Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 12: Power metering and monitoring devices (PMD) (IEC 61557-12:2018/A1:2021)

This part of IEC 61557 specifies requirements for power metering and monitoring devices (PMD) that measure and monitor the electrical quantities within electrical distribution systems, and optionally other external signals. These requirements also defin the performance of PMD in single- and three-phace AC or DC systems having rated voltages up to 1000 V AC or up to 1500 V DC.
These devices are fixed or portable. They are intended to be used indoors and/or outdoors.
Power metering and monitoring devices  (PMD), as defined in this document, give additional safety information, which aids the verification of the installation and enhances the performance of the distribution systems.
Additionally, this document specifies requirements for measurement functions dedicated to metering and monitoring of electrical parameters called power metering and monitoring function (PMF) which can be embedded in equipment (EMPF) that is not classified as PMD and for which the main function is not power metering and monitoring.
Requirements for power metering and monitoring function (PMF) and additional requirements for equipments embedding power metering and monitoring function (EPMF) are described in Annex H.
The power metering and monitoring devices (PMD) for electrical parameters described in this document are used for general industrial and commercial applications.
This document does not address functional safety and cyber security aspects.
This document is not applicable to:
- electricity metering equipment that complies with IEC 62053-21, IEC 62053-22, IEC 62053-23 and IEC 62053-24. Nevertheless, uncertainties defined in this document for active and reactive energy measurement are derived from those defined in IEC 62053 (all parts);
- the measurement and monitoring of electrical parameters defined in IEC 61557-2 to IEC 61557-9 and IEC 61557-13 or in IEC 62020;
- power quality instrument (PQI) according IEC 62586 (all parts);
- devices covered by IEC 60051 (all parts) (direct acting analogue electrical measuring instrument).
Note 1 Generally such types of devices are used in the following applications or for the following general needs:
- energy management inside the installation, such as facilitating the implementation of documents such as ISO 50001 and IEC 60364-8-1;
- monitoring and/or measurement of electrical parameters;
- measurement and/or monitoring of the quality of energy inside commercial/industrial installations.
Note 2 A measuring and monitoring device of electrical parameters usually consists of several functional modules. All or some of the functional modules are combined in one device. Examples of fuctnional modules are:
- measurement and monitoring of several electrical parameters simultaneously;
- energy measurement and/or monitoring, as well as sometimes compliance with aspects of building regulations;
- alarms functions;
- demand side quality (current and voltage harmonics, over/under voltages, voltage dips and swells, etc.).
Note 3 PMD are historically called power meter, power monitor, power monitor device, power energy monitoring device, power analyser, multifunction meter, measuring multifunction equipment, energe meters.
Note 4 Metering, measuring and monitoring applications are explained in Annex A.

Elektrische Sicherheit in Niederspannungsnetzen bis AC 1 000 V und DC 1 500 V - Geräte zum Prüfen, Messen oder Überwachen von Schutzmaßnahmen - Teil 12: Geräte zur Energiemessung und -überwachung (PMD) (IEC 61557-12:2018/A1:2021)

Sécurité électrique dans les réseaux de distribution basse tension jusqu'à 1 000 V c.a. et 1 500 V c.c. - Dispositifs de contrôle, de mesure ou de surveillance de mesures de protection - Partie 12: Dispositifs de comptage et de surveillance du réseau électrique (PMD) (IEC 61557-12:2018/A1:2021)

Le contenu du corrigendum 1 (2022-09) a été pris en considération dans cet exemplaire.

Električna varnost v nizkonapetostnih razdelilnih sistemih za izmenične napetosti do 1 kV in enosmerne napetosti do 1,5 kV - Oprema za preskušanje, merjenje ali nadzorovanje zaščitnih ukrepov - 12. del: Naprave za merjenje in nadzorovanje moči (PMD) - Dopolnilo A1 (IEC 61557-12:2018/A1:2021)

