Fire detection and fire alarm systems - Part 13: Compatibility and connectability assessment of system components

This document specifies the requirements for compatibility and connectability assessment of components of fire detection and fire alarm system or voice alarm system as a subsystem of fire detection and fire alarm system. The components comply either with the requirements of EN 54 or with a manufacturer’s specification where there is no EN 54 standard. This document only includes system requirements when these are necessary for compatibility assessment.
This document covers transmission path only between components. However ,requirements for TP between components of a function which is distributed are covered by the relevant EN 54 standard and not by this document.
This document also specifies requirements for the integrity of the fire detection and fire alarm system when connected to other systems.
This document does not specify the manner in which the system is designed, installed and used in any particular application.
This document recognizes that it is not practical to assess the compatibility or connectability of components in all possible configurations. Methods of assessment are specified to reach an acceptable degree of confidence within pre-determined operational and environmental conditions.
This document specifies requirements related to compatibility and connectability assessment methods and tests for the components belonging to FDAS or connecting FDAS. This document does not cover components or functions which are not included in a FDAS.
This document is applicable to systems where the components are interconnected by electrical wires or optical fibre or by radio frequency links or by any combination. For other interconnection technology between components , this standard may be used as a guidance.
NOTE Other European Standards are expected to cover the requirements of the other systems to which the fire detection and fire alarm system may be connected.

Brandmeldeanlagen — Teil 13: Bewertung der Kompatibilität und Anschließbarkeit von Systembestandteilen

Dieses Dokument legt die Anforderungen an die Bewertung der Kompatibilität und Anschließbarkeit von Bestandteilen von Brandmelde- und Feueralarmanlagen oder Sprachalarmierungsanlagen als Teilsystem einer Brandmelde- und Feueralarmanlage fest. Die Bestandteile entsprechen entweder den Anforderungen der Normenreihe EN 54 oder, sofern keine Norm der Reihe EN 54 besteht, einer Herstellerspezifikation. Dieses Dokument enthält nur Systemanforderungen, die für die Bewertung der Kompatibilität erforderlich sind.
Das vorliegende Dokument behandelt ausschließlich den Übertragungsweg zwischen den Bestandteilen. Anforderungen an Übertragungswege zwischen Bestandteilen einer Funktion, die verteilt ist, werden jedoch von der entsprechenden Norm der Reihe EN 54 behandelt und nicht in diesem Dokument.
Dieses Dokument legt auch Anforderungen an die Unversehrtheit von Brandmelde- und Feueralarmanlagen fest, wenn diese mit anderen Systemen verbunden sind.
Mit diesem Dokument werden keine Festlegungen über Ausführung, Einbau und Betrieb in einer bestimmten Anwendung getroffen.
Dieses Dokument berücksichtigt, dass die Bewertung der Kompatibilität bzw. Anschließbarkeit von Bestandteilen nicht für alle möglichen Konfigurationen zweckmäßig ist. Es werden Bewertungsverfahren innerhalb vorher festgelegter Betriebs- und Umgebungsbedingungen angegeben, die Schlussfolgerungen mit einem zufrieden stellenden Sicherheitsgrad zulassen.
Dieses Dokument legt Anforderungen an Verfahren zur Bewertung der Kompatibilität und Anschließbarkeit der Bestandteile von Brandmelde- und Feueralarmanlagen bzw. solchen Bauteilen fest, mit denen die Brandmelde- und Feueralarmanlage verbunden ist. Dieses Dokument behandelt keine Bauteile oder Funktionen, die nicht in einer Brandmelde- und Feueralarmanlage enthalten sind.
Dieses Dokument gilt für Anlagen, deren Bestandteile durch elektrische Leitungen, Lichtwellenleiter oder über Hochfrequenzverbindungen oder eine Kombination daraus miteinander verbunden sind. Für sonstige Techniken zur Verbindung von Bauteilen miteinander darf die vorliegende Norm als Leitfaden angewendet werden.
ANMERKUNG   Für die Anforderungen an andere Systeme, an die eine Brandmeldeanlage angeschlossen werden darf, gelten andere Europäische Normen.

