Standard Test Method for Determining the Fire-Test Response Characteristics of a Building Spandrel-Panel Assembly Due to External Spread of Fire

SIGNIFICANCE AND USE
5.1 This test method provides for the following measurements and evaluations:  
5.1.1 Ability of the spandrel-panel assembly to resist the passage of flames or hot gases sufficient to ignite a cotton pad, or be visible to an observer.  
5.1.2 Transmission of heat through, and above, the spandrel-panel assembly using heat flux and unexposed surface temperature measurements.  
5.2 This test method does not provide the following:  
5.2.1 This test method does not evaluate the fire propagation characteristics of exterior nonload-bearing wall assemblies containing combustible components, or flame spread over the test assembly.  
5.2.2 This test method does not evaluate the fire-test-response characteristics of the perimeter joint protection between the floor assembly and the exterior wall assembly. This is covered in Test Method E2307.  
5.2.3 Evaluation of the degree to which the spandrel-panel assembly contributes to the fire hazard by generation of smoke, toxic gases, or other products of combustion,  
5.2.4 Measurement of the degree of control or limitation of the passage of smoke or products of combustion through the spandrel-panel assembly,  
5.2.5 Measurement of flame spread over the surface of the spandrel-panel assembly or exterior wall assembly,  
5.2.6 Durability of the test specimen under actual service conditions, including the effects of cycled temperature,  
5.2.7 Effects of loads (for example, wind, seismic, etc.) on the spandrel-panel assembly established by this test method,  
5.2.8 Movement capabilities of the test specimen,  
5.2.9 Other attributes of the test specimen, such as wear resistance, chemical resistance, air infiltration, water-tightness, and so forth, and  
5.2.10 Lateral spread of flame from the compartment of fire origin to adjacent spaces.  
5.3 In this test method, the test specimens are subjected to one or more specific test conditions. When different test conditions are substituted or the end-use conditions are changed,...
SCOPE
1.1 This test method evaluates the fire-test response characteristics of a spandrel-panel assembly spanning the intersection of a floor assembly.  
1.2 This test method is used to assess the spandrel-panel assembly’s ability to impede spread of fire to the interior of the room or the story immediately above it via fire spread from the exterior of a building, and provide a quantitative measure of the fire hazard in terms of an I-Rating, T-Rating, and F-Rating from a specified set of fire conditions involving specific materials, products, or assemblies.  
1.3 This test evaluates the performance of the portions of the exterior wall installed between vertically adjacent window openings in multi-story buildings.  
1.4 This test method addresses the potential for fire spread to a single story immediately above the room of fire origin.  
1.5 The test method simulates a fire in a post-flashover condition in a compartment that is venting to the exterior through a window opening.  
1.6 The fire exposure conditions within the test room are those specified by this test method for the first 30 min of exposure and then conform to Test Methods E119 time-temperature curve for the remainder of the test. The fire exposure on the exterior surface of the test specimen comprises both the exposure from the fire plume exiting the window opening of the test room and the exterior burner, although the fire exposure on the exterior surface of the test assembly is not equivalent to that of Test Methods E119.  
1.7 This test method specifies the heating conditions, methods of test, and criteria for evaluation of a building’s spandrel-panel assembly. Specimens are not tested using any super-imposed axial load.  
1.8 Test results establish the performance of the spandrel-panel assembly during the fire-exposure period and shall not be construed as having determined the suitability of a spandrel-panel assembly for use after that exposure.  
1.9 ...