Ta del standarda IEC 61557 določa zahteve za naprave za merjenje in nadzorovanje moči (PMD), ki se uporabljajo za merjenje in nadzorovanje električnih veličin v električnih razdelilnih sistemih, ter izbirno za druge zunanje signale. Te zahteve določajo tudi zmogljivost eno- in trifaznih izmeničnih ali enosmernih sistemov z nazivno napetostjo do 1000 V izmenične napetosti oziroma do 1500 V enosmerne napetosti.
Te naprave so fiksne ali prenosne. Namenjene so notranji in/ali zunanji uporabi. Naprave za merjenje in nadzorovanje moči, kot so opredeljene v tem dokumentu, zagotavljajo dodatne varnostne informacije, ki so v pomoč pri preverjanju inštalacije in izboljšajo zmogljivost razdelilnih sistemov.
Naprave za merjenje in nadzorovanje moči za električne parametre, opisane v tem dokumentu, se uporabljajo za splošne industrijske in komercialne namene.
Ta dokument ne obravnava vidikov funkcijske in kibernetske varnosti.
Ta dokument se ne uporablja za:
– opremo za merjenje električne energije, ki je skladna s standardi IEC 62053-21, IEC 62053-22, IEC 62053-23 in IEC 62053-24. Kljub temu negotovosti, opredeljene v tem dokumentu za merjenje aktivne in jalove energije, izhajajo iz tistih, ki so opredeljene v standardu IEC 62053 (vsi deli);
– merjenje in nadzorovanje električnih parametrov, opredeljenih v standardih od IEC 61557-2 do IEC 61557-9 in IEC 61557-13 ali v standardu IEC 62020;
– instrument za kakovost napajanja (PQI) v skladu s standardom IEC 62586 (vsi deli);
– naprave, zajete v standardu IEC 60051 (vsi deli) (neposredni analogni električni merilni instrument).
OPOMBA 1: Takšne vrste naprav se na splošno uporabljajo za naslednje vrste uporabe ali za naslednje splošne potrebe:
– upravljanje energije znotraj inštalacije, npr. lažje izvajanje dokumentov, kot sta standarda ISO 50001 in IEC 60364-8-1;
– nadzorovanje in/ali merjenje električnih parametrov;
– merjenje in/ali nadzorovanje kakovosti energije znotraj komercialnih/industrijskih inštalacij.
OPOMBA 2: Naprava za merjenje in nadzorovanje električnih parametrov je običajno sestavljena iz več funkcijskih modulov. V eni napravi so združeni vsi ali samo nekateri funkcijski moduli. Primeri funkcijskih modulov:
– sočasno merjenje in nadzorovanje različnih električnih parametrov;
– merjenje in/ali nadzorovanje energije ter včasih tudi skladnost z vidiki gradbenih predpisov;
– funkcije alarma;
– kakovost na strani povpraševanja (tokovna in napetostna skladnost, previsoka/prenizka napetost, napetostni upadi in udari itd.).
OPOMBA 3: Naprave za merjenje in nadzorovanje moči se zgodovinsko imenujejo merilnik moči, električni monitor, električna nadzorna naprava, analizator moči, večfunkcijski merilnik, večfunkcijska oprema za merjenje, števec energije.
OPOMBA 4: Aplikacije v zvezi s števci ter aplikacije merjenja in nadzorovanja so pojasnjene v dodatku A.

General Information

Status
Published
Public Enquiry End Date
15-Nov-2020
Publication Date
01-Feb-2022
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
13-Jan-2022
Due Date
20-Mar-2022
Completion Date
02-Feb-2022

Relations

Overview

EN IEC 61557-12:2022/A1:2022 specifies requirements for power metering and monitoring devices (PMD) used in low-voltage distribution systems (rated up to 1 000 V AC and 1 500 V DC). It covers fixed and portable PMD for single- and three-phase AC or DC systems, intended for indoor and/or outdoor use. The standard defines performance, measurement functions and testing requirements for PMD, and introduces requirements for embedded measurement functions - the power metering and monitoring function (PMF) - when integrated within equipment whose primary function is not metering (referred to as EPMF). EN IEC 61557-12 focuses on delivering safety-related information to support installation verification and improve distribution-system performance; it does not address functional safety or cybersecurity.

Key topics and technical requirements

  • Scope and applicability: PMD and PMF for general industrial and commercial applications; single- and three-phase AC/DC systems up to specified voltages.
  • Performance and measurement: Requirements for electrical quantities and measurement uncertainty (active/reactive energy uncertainties are derived from IEC 62053 series).
  • Device types: Fixed or portable PMD, and embedded PMF within other equipment (EPMF).
  • Environmental and installation: Indoor/outdoor suitability and association with sensing devices such as instrument transformers (IEC 61869 series) or transducers (IEC 60688).
  • Annex H: Normative requirements and tests specific to PMF and additional requirements for EPMF.
  • Exclusions: Not applicable to electricity meters complying with IEC 62053-21/22/23/24, power quality instruments per IEC 62586, direct analogue instruments covered by IEC 60051, or measurement functions already covered in IEC 61557-2 to -9 and -13 or IEC 62020.

Applications and users

  • Who uses it: Meter and PMD manufacturers, electrical equipment designers, switchgear/inverter vendors embedding PMF, testing laboratories, electrical installers, facility managers, energy managers, and compliance officers.
  • Typical applications: Energy management and monitoring (supports ISO 50001 implementation), verification of electrical installations, building and industrial energy metering, power-quality monitoring, alarms and demand-side management.
  • Practical value: Ensures consistent measurement performance, supports regulatory compliance and energy optimization programs, and standardizes testing for both standalone PMD and embedded metering functions.

Related standards

  • IEC 62053 (electricity metering) - uncertainties and energy measurement background
  • IEC 61869 (instrument transformers) and IEC 60688 (transducers) - sensing interfaces
  • IEC 62586 (power quality instruments), IEC 60051 (analogue instruments) - excluded device classes
  • Annex H references: IEC 60255, IEC 60755, IEC 60947 series, IEC 61000-4-x (EMC), IEC 62040, IEC 62109-2, IEC 62310, etc.

Keywords: EN IEC 61557-12:2022/A1:2022, power metering and monitoring devices, PMD, PMF, EPMF, low voltage distribution, 1 000 V AC, 1 500 V DC, energy management, IEC 62053.

