with an
operating pressure greater than 0,5 bar for industrial
installations and greater than 5 bar for industrial and non-
industrial installations - Part 2: Detailed functional
requirements for commissioning, operation and
maintenance
Alimentation en gaz - Installation intérieure de Gasversorgungssysteme - Gas-Leitungsanlagen mit
pression de service plus de 0.5 bar pour les einem Betriebsdruck größer 0.5 bar für industrielle
installations industrielles et plus de 5 bar pour les Installationen und größer 5 bar für industrielle und
installations industrielles et non-industrielles - Partie 2 nicht-industrielle Installationen - Teil 2: Detaillierte
: Prescriptions fonctionelles et détaillées pour la mise funktionale Anforderungen an Inbetriebnahme, Betrieb
en service, l'exploitation et la maintenance und Instandhaltung
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 234.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15001-2:2017 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 6
3 Terms and definitions . 6
3.1 Definitions relating to pressure . 6
3.2 Definitions relating to the gas installation . 7
3.3 Definitions relating to means of isolation . 8
3.4 Definitions relating to components . 8
3.5 Definitions relating to tests . 8
3.6 Definitions relating to commissioning, operation and maintenance . 9
3.7 Definitions relating to pressure regulating and metering . 10
4 General . 10
4.1 Installation drawings and technical file. 10
4.2 Changes affecting an existing installation . 11
4.3 Quality system . 11
4.4 Protection against hazards . 11
4.4.1 Electrical installation in hazardous area . 11
4.4.2 Gas detection systems . 11
4.5 Protection against adverse influences . 12
5 Commissioning . 12
5.1 General . 12
5.2 Purging . 12
5.2.1 General . 12
5.2.2 Setting and checking regulators and safety devices . 13
5.2.3 Inspection of gas pressure boosters/compressors . 13
6 Operation and maintenance . 13
6.1 Requirements involving operation and maintenance . 13
6.1.1 Identification of buried services . 13
6.1.2 Depth of cover . 13
6.1.3 External hazards . 14
6.1.4 Supporting structures . 14
6.2 Operation . 14
6.2.1 General . 14
6.2.2 Properties of fuel gas . 14
6.2.3 Pressure control systems . 15
6.2.4 Effects of construction and other activities on the installation. 15
6.2.5 Prevention of migration of gas into buildings . 15
6.2.6 Trees and plants . 15
6.2.7 Emergencies . 15
6.3 Maintenance . 16
6.3.1 General . 16
6.3.2 Safety engineering . 16
6.3.3 Appliance isolating valves. 17
6.3.4 Identification of above-ground gas pipework . 17
2
---------------------- Page: 4 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
6.3.5 Detail engineering . 17
6.3.6 Work on pipework . 17
6.3.7 Inspections . 18
6.3.8 Operability check on valves . 19
6.3.9 Pressure control systems. 20
6.3.10 Pressure settings . 20
6.3.11 Installation of pressure regulating systems . 20
6.3.12 Filters and liquid separators . 20
6.3.13 Corrosion protection . 20
6.3.14 Hazardous areas. 21
6.3.15 Hot working in hazardous areas . 21
6.3.16 Hot tapping. 22
Annex A (informative) Significant technical changes between this European standard and
the previous version EN 15001-2:2008 . 23
Bibliography . 25
3
---------------------- Page: 5 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
European foreword
This document (prEN 15001-2:2017) has been prepared by Technical Committee CEN/TC 234 “Gas
supply”, the secretariat of which is held by DIN.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 15001-2:2008.
A list of the significant changes compared to EN 15001-2:2008 can be found in Annex A, Table A.1.
The scope of this revised standard is extended with biomethane and vaporized LNG gases. This
standard is not designed for various mixtures of natural gas and hydrogen which may be allowed in the
different member states.
