Fire detection and fire alarm systems - Part 25: Components using radio links

This document specifies requirements, test methods and performance criteria for components used in fire alarms systems, installed in and around buildings, which use radio links to communicate. Where components work together and this requires knowledge of the system design, this document also specifies requirements on the system.
When the fire detection and fire alarm systems (FDAS) use wired and radio links, the relevant parts of EN 54 apply.

Brandmeldeanlagen - Teil 25: Bestandteile, die Hochfrequenz-Verbindungen nutzen

Dieses Dokument legt Anforderungen, Prüfverfahren und Leistungsmerkmale für Bestandteile von Brandmeldeanlagen, die Funkverbindungen nutzen und die in Brandmeldesystemen in und an Gebäuden verwendet werden.
Da das Zusammenwirken der Bestandteile Kenntnisse über das Brandmeldesystem erfordert, enthält dieses Dokument ebenfalls Systemanforderungen.
Werden in Brandmeldeanlagen (BMA) sowohl Leitungen als auch Funkverbindungen verwendet, gelten die entsprechenden Teile von EN 54.

Systèmes de détection et d'alarme incendie - Partie 25: Composants utilisant des liaisons radioélectriques

Le présent document définit les exigences, les méthodes d'essai et les criteres de performance pour les composants utilisés dans les systemes d'alarme incendie installés dans les bâtiments et autour de ceux-ci, qui utilisent des liaisons radioélectriques pour communiquer.
Lorsque les composants fonctionnent ensemble et que cela nécessite la connaissance de la conception du systeme, le présent document spécifie également les exigences relatives au systeme.
Lorsque les systemes de détection et d'alarme incendie (SDAI) emploient des liaisons radioélectriques et filaires, les parties concernées de la série EN 54 s'appliquent.

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 25. del: Sestavni deli za radijske povezave

Ta evropski standard določa zahteve, preskusne metode in merila za delovanje za sestavne dele, ki se uporabljajo v sistemih za javljanje požara ter alarmiranje, nameščene v in okoli stavb, ki uporabljajo radijsko frekvenčne povezave (RF povezave) za komunikacijo. Prav tako podaja zahteve za vrednotenje skladnosti sestavnih delov z zahtevami tega evropskega standarda. Kadar sestavni deli delujejo skupaj, kar zahteva poznavanje načrtovanja sistema, ta dokument prav tako določa zahteve za sistem. Kadar sistemi za odkrivanje in javljanje požara ter alarmiranje (FDAS) uporabljajo ožičene in RF povezave, veljajo ustrezni deli EN 54 skupaj z tem dokumentom. Zahteve, ki se nanašajo na ožičene povezave, so izpodrinjene ali spremenjene z tistimi, ki so vključene v ta evropski standard. Ta dokument ne omejuje: - predvidene uporabe radijskega spektra, npr. frekvence, izhodno moč naprav; - dovoljenega največje števila sestavnih delov, ki uporabljajo RF povezave v okviru FSAD ali ene prenosne potu in/ali RF povezave; - dovoljeno največje število sestavnih delov, na katere vpliva izguba ene poti prenosa in/ali RF povezave. Te zahteve se nanašajo na nacionalne predpise in se lahko razlikujejo med državami članicami.

General Information

Status
Published
Publication Date
27-May-2008
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
12-May-2008
Due Date
17-Jul-2008
Completion Date
28-May-2008

Relations

Buy Standard

Standard
EN 54-25:2008
English language
52 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 54-25:2008
01-julij-2008
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 25. del: Sestavni deli za
radijske povezave
Fire detection and fire alarm systems - Part 25: Components using radio links
Brandmeldeanlagen - Teil 25: Bestandteile, die Hochfrequenz-Verbindungen nutzen
Systèmes de détection et d'alarme incendie - Partie 25: Composants utilisant des
liaisons radioélectriques
Ta slovenski standard je istoveten z: EN 54-25:2008
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 54-25:2008 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 54-25:2008