Amendment
SIST EN IEC 61557-12:2022/A1:2022
English language
26 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-marec-2022
Električna varnost v nizkonapetostnih razdelilnih sistemih za izmenične napetosti
do 1 kV in enosmerne napetosti do 1,5 kV - Oprema za preskušanje, merjenje ali
nadzorovanje zaščitnih ukrepov - 12. del: Naprave za merjenje in nadzorovanje
moči (PMD) - Dopolnilo A1 (IEC 61557-12:2018/A1:2021)
Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC -
Equipment for testing, measuring or monitoring of protective measures - Part 12: Power
metering and monitoring devices (PMD) (IEC 61557-12:2018/A1:2021)
Elektrische Sicherheit in Niederspannungsnetzen bis AC 1 000 V und DC 1 500 V -
Geräte zum Prüfen, Messen oder Überwachen von Schutzmaßnahmen - Teil 12: Geräte
zur Energiemessung und -überwachung (PMD) (IEC 61557-12:2018/A1:2021)
Sécurité électrique dans les réseaux de distribution basse tension jusqu'à 1 000 V c.a. et
1 500 V c.c. - Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection - Partie 12: Dispositifs de comptage et de surveillance du réseau électrique
(PMD) (IEC 61557-12:2018/A1:2021)
Ta slovenski standard je istoveten z: EN IEC 61557-12:2022/A1:2022
ICS:
17.220.20 Merjenje električnih in Measurement of electrical
magnetnih veličin and magnetic quantities
29.080.01 Električna izolacija na Electrical insulation in
splošno general
29.240.01 Omrežja za prenos in Power transmission and
distribucijo električne energije distribution networks in
na splošno general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61557-12:2022/A1

NORME EUROPÉENNE
EUROPÄISCHE NORM January 2022
ICS 17.220.20; 29.080.01; 29.240.01

English Version
Electrical safety in low voltage distribution systems up to 1 000 V
AC and 1 500 V DC - Equipment for testing, measuring or
monitoring of protective measures - Part 12: Power metering and
monitoring devices (PMD)
(IEC 61557-12:2018/A1:2021)
Sécurité électrique dans les réseaux de distribution basse Elektrische Sicherheit in Niederspannungsnetzen bis AC 1
tension jusqu'à 1 000 V c.a. et 1 500 V c.c. - Dispositifs de 000 V und DC 1 500 V - Geräte zum Prüfen, Messen oder
contrôle, de mesure ou de surveillance de mesures de Überwachen von Schutzmaßnahmen - Teil 12: Geräte zur
protection - Partie 12: Dispositifs de comptage et de Energiemessung und -überwachung (PMD)
surveillance du réseau électrique (PMD) (IEC 61557-12:2018/A1:2021)
(IEC 61557-12:2018/A1:2021)
This amendment A1 modifies the European Standard EN IEC 61557-12:2022; it was approved by CENELEC on 2021-06-25. CENELEC
members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this amendment the
status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as
the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61557-12:2022/A1:2022 E

European foreword
The text of document 85/755/FDIS, future IEC 61557-12/A1, prepared by IEC/TC 85 "Measuring
equipment for electrical and electromagnetic quantities" was submitted to the IEC-CENELEC parallel
vote and approved by CENELEC as EN IEC 61557-12:2022/A1:2022.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022-07-07
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2026-11-10
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a Standardization Request given to CENELEC by the
European Commission and the European Free Trade Association.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 61557-12:2018/A1:2021 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 60688 NOTE Harmonized as EN 60688
IEC 61869 (series) NOTE Harmonized as EN IEC 61869 (series)

IEC 61557-12 ®
Edition 2.0 2021-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
A MENDMENT 1
AM ENDEMENT 1
Electrical safety in low voltage distribution systems up to 1 000 V AC and

1 500 V DC – Equipment for testing, measuring or monitoring of protective

measures –
Part 12: Power metering and monitoring devices (PMD)

Sécurité électrique dans les réseaux de distribution basse tension jusqu’à

1 000 V en courant alternatif et 1 500 V en courant continu – Dispositifs de

contrôle, de mesure ou de surveillance de mesures de protection –

Partie 12: Dispositifs de comptage et de surveillance du réseau électrique (PMD)

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 17.220.20; 29.080.01; 29.240.01 ISBN 978-2-8322-9662-2

– 2 – IEC 61557-12:2018/AMD1:2021
© IEC 2021
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTRICAL SAFETY IN LOW VOLTAGE DISTRIBUTION
SYSTEMS UP TO 1 000 V AC AND 1 500 V DC –
EQUIPMENT FOR TESTING, MEASURING OR
MONITORING OF PROTECTIVE MEASURES –

Part 12: Power metering and monitoring devices (PMD)

