Fire detection and fire alarm systems - Part 31: Multi-sensor fire detectors - Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors

This European Standard specifies requirements, test methods and performance criteria for point-type multi-sensor fire detectors for use in fire detection and fire alarm systems installed in and around buildings (see EN 54 1:2011), incorporating in one mechanical enclosure at least one optical or ionization smoke sensor and at least one carbon monoxide (CO) sensor and optionally one or more heat sensors, utilizing the combination of the detected phenomena. This European Standard covers only modes of operation, where at least the signals of both smoke and carbon monoxide sensors are continuously evaluated.
This European Standard provides for the assessment and verification of constancy of performance (AVCP) of point detectors using a combination of smoke, carbon monoxide and optionally heat sensors to this EN.
Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors, which are having special characteristics suitable for the detection of specific fire risks are not covered by this European Standard. The performance requirements for any additional functions are beyond the scope of this standard (e.g. additional features or enhanced functionality for which this European Standard does not define a test or assessment method).

Brandmeldeanlagen - Teil 31: Mehrfachsensor-Brandmelder - Punktförmige Melder mit kombinierten Rauch-, CO- und optionalen Wärmesensoren

Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für punktförmige Mehrfachsensor-Brandmelder fest, die in Brandmelde- und Feueralarmanlagen in und um Gebäude eingesetzt werden (siehe EN 54 1:2011) und die in einem Gehäuse mindestens einen Rauchsensor nach dem Durchlicht- oder Ionisationsprinzip und mindestens einen Kohlenmonoxid- (CO-)Sensor sowie optional einen oder mehrere Wärmesensoren enthalten, welche die Kombination der erkannten Brandphänomene nutzen. Diese Norm gilt nur für Betriebsarten, bei denen mindestens die Signale von sowohl Rauch- als auch Kohlenmonoxidmeldern kontinuierlich bewertet werden.
Diese Europäische Norm enthält die Bewertung und Überprüfung der Leistungsbeständigkeit (AVCP) von punktförmigen Mehrfachsensor-Brandmeldern mit kombinierten Rauch- und CO-Sensoren und optionalen Wärmesensoren nach dieser EN.
Punktförmige Melder mit kombinierten Rauch- und CO-Sensoren und optionalen Wärmesensoren mit speziellen Merkmalen, geeignet für die Erkennung besonderer Brandrisiken, sind nicht Gegenstand dieser Norm. Die Leistungsanforderungen an alle zusätzlichen Funktionen fallen nicht in den Anwendungsbereich dieser Norm (z. B. werden in dieser Norm für zusätzliche Merkmale oder für eine verbesserte Funktionstüchtigkeit keine Prüf  oder Bewertungsverfahren festgelegt).

Systèmes de détection et d'alarme incendie - Partie 31: Détecteurs d'incendie multicapteurs - Détecteurs ponctuels combinant l'utilisation de capteurs de fumée, de capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur

La présente Norme européenne spécifie les exigences, les méthodes d’essai et les critères de performance applicables aux détecteurs d’incendie ponctuels multicapteurs destinés à être utilisés dans les systèmes de détection d’incendie et d'alarme incendie installés dans les bâtiments et aux alentours (voir EN 54 1:2011), incorporant dans une seule enveloppe mécanique au moins un capteur de fumée optique ou à ionisation et au moins un capteur de monoxyde de carbone (CO) et éventuellement un ou plusieurs capteurs de chaleur, en utilisant la combinaison des phénomènes détectés. La présente Norme européenne traite uniquement des modes de fonctionnement, dans lesquels au moins les signaux des capteurs de fumée et des capteurs de monoxyde de carbone sont évalués en continu.
La présente Norme européenne prévoit l'évaluation et la vérification de la constance des performances (EVCP) des détecteurs ponctuels combinant l’utilisation de capteurs de fumée, de capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur de la présente Norme européenne.
Les détecteurs ponctuels combinant l’utilisation de capteurs de fumée, de capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur possédant des caractéristiques particulières adaptées à la détection de risques d’incendie spécifiques ne sont pas pris en compte dans la présente Norme européenne. Les exigences de performance relatives à toute autre fonction ne relèvent pas du domaine d’application de la présente norme (par exemple, des caractéristiques supplémentaires ou une fonctionnalité améliorée pour lesquelles la présente Norme européenne ne définit pas d’essai ou de méthode d’évaluation).