---------------------- Page: 2 ----------------------

SIST EN 54-25:2008
EUROPEAN STANDARD
EN 54-25
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2008
ICS 13.220.20

English Version
Fire detection and fire alarm systems - Part 25: Components
using radio links
Systèmes de détection et d'alarme incendie - Partie 25: Brandmeldeanlagen - Teil 25: Bestandteile, die
Composants utilisant des liaisons radioélectriques Hochfrequenz-Verbindungen nutzen
This European Standard was approved by CEN on 20 January 2008.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-25:2008: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
Contents Page
Foreword .4
Introduction.6
1 Scope.7
2 Normative references.7
3 Terms, definitions and abbreviations .8
3.1 Terms and definitions .8
3.2 Abbreviations.10
4 System requirements.10
4.1 General .10
4.2 Radio frequency links .10
4.2.1 Immunity to site attenuation .10
4.2.2 Alarm signal integrity.11
4.2.3 Identification of the RF linked component .11
4.2.4 Receiver performance.11
4.2.5 Immunity to interference .12
4.2.6 Loss of communication .12
4.2.7 Antenna .13
5 Components requirements.13
5.1 Compliance .13
5.2 General .13
5.3 Power supply equipment.13
5.4 Environmental related requirements.14
5.4.1 General .14
5.4.2 General test procedure .14
5.4.3 Provision for testing .15
6 Documentation .15
7 Marking.16
8 Tests .16
8.1 General requirements .16
8.1.1 General .16
8.1.2 Standard atmospheric conditions for testing .16
8.1.3 Operating conditions for tests.16
8.1.4 Mounting and orientation .16
8.1.5 Tolerances.16
8.2 System tests .17
8.2.1 Test schedule for system tests.17
8.2.2 Test for immunity to site attenuation .17
8.2.3 Test for alarm signal integrity.18
8.2.4 Test for identification of RF linked components.18
8.2.5 Test for the receiver performance .18
8.2.6 Test for mutual disturbance between systems of the same manufacturer.19
8.2.7 Test of compatibility with other band users.20
8.2.8 Test for the detection of a loss of communication on a link .21
8.2.9 Test of the antenna .22
8.3 Components tests .22
8.3.1 General .22
8.3.2 Test schedule for components tests.22
2

---------------------- Page: 4 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
8.3.3 Verification of the service life of the autonomous power source(s) . 24
8.3.4 Test for the low power condition fault signal . 24
8.3.5 Test for the polarity reversal. 25
8.3.6 Repeatability test . 26
8.3.7 Reproducibility test. 26
8.3.8 Variation of supply parameters . 27
8.3.9 Dry heat (operational). 27
8.3.10 Dry heat (endurance) . 28
8.3.11 Cold (operational) . 28
8.3.12 Damp heat, cyclic (operational). 29
8.3.13 Damp heat, steady state (operational). 30
8.3.14 Damp heat, steady state (endurance) . 31
8.3.15 SO -corrosion (endurance) . 31
2
8.3.16 Shock (operational). 32
8.3.17 Impact (operational). 33
8.3.18 Vibration, sinusoidal (operational). 33
8.3.19 Vibration, sinusoidal (endurance) . 34
8.3.20 Electromagnetic Compatibility (EMC), Immunity tests (operational) . 35
Annex A (normative) Test configuration by using radio frequency shielded test equipment . 36
Annex B (normative) Immunity to site attenuation (path loss). 40
Annex C (informative) Data and calculation of the service life of the autonomous power source(s) . 41
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC). 43
Bibliography . 52

