SIST EN 16282-5:2017
(Main)Equipment for commercial kitchens - Components for ventilation in commercial kitchens - Part 5: Air duct - Design and dimensioning
Equipment for commercial kitchens - Components for ventilation in commercial kitchens - Part 5: Air duct - Design and dimensioning
This European Standard specifies requirements for the design, construction and operation of the air duct in commercial kitchens, including technical safety, ergonomic and hygienic features.
This European Standard is applicable to ventilation systems in commercial kitchens, associated areas and other installations processing foodstuffs intended for commercial use. Kitchens and associated areas are special rooms in which meals are prepared, where tableware and equipment is washed, cleaned and food is stored and food waste areas.
This European Standard is applicable to kitchen ventilation systems except those used in domestic kitchens.
A method of verification of each requirement is also specified.
Unless otherwise specified, the requirements of this standard should be checked by way of inspection and/or measurement.
NOTE Please note the possible existence of additional or alternative local national regulations on installation, appliance requirements and inspection, maintenance and operation.
Großküchengeräte - Einrichtungen zur Be- und Entlüftung von gewerblichen Küchen - Teil 5: Luftleitungen - Gestaltung und Dimensionierung
Diese Europäische Norm legt Anforderungen an die Gestaltung, die Konstruktion und den Betrieb von Luftleitungen gewerblich genutzter Küchen fest, einschließlich der technischen Sicherheit, ergonomischer und hygienischer Aspekte.
Diese Europäische Norm gilt für Lüftungsanlagen in gewerblich genutzten Küchen, dazugehörige Bereiche und andere Installationen in der Lebensmittelverarbeitung, die für den gewerblichen Gebrauch bestimmt sind. Küchen sowie dazugehörige Bereiche sind spezielle Räume, in denen Speisen zubereitet, Geschirr/Geräte gewaschen bzw. gesäubert werden und Lebensmittel gelagert und entsorgt werden.
Diese Europäische Norm gilt nicht für Lüftungsanlagen, die für den Privathaushalt bestimmt sind.
Ein Verfahren zur Überprüfung der Anforderungen ist auch festgelegt.
Sofern nicht anders festgelegt, sollten die Anforderungen dieser Norm durch Begutachtung und/oder Nachmessen überprüft werden.
ANMERKUNG Bitte die mögliche Existenz zusätzlicher oder alternativer lokaler oder nationaler Vorschriften über Installation, Geräteanforderungen und Inspektion, Wartung und Betrieb beachten
Équipement pour cuisines professionnelles - Éléments de ventilation pour cuisines professionnelles - Partie 5: Conduit d'air - Conception et dimensionnement
La présente Norme européenne spécifie les exigences relatives à la conception, la construction et au fonctionnement des conduits d'air dans les cuisines professionnelles, y compris les caractéristiques techniques de sécurité, d'ergonomie et d'hygiène.
La présente Norme européenne s'applique aux systèmes de ventilation installés dans les cuisines professionnelles, les zones associées et les autres installations de transformation de produits alimentaires destinées à un usage professionnel. Les cuisines et les zones associées sont des pièces spéciales dans lesquelles les repas sont préparés, la vaisselle et les ustensiles sont lavés et nettoyés, les produits alimentaires sont stockés, et des zones de déchets alimentaires.
La présente Norme européenne s'applique aux systèmes de ventilation pour cuisines excepté ceux utilisés dans les cuisines domestiques.
Une méthode de vérification de chaque exigence est également spécifiée.
Sauf spécification contraire, il convient que les exigences de la présente norme soient vérifiées par inspection et/ou mesurage.
NOTE Noter l'existence possible de réglementations nationales complémentaires ou alternatives concernant l'installation, les exigences relatives aux appareils, l'inspection, la maintenance et le fonctionnement.
Oprema za profesionalne kuhinje - Sestavni deli za prezračevanje kuhinj - 5. del: Kanali - Projektiranje in dimenzioniranje
Ta evropski standard določa zahteve za projektiranje, gradnjo in delovanje kanalov, vključno s tehnično varnostjo, ergonomičnostjo in higieničnostjo.
Ta evropski standard se uporablja za prezračevalne sisteme v kuhinjah, povezanih prostorih in za druge naprave za predelavo živil, namenjenih komercialni uporabi. Kuhinje in povezani prostori so posebni prostori, v katerih se pripravljajo jedi, kjer se pere in čisti jedilni pribor ter opremo in se shranjuje hrana.
Ta evropski standard se ne uporablja za prezračevalne sisteme v domačih kuhinjah.
Opredeljena je tudi metoda za preverjanje posamezne zahteve.
Če ni drugače določeno, se zahteve tega standarda preverjajo s pregledom in/ali meritvami.
OPOMBA Upoštevajte morebitne dodatne ali alternativne nacionalne predpise glede namestitve, zahteve glede aparatov ter pregleda, vzdrževanja in obratovanja.
