Standard Test Method for Shock Testing of Structural Insulation of A-Class Divisions Constructed of Steel or Aluminum

SIGNIFICANCE AND USE
4.1 This test method evaluates the ability of a non-combustible passive fire protection system installed on structural divisions on commercial ships to function after shock loading.  
4.2 The shock loading is accomplished by conducting impact testing of a test specimen consisting of insulation on a standard steel or aluminum structural core installed on a medium weight shock test machine.  
4.3 Following the shock testing the shocked test specimen and an unshocked test specimen are tested for fire resistance. Both shocked and unshocked test specimens are installed side-by-side in a fixture and fire tested at the same time.  
4.4 The fire resistance for both specimens is measured and recorded.  
4.5 Other passive fire protection systems using the same insulation materials and attachment methods and having lower fire resistance ratings will be accepted without additional shock testing.
SCOPE
1.1 The purpose of the specification is to evaluate insulation installed on steel or aluminum structural division as defined in IMO resolution A.754 (18) to ensure the insulation is not degraded in the event of a shock.  
1.2 The non-combustible passive fire protection insulation shall be installed, which will meet the highest level of commercial fire resistance expected. Lower levels of fire resistance will be allowed without additional shock testing.  
1.3 This test method is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of the materials, products or assemblies under actual fire conditions.  
1.4 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.  
1.5 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Apr-2013
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM F2877-13 - Standard Test Method for Shock Testing of Structural Insulation of A-Class Divisions Constructed of Steel or Aluminum
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM F2877-13 - Standard Test Method for Shock Testing of Structural Insulation of A-Class Divisions Constructed of Steel or Aluminum
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F2877 − 13 AnAmerican National Standard
Standard Test Method for
Shock Testing of Structural Insulation of A-Class Divisions
1
Constructed of Steel or Aluminum
This standard is issued under the fixed designation F2877; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
Passive fire protection materials have been required and used on commercial ships for decades.The
passive systems include the non-combustible insulation material and its means of attachment to steel
or aluminum divisions. The passive system has been evaluated in a standard fire test using a standard
steel or aluminum structural core. No impact loading has been required prior to testing for fire
resistance.
The United States Navy requires shock testing of passive fire protection prior to fire resistance
testing; this test is defined in MIL-STD-3020, Fire Resistance of U.S. Naval Surface Ships, 7
November, 2007. The technology to economically shock test the passive fire protection systems was
developed 50 years ago, and equipment in commercial laboratories is available.
After the terrorist attack on September 11, 2001 it is our responsibility that we add a level of shock
2
protection to our passive fire protection systems on commercial ships where appropriate. Many of the
passive fire protection systems used today are mechanically fastened and will perform the intended
function after a shock event.
Passive fire protection insulation may have thermal or acoustic treatments added to the insulated
division. These treatments add mass to the fire protection system and their effect on shock is not
included in this specification.
TABLE OF CONTENTS
Introduction
Section 1 Scope
Section 2 Referenced Documents
Section 3 Terminology
Section 4 Significance and Use
Section 5 Shock Test Prior to Fire Resistance
Test
Section 6 Criteria to Evaluate Shock Test
Specimen
Section 7 Post Shock Fire Resistance Test
Section 8 Criteria to Evaluate the Fire
Resistance of the Shock Test
Specimen
Section 9 Test Report
Section 10 Precision and Bias
Section 11 Key Words
1. Scope
1
1.1 The purpose of the specification is to evaluate insulation
This test method is under the jurisdiction of ASTM Committee F25 on Ships
and Marine Technology and is the direct responsibility of Subcommittee F25.02 on
installed on steel or aluminum structural division as defined in
Insulation/Processes.
IMO resolution A.754 (18) to ensure the insulation is not
Current edition approved May 1, 2013. Published May 2013. Originally
ε1
degraded in the event of a shock.
approved in 2011. Last previous edition approved in 2011 as F2877 – 11 .
DOI:10.1520/F2877-13.
