Cables of rated voltages up to and including 450/750 V and having cross-linked insulation - Part 10: EPR insulated and polyurethane sheathed flexible cables

This Part 10 of the HD details the particular requirements for ethylene-propylene rubber insulated, and thermoplastic polyurethane sheathed cable for a maximum conductor temperature of 90 °C and lowest handling temperature of –40 °C. Each cable shall comply with the appropriate requirements given in Part 1 of this HD and the particular requirements of this part. NOTE The overall dimensions of the cables in this part of HD 22 have been calculated in accordance with EN 60719.

Starkstromleitungen mit vernetzter Isolierhülle für Nennspannungen bis 450/750 V - Teil 10: EPR-isolierte flexible Starkstromleitungen mit Polyurethanmantel

Dieser Teil 10 des HD enthält besondere Bestimmungen der Ethylen-Propylen-Gummi isolierte und mit thermoplastischem Polyurethan ummantelten Leitungen mit einer maximalen Leitertemperatur von 90 °C und einer niedrigsten Gebrauchstemperatur von -40 °C. Alle Leitungen müssen mit den in Teil 1 von diesem HD angegebenen Anforderungen und den besonderen Anforderungen dieses Teils übereinstimmen. ANMERKUNG Die Außenmaße der Leitungen nach diesem Teil des HD 22 sind in Übereinstimmung mit EN 60719 errechnet worden.

Conducteurs et câbles isolés avec des matériaux réticulés de tension assignée au plus égale à 450/750 V - Partie 10: Câbles souples à isolation EPR et gaine polyuréthane

La présente Partie 10 du HD précise les spécifications particulières applicables aux câbles isolés au caoutchouc d'éthylène propylène, sous gaine en polyuréthane thermoplastique pour une température maximale de l'âme de 90°C et une température de manutention la plus basse de -40°C. Les câbles doivent répondre aux prescriptions appropriées données dans la Partie 1 de ce HD et aux prescriptions particulières figurant dans la présente partie. NOTE Les dimensions extérieures de la présente partie du HD 22 ont été calculées conformément à la CEI 60719.

Kabli z omreženo izolacijo za naznačene napetosti do vključno 450/750 V – 10. del: Zvijavi kabli, izolirani z EPR in oplaščeni z poliuretanom

Ta standard označuje posebne zahteve za termoplastične, zvijave kable, izolirane z EPR in oplaščene z poliuretanom pri najvišje mogoči prevodni temperaturi  90 0C in pri najnižje mogoči temperaturi - 40 oC.

General Information

Status
Withdrawn
Publication Date
21-Feb-2007
Withdrawal Date
30-Nov-2008
Technical Committee
Drafting Committee
Parallel Committee
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
17-Jan-2014
Completion Date
17-Jan-2014

Relations

Buy Standard

Standardization document
HD 22.10 S2:2007
English language
13 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-junij-2007
1DGRPHãþD
SIST HD 22.10 S1:1998
SIST HD 22.10 S1:1998/A1:1999
.DEOL]RPUHåHQRL]RODFLMR]DQD]QDþHQHQDSHWRVWLGRYNOMXþQR9±GHO
=YLMDYLNDEOLL]ROLUDQL](35LQRSODãþHQL]SROLXUHWDQRP
Cables of rated voltages up to and including 450/750 V and having cross-linked
insulation -- Part 10: EPR insulated and polyurethane sheathed flexible cables
Starkstromleitungen mit vernetzter Isolierhülle für Nennspannungen bis 450/750 V - Teil
10: EPR-isolierte flexible Starkstromleitungen mit Polyurethanmantel
Conducteurs et câbles isolés avec des matériaux réticulés de tension assignée au plus
égale a 450/750 V - Partie 10: Câbles souples a isolation EPR et gaine polyuréthane
Ta slovenski standard je istoveten z: HD 22.10 S2:2007
ICS:
29.060.20 Kabli Cables
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

HARMONIZATION DOCUMENT
HD 22.10 S2
DOCUMENT D'HARMONISATION
February 2007
HARMONISIERUNGSDOKUMENT
ICS 29.060.20 Supersedes HD 22.10 S1:1994 + A1:1999

English version
Cables of rated voltages up to and including 450/750 V
and having cross-linked insulation -
Part 10: EPR insulated and polyurethane sheathed flexible cables

Conducteurs et câbles isolés avec  Starkstromleitungen mit vernetzter
des matériaux réticulés de tension Isolierhülle für Nennspannungen
assignée au plus égale à 450/750 V - bis 450/750 V -
Partie 10: Câbles souples Teil 10: EPR-isolierte flexible
à isolation EPR Starkstromleitungen
et gaine polyuréthane mit Polyurethanmantel

This Harmonization Document was approved by CENELEC on 2006-12-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this
Harmonization Document at national level.

Up-to-date lists and bibliographical references concerning such national implementations may be obtained on
application to the Central Secretariat or to any CENELEC member.

This Harmonization Document exists in three official versions (English, French, German).