General Information
- Status
- Published
- Public Enquiry End Date
- 11-Jan-2015
- Publication Date
- 07-Sep-2017
- Technical Committee
- OGS - Heating for buildings
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 05-Sep-2017
- Due Date
- 10-Nov-2017
- Completion Date
- 08-Sep-2017
Relations
- Effective Date
- 01-Oct-2017
Overview
EN 16282-5:2017 - part of the CEN series on equipment for commercial kitchens - specifies design, construction and operation requirements for air ducts used in commercial kitchen ventilation systems. It applies to ventilation in commercial kitchens and associated food-processing areas (not domestic kitchens) and covers technical safety, fire protection, ergonomic and hygienic features. Each requirement includes a method of verification, typically by inspection and/or measurement.
Key Topics
- Scope and applicability: For commercial kitchen ventilation, exhaust/outlet and supply/outside air ducts; not for domestic kitchens.
- Functional design:
- Minimise pressure loss through smooth internal joints, no sudden cross‑section changes and an inner bend radius ≥ 100 mm; angle changes < 45° where possible.
- Avoid flexible ducts in kitchens (difficult to clean); certain outlet caps (e.g., “Chinaman’s hat”) are prohibited.
- Dimensioning uses flow‑velocity guide values (see standard) while considering allowable sound pressure and pressure loss.
- Air leakage:
- Supply/outside ducts: at least air leakage class B (EN 12237 / EN 1507).
- Extract/outlet ducts: air leakage class C (EN 12237 / EN 1507 / EN 13779).
- Materials & construction:
- Recommended materials include stainless steel (per EN 10088‑1), galvanised steel or suitable concrete with cleanable surfaces.
- Mounting: galvanised supports with sound insulation, minimum M10 threaded rods; avoid galvanic contact between dissimilar metals.
- Fire protection:
- Ducts must resist deformation in fire; allow for thermal expansion (restrained spans ideally ≤ 5 m or use compensators).
- Ducts penetrating fire-resisting elements must match the fire resistance or incorporate shut‑off devices.
- Hygiene & maintenance:
- Keep duct runs short, linear and sloped to a drainable collection point; avoid underside longitudinal joints.
- Extract/outlet ducts must be aerosol‑tight; aerosol separation is required before aerosol enters ductwork.
- Silencers must be health‑safe, cleanable, liquid‑ and aerosol‑resistant and removable with basic tools.
- Verification: Inspection and/or measurement per the standard (e.g., EN 12599 for system handover).
Applications
Who uses EN 16282-5:2017:
- HVAC and kitchen ventilation designers and consultants
- Architects and building services engineers
- Equipment manufacturers (ductwork, silencers, dampers)
- Installers, commissioning engineers and facility managers
- Inspectors and regulatory authorities ensuring safe, hygienic kitchen exhaust systems
Practical benefits: improved energy efficiency, reduced fire risk, easier cleaning and maintenance, and compliance with European ductwork performance classes.
Related Standards
- EN 16282 series (Parts 1–8) - broader kitchen ventilation requirements
- EN 12237, EN 1507 (duct leakage/strength), EN 13779 (ventilation performance), EN 10088‑1 (stainless steels), EN 12599 (handover measurement) - all normatively referenced.
Note: Local national regulations or additional appliance/inspection rules may apply and should be checked alongside this standard.
Frequently Asked Questions
SIST EN 16282-5:2017 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Equipment for commercial kitchens - Components for ventilation in commercial kitchens - Part 5: Air duct - Design and dimensioning". This standard covers: This European Standard specifies requirements for the design, construction and operation of the air duct in commercial kitchens, including technical safety, ergonomic and hygienic features. This European Standard is applicable to ventilation systems in commercial kitchens, associated areas and other installations processing foodstuffs intended for commercial use. Kitchens and associated areas are special rooms in which meals are prepared, where tableware and equipment is washed, cleaned and food is stored and food waste areas. This European Standard is applicable to kitchen ventilation systems except those used in domestic kitchens. A method of verification of each requirement is also specified. Unless otherwise specified, the requirements of this standard should be checked by way of inspection and/or measurement. NOTE Please note the possible existence of additional or alternative local national regulations on installation, appliance requirements and inspection, maintenance and operation.
This European Standard specifies requirements for the design, construction and operation of the air duct in commercial kitchens, including technical safety, ergonomic and hygienic features. This European Standard is applicable to ventilation systems in commercial kitchens, associated areas and other installations processing foodstuffs intended for commercial use. Kitchens and associated areas are special rooms in which meals are prepared, where tableware and equipment is washed, cleaned and food is stored and food waste areas. This European Standard is applicable to kitchen ventilation systems except those used in domestic kitchens. A method of verification of each requirement is also specified. Unless otherwise specified, the requirements of this standard should be checked by way of inspection and/or measurement. NOTE Please note the possible existence of additional or alternative local national regulations on installation, appliance requirements and inspection, maintenance and operation.