Système de détection incendie - Partie 13: Évaluation de la compatibilité et de l'aptitude au raccordement des composants d’un système

Le présent document spécifie les exigences relatives à l’évaluation de la compatibilité et de l’aptitude au raccordement des composants du système de détection et d’alarme incendie ou du système d'alarme vocale en tant que sous-système du système de détection et d’alarme incendie. Les composants sont conformes soit aux exigences de l’EN 54 soit aux spécifications du fabricant en l’absence de la partie applicable de l’EN 54. Ce document comporte uniquement des exigences afférentes au système lorsque celles-ci sont nécessaires à l’évaluation de la compatibilité.
Le présent document couvre uniquement les voies de transmission entre les composants. Toutefois, les exigences relatives aux voies de transmission (VT) entre les composants d'une fonction répartie sont couvertes par la partie correspondante de l’EN 54 et non par le présent document.
Le présent document spécifie également les exigences relatives à l’intégrité du système de détection et d’alarme incendie lorsque ce dernier est raccordé à d’autres systèmes.
Le présent document ne spécifie pas la manière dont le système est conçu, installé et utilisé pour une application particulière quelconque.
Il est admis dans le présent document qu’il n’est pas possible d’évaluer la conformité ou l’aptitude au raccordement des composants dans toutes les configurations possibles. Des méthodes d’évaluation sont donc spécifiées qui permettent de tirer des conclusions présentant un degré de confiance acceptable dans des conditions opérationnelles et environnementales prédéterminées.
Le présent document spécifie les exigences relatives aux méthodes et essais d’évaluation de la compatibilité et de l’aptitude au raccordement des composants appartenant au système de détection et d'alarme incendie (SDAI) ou raccordés à celui-ci. Ce document ne couvre pas les composants ou fonctions ne faisant pas partie d'un système de détection et d'alarme incendie (SDAI).
Ce document s’applique aux systèmes où les composants sont interconnectés par des câbles électriques, des fibres optiques, des liaisons radioélectriques, ou par n’importe quelle combinaison. Ce document peut servir de guide pour d'autres techniques d'interconnexion entre les composants.
NOTE   D’autres normes européennes devraient traiter des exigences applicables aux autres systèmes auxquels le système de détection et d’alarme incendie peut être raccordé.

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 13. del: Ocenjevanje združljivosti in povezljivosti sestavnih delov sistemov

Ta dokument določa zahteve za ocenjevanje združljivosti in povezljivosti sestavnih delov sistema za odkrivanje in javljanje požara ali sistemov glasovnega javljanja, ki delujejo kot podsistem sistema za odkrivanje in javljanje požara. Sestavni deli so skladni z zahtevami standarda EN 54 ali s specifikacijo proizvajalca, če ni veljavnega standarda EN 54. Ta dokument vključuje samo sistemske zahteve, če so potrebne za oceno združljivosti.
Ta dokument zajema samo pot prenosa med sestavnimi deli. Vendar so zahteve za pot prenosa med sestavnimi deli porazdeljene funkcije zajete v ustreznem standardu EN 54 in ne v tem dokumentu.
Ta dokument določa tudi zahteve za celovitost sistema za odkrivanje in javljanje požara, ko je ta povezan z drugimi sistemi.
Ta dokument ne določa načina zasnove, namestitve in uporabe sistema pri kateri koli posamezni vrsti uporabe.
Ta dokument upošteva, da ocena združljivosti ali povezljivosti sestavnih delov v vseh mogočih konfiguracijah ni praktična. Metode za oceno so določene na način, s katerim se doseže sprejemljiva stopnja zaupanja v okviru vnaprej določenih obratovalnih in okoljskih pogojev.
Ta dokument določa zahteve v zvezi z metodami za ocenjevanje združljivosti in povezljivosti ter s preskušanjem sestavnih delov, ki so del sistema za odkrivanje in javljanje požara ali so z njim povezani. Ta dokument ne zajema sestavnih delov ali funkcij, ki niso del sistema za odkrivanje in javljanje požara.
Ta dokument se uporablja za sisteme, pri katerih so sestavni deli medsebojno povezani z električnimi žicami ali optičnimi vlakni, prek radiofrekvenčnih povezav ali s kombinacijo navedenih možnosti. Za drugo tehnologijo medsebojnega povezovanja sestavnih delov se ta standard lahko uporablja kot vodilo.
OPOMBA: Predvideno je, da druge sisteme, s katerimi so lahko sistemi za odkrivanje in javljanje požara povezani, obravnavajo drugi evropski standardi.