3

---------------------- Page: 5 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
Foreword
This document (EN 54-25:2008) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by September 2008, and conflicting national standards shall be
withdrawn at the latest by March 2011.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
EN 54 Fire detection and fire alarm systems consists of the following parts:
 Part 1: Introduction
 Part 2: Control and indicating equipment
 Part 3: Fire alarm devices – Sounders
 Part 4: Power supply equipment
 Part 5: Heat detectors – Point detectors
 Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionisation
 Part 10: Flame detectors – Point detectors
 Part 11: Manual call points
 Part 12: Smoke detectors – Line detectors using an optical light beam
 Part 13: Compatibility assessment of system components
 Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
 Part 15: Point detectors using a combination of detected fire phenomena
 Part 16: Voice alarm control and indicating equipment
 Part 17: Short-circuit isolators
 Part 18: Input/output devices
 Part 20: Aspirating smoke detectors
 Part 21: Alarm transmission and fault warning routing equipment
4

---------------------- Page: 6 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
 Part 22: Line-type heat detectors
 Part 23: Fire alarm devices – Visual alarms
 Part 24: Components of voice alarm systems – Loudspeakers
 Part 25: Components using radio links
1)
 Part 26: Point fire detectors using carbon monoxide sensors
1)
 Part 27: Duct smoke detectors
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

1) Under preparation.
5

---------------------- Page: 7 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
Introduction
The aim of this European Standard is to define additional requirements to other parts of EN 54 and tests that
allow radio fire detection systems and components complying with them to be at least efficient and stable as
wired fire detection systems and components complying with the current requirements of cable based systems
in the EN 54 standards.
System and component aspects are dealt with in this European Standard because it is difficult to describe the
components of a radio-linked system separately.
Capacity limitations with respect to the use of radio components may be specified in national technical rules or
guidelines.
Technical aspects of the assessment of frequencies, bands and channels should be considered.
6

---------------------- Page: 8 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
1 Scope
This European Standard specifies requirements, test methods and performance criteria for components used
in fire alarms systems, installed in and around buildings, which use radio frequency links (RF links) to
communicate. It also provides requirements for the evaluation of conformity of the components to the
requirements of this European Standard.
Where components work together and this requires knowledge of the system design, this document also
specifies requirements on the system.
When the fire detection and fire alarm systems (FDAS) use wired and RF links, the relevant parts of EN 54
apply together with this document. Requirements relevant to wire links are superseded or modified by those
included in this European Standard.
This document does not restrict:
 the intended use of radio spectrum, e.g. frequency, power output of devices;
 the allowed maximum number of the components using RF links within the FDAS or one transmission
path and/or RF link;
 the allowed maximum number of the components affected by loss of one transmission path and/or RF link.
These requirements relate to national regulations and can vary from member state to member state.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-2, Fire detection and fire alarm systems — Part 2: Control and indicating equipment
EN 54-4, Fire detection and fire alarm systems — Part 4: Power supply equipment
EN 54-5, Fire detection and fire alarm systems — Part 5: Heat detectors — Point detectors
EN 54-11, Fire detection and fire alarm systems — Part 11: Manual call points
EN 50130-4, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: Immunity
requirements for components of fire, intruder and social alarm systems
EN 60068-2-1, Environmental testing — Part 2-1: Tests — Tests A: Cold (IEC 60068-2-1:2007)
EN 60068-2-2, Basic environmental testing procedures — Part 2-2: Tests — Tests B: Dry heat
(IEC 60068-2-2:1974 + IEC 60068-2-2A:1976)
EN 60068-2-6, Environmental testing — Part 2-6: Tests — Tests Fc: Vibration (sinusoidal) (IEC 60068-2-
6:1995 + Corrigendum 1995)
EN 60068-2-27, Basic environmental testing procedures — Part 2: Tests — Test Ea and guidance: Shock
(IEC 60068-2-27:1987)
EN 60068-2-30, Environmental testing — Part 2-30: Tests — Test Db: Damp heat, cyclic (12 h + 12 h cycle)
(IEC 60068-2-30:2005)
7