SIST EN 16282-5:2017 is classified under the following ICS (International Classification for Standards) categories: 91.140.30 - Ventilation and air-conditioning systems; 97.040.99 - Other kitchen equipment. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN 16282-5:2017 has the following relationships with other standards: It is inter standard links to oSIST prEN 16282-5:2011. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase SIST EN 16282-5:2017 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Großküchengeräte - Einrichtungen zur Be- und Entlüftung von gewerblichen Küchen - Teil 5: Luftleitungen - Gestaltung und DimensionierungÉquipement pour cuisines professionnelles - Éléments de ventilation pour cuisines professionnelles - Partie 5: Conduit d'air - Conception et dimensionnementEquipment for commercial kitchens - Components for ventilation in commercial kitchens - Part 5: Air duct - Design and dimensioning97.040.99Druga kuhinjska opremaOther kitchen equipment91.140.30VLVWHPLVentilation and air-conditioning systemsICS:Ta slovenski standard je istoveten z:EN 16282-5:2017SIST EN 16282-5:2017en,fr,de01-oktober-2017SIST EN 16282-5:2017SLOVENSKI
STANDARD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 16282-5
July
t r s y ICS
{ yä r v rä { { English Version
Equipment for commercial kitchens æ Components for ventilation in commercial kitchens æ Part
wã Air ductâ Design and dimensioning Équipement pour cuisines professionnelles æ Éléments de ventilation pour cuisines professionnelles æ Partie
wã Conduit d 5air æ Conception et dimensionnement
Bauelemente in gewerblichen Küchen æ Einrichtungen zur Beæ und Entlüftung æ Teil
wã Luftleitungenâ Gestaltung und Dimensionierung This European Standard was approved by CEN on
s s May
t r s yä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Serbiaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey and United Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
t r s y CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s x t z tæ wã t r s y ESIST EN 16282-5:2017
European foreword . 3 1 Scope . 4 2 Normative references . 4 3 Terms and definitions . 4 4 Construction and function . 6 4.1 General . 6 4.2 Functional requirements. 6 4.3 Materials . 9 4.4 Mounting elements . 9 5 Safety requirements . 9 5.1 General . 9 5.2 Fire protection requirements . 10 6 Hygienic requirements. 11 6.1 General hygienic requirements . 11 6.2 Air treatment . 11 6.3 Cleaning . 11 6.4 Fans in extract air ducts . 13 7 Installation and operating instructions . 13 Bibliography . 15
Figure 1 — Chinamans hat type air outlet SIST EN 16282-5:2017
...
The article discusses the SIST EN 16282-5:2017 standard, which focuses on equipment for commercial kitchens and specifically on components for ventilation in these kitchens. The standard provides requirements for the design, construction, and operation of the air ducts used in commercial kitchens, with a focus on technical safety, ergonomic features, and hygiene. It is applicable to ventilation systems in commercial kitchens, associated areas, and other installations that handle food for commercial use. However, it does not apply to ventilation systems in domestic kitchens. The standard also specifies a method for verifying each requirement, which should be checked through inspection and/or measurement. It is important to note that there may be additional or alternative local regulations regarding installation, appliance requirements, and inspection, maintenance, and operation.
記事タイトル:SIST EN 16282-5: 2017-商業用キッチンの機器-商業用キッチンの換気の構成要素-第5部:空気ダクト-設計と寸法決定 記事内容:このヨーロッパ標準は、技術的な安全性、人間工学的な特徴、衛生的な特徴を含む空気ダクトの設計、建設、運用に関する要件を定めています。 このヨーロッパ標準は、商業キッチン、関連エリア、および商業的な目的で使用される食品処理施設における換気システムに適用されます。キッチンや関連エリアは、食事の準備が行われ、食器や機器が洗浄され、食品が保管される特別な部屋です。 このヨーロッパ標準は、家庭用キッチンで使用される換気システムには適用されません。 各要件の検証方法も指定されています。 ただし、設置、機器要件、検査、保守、および操作に関して個別または代替の現地の国家規制が存在する可能性があることに留意してください。
기사 제목 : SIST EN 16282-5:2017 - 상업용 주방용 장비 - 상업용 주방에서의 환기를 위한 구성 요소 - 제5부 : 공기 도관 - 설계와 치수 결정 기사 내용 : 이 유럽 표준은 기술적인 안전, 인체 공학적 기능 및 위생적인 기능을 포함한 공기 도관의 설계, 건설 및 운영에 대한 요구 사항을 명시합니다. 이 유럽 표준은 상업용 주방, 관련 공간 및 상업적인 목적으로 사용되는 식품을 처리하는 기타 설치물에 대한 환기 시스템에 적용됩니다. 주방 및 관련 공간은 식사를 준비하는 특별한 공간이며, 식기 및 장비를 세척하고 청소하며 식품을 저장하는 곳입니다. 이 유럽 표준은 가정용 주방에서 사용되는 환기 시스템에는 적용되지 않습니다. 각 요구 사항의 확인 방법도 명시되어 있습니다. 그 외의 지침이나 대체 가능한 국가별 지침이 설치, 기기 요구 사항 및 검사, 유지 보수 및 운영에 대해 가능성이 있음을 유념해야 합니다.










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...