With respect to hydrogen there are proposals to inject hydrogen (H2) from renewable sources into the
natural gas network. Investigations have been conducted to evaluate the impact. According to EN 16726
at present it is not possible to specify a limiting hydrogen value which would generally be valid for all
parts of the European gas infrastructure.
There is a complete suite of functional standards prepared by CEN/TC 234 “Gas infrastructure” to cover
all parts of the gas supply system from the input of gas to the transmission system up to the inlet
connection of the gas appliances, whether for domestic, commercial or industrial purposes.
In preparing this standard, a basic understanding of gas supply by the user has been assumed.
In the event of conflicts in terms of more restrictive requirements in national legislation/regulation
with the requirements of this standard, national legislation/regulation takes precedence as illustrated
in CEN/TR 13737.
NOTE CEN/TR 13737 contains:
— clarification of relevant legislation/regulations applicable in a country;
— if appropriate, more restrictive national requirements;
— national contact point for the latest information.
Gas supply systems are complex and the importance on safety of their construction and use has led to
the development of very detailed codes of practice and operating manuals in the member countries.
These detailed statements embrace recognized standards of gas engineering and the specific
requirements imposed by the legal structures of the member countries.
4
---------------------- Page: 6 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
1 Scope
This European Standard specifies detailed functional requirements for the commissioning, operation
and maintenance of
— industrial gas installations and assemblies with an operating pressure greater than 0,5 bar; and of
— non-industrial gas installations (residential and commercial) with an operating pressure greater
than 5 bar,
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas
appliance; normally the inlet isolation valve. This European Standard also covers the pipework to the
inlet connection of a gas appliance that is not included within the scope of the appliance standard.
NOTE 1 The use of the term installation and pipework is interchangeable.
Apart from the exceptions stated below, this standard applies to gas installations operating at ambient
temperatures between –20 °C and 40 °C and operating pressures up to and including 60 bar. For
operating conditions outside these limitations, reference should additionally be made to EN 13480 for
metallic pipework.
For industrial gas installations up to and including 0,5 bar and for non-industrial (residential and
commercial) gas installations up to and including 5 bar EN 1775 applies.
For gas installations that do not fall within the scope of EN 1775 or other European Standards, this
European Standard applies.
In this European Standard, the term “gas“ refers to combustible gases, which are gaseous at 15 °C and
1 013 mbar absolute atmospheric pressure. These gases are commonly referred to as manufactured gas,
natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family
gases as classified in EN 437:2003+A1:2009., Table 1 The given values are considered as normal
conditions for all volumes given in this standard.
This European Standard is applicable to installation pipework for the carriage of:
— processed, non-toxic and non-corrosive natural gas according to EN 437:2003+A1:2009 and
EN 16726 “Gas infrastructure - Quality of gas - Group H”;
— vaporized LNG;
— biomethane, complying with EN 16723-1;
— vaporized LNG.
NOTE 2 The specification of vaporized LNG is equal to that of natural gas as classified in
EN 437:2003+A1:2009.
This European Standard does not cover pipework for hydrogen rich gases that fall outside the
definitions within EN 437:2003+A1:2009. LPG storage vessels (including all ancillaries fitted directly to
storage vessels) are excluded. Also excluded are LPG installations and sections of LPG installations
operating at vapour pressure (e.g. between the storage vessel and its pressure regulator).
In this European Standard, all pressures are gauge pressures unless otherwise stated.
This European Standard specifies common basic principles for gas supply systems. Users of this
European Standard should be aware that more detailed national standards and/or code of practice may
exist in the CEN member countries.
5
---------------------- Page: 7 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
This European Standard is intended to be applied in association with these national standards and/or
codes of practice setting out the above-mentioned basic principles.
For gas installations within the scope of this standard, national legislation and regulations are meant to
be taken into account.
Functional requirements for design, selection of materials, construction, inspection and testing of
industrial gas installations and assemblies with an operating pressure greater than 0,5 bar and of gas
installations greater than 5 bar in buildings and areas intended for residential, commercial, public and
mixed uses are described in EN 15001-1.