---------------------- Page: 9 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
EN 60068-2-42, Environmental testing — Part 2-42: Test methods — Test Kc: Sulphur dioxide test for
contacts and connections (IEC 60068-2-42:2003)
EN 60068-2-78, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state
(IEC 60068-2-78:2001)
EN 300113-1 V 1.4.1:2002, Electromagnetic compatibility and Radio spectrum Matters (ERM) — Land mobile
service — Radio equipment intended for the transmission of data (and/or speech) using constant or non-
constant envelope modulation and having an antenna connector — Part 1: Technical characteristics and
methods of measurement
EN 300220-1 V 1.3.1:2000, Electromagnetic compatibility and Radio spectrum Matters (ERM) — Short range
devices — Radio equipment to be used in the 25 MHz to 1000 MHz frequency range with power levels
ranging up to 500 mW — Part 1: Technical characteristics and test methods
EN ISO 9001, Quality management systems — Requirements (ISO 9001:2000)
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in the relevant part of EN 54 and the
following apply.
3.1.1
antenna
element of a radio component of the fire detection and fire alarm system (FDAS) that allows coupling between
the component and the media where radio frequency (RF) waves are propagated
3.1.2
assigned band
frequency band within which the equipment is authorised to operate
3.1.3
site attenuation
degradation of the RF signal due to either path loss or a change in the environment of the FDAS after its
installation
NOTE Site attenuation can be changed by e.g. installation or relocation of reflection or absorption materials.
3.1.4
autonomous power source
independent power supply equipment (i.e. without any link with the public power supply or an equivalent
system) not rechargeable during operation and able by itself to allow the supplied component to run
NOTE An autonomous power source is e.g. a primary battery.
3.1.5
base station
transceiver in the system which communicates with a certain number of components
3.1.6
collision
simultaneous transmissions, from two or more transmitters belonging to the same system, of sufficient signal
strength to cause, by mutual interaction, corruption or obliteration of the information carried by the RF signals
8

---------------------- Page: 10 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
3.1.7
compatibility
capacity of a component of the system to operate with another component of this system, in the limits
specified by the manufacturer and by the applicable product standard if this standard exists and in specified
configurations of the system
3.1.8
fire detection and fire alarm system
FDAS
group of components including a CIE which, when arranged in (a) specified configuration(s), is capable of
detecting and indicating a fire, and giving signals for appropriate action
[EN 54-13:2005, definition 3.1.7]
3.1.9
identification code
part of a message used to identify a transmitting RF communication device belonging to the system
3.1.10
intermediate element
device connected to a transmission path of a fire detection and fire alarm system, used to receive and/or
transmit signals necessary for the operation of the fire detection and fire alarm system
NOTE An intermediate element meets the requirements of an input/output device in accordance with EN 54-18 but it
is not restricted to electrical signals.
3.1.11
manufacturer
natural or legal person, who places the product on the market under his own name
NOTE Normally, the manufacturer designs and manufactures the product himself. A manufacturer can also design,
manufacture, assemble, pack, process or label the product as subcontractor or he assembles, packs, processes, or labels
products as ready-made products.
3.1.12
radio frequency link
RF link
means of communication between at least two points, using RF wave propagation
NOTE The RF link is the equivalent to the transmission path as defined in other parts of EN 54.
3.1.13
radio part
component or part of the component incorporating the receiver and/or transmitter
NOTE The radio part can include a power supply, e.g. an autonomous power source.
3.1.14
receiver
device which receives the RF energy corresponding to a RF link
NOTE The receiver can be incorporated in a component of the FDAS.
3.1.15
RF interference
RF transmission from any other source other than any component of the FDAS that may cause corruption or
obliteration of wanted signals and not conforming to the definition of collision or message substitution
9