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 31. del: Večsenzorski javljalniki  požara - Kombinirani točkovni javljalniki požara s senzorji za zaznavanje dima, ogljikovega monoksida in izbrane toplote

Ta evropski standard določa zahteve, preskusne metode in merila učinkovitosti za točkovne večsenzorske javljalnike požara za uporabo v sistemih za odkrivanje in javljanje požara ter sistemih požarnega alarma, nameščenih v stavbah (glej EN 54 1:2011), ki v enem mehanskem ohišju vsebujejo najmanj en optični ali ionizacijski senzor za zaznavanje dima in vsaj en senzor za zaznavanje ogljikovega monoksida (CO) ter poljubno število senzorjev toplote z uporabo kombinacije zaznanih pojavov. Ta evropski standard zajema samo načine delovanje, pri katerih se nenehno ocenjujejo vsaj signali senzorjev za dim in ogljikov monoksid.
Ta evropski standard določa zahteve glede ocenjevanja in preverjanja nespremenljivosti delovanja (AVCP) točkovnih detektorjev na podlagi kombinacije senzorjev za dim, ogljikov monoksid in izbirno tudi toploto glede na ta EN.
Točkovni detektorji, ki uporabljajo kombinacijo senzorjev za dim, ogljikov monoksid in izbirno tudi toploto ter imajo posebne lastnosti, ustrezne za zaznavanje posebnih tveganj požara, niso zajeti v tem evropskem standardu. Zahteve glede učinkovitosti za katere koli dodatne funkcije se v tem standardu ne obravnavajo (npr. dodatne funkcije ali izboljšana funkcionalnost, za katero ta evropski standard ne določa preskusne ali ocenjevalne metode).

General Information

Status
Published
Publication Date
19-May-2016
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
06-May-2016
Due Date
11-Jul-2016
Completion Date
20-May-2016

Relations

Buy Standard

Standard
EN 54-31:2015+A1:2016
English language
107 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 54-31:2015+A1:2016
01-junij-2016
1DGRPHãþD
SIST EN 54-31:2015
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO9HþVHQ]RUVNL
MDYOMDOQLNLSRåDUD.RPELQLUDQLWRþNRYQLMDYOMDOQLNLSRåDUDVVHQ]RUML]D
]D]QDYDQMHGLPDRJOMLNRYHJDPRQRNVLGDLQL]EUDQHWRSORWH
Fire detection and fire alarm systems - Part 31: Multi-sensor fire detectors - Point
detectors using a combination of smoke, carbon monoxide and optionally heat sensors
Brandmeldeanlagen - Teil 31: Mehrfachsensor-Brandmelder - Punktförmige Melder mit
kombinierten Rauch-, CO- und optionalen Wärmesensoren
Systèmes de détection et d'alarme incendie - Partie 31: Détecteurs d'incendie
multicapteurs - Détecteurs ponctuels combinant l'utilisation de capteurs de fumée, de
capteurs de monoxyde de carbone et éventuellement de capteurs de chaleur
Ta slovenski standard je istoveten z: EN 54-31:2014+A1:2016
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 54-31:2015+A1:2016 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 54-31:2015+A1:2016

---------------------- Page: 2 ----------------------

SIST EN 54-31:2015+A1:2016


EN 54-31:2014+A1
EUROPEAN STANDARD

NORME EUROPÉENNE

April 2016
EUROPÄISCHE NORM
ICS 13.220.20 Supersedes EN 54-31:2014
English Version