AMENDMENT 1
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
Amendment 1 to IEC 61557-12:2018 has been prepared by IEC technical committee 85:
Measuring equipment for electrical and electromagnetic quantities.
The text of this amendment is based on the following documents:
FDIS Report on voting
85/755/FDIS 85/764/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
IEC 61557-12:2018/AMD1:2021 – 3 –
© IEC 2021
The language used for the development of this Amendment is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/standardsdev/publications/.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
___________
1 Scope
Replace the existing text of this clause by the following new text:
This part of IEC 61557 specifies requirements for power metering and monitoring devices (PMD)
that measure and monitor the electrical quantities within electrical distribution systems, and
optionally other external signals. These requirements also define the performance of PMD in
single- and three-phase AC or DC systems having rated voltages up to 1 000 V AC or up to
1 500 V DC.
These devices are fixed or portable. They are intended to be used indoors and/or outdoors.
Power metering and monitoring devices (PMD), as defined in this document, give additional
safety information, which aids the verification of the installation and enhances the performance
of the distribution systems.
Additionally, this document specifies requirements for measurement functions dedicated to
metering and monitoring of electrical parameters called power metering and monitoring function
(PMF) which can be embedded in equipment (EPMF) that is not classified as PMD and for which
the main function is not power metering and monitoring.
Requirements for power metering and monitoring function (PMF) and additional requirements
for equipment embedding power metering and monitoring function (EPMF) are described in
Annex H.
The power metering and monitoring devices (PMD) for electrical parameters described in this
document are used for general industrial and commercial applications.
The power metering and monitoring devices (PMD) can be associated with sensing devices
such as but not limited to instruments transformers compliant to IEC 61869 series of standards
or with transducers compliant to IEC 60688.
This document does not address functional safety and cyber security aspects.

– 4 – IEC 61557-12:2018/AMD1:2021
© IEC 2021
This document is not applicable to:
– electricity metering equipment that complies with IEC 62053-21, IEC 62053-22, IEC 62053-
23 and IEC 62053-24. Nevertheless, uncertainties defined in this document for active and
reactive energy measurement are derived from those defined in IEC 62053 (all parts);
– the measurement and monitoring of electrical parameters defined in IEC 61557-2 to
IEC 61557-9 and IEC 61557-13 or in IEC 62020;
– power quality instrument (PQI) according IEC 62586 (all parts);
– devices covered by IEC 60051 (all parts) (direct acting analogue electrical measuring
instrument).
NOTE 1 Generally such types of devices are used in the following applications or for the following general needs:
– energy management inside the installation, such as facilitating the implementation of documents such as
ISO 50001 and IEC 60364-8-1;
– monitoring and/or measurement of electrical parameters;
– measurement and/or monitoring of the quality of energy inside commercial/industrial installations.
NOTE 2 A measuring and monitoring device of electrical parameters usually consists of several functional modules.
All or some of the functional modules are combined in one device. Examples of functional modules are:
– measurement and monitoring of several electrical parameters simultaneously;
– energy measurement and/or monitoring, as well as sometimes compliance with aspects of building regulations;
– alarms functions;
– demand side quality (current and voltage harmonics, over/under voltages, voltage dips and swells, etc.).
NOTE 3 PMD are historically called power meter, power monitor, power monitor device, power energy monitoring
device, power analyser, multifunction meter, measuring multifunction equipment, energy meters.
NOTE 4 Metering, measuring and monitoring applications are explained in Annex A.
3 Terms, definitions and notations
Add the following new definitions:
3.1.16
power metering and monitoring function
PMF
measurement function dedicated to metering and monitoring electrical parameters within
electrical distribution systems embedded in an equipment that is not a PMD and complies to
another IEC product standard
3.1.17
equipment embedding PMF
EPMF
equipment or arrangement of equipment embedding PMF whose main function is not metering
and monitoring of electrical parameters
Note 1 to entry: Such equipment are uninterruptible power systems (UPS), static transfer systems (STS), circuit
breakers, transfer switching equipment (TSE), switches, disconnectors, switch-disconnectors, fuse-combination
units, programmable controllers (PLC), inverter for use in photovoltaic power systems, adjustable speed electrical
power drive systems, protection relay, residual current devices (RCDs, RCBOs), residual current monitoring devices
(RCM), load-shedding equipment (LSE), bi-directional grid connected power converters.

IEC 61557-12:2018/AMD1:2021 – 5 –
© IEC 2021
Add the following new Annex H:
Annex H
(normative)
Requirements for power metering and monitoring function (PMF)
and additional requirements for equipment embedding power
metering and monitoring function (EPMF)
H.1 Scope
This annex specifies additional requirements and tests for equipment embedding a power
metering and monitoring function (EPMF) whose main function is not measurement and its
embedded power metering and monitoring function (PMF).
When not otherwise stated in this annex, the core of this document is applied to EPMF or PMF
as appropriate when reading “PMD” in the core document.
NOTE The annex follows the same structure as the core document.
H.2 Normative references
Clause 2 applies.
In addition, the following standards apply:
IEC 60255 (all parts), Measuring relays and protection equipment
IEC 60755, General safety requirements for residual current operated protective devices
IEC 60898 (all parts), Electrical accessories – Circuit-breakers for overcurrent protection for
household and similar installations
IEC 60947-2, Low-voltage switchgear and controlgear – Part 2: Circuit-breakers
IEC 60947-3, Low-voltage switchgear and controlgear – Part 3: Switches, disconnectors,
switch-disconnectors and fuse-combination units
IEC 60947-6-1, Low-voltage switchgear and controlgear – Part 6-1: Multiple function equipment
– Transfer switching equipment
IEC 61000-4-8, Electromagnetic compatibility (EMC) – Part 4-8: Testing and measurement
techniques – Power frequency magnetic field immunity test
IEC 61000-4-19, Electromagnetic compatibility (EMC) – Part 4-19: Testing and measurement
techniques – Test for immunity to conducted, differential mode disturbances and signalling in
the frequency range 2 kHz to 150 kHz at a.c. power ports
IEC 61008 (all parts), Residual current operated circuit-breakers without integral overcurrent
protection for household and similar uses (RCCBs)
IEC 61009 (all parts), Residual current operated circuit-breakers with integral overcurrent
protection for household and similar uses (RCBOs)
IEC 61131 (all parts), Programmable controllers