General Information

Status
Withdrawn
Public Enquiry End Date
14-Oct-2014
Publication Date
11-Apr-2017
Withdrawal Date
09-Jan-2020
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
10-Jan-2020
Due Date
02-Feb-2020
Completion Date
10-Jan-2020

Relations

Buy Standard

Standard
EN 54-13:2017
English language
31 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 54-13:2017
01-maj-2017
1DGRPHãþD
SIST EN 54-13:2005
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 13. del: Ocenjevanje
združljivosti in povezljivosti sestavnih delov sistemov
Fire detection and fire alarm systems - Part 13: Compatibility and connectability
assessment of system components
Brandmeldeanlagen — Teil 13: Bewertung der Kompatibilität und Anschließbarkeit von
Systembestandteilen
Système de détection incendie - Partie 13: Évaluation de la compatibilité et de l'aptitude
au raccordement des composants d’un système
Ta slovenski standard je istoveten z: EN 54-13:2017
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 54-13:2017 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 54-13:2017

---------------------- Page: 2 ----------------------

SIST EN 54-13:2017


EN 54-13
EUROPEAN STANDARD

NORME EUROPÉENNE

February 2017
EUROPÄISCHE NORM
ICS 13.220.20 Supersedes EN 54-13:2005
English Version

Fire detection and fire alarm systems - Part 13:
Compatibility and connectability assessment of system
components
Systèmes de détection incendie - Partie 13: Évaluation Brandmeldeanlagen - Teil 13: Bewertung der
de la compatibilité et de l'aptitude au raccordement Kompatibilität und Anschließbarkeit von
des composants d'un système Systembestandteilen
This European Standard was approved by CEN on 14 November 2016.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-13:2017 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
Contents Page

European foreword . 5
Introduction . 8
1 Scope . 9
2 Normative references . 9
3 Terms, definitions and abbreviations . 10
3.1 Terms and definitions . 10
3.2 Abbreviations . 11
4 Requirements . 11
4.1 Compliance . 11
4.2 Basic requirements . 12
4.3 Transmission path(s) . 12
4.3.1 General . 12
4.3.2 TP using wires . 13
4.3.3 TP using radio frequency link . 13
4.3.4 TP using optical fibre . 13
4.3.5 Network TP . 13
4.4 Documentation . 14
4.4.1 General . 14
4.4.2 Documentation for compatibility . 14
4.4.3 Documentation for connectability . 14
4.4.4 Software documentation . 15
5 Assessment methods and tests. 15
5.1 General . 15
5.2 Provision of equipment and supporting information and tools . 15
5.3 Configuration . 16
5.3.1 General . 16
5.3.2 Configuration at field level for assessment . 16
5.3.3 Configuration at control level for network assessment . 16
5.4 Standard atmospheric conditions for testing . 17
5.5 Functional test for compatibility assessment on field level . 17
5.5.1 The objective of the test . 17
5.5.2 Test schedule . 17
5.5.3 Functional tests for compatibility in the different conditions . 18
5.6 Functional tests for connectability assessment on field level . 22
5.6.1 The objective of the test . 22
5.6.2 Test schedule . 22
5.6.3 Functional test for connectability . 22
Annex A (informative) Example of levels used in FDAS . 23
Annex B (informative) Classification of functions of the FDAS . 24
B.1 General . 24
B.2 Fire detection function . 24
2