2
JOM, 53(12), 2001 pp 8-12 and www.nist.gov/public.affairs/releases/wtc-
briefing-april0505.htm
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F2877 − 13
1.2 The non-combustible passive fire protection insulation rial;
shall be installed, which will meet the highest level of (b) They are suitably stiffened;
commercial fire resistance expected. Lower levels of fire (c) They are insulated with approved non-combustible ma-
resistance will be allowed without additional shock testing. terials such that the average temperature of the unexposed side
will not rise more than 140°C above the original temperature,
1.3 This test method is used to measure and describe the
nor will the temperature, at any one point, including any joint,
responseofmaterials,products,orassembliestoheatandflame
rise more than 180°C above the original temperature, with the
under controlled conditions, but does not by itself incorporate
time listed below:
all factors required for fire-hazard or fire-risk assessment of the
class “A-60” 60 min
materials, products or assemblies under actual fire conditions.
class “A-30” 30 min
class “A-15” 15 min
1.4 Fire testing is inherently hazardous. Adequate safe-
class “A-0” 0 min
guards for personnel and property shall be employed in
conducting these tests.
(d) They are so constructed as to be capable of preventing
the passage of smoke and flame to the end of the one-hour
1.5 The values stated in either SI units or inch-pound units
standard fire test; and
are to be regarded separately as standard. The values stated in
(e) The Administration required a test of a prototype bulk-
each system may not be exact equivalents; therefore, each
head or deck in accordance with the Fire Test Procedures
system shall be used independently of the other. Combining
Code to ensure that it meets the above requirements for in-
v
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: F2877 − 11 F2877 − 13 An American National Standard
Standard Test Method for
Shock Testing of Structural Insulation of A-Class Divisions
1
Constructed of Steel or Aluminum
This standard is issued under the fixed designation F2877; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
ε NOTE—Editorially corrected the title in February 2012.
INTRODUCTION
Passive fire protection materials have been required and used on commercial ships for decades. The
passive systems include the non-combustible insulation material and its means of attachment to steel
or aluminum divisions. The passive system has been evaluated in a standard fire test using a standard
steel or aluminum structural core. No impact loading has been required prior to testing for fire
resistance.
The United States Navy requires shock testing of passive fire protection prior to fire resistance
testing; this test is defined in MIL-STD-3020, Fire Resistance of U.S. Naval Surface Ships, 7
November, 2007. The technology to economically shock test the passive fire protection systems was
developed 50 years ago, and equipment in commercial laboratories is available.
After the terrorist attack on September 11, 2001 it is our responsibility that we add a level of shock
2
protection to our passive fire protection systems on commercial ships where appropriate. Many of the
passive fire protection systems used today are mechanically fastened and will perform the intended
function after a shock event.
Passive fire protection insulation may have thermal or acoustic treatments added to the insulated
division. These treatments add mass to the fire protection system and their effect on shock is not
included in this specification.
TABLE OF CONTENTS
TABLE OF CONTENTS
Introduction
Section 1 Scope
Section 2 Referenced Documents
Section 3 Terminology
Section 4 Significance and Use
Section 5 Shock Test Prior to Fire
Resistance Test
Section 6 Criteria to Evaluate Shock Test
Specimen
Section 7 Post Shock Fire Resistance Test
Section 8 Criteria to Evaluate the Fire
Resistance of the Shock Test
Specimen
Section 9 Test Report
Section Precision and Bias
10
Section Key Words
11
1. Scope
1.1 The purpose of the specification is to evaluate insulation installed on steel or aluminum structural division as defined in IMO
resolution A.754 (18) to ensure the insulation is not degraded in the event of a shock.
1
This test method is under the jurisdiction of ASTM Committee F25 on Ships and Marine Technology and is the direct responsibility of Subcommittee F25.02 on
Insulation/Processes.
Current edition approved Jan. 1, 2011May 1, 2013. Published March 2011May 2013. DOI:10.1520/F2877-11. Originally approved in 2011. Last previous edition approved
ε1
in 2011 as F2877 – 11 . DOI:10.1520/F2877-13.
2
JOM, 53(12), 2001 pp 8-12 and www.nist.gov/public.affairs/releases/wtc-briefing-april0505.htm
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F2877 − 13
1.2 The non-combustible passive fire protection insulation shall be installed, which will meet the highest level of commercial
fire resistance expected. Lower levels of fire resistance will be allowed without additional shock testing.
1.3 This test method is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of the materials,
products or assemblies under actual fire conditions.
1.4 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these
tests.
1.5 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each
system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the
two systems may result in non-conformance with the standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limi
...