– 6 – IEC 61557-12:2018/AMD1:2021
© IEC 2021
IEC 61800 (all parts), Adjustable speed electrical power drive systems
IEC 62020 (all parts), Electrical accessories – Residual current monitors (RCMs)
IEC 62040 (all parts), Uninterruptible power systems (UPS)
IEC 62109-2, Safety of power converters for use in photovoltaic power systems – Part 2:
Particular requirements for inverters
IEC 62310 (all parts), Static transfer systems (STS)
IEC 62423, Type F and type B residual current operated circuit-breakers with and without
integral overcurrent protection for household and similar uses
IEC 62909 (all parts), Bi-directional grid connected power converters
IEC 62962, Particular requirements for load-shedding equipment (LSE)
H.3 Terms, definitions and notations
Clause 3 applies.
H.4 Requirements for PMF and additional requirements for EPMF
H.4.1 General requirements
The equipment that may embed EPMF shall be chosen in the equipment list defined in Table H.1.
Table H.1 – List of equipment that may embed EPMF
Equipment IEC Standard
Uninterruptible power systems (UPS) IEC 62040 series
Static transfer systems (STS) IEC 62310 series
Circuit-breakers IEC 60947-2, IEC 60898 series
Transfer switching equipment (TSE) IEC 60947-6-1
Switches, disconnectors, switch-disconnectors and IEC 60947-3
fuse-combination units
Programmable controllers (PLC) IEC 61131 series
Inverter for use in photovoltaic power systems IEC 62109-2
Adjustable speed electrical power drive systems IEC 61800
Protection relay IEC 60255
Residual current devices (RCD, RCBO) IEC 61008 series, IEC 61009 series, IEC 62423,
IEC 60947-2, IEC 60755 series
Residual current monitoring devices (RCM) IEC 62020 series
Load-shedding equipment (LSE) IEC 62962
Bi-directional grid connected power converters IEC 62909 series

The requirements of 4.2 to 4.12 apply with the modifications specified in this annex.
H.4.2 EPMF general architecture
This subclause provides information about a possible implementation of a PMF in an EPMF.

IEC 61557-12:2018/AMD1:2021 – 7 –
© IEC 2021
Figure H.1 shows the common organization of an EPMF including its main function and PMF.
Organization of the measurement chain of EPMF: the electrical quantity can be measured either
directly or via voltage and/or current sensors (see also H.4.4).

NOTE 1 It is not necessary that the parts in the dotted lines be included in PMF.
NOTE 2 I/O are analog and/or digital signals with alarms.
NOTE 3 Communications may be ensured by the EPMF or by the PMF part.
Figure H.1 – Example of architecture of EPMF
H.4.3 Classification of PMF
4.3 applies to PMF classified according to Table H.2.
Table H.2 – Functional classification of PMF with minimal required functions
b
PMF type
Functionalities
PMF-I PMF-II PMF-III
a
symbol
Energy efficiency Basic power Advanced power monitoring
monitoring /network performance
 
P
Q  
S  
E
  
a
E
 
r
E

ap
f  
I  
I

N
U and/or V  
– 8 – IEC 61557-12:2018/AMD1:2021
© IEC 2021
b
PMF type
Functionalities
PMF-I PMF-II PMF-III
a
symbol
Energy efficiency Basic power Advanced power monitoring
monitoring /network performance
PF  
THD and/or THD
u v
and/or THD-R and/or

u
THD-R
v
THD and/or THD-R

i i
a
Only total quantities are mandatory.
b
For PMF other than PMF-I, PMF-II and PMF-III, called PMF-x, other combinations of functions are allowed and
shall be specified by the manufacturer.