---------------------- Page: 4 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
B.3 Fire alarm to occupants in the premises . 24
B.4 Fire alarm to summon external assistance (usually the fire brigade) . 24
B.5 Activation of fire protection function . 24
B.5.1 Equipment directly triggered by the FDAS . 24
B.5.2 Systems driven by the information coming from the FDAS . 24
B.6 Remote indication 1 (remote panels, fire brigade panels, etc.) . 24
B.7 Remote indication 2 (printers, interface to building management system, etc.) . 25
B.8 Input function . 25
B.9 Output function . 25
B.10 Devices used to connect transmission paths (gateway, data switch, etc.) . 25
Annex C (informative) Example methodology for theoretical analysis . 26
C.1 Introduction. 26
C.2 Method of test . 26
C.2.1 General . 26
C.2.2 List of characteristics . 26
C.2.2.1 Mechanical connections . 26
C.2.2.2 Power supply and distribution analysis . 26
C.2.2.2.1 Voltage range . 26
C.2.2.2.2 Current . 27
C.2.2.2.3 Supply characteristics . 27
C.2.2.2.4 Power supply voltage range . 27
C.2.2.2.5 Fault performance . 27
C.2.2.3 Data exchange analysis . 27
C.2.2.3.1 General . 27
C.2.2.3.2 Transmission characteristics . 27
C.2.2.3.2.1 General . 27
C.2.2.3.2.2 Voltage range . 27
C.2.2.3.2.3 Current . 28
C.2.2.3.2.4 Timing. 28
C.2.2.3.2.5 Tolerances . 28
C.2.2.3.2.6 Fault performance. 28
C.2.2.3.3 Transmission protocol(s) . 28
C.2.2.4 Functionality . 28
C.2.2.4.1 General . 28
C.2.2.4.2 Received data . 28
C.2.2.4.3 Transmitted data . 28
3

---------------------- Page: 5 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
Annex D (normative) Software design documentation . 29
Annex E (informative) Flowchart for assessment of compatibility / connectability . 31


4

---------------------- Page: 6 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
European foreword
This document (EN 54-13:2017) has been prepared by Technical Committee CEN/TC 72 “Fire detection
and fire alarm system”, the secretariat of which is held by BSI.
This document supersedes EN 54-13:2005.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by August 2017, and conflicting national standards shall
be withdrawn at the latest by August 2017.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent
rights.
EN 54-13 has been revised to update the standard by taking into account new techniques of
communication and new technologies available on the market.
It includes new clauses and annexes as follows:
— Clause 4.3. Transmission paths
— Annexe A example of levels used in fire detection and alarm system
— Annexe D software design documentation
— Annexe E flowchart for assessment
The main technical modifications are the followings:
— The standard is applicable to electrical wires, optical fibre or radio frequency connection.
— EN 54-1: 2011 is taken into account and leads to delete the flowchart of functions.
— Introduction of levels (field, control and management) and network transmission path to consider
new technique of configuration.
— Transfer of product requirements covering partial open and partial short circuits to an optional
clause included in EN 54-2.
EN 54 is published in a series of parts. Information on the relationship between this document and
other standards of the EN 54 series is given in Annex A of EN 54-1:2011.
EN 54, Fire detection and fire alarm systems consists of the following parts:
— Part 1: Introduction
— Part 2: Control and indicating equipment
— Part 3: Fire alarm devices – Sounders
— Part 4: Power supply equipment
5