---------------------- Page: 11 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
3.1.16
service life
period of useful life of an autonomous power source under specified conditions
3.1.17
special tool
device not normally carried by the public (e.g. a key), normally provided by the manufacturer and which is
used for opening the enclosure of the component to detach the antenna
NOTE It is intended to deter unauthorised access to the antenna, while being available on site either at a defined
location or from a "responsible person" familiar with and having knowledge of the system.
3.1.18
transmitter
device which generates the RF energy necessary for a RF link
NOTE The transmitter can be incorporated in a component of the FDAS.
3.2 Abbreviations
For the purposes of this document, the following abbreviations apply.
CIE Control and indicating equipment
FDAS Fire detection and fire alarm systems
PSE Power supply equipment
RF Radio frequency
4 System requirements
4.1 General
The requirements of this document shall be applied, together with requirements of the relevant part of EN 54,
where the radio-linked component has the same function as the component covered by that part and when not
otherwise specified in this European Standard.
For example, an RF linked component having the function of a heat detector shall comply with
EN 54-5 and a component having the function of a manual call point shall comply with EN 54-11.
4.2 Radio frequency links
4.2.1 Immunity to site attenuation
The manufacturer shall provide means either in the component itself or by the system configuration to ensure
that a site attenuation, which may be caused by influences for different reasons on site, may not affect the RF
link adversely in a way that communication between components is not possible. This reserve of site
attenuation shall be specified as follows:
a) at least 10 dB up to frequencies of 10 MHz;
b) for frequencies of > 10 MHz as calculated in Annex B.
10

---------------------- Page: 12 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
The manufacturer shall provide the necessary documentation and/or means for the assessment which permits
the full functionality of the component to be assessed. If these means are a part of the component, the user
shall not be able to interfere with these means.
The test includes verification by an assessment and shall be carried out in accordance with 8.2.2.
4.2.2 Alarm signal integrity
The components of the system shall use a transmission protocol on the transmission path and/or the RF link
to ensure that no alarm message is lost.
The test shall be carried out in accordance with 8.2.3.
4.2.3 Identification of the RF linked component
4.2.3.1 Each RF linked component shall be identified by an individual identification code as belonging to
one specific FDAS.
4.2.3.2 The manufacturer shall provide means to ensure that a RF linked component shall not be
accepted by other FDAS.
The test shall be carried out in accordance with 8.2.4.
4.2.3.3 The manufacturer shall provide the necessary documentation and/or means for the assessment
of this requirement.
4.2.4 Receiver performance
The receiver shall meet the requirements given in Table 1.
Table 1 — Minimum receiver performance characteristics
Frequency offset from Notes
Characteristics Limit
the working frequency
Adjacent channel For all band widths and
≥ 35 dB

selectivity modulation schemes
≥ 40 dB ± 1 MHz
In direct sequence spread
≥ 45 dB ± 2 MHz
Blocking or spectrum systems (DSSS) the
working frequency is the centre
desensitization
≥ 60 dB ± 5 MHz
frequency
≥ 65 dB ± 10 MHz
Spurious response
≥ 40 dB  
rejection

The manufacturer of the receiver shall provide a test report by a test laboratory to demonstrate that the
requirements of this clause are fulfilled. If the manufacturer cannot provide this evidence, the tests described
in 8.2.5 shall be carried out. The manufacturer shall provide the means to carry out the test, e.g. stop
frequency hopping.
11

---------------------- Page: 13 ----------------------

SIST EN 54-25:2008
EN 54-25:2008(E)
4.2.5 Immunity to interference
4.2.5.1 General
The following kind of interferences on the RF link shall be covered:
a) radio influences from own system;
b) radio influences from other users of the spectrum.
The following influences are not covered:
c) random influences as a result of electromagnetic effects, because these are covered by EMC guidelines
(see EN 50130-4);
d) deliberate attacks on the radio controlled transmission paths with the help of electromagnetic effects
(sabotage via the radio controlled route), because no special sabotage resistance is required for fire
alarm systems in the parts of EN 54.
4.2.5.2 Availability of RF link in two or more technically similar systems coming from the same
manufacturer
In the case of two or more technically similar systems coming from the same manufacturer operating within
the radio range it shall be ensured that the RF links do not mutually impede one another.
The manufacturer shall specify the means. The means shall be suitable to ensure the availability of all parts of
the system in all expected system configurations.
The test shall be carried out in accordance with 8.2.6.
4.2.5.3 Availability of the RF link in the presence of other band users
The manufacturer shall take measures to ensure that signal transmission
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.