Generally, additional safety precautions may be necessary where non odorized gas is used. For non-
industrial purposes, the gas should be odorized.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 12954, Cathodic protection of buried or immersed metallic structures - General principles and
application for pipelines
prEN 15001-1:2017, Gas Infrastructure - Gas installation pipework with an operating pressure greater
than 0,5 bar for industrial installations and greater than 5 bar for industrial and non-industrial
installations - Part 1: Detailed functional requirements for design, materials, construction, inspection and
testing
EN 60079-14, Explosive atmospheres - Part 14: Electrical installations design, selection and erection
EN 60079-17, Explosive atmospheres — Part 17: Electrical installations inspection and maintenance
EN 60079-29-1, Explosive atmospheres — Part 29-1: Gas detectors – Performance requirements of
detectors for flammable gases
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 Definitions relating to pressure
3.1.1
pressure
gauge pressure of the fluid inside the system, measured in static conditions
3.1.2
maximum allowable pressure
PS
maximum pressure for which pipework is designed in accordance with the strength requirements in
this document
Note 1 to entry: For this standard, PS is equivalent to the design pressure (DP).
6
---------------------- Page: 8 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
3.1.3
maximum incidental pressure
MIP
maximum pressure which pipework can experience during a short time, limited by the safety devices
3.1.4
operating pressure
OP
pressure which occurs within pipework under normal operating conditions
3.2 Definitions relating to the gas installation
3.2.1
pipework
assembly of pipes and fittings
3.2.2
component
item from which a gas supply system or installation is constructed and for which a distinction is drawn
between the following groups of components:
— ancillaries (for example pressure regulators, valves, safety devices, expansion joints, and insulating
joints);
— pipes, including bends made from pipe;
— instrumentation pipework;
— fittings (for example reducers, tees, factory-made elbows, flanges, dome ends, welding stubs, and
mechanical joints)
3.2.3
point of delivery
point where the gas is transferred to the user
Note 1 to entry: This can be at a means of isolation or at the meter outlet connection and is normally at the
point of transfer of ownership.
3.2.4
user
person responsible for the safety of the gas installation and associated risks on a site
Note 1 to entry: Normally the user will be the site occupier or owner. It should be assumed that every user has a
responsibility for work performed on their site, whether or not the work is performed directly for the user or not.
This does not mean that they cannot take advice from an independent specialist.
3.2.5
installation pipework
pipework including components and stations downstream of the point of delivery terminating at the
appliance inlet connection
Note 1 to entry: This pipework is normally the property of the customer.
3.2.6
ventilated space
space where the air is continuously changed by natural or mechanical means
7
---------------------- Page: 9 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
3.2.7
duct
space specifically designed and constructed for the passage of building services
EXAMPLE Building services include gas pipework, water systems, power and telecommunication cables
3.2.8
ventilation duct
duct forming part of the structure of the building and intended exclusively for ventilation purposes
3.3 Definitions relating to means of isolation
3.3.1
means of isolation
device that is intended to interrupt the gas flow in pipework
EXAMPLE a manually operable valve
3.4 Definitions relating to components
3.4.1
regulator
device which reduces the gas pressure to a set value and maintains it within prescribed limits
3.4.2
insulating joint
fitting installed to insulate electrically one section of pipework from another
3.4.3
sleeve
protective pipe through which a gas pipe passes
3.4.4
vent pipe
pipework connected to a safety or control device to release gas at a safe location
3.4.5
creep relief valve
device designed to release a limited flow of gas in the event of an unacceptable pressure being detected
within the system it protects
3.4.6
instrumentation pipework
pipework required for the proper functioning of the ancillaries installed within the pressure regulating
installation
EXAMPLES Sensing, measuring, auxiliary and sampling lines
3.5 Definitions relating to tests
3.5.1
strength test
specific procedure intended to verify that the pipework meets the requirements for mechanical
strength