Fire detection and fire alarm systems - Part 31: Multi-
sensor fire detectors - Point detectors using a combination
of smoke, carbon monoxide and optionally heat sensors
Systèmes de détection et d'alarme incendie - Partie 31: Brandmeldeanlagen - Teil 31: Mehrfachsensor-
Détecteurs d'incendie multicapteurs - Détecteurs Brandmelder - Punktförmige Melder mit kombinierten
ponctuels combinant l'utilisation de capteurs de fumée, Rauch-, CO- und optionalen Wärmesensoren
de capteurs de monoxyde de carbone et
éventuellement de capteurs de chaleur
This European Standard was approved by CEN on 25 October 2014 and includes Amendment 1 approved by CEN on 31 January
2016.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-31:2014+A1:2016 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 54-31:2015+A1:2016
EN 54-31:2014+A1:2016 (E)
Contents Page
European foreword . 6
Introduction . 8
1 Scope . 9
2 Normative references . 9
3 Terms and definitions . 10
4 Requirements . 10
4.1 General . 10
4.2 Categorization . 10
4.3 Nominal activation conditions/sensitivity . 11
4.3.1 Individual alarm indication . 11
4.3.2 Response to slowly developing fires, aging and contamination . 11
4.3.3 Rate sensitive CO response . 11
4.3.4 Repeatability of smoke response . 12
4.3.5 Directional dependence of smoke response . 12
4.3.6 Repeatability of CO response . 12
4.3.7 Directional dependence of CO response . 12
4.3.8 Directional dependence of heat response . 12
4.3.9 Lower limit of heat response . 12
4.3.10 Reproducibility of smoke response . 12
4.3.11 Reproducibility of CO response . 12
4.3.12 Reproducibility of heat response . 12
4.3.13 Air movement . 12
4.3.14 Dazzling . 12
4.4 Operational reliability . 13
4.4.1 Connection of ancillary devices . 13
4.4.2 Monitoring of detachable detectors . 13
4.4.3 Manufacturer's adjustments . 13
4.4.4 On-site adjustment of response behaviour . 13
4.4.5 Protection against the ingress of foreign bodies . 13
4.4.6 Software controlled detectors . 13
4.4.7 Long term stability . 15
4.5 Tolerance to supply parameters - Variation in supply parameters . 15
4.6 Performance parameters under fire conditions - Fire sensitivity . 15
4.7 Durability of nominal activation conditions/sensitivity . 15
4.7.1 Temperature resistance . 15
4.7.2 Humidity resistance . 15
4.7.3 Shock and vibration resistance . 16
4.7.4 Electrical stability - EMC, immunity (operational) . 16
4.7.5 Resistance to chemical agents . 16
4.8 Detector sensitivity to single fire phenomena. 17
4.8.1 Sensitivity to smoke . 17
4.8.2 Sensitivity to carbon monoxide . 17
4.8.3 Sensitivity to heat . 17
5 Testing, assessment and sampling methods . 17
2

---------------------- Page: 4 ----------------------

SIST EN 54-31:2015+A1:2016
EN 54-31:2014+A1:2016 (E)
5.1 General . 17
5.1.1 Atmospheric conditions for tests . 17
5.1.2 Operating conditions for tests . 17
5.1.3 Mounting arrangements. 18
5.1.4 Tolerances . 18
5.1.5 Measurement of smoke response value . 18
5.1.6 Measurement of CO response value . 19
5.1.7 Measurement of heat response value . 20
5.1.8 Provision for tests . 20
5.1.9 Test schedule . 21
5.2 Nominal activation conditions/sensitivity . 22
5.2.1 Individual alarm indication . 22
5.2.2 Response to slowly developing fires, aging and contamination . 22
5.2.3 Rate sensitive CO response . 23
5.2.4 Repeatability of smoke response . 23
5.2.5 Directional dependence of smoke response . 24
5.2.6 Repeatability of CO response . 24
5.2.7 Directional dependence of CO response . 25
5.2.8 Directional dependence of heat response . 25
5.2.9 Lower limit of heat sensitivity . 26
5.2.10 Reproducibility of smoke response . 26
5.2.11 Reproducibility of CO response . 27
5.2.12 Reproducibility of heat response . 27
5.2.13 Air movement. 27
5.2.14 Dazzling . 28
5.3 Operational reliability . 29
5.3.1 Connection of ancillary devices . 29
5.3.2 Monitoring of detachable detectors . 29
5.3.3 Manufacturer's adjustments. 29
5.3.4 On-site adjustment of behaviour . 29
5.3.5 Protection against the ingress of foreign bodies . 29
5.3.6 Software controlled devices . 29
5.3.7 Long term stability . 29
5.4 Tolerance to supply parameters . 30
5.4.1 Variation in supply parameters . 30
5.5 Performance parameters under fire conditions . 31
5.5.1 Fire sensitivity . 31
5.6 Durability of nominal activation conditions/sensitivity . 33
5.6.1 Temperature resistance . 33
5.6.2 Humidity resistance . 36
5.6.3 Shock and vibration resistance . 41
5.6.4 Electrical stability . 46
5.6.5 Resistance to chemical agents . 47
5.7 Non-response to single fire phenomena . 50
5.7.1 Sensitivity to smoke . 50
5.7.2 Sensitivity to carbon monoxide . 51
5.7.3 Sensitivity to heat . 51
6 Classification and designation . 52
7 Marking, Labelling and Packaging . 52
Annex A (normative) Smoke tunnel for smoke response values . 54
Annex B (normative) Test aerosol for smoke response value measurements . 55
3