H.4.4 Structure of EPMF
4.4 applies to EPMF with the following modification.
Depending on the EPMF, the electrical quantity can be measured either directly or via voltage
and/or current sensors as shown in Table H.3.
Table H.3 – Structure of EPMF
Current measurement
Sensor operated EPMF Direct connected EPMF
(current sensors out of EPMF) (current sensors in EPMF)
EPMF Sx EPMF Dx
Direct connected EPMF EPMF SD EPMF DD
(voltage sensors in EPMF)
(Semi-direct insertion) (Direct insertion)
EPMF xD
Sensor operated EPMF EPMF SS EPMF DS
(voltage sensors out of EPMF)
(Indirect insertion) (Semi-direct insertion)
EPMF xS
H.4.5 List of applicable performance classes for PMF
4.5 applies.
H.4.6 Operating and reference conditions
H.4.6.1 Reference conditions
4.6.1 applies for performance class tests of the PMF. For other tests, reference test conditions
of the EPMF standard apply.
H.4.6.2 Rated operating conditions
If rated operating conditions are not defined by the standard of the equipment where PMF is
embedded, 4.6.2 applies.
NOTE Rated operating conditions may be also called environmental conditions (or similar wording) in other
standards.
Voltage
measurement
IEC 61557-12:2018/AMD1:2021 – 9 –
© IEC 2021
H.4.7 Start-up conditions for EPMF
4.7 applies.
H.4.8 Requirements for PMF
All PMF embedded in an EPMF and covered by this document shall comply with the
requirements of this document given in 4.8 with the following modifications or additions.
Subclause 4.8 describes a list of functions. Depending on the purpose of the measurement, all
or a subset of the functions listed shall be measured by the PMF.
The starting current and the specified measuring range of current shall be chosen according to
the structure of EPMF given in Table H.3 and Table H.4.
Table H.4 – Value of current according to the type of EPMF
Structure of EPMF Starting current and specified measuring range of current identical to
EPMF Dx PMD Dx
EPMF Sx PMD Sx
In reference conditions, signals are sinusoidal, so in this case the power factor = cos ϕ, see Table 11.

For EMC influence quantities:
– If EMC requirements are covered by the standard of the equipment where PMF is
embedded, EMC levels and test conditions defined in the EPMF standard apply;
– If EMC requirements are not covered by the standard of the equipment where PMF is
embedded, 4.8 applies.
For temperature influence quantities, the influence range is based on the rated operating range
according to H.4.6.2.
H.4.9 General mechanical requirements
If mechanical requirements are not defined by the standard of the equipment where PMF is
embedded, 4.9 applies.
H.4.10 Safety requirements
An equipment safety standard required by the EPMF type shall apply. If safety requirements
are not defined by the product standard of equipment where PMF is embedded, 4.10 applies.
In addition, a risk assessment of the PMF shall be done. In case of doubt, IEC 61010-2-30 or
any relevant safety standard shall apply.
H.4.11 EMC requirements
If EMC requirements are not defined by the standard of the equipment where PMF is embedded,
4.11 applies.
H.4.12 Inputs and/or outputs
If inputs and/or outputs requirements are not defined by the standard of the equipment where
PMF is embedded, 4.12 applies.

– 10 – IEC 61557-12:2018/AMD1:2021
© IEC 2021
H.5 Marking and operating instructions
H.5.1 General
If marking and operating instructions requirements are not covered by the standard of the
equipment where PMF is embedded, 5.1 applies.
H.5.2 Marking
At minimum if relevant, symbol 14 according to IEC 61010-1 shall be marked on the EPMF.
H.5.3 Operating, installation and maintenance instructions
H.5.3.1 General
If operating, installation and maintenance instructions requirements are not covered by the
standard of the equipment where PMF is embedded, 5.3.1 applies.
In addition, the following requirements apply:
H.5.3.2 General characteristics
5.3.2 applies.
H.5.3.3 Essential characteristics
H.5.3.3.1 Characteristics of EPMF
The characteristics of the EPMF shall be specified in a table as specified in Table H.5 with the
following items:
a) power quality assessment function (if any);
b) classification of the PMF and the EPMF according to H.4.3 and H.4.4;
c) temperature of the EPMF according to H.4.6.2;
d) humidity and altitude conditions of the EPMF according to H.4.6.2;
e) active power or active energy function (if existing) performance class acc
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