8
---------------------- Page: 10 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
3.5.2
tightness test
specific procedure intended to verify that the pipework meets the requirements for tightness
3.5.3
leak detection fluid
specially formulated fluid and foaming product that gives a clear indication that a leak exists when
applied to an element of pipework
3.6 Definitions relating to commissioning, operation and maintenance
3.6.1
admission of gas
operation of replacing the air or inert gas contained in pipework with distributed gas
3.6.2
purging from gas
operation of replacing the distributed gas in pipework with air or inert gas
3.6.3
purging
process for safety removing air or inert gas from pipework and/or pipeline components and replacing it
with gas, or the reverse process
3.6.3.1
direct purging
displacement of air by gas or vice versa;
3.6.3.2
indirect purging
displacement of air by inert gas followed by the displacement by gas or vice versa: alternatively by
means of a barrier (a slug of inert gas or a pig) between the air and the gas or vice versa
3.6.4
commissioning
activities required to fill and to pressurise pipework, stations, equipment and assemblies with gas and
to put them into operation
3.6.5
decommissioning
activities required to take out of service any pipework, stations, equipment and assemblies filled with
gas and to disconnect them from the rest of the system
3.6.6
competent person
person who is trained, experienced and approved to perform activities relating to gas pipework
Note 1 to entry: Means of approval are determined within each country.
3.6.7
hot tapping
procedure involving the safe use of heat, e.g. welding or fusion, to affix an attachment to a section of
pipework containing gas at pressure
9
---------------------- Page: 11 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
3.6.8
hot work
work that can provide an ignition source
3.7 Definitions relating to pressure regulating and metering
3.7.1
gas pressure control and metering system
system comprising all equipment, together with inlet and outlet piping up to and including the isolating
valves, which together performs the functions of pressure regulation, pressure safety and/or
quantitative gas measurement, whether or not including pressure boosting and/or gas mixing facilities
4 General
4.1 Installation drawings and technical file
Any change to the installation pipework shall be recorded in the technical file and on the installation
drawings required in prEN 15001-1.
Special attention shall be given to ensure that, after completion of commissioning, the technical file is
correctly updated to record any changes made in respect of the following:
1) diagram of the installation pipework and pressure regulation installations;
2) details of design standards used, evidence of testing of materials and components along with any
Certificates issued by the test bodies/manufacturers;
3) maximum allowable pressures and temperatures, maximum and minimum;
4) flow rates and discharge capacities;
5) function and duty of protective controls;
6) corrosion allowances;
7) material wall thickness of pipes;
8) materials specified;
9) welding standards and test procedures;
10) commissioning procedure;
11) testing and re-testing procedures;
12) purging procedures or methodology;
13) setting of pressure regulators and safety devices;
14) operating manual including decommissioning and maintenance procedures including in-service
inspections;
15) changes made during the commissioning procedure.
10
---------------------- Page: 12 ----------------------
oSIST prEN 15001-2:2017
prEN 15001-2:2017 (E)
4.2 Changes affecting an existing installation
Alterations or modifications to the installation including electrical equipment that changes its original
characteristics, purpose and/or type, shall be carried out in accordance with prEN 15001-1.
4.3 Quality system
The life of a gas installation can be divided into four phases:
— design (see prEN 15001-1);
— construction and testing (see prEN 15001-1);
— commissioning, as covered in this standard;
— operation and maintenance, as covered in this standard.
A quality system shall be applied to the operation and maintenance activities in accordance with this
European Standard.
Reference may be made to EN ISO 9000 or to equivalent quality systems.
After the gas installation has been commissioned, a precisely defined programme of operation,
maintenance and condition monitoring should maintain the integrity of the pipework.
4.4 Protection against hazards
4.4.1 Electrical installation in hazardous area
When an area has been classified as hazardous (see EN 60079-10) subsequent electrical installations
shall comply wit
...