---------------------- Page: 7 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
— Part 5: Heat detectors – Point detectors
— Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
— Part 10: Flame detectors – Point detectors
— Part 11: Manual call points
— Part 12: Smoke detectors – Line detectors using an optical beam
— Part 13: Compatibility assessment of system components
— Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
— Part 15: Point detectors using a combination of detected phenomena
— Part 16: Voice alarm control and indicating equipment
— Part 17: Short-circuit isolators
— Part 18: Input/output devices
— Part 20: Aspirating smoke detectors
— Part 21: Alarm transmission and fault warning routing equipment
— Part 22: Resettable line-type heat detectors
— Part 23: Fire alarm devices – Visual alarm devices
— Part 24: Components of voice alarm systems – Loudspeakers
— Part 25: Components using radio links
— Part 26: Carbon monoxide detectors – Point detectors
— Part 27: Duct smoke detectors
— Part 28: Non-resettable line-type heat detectors
— Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors
— Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat
sensors
— Part 31: Multi-sensor fire detectors – Point detectors using a combination of smoke, carbon monoxide
and optionally heat sensors
— Part 32: Guidelines for the planning, design, installation, commissioning, use and maintenance of voice
alarm systems
NOTE This list includes standards that are in preparation and other standards may be added. For current
status of published standards refer to www.cen.eu.
6

---------------------- Page: 8 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
EN 54-1 provides additional information about the components performing the functions of a fire
detection and fire alarm system.
EN 54-25 provides additional information and requirements about systems using radio frequency links.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
7

---------------------- Page: 9 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
Introduction
The fire detection function is to detect a fire at the earliest practicable moment, and to give signals and
indications so that appropriate action can be taken.
The fire alarm function is to give, at least, audible and/or visible signals to the occupants of a building
who may be at risk from fire.
A fire detection and fire alarm system (including voice alarm system) may combine the functions of
detection and alarm in a single system, and typically consists of a number of inter-linked components
including automatic fire detectors, manual call points and alarm devices. These components are
connected to control and indicating equipment by means of one or more transmission paths. All system
components, including the control and indicating equipment, are also directly or indirectly connected to
a power supply.
A separate voice alarm system can be assessed for compatibility and connectability independently of
the fire detection and alarm system.
A fire detection and fire alarm system may also be linked to remote fault and fire alarm monitoring
stations, and to fire protection and/or building management systems. However these systems are not
considered as part of the fire detection and fire alarm system.
It is necessary that all the components constituting the fire detection and fire alarm system are
compatible or connectable, and that requirements relating to the performance of the overall system are
fulfilled.
Differentiation is made between components classified as components type 1 and other components
classified as components type 2.
As the possible configurations of fire detection and fire alarm systems are unlimited, the assessment is
only carried out on the configuration(s) declared by the applicant.
The intended use of this standard is to demonstrate the compatibility and connectability of components
even if they are not defined by an EN 54 standard.
8

---------------------- Page: 10 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
1 Scope
This European Standard specifies the requirements for compatibility and connectability assessment of
components of fire detection and fire alarm systems (including voice alarm systems as a subsystem of
fire detection and fire alarm system). The components conform to either with the requirements of
EN 54 or with a manufacturer’s specification where there is no EN 54 standard.
The requirements for the transmission path used for a distributed function are covered by the relevant
EN 54 standard and not by this document.
This document also specifies requirements for the integrity of the fire detection and fire alarm system
when connected to other systems.
This document does not specify the manner in which the system is designed, installed and used in any
particular application.
This document recognizes that it is not practical to assess the compatibility or connectability of
components in all possible configurations. Methods of assessment are specified to reach an acceptable
degree of confidence within pre-determined operational and environmental conditions.
This document specifies requirements related to compatibility and connectability assessment methods
and tests for the components belonging to FDAS or connecting FDAS.
This document does not cover components or functions which are not included in a FDAS like functions
achieved by a building management system.
This document is applicable to systems where the components are interconnected by electrical wires or
optical fibre or by radio frequency links or by any combination. For other interconnection technology
between components this standard may be used as a guidance.
NOTE Other European Standards are expected to cover the requirements of the other systems which may be
connected to the fire detection and fire alarm system.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 50130-4, Alarm systems - Part 4: Electromagnetic compatibility - Product family standard: Immunity
requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems
EN 50130-5, Alarm systems - Part 5: Environmental test methods
EN 60068-1, Environmental testing - Part 1: General and guidance
EN 54-1:2011, Fire detection and fire alarm systems - Part 1: Introduction
EN 54-2, Fire detection and fire alarm systems - Part 2: Control and indicating equipment
EN 54-4, Fire detection and fire alarm systems - Part 4: Power supply equipment
EN 54-16, Fire detection and fire alarm systems - Part 16: Voice alarm control and indicating equipment
EN 54-25, Fire detection and fire alarm systems - Part 25: Components using radio links
9