---------------------- Page: 5 ----------------------

SIST EN 54-31:2015+A1:2016
EN 54-31:2014+A1:2016 (E)
Annex C (normative) Smoke measuring instruments . 56
C.1 Obscuration meter . 56
C.2 Measuring ionization chamber (MIC) . 56
Annex D (normative) Gas test chamber for CO response threshold value and cross-
sensitivity to chemical agents . 60
Annex E (normative) Heat tunnel for heat response value . 61
Annex F (normative) Measuring instruments for CO . 62
F.1 General . 62
F.2 CO measuring instrument . 62
Annex G (informative) Establishing exposure levels of chemical agents. 63
G.1 General . 63
G.2 Establishing concentration of chemical agents for test gases 1 to 9 of 5.6.5.3 . 63
G.3 Verification of test chamber leakage . 63
G.4 Establishing concentration of ozone . 63
Annex H (normative) Apparatus for dazzling test. 64
Annex I (informative) Apparatus for impact test. 66
Annex J (normative) Fire test room . 68
Annex K (normative) Open wood fire (TF1) . 70
K.1 Fuel . 70
K.2 Arrangement . 70
K.3 Method of ignition . 70
K.4 Variables . 70
K.5 End-of-test condition . 70
K.6 Test validity criteria . 70
Annex L (normative) Smouldering (pyrolysis) wood fire (TF2) . 74
L.1 Fuel . 74
L.2 Hotplate . 74
L.3 Arrangement . 74
L.4 Heating rate . 74
L.5 End-of-test condition . 74
L.6 Test validity criteria . 74
Annex M (normative) Glowing smouldering cotton fire (TF3) . 79
M.1 Fuel . 79
M.2 Arrangement . 79
M.3 Ignition . 80
M.4 End-of-test condition . 81
M.5 Test validity criteria . 81
Annex N (normative) Open plastics (polyurethane) fire (TF4) . 84
N.1 Fuel . 84
N.2 Conditioning . 84
N.3 Arrangement . 84
N.4 Ignition . 84
N.5 Method of ignition . 84
N.6 End-of-test condition . 84
N.7 Test validity criteria . 84
Annex O (normative) Liquid (heptane) fire (TF5) . 87
O.1 Fuel . 87
4

---------------------- Page: 6 ----------------------

SIST EN 54-31:2015+A1:2016
EN 54-31:2014+A1:2016 (E)
O.2 Arrangement . 87
O.3 Ignition . 87
O.4 End-of-test condition . 87
O.5 Test validity criteria . 87
Annex P (normative) Low temperature black smoke (decalene) liquid fire (TF8) . 90
P.1 Fuel . 90
P.2 Arrangement . 90
P.3 Ignition . 90
P.4 End-of-test condition . 90
P.5 Test validity criteria . 90
Annex Q (informative) Information concerning the construction of the smoke tunnel . 93
Annex R (informative) Information concerning the construction of the gas test chamber . 96
Annex S (informative) Construction of the heat tunnel . 98
Annex T (informative) Information concerning test procedures and requirements for
response to slowly developing fires, aging and contamination . 101
Annex U (informative) Information concerning the construction of the measuring ionization
chamber . 105
Bibliography . 107

5

---------------------- Page: 7 ----------------------

SIST EN 54-31:2015+A1:2016
EN 54-31:2014+A1:2016 (E)
European foreword
This document (EN 54-31:2014+A1:2016) has been prepared by Technical Committee CEN/TC 72 “Fire
detection and fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by October 2016, and conflicting national standards shall
be withdrawn at the latest by December 2017.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent
rights.
This document includes Amendment 1 approved by CEN on 2016-01-31.
This document supersedes EN 54-31:2014.
The start and finish of text introduced or altered by amendment is indicated in the text by tags !".
EN 54, Fire detection and fire alarm systems, consists of the following parts:
— Part 1: Introduction
— Part 2: Control and indicating equipment
— Part 3: Fire alarm devices – Sounders
— Part 4: Power supply equipment
— Part 5: Heat detectors – Point detectors
— Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
— Part 10: Flame detector – Point detectors
— Part 11: Manual call points
— Part 12: Smoke detectors – Line detector using an optical light beam
...