Frequently Asked Questions

SIST EN IEC 61557-12:2022/A1:2022 is a amendment published by the Slovenian Institute for Standardization (SIST). Its full title is "Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 12: Power metering and monitoring devices (PMD) (IEC 61557-12:2018/A1:2021)". This standard covers: This part of IEC 61557 specifies requirements for power metering and monitoring devices (PMD) that measure and monitor the electrical quantities within electrical distribution systems, and optionally other external signals. These requirements also defin the performance of PMD in single- and three-phace AC or DC systems having rated voltages up to 1000 V AC or up to 1500 V DC. These devices are fixed or portable. They are intended to be used indoors and/or outdoors. Power metering and monitoring devices (PMD), as defined in this document, give additional safety information, which aids the verification of the installation and enhances the performance of the distribution systems. Additionally, this document specifies requirements for measurement functions dedicated to metering and monitoring of electrical parameters called power metering and monitoring function (PMF) which can be embedded in equipment (EMPF) that is not classified as PMD and for which the main function is not power metering and monitoring. Requirements for power metering and monitoring function (PMF) and additional requirements for equipments embedding power metering and monitoring function (EPMF) are described in Annex H. The power metering and monitoring devices (PMD) for electrical parameters described in this document are used for general industrial and commercial applications. This document does not address functional safety and cyber security aspects. This document is not applicable to: - electricity metering equipment that complies with IEC 62053-21, IEC 62053-22, IEC 62053-23 and IEC 62053-24. Nevertheless, uncertainties defined in this document for active and reactive energy measurement are derived from those defined in IEC 62053 (all parts); - the measurement and monitoring of electrical parameters defined in IEC 61557-2 to IEC 61557-9 and IEC 61557-13 or in IEC 62020; - power quality instrument (PQI) according IEC 62586 (all parts); - devices covered by IEC 60051 (all parts) (direct acting analogue electrical measuring instrument). Note 1 Generally such types of devices are used in the following applications or for the following general needs: - energy management inside the installation, such as facilitating the implementation of documents such as ISO 50001 and IEC 60364-8-1; - monitoring and/or measurement of electrical parameters; - measurement and/or monitoring of the quality of energy inside commercial/industrial installations. Note 2 A measuring and monitoring device of electrical parameters usually consists of several functional modules. All or some of the functional modules are combined in one device. Examples of fuctnional modules are: - measurement and monitoring of several electrical parameters simultaneously; - energy measurement and/or monitoring, as well as sometimes compliance with aspects of building regulations; - alarms functions; - demand side quality (current and voltage harmonics, over/under voltages, voltage dips and swells, etc.). Note 3 PMD are historically called power meter, power monitor, power monitor device, power energy monitoring device, power analyser, multifunction meter, measuring multifunction equipment, energe meters. Note 4 Metering, measuring and monitoring applications are explained in Annex A.

This part of IEC 61557 specifies requirements for power metering and monitoring devices (PMD) that measure and monitor the electrical quantities within electrical distribution systems, and optionally other external signals. These requirements also defin the performance of PMD in single- and three-phace AC or DC systems having rated voltages up to 1000 V AC or up to 1500 V DC. These devices are fixed or portable. They are intended to be used indoors and/or outdoors. Power metering and monitoring devices (PMD), as defined in this document, give additional safety information, which aids the verification of the installation and enhances the performance of the distribution systems. Additionally, this document specifies requirements for measurement functions dedicated to metering and monitoring of electrical parameters called power metering and monitoring function (PMF) which can be embedded in equipment (EMPF) that is not classified as PMD and for which the main function is not power metering and monitoring. Requirements for power metering and monitoring function (PMF) and additional requirements for equipments embedding power metering and monitoring function (EPMF) are described in Annex H. The power metering and monitoring devices (PMD) for electrical parameters described in this document are used for general industrial and commercial applications. This document does not address functional safety and cyber security aspects. This document is not applicable to: - electricity metering equipment that complies with IEC 62053-21, IEC 62053-22, IEC 62053-23 and IEC 62053-24. Nevertheless, uncertainties defined in this document for active and reactive energy measurement are derived from those defined in IEC 62053 (all parts); - the measurement and monitoring of electrical parameters defined in IEC 61557-2 to IEC 61557-9 and IEC 61557-13 or in IEC 62020; - power quality instrument (PQI) according IEC 62586 (all parts); - devices covered by IEC 60051 (all parts) (direct acting analogue electrical measuring instrument). Note 1 Generally such types of devices are used in the following applications or for the following general needs: - energy management inside the installation, such as facilitating the implementation of documents such as ISO 50001 and IEC 60364-8-1; - monitoring and/or measurement of electrical parameters; - measurement and/or monitoring of the quality of energy inside commercial/industrial installations. Note 2 A measuring and monitoring device of electrical parameters usually consists of several functional modules. All or some of the functional modules are combined in one device. Examples of fuctnional modules are: - measurement and monitoring of several electrical parameters simultaneously; - energy measurement and/or monitoring, as well as sometimes compliance with aspects of building regulations; - alarms functions; - demand side quality (current and voltage harmonics, over/under voltages, voltage dips and swells, etc.). Note 3 PMD are historically called power meter, power monitor, power monitor device, power energy monitoring device, power analyser, multifunction meter, measuring multifunction equipment, energe meters. Note 4 Metering, measuring and monitoring applications are explained in Annex A.

SIST EN IEC 61557-12:2022/A1:2022 is classified under the following ICS (International Classification for Standards) categories: 17.220.20 - Measurement of electrical and magnetic quantities; 29.080.01 - Electrical insulation in general; 29.240.01 - Power transmission and distribution networks in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN IEC 61557-12:2022/A1:2022 has the following relationships with other standards: It is inter standard links to SIST EN IEC 61557-12:2022, SIST EN IEC 61557-12:2022/A1:2022/AC:2022. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN IEC 61557-12:2022/A1:2022 is associated with the following European legislation: EU Directives/Regulations: 2014/30/EU, 2014/35/EU; Standardization Mandates: M/511, M/552. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase SIST EN IEC 61557-12:2022/A1:2022 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