---------------------- Page: 11 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1, those given in each
relevant part of EN 54 product standard and the following apply.
3.1.1
configuration
topological arrangement of components connected through transmission paths to control and
indicating equipment
3.1.2
compatibility for component type 1
ability of a component type 1 to operate with other type 1 components of the FDAS:
— within the limits specified for each component given in the documentation;
— within the specified limits given by the relevant parts of EN 54, or given by the applicant; if no
EN 54 part applies;
— within specified configurations of systems
3.1.3
component type 1
device performing a function A, B, C, D, E, G, J, L, M, for fire detection and fire alarm as defined in EN 54-
1 or device performing another function declared as component type 1 by the applicant
Note 1 to entry: For example function N. See Annex B.
3.1.4
component type 2
device other than type 1 and which is connected to a type 1 component
3.1.5
connectability for component type 2
ability of component type 2 to operate without jeopardizing the performance of the fire detection and
fire alarm system
3.1.6
control level
level where control and indication functions are provided
Note 1 to entry: See drawing in Annex A.
Note 2 to entry: CIE and VACIE belong to that level.
3.1.7
field level
level where detection, activation and fire alarm functions are provided
Note 1 to entry: See drawing in Annex A.
Note 2 to entry: Detectors, input / output devices and sounders and visual alarm devices belong to that level.
10

---------------------- Page: 12 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
3.1.8
management level
level where management functions are provided (such as management stations)
Note 1 to entry: See drawing in Annex A
3.1.9
network topology
configuration of network including both the categories of node and interconnection of TP between them
3.1.10
network node
device with a unique network address
3.1.11
networked CIE
Networked CIE comprise more than one CIE (function B in EN 54-1) or more than one VACIE, (function
M in EN 54-1) or a combination of both function B and M, which are interconnected on a fault tolerant
transmission path which forms the network
3.1.12
testing authority
certification body or testing laboratory
3.2 Abbreviations
FDAS Fire Detection and Fire Alarm System
TP Transmission Path
CIE Control and Indicating Equipment
VACIE Voice Alarm Control and Indicating Equipment
VAS Voice Alarm System
PSE Power Supply Equipment
OEM Original Equipment Manufacturer
4 Requirements
4.1 Compliance
In order to conform to this standard, compatibility of the components type 1 or connectability of the
components type 2 within the FDAS shall meet the requirements listed in Clause 4. This shall be verified
by theoretical assessment (5.1) with reference to the required documentation (4.4). When this is an
outcome of the theoretical assessment, configuration (s) according to (5.3) shall be tested as described
using the relevant selection of functional tests defined in 5.5 and 5.6 and shall meet the criteria of
acceptance of the tests.
11

---------------------- Page: 13 ----------------------

SIST EN 54-13:2017
EN 54-13:2017 (E)
4.2 Basic requirements
4.2.1 The applicant shall provide a list of the devices of the FDAS and those devices not covered by
EN 54 shall be declared as component type 1 or component type 2.
4.2.2 The different FDAS configurations intended to be used shall be described within the applicant’s
documentation.
4.2.3 All the different configurations declared by the applicant shall be considered and representative
configurations shall be assessed to meet the requirements of this document.
NOTE Representative configurations are defined by agreement between the applicant and the testing
authority.
4.2.4 Each type 1 component shall be powered directly or indirectly by a PSE which conforms to the
requirements in EN 54-4 except for some radio link components in accordance with EN 54-25 which
may be powered by batteries.
4.2.5 Each type 1 component shall meet the requirements of the relevant part of EN 54.
In the case where the component type 1 is not covered by EN 54 series it shall meet the following:
a) conformity of the functionality (indicatio
...