General Information

Status
Published
Publication Date
31-Oct-2023
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E2874-23 - Standard Test Method for Determining the Fire-Test Response Characteristics of a Building Spandrel-Panel Assembly Due to External Spread of Fire
English language
18 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E2874-23 - Standard Test Method for Determining the Fire-Test Response Characteristics of a Building Spandrel-Panel Assembly Due to External Spread of Fire
English language
18 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: E2874 − 23 An American National Standard
Standard Test Method for
Determining the Fire-Test Response Characteristics of a
Building Spandrel-Panel Assembly Due to External Spread
1
of Fire
This standard is issued under the fixed designation E2874; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
This standard test method evaluates the ability of the spandrel-panel assembly in an exterior wall
assembly, with or without glazing, to impede the spread of fire to the interior of the room or the story
immediately above it via fire spread from the exterior of a building. A building spandrel-panel
assembly includes the exterior wall spandrel-panel assembly and any glazing. The spandrel-panel
assembly is a unique building construction detail not addressed by other fire test methods.
A building’s spandrel-panel assembly impedes the vertical spread of fire from the floor of origin to
the floor immediately above it, via an exterior fire exposure.
This test method describes criteria used to determine the fire performance of spandrel-panel
assemblies when subjected to standard fire exposure conditions. This test method is intended to
simulate a possible fire exposure due to a post flashover compartment fire venting through an opening,
onto the exterior surface of a spandrel-panel assembly.
1. Scope 1.6 The fire exposure conditions within the test room are
those specified by this test method for the first 30 min of
1.1 This test method evaluates the fire-test response charac-
exposure and then conform to Test Methods E119 time-
teristics of a spandrel-panel assembly spanning the intersection
temperature curve for the remainder of the test. The fire
of a floor assembly.
exposure on the exterior surface of the test specimen comprises
1.2 This test method is used to assess the spandrel-panel
both the exposure from the fire plume exiting the window
assembly’s ability to impede spread of fire to the interior of the
opening of the test room and the exterior burner, although the
room or the story immediately above it via fire spread from the
fire exposure on the exterior surface of the test assembly is not
exterior of a building, and provide a quantitative measure of
equivalent to that of Test Methods E119.
the fire hazard in terms of an I-Rating, T-Rating, and F-Rating
1.7 This test method specifies the heating conditions, meth-
from a specified set of fire conditions involving specific
ods of test, and criteria for evaluation of a building’s spandrel-
materials, products, or assemblies.
panel assembly. Specimens are not tested using any super-
1.3 This test evaluates the performance of the portions of
imposed axial load.
the exterior wall installed between vertically adjacent window
1.8 Test results establish the performance of the spandrel-
openings in multi-story buildings.
panel assembly during the fire-exposure period and shall not be
1.4 This test method addresses the potential for fire spread
construed as having determined the suitability of a spandrel-
to a single story immediately above the room of fire origin.
panel assembly for use after that exposure.
1.5 The test method simulates a fire in a post-flashover
1.9 This test method does not provide quantitative informa-
condition in a compartment that is venting to the exterior
tion about the spandrel-panel assembly relative to the rate of
through a window opening.
leakage of smoke or gases, or both.
1.9.1 This test method does not evaluate the fire-test-
response characteristics of perimeter joint protection between
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire
the floor assembly and the exterior wall assembly. This is
Standards and is the direct responsibility of Subcommittee E05.11 on Fire
Resistance. covered in Test Method E2307.
Current edition approved Nov. 1, 2023. Published December 2023. Originally
1.10 This test method does not evaluate the fire-test-
approved in 2019. Last previous edition approved in 2019 as E2874 – 19. DOI:
10.1520/E2874-23. response characteristics or fire propagation propensity of
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2874 − 23
material installed on, or within, exterior non-load-bearing wall Bearing Wall Assemblies Containing Combustible Com-
assemblies containing combustible components. This is cov- ponents Using the Inte
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E2874 − 19 E2874 − 23 An American National Standard
Standard Test Method for
Determining the Fire-Test Response Characteristics of a
Building Spandrel-Panel Assembly Due to External Spread
1
of Fire
This standard is issued under the fixed designation E2874; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
This standard test method evaluates the ability of the spandrel-panel assembly in an exterior wall
assembly, with or without glazing, to impede the spread of fire to the interior of the room or the story
immediately above it via fire spread from the exterior of a building. A building spandrel-panel
assembly includes the exterior wall spandrel-panel assembly and any glazing. The spandrel-panel
assembly is a unique building construction detail not addressed by other fire test methods.
A building’s spandrel-panel assembly impedes the vertical spread of fire from the floor of origin to
the floor immediately above it, via an exterior fire exposure.
This test method describes criteria used to determine the fire performance of spandrel-panel
assemblies when subjected to standard fire exposure conditions. This test method is intended to
simulate a possible fire exposure due to a post flashover compartment fire venting through an opening,
onto the exterior surface of a spandrel-panel assembly.
1. Scope
1.1 This test method evaluates the fire-test response characteristics of a spandrel-panel assembly spanning the intersection of a
floor assembly.
1.2 This test method is used to assess the spandrel-panel assembly’s ability to impede spread of fire to the interior of the room
or the story immediately above it via fire spread from the exterior of a building, and provide a quantitative measure of the fire
hazard in terms of an I-Rating, T-Rating, and F-Rating from a specified set of fire conditions involving specific materials, products,
or assemblies.
1.3 This test evaluates the performance of the portions of the exterior wall installed between vertically adjacent window openings
in multi-story buildings.
1.4 This test method addresses the potential for fire spread to a single story immediately above the room of fire origin.
1.5 The test method simulates a fire in a post-flashover condition in a compartment that is venting to the exterior through a window
opening.
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.
Current edition approved Feb. 1, 2019Nov. 1, 2023. Published March 2019December 2023. Originally approved in 2019. Last previous edition approved in 2019 as
E2874 – 19. DOI: 10.1520/E2874-19.10.1520/E2874-23.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2874 − 23
1.6 The fire exposure conditions within the test room are those specified by this test method for the first 30 min of exposure and
then conform to Test Methods E119 time-temperature curve for the remainder of the test. The fire exposure on the exterior surface
of the test specimen comprises both the exposure from the fire plume exiting the window opening of the test room and the exterior
burner, although the fire exposure on the exterior surface of the test assembly is not equivalent to that of Test Methods E119.
1.7 This test method specifies the heating conditions, methods of test, and criteria for evaluation of a building’s spandrel-panel
assembly. Specimens are not tested using any super-imposed axial load.
1.8 Test results establish the performance of the spandrel-panel assembly during the fire-exposure period and shall not be
construed as having determined the suitability of a spandrel-panel assembly for use after that exposure.
1.9 This test method does not provide quantitative information about the spandrel-panel assembly relative to the rate of leakage
of smoke or gases, or both.
1.9.1 This test method does not evaluate the fire-test-response characteristics of perimeter joint protection between the floor
assembly and the exterior wall assembly. This is covered in Test Method E2307.
1.10 This test method does not evaluate the fire-test-response characteristics or fire propagation propensity of material installed
on, or within, exter
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.