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2007 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 22.10 S2:2007 E
Foreword
This Harmonization Document was prepared by the Technical Committee CENELEC TC 20, Electric
cables.
The text of the draft was submitted to the Unique Acceptance Procedure and was approved by CENELEC
as HD 22.10 S2 on 2006-12-01.
This Harmonization Document supersedes HD 22.10 S1:1994 + A1:1999.
The following dates were fixed:
– latest date by which the existence of the HD
(doa) 2007-06-01
has to be announced at national level
– latest date by which the HD has to be implemented
at national level by publication of a harmonized
national standard or by endorsement (dop) 2007-12-01
– latest date by which the national standards conflicting
with the HD have to be withdrawn (dow) 2008-12-01

HD 22, Cables of rated voltages up to and including 450/750 V and having cross-linked
insulation, now has the following parts:

HD 22.1 S4 General requirements

1)
HD 22.2 S3 Test methods
HD 22.3 S4 Heat resistant silicone rubber insulated cables
HD 22.4 S4 Cords and flexible cables
HD 22.5 (Spare)
HD 22.6 S2 Arc welding cables
HD 22.7 S2 Cables with increased heat resistance for internal wiring for a conductor
temperature of 110 °C
HD 22.8 S2 Polychloroprene or equivalent synthetic elastomer sheathed cable for
decorative chains
HD 22.9 S3 Single core halogen-free non-sheathed cables for fixed wiring having low
emission of smoke
HD 22.10 S2 EPR insulated and polyurethane sheathed flexible cables
HD 22.11 S2 EVA cords and flexible cables
HD 22.12 S2 Heat resistant EPR cords and flexible cables
HD 22.13 S2 Halogen-free flexible cables having low emission of smoke
HD 22.14 S3 Cords for applications requiring high flexibility
HD 22.15 S2 Multicore cables insulated and sheathed with heat resistant silicone
rubber
HD 22.16 S2 Water resistant polychloroprene or equivalent synthetic elastomer
sheathed cables
__________
1)
HD 22.2 has been superseded by EN 50395 and EN 50396

- 3 - HD 22.10 S2:2007
Contents
Page
1 Scope.4
2 Normative references.4
3 EPR insulated and polyurethane sheathed flexible cable (300/500 V) .4
3.1 Code designation.4
3.2 Rated voltage.4
3.3 Construction.4
3.4 Tests.5
3.5 Guide to use (informative) .5
4 EPR insulated and polyurethane sheathed flexible cable (450/750 V) .8
4.1 Code designation.8
4.2 Rated voltage.8
4.3 Construction.8
4.4 Tests.9
4.5 Guide to use (informative) .9
Annex A (normative) Requirements for compatibility test .12
Bibliography.13
Table 1 – Dimensions of Type H05BQ-F .6
Table 2 – Tests for type H05BQ-F.7
Table 3 – Dimensions of Type H07BQ-F .10
Table 4 – Tests for type H07BQ-F.11
Table A.1 – Requirements .12

1 Scope
This Part 10 of the HD details the particular requirements for ethylene-propylene rubber
insulated, and thermoplastic polyurethane sheathed cable for a maximum conductor temperature
of 90 °C and lowest handling temperature of –40 °C.

Each cable shall comply with the appropriate requirements given in Part 1 of this HD and the
particular requirements of this part.

NOTE The overall dimensions of the cables in this part of HD 22 have been calculated in accordance with EN 60719.

2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 50363-1 Insulating, sheathing and covering materials for low voltage energy
cables –
Part 1: Cross-linked elastomeric insulating compounds
EN 50363-10-2 Insulating, sheathing and covering materials for low voltage energy
cables –
Part 10-2: Miscellaneous sheathing compounds – Thermoplastic
polyurethane
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non-electrical test methods for low voltage energy cables
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60811 series Insulating and sheathing materials of electric and optical cables –
Common test methods (IEC 60811 series)

3 EPR insulated and polyurethane sheathed flexible cable (300/500 V)
3.1 Code designation
H05BQ-F.
3.2 Rated voltage
300/500 V.
3.3 Construction
3.3.1 Conductor
Number of conductors: 2, 3, 4 or 5.
The conductors shall be in accordance with the requirements given in EN 60228 for Class 5
conductors. The wires may be plain or tinned.

3.3.2 Separator
A separator of suitable material may be applied around each conductor.

3.3.3 Insulation
The insulation shall be rubber compound of type EI 6 to EN 50363-1 applied around each
conductor.
The insulation shall be applied by extrusion.

- 5 - HD 22.10 S2:2007
The insulation thickness shall comply with the specified value given in Table 1, column 2.

3.3.4 Assembly of cores and filler, if any
The cores shall be twisted together.

A centre filler may be used.
3.3.5 Inner covering
The twisted cores may be covered by either:

- an extruded inner covering of an non-crosslinked rubber or plastic compound; or by
- a separating tape of suitable material, which may be combined with separate fillers.

Alternatively the sheath may fill the spaces between cores.
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.