この記事は、"SIST EN IEC 61557-12:2022/A1:2022 - 電気安全 - 1,000 V ACおよび1,500 V DCまでの低圧配電システム - 保護措置のテスト、計測またはモニタリングのための機器 - パート12:電力計測およびモニタリングデバイス(PMD)(IEC 61557-12:2018/A1:2021)"について語っています。この記事では、電気配電システム内の電気量を計測およびモニタリングするPMD(電力計測およびモニタリングデバイス)に関する要件を定めています。これらの要件は、定格電圧1,000 V ACまたは1,500 V DCまでの単相および三相のACまたはDCシステムにおけるPMDの性能も定義しています。これらのデバイスは固定式または携帯式であり、屋内および/または屋外で使用されることを意図しています。このドキュメントで定義されたPMDは、設置の検証を支援し、配電システムのパフォーマンスを向上させるための追加の安全情報を提供します。さらに、この文書では、電力計測およびモニタリング機能(PMF)に特化した計測機能の要件も定めています。これはPMDと分類されず、主な機能が電力計測およびモニタリングではない機器(EMPF)に組み込まれる場合に適用されます。電力計測およびモニタリング機能(PMF)および電力計測およびモニタリング機能(EPMF)を組み込んだ機器に対する追加の要件は、付録Hに記載されています。本文書で説明されている電気パラメータの電力計測およびモニタリングデバイス(PMD)は、一般的な産業および商業用途に使用されます。この文書は機能的な安全性およびサイバーセキュリティの側面には触れていません。また、次のいくつかには適用されません。- IEC 62053-21、IEC 62053-22、IEC 62053-23、およびIEC 62053-24に準拠する電力計測機器。ただし、本文書で定義された有効および無効エネルギーの測定に対する不確実性は、IEC 62053の定義から派生しています。- IEC 61557-2からIEC 61557-9およびIEC 61557-13またはIEC 62020で定義された電気パラメータの計測およびモニタリング。- IEC 62586の電力品質計器(すべての部分)。- IEC 60051(すべての部分)によってカバーされるデバイス(直接動作アナログ電気測定器)。この記事では、電力計測およびモニタリングデバイスの応用と機能モジュールの例について詳細を提供しています。

The article discusses the SIST EN IEC 61557-12:2022/A1:2022 standard, which focuses on electrical safety in low voltage distribution systems. Specifically, it provides requirements for power metering and monitoring devices (PMD) that measure and monitor electrical quantities in AC or DC systems up to 1000 V AC or 1500 V DC. These devices can be fixed or portable and are used both indoors and outdoors. They enhance the safety and performance of distribution systems by providing additional safety information. The document also specifies requirements for power metering and monitoring functions (PMF) that can be embedded in equipment. The standard is applicable to general industrial and commercial applications but does not cover functional safety and cyber security aspects. It is not applicable to electricity metering equipment complying with other standards, as well as other measurement and monitoring devices and power quality instruments. The article provides further details on the applications and features of power metering and monitoring devices.

기사의 제목은 "SIST EN IEC 61557-12:2022/A1:2022 - 저압 배전 시스템에서의 전기 안전 1,000 V AC 및 1,500 V DC까지 - 보호 조치를 테스트, 측정 또는 모니터링하는 장비 - 파트 12: 전력 측정 및 모니터링 장치 (PMD) (IEC 61557-12:2018/A1:2021)"입니다. 이 기사는 저전압 배전 시스템에서 전력 측정 및 모니터링 장치에 대한 요구 사항을 명시합니다. 이 요구 사항은 전기 배전 시스템 내의 전기량 및 선택적으로 다른 외부 신호를 측정하고 모니터링하는 PMD의 성능도 정의합니다. 이러한 장치는 실내 및/또는 야외에서 사용되며, 설치 검증을 위해 부가적인 안전 정보를 제공하고 배전 시스템의 성능을 향상시킵니다. 또한, 이 문서는 PMD로 분류되지 않은 주요 기능이 전력 측정 및 모니터링이 아닌 장비 (EMPF)에 내장될 수 있는 전력 측정 및 모니터링 기능 (PMF)에 대한 요구 사항을 명시합니다. PMF 및 전력 측정 및 모니터링 기능을 내장한 장비 (EPMF)에 대한 추가 요구 사항은 부록 H에 설명되어 있습니다. 이 문서는 일반 산업 및 상업용 응용 프로그램에 사용되는 전기 매개 변수의 전력 측정 및 모니터링 장치 (PMD)를 다룹니다. 이 문서는 기능적 안전 및 사이버 보안 측면을 다루지 않습니다. 또한, 이 문서는 다음에 적용되지 않습니다. - IEC 62053-21, IEC 62053-22, IEC 62053-23 및 IEC 62053-24를 준수하는 전기 계량 장치. 그러나 활성 및 리액티브 에너지 측정을 위한이 문서에서 정의 된 불확실성은 IEC 62053의 정의에서 파생되었습니다. - IEC 61557-2에서 IEC 61557-9 및 IEC 61557-13 또는 IEC 62020에서 정의된 전기 매개 변수의 측정 및 모니터링. - IEC 62586 (모든 부분)에 따른 전력 품질 계기 (PQI). - IEC 60051 (모든 부분) (직접 작동하는 아날로그 전기 측정 기기)에 대한 장치. 이 문서는 전력 측정 및 모니터링 장치의 응용 및 기능 모듈에 대한 예시도 제공합니다.