EN 50525-3-21:2011
(Main)Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-21: Cables with special fire performance - Flexible cables with halogen-free crosslinked insulation, and low emission of smoke
Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-21: Cables with special fire performance - Flexible cables with halogen-free crosslinked insulation, and low emission of smoke
EN 50525-3-21 applies to flexible cables, insulated and sheathed with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltage U0/U 450/750 V. The cables are intended for the connection of equipment and machinery to the fixed supply. The maximum conductor operating temperature for each of the cables in this standard is 90 °C. NOTE 2 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-21 should be read in conjunction with EN 50525-1, which specifies general requirements.
Kabel und Leitungen - Starkstromleitungen mit Nennspannungen bis 450/750 V (U0/U) - Teil 3-21: Starkstromleitungen mit verbessertem Verhalten im Brandfall - Flexible halogenfreie, raucharme Leitungen mit vernetzter Isolierung
Câbles électriques - Câbles d’énergie basse tension de tension assignée au plus égale à 450/750 V (U0/U) - Partie 3-21: Câbles à performances spéciales au feu - Câbles souples isolés en matériau élastomère réticulé sans halogène, à faible dégagement de fumée
Električni kabli - Nizkonapetostni energetski kabli z naznačeno napetostjo do vključno 450/750 V (U0/U) - 3-21. del: Kabli s posebnimi ognjevarnimi lastnostmi - Zvijavi kabli z zamreženo izolacijo brez halogenov in z nizko emisijo dima
EN 50525-3-21 velja za zvijave kable, ki so oplaščeni in imajo zamreženo izolacijo brez halogenov ter nizko emisijo dima in korozivnih plinov pri izpostavljenosti ognju. Nizka emisija korozivnih plinov se preverja kot del kontrole, da ni prisotnih halogenov. Ti kabli imajo nazivno napetost U0/U do vključno 450/750 V. Povezujejo opremo in stroje s fiksnim napajanjem. Maksimalna delovna temperatura pretvornika za vsakega od kablov iz tega standarda je 90 °C.
General Information
Relations
Overview
EN 50525-3-21:2011 is a CLC (CENELEC) European standard for low voltage energy cables (rated U0/U up to and including 450/750 V) with special fire performance. It covers flexible cables with halogen‑free cross‑linked insulation and sheath that give low emission of smoke and corrosive gases when exposed to fire. These cables are intended primarily for the connection of equipment and machinery to fixed supplies and have a maximum conductor operating temperature of 90 °C. The common CENELEC code marking for cables in this standard is H07ZZ‑F.
Key topics and technical requirements
- Scope & intended use: Flexible power cables for equipment/machinery connections at low voltage (U0/U 450/750 V).
- Materials:
- Insulation: cross‑linked compound Type EI 8 per EN 50363-5.
- Sheath: cross‑linked compound Type EM 8 (single layer) or EM 8/EM 10 (two layers) per EN 50363-6.
- Constructional requirements:
- Conductors: class 5 (flexible) per EN 60228.
- Defined conductor size ranges (examples from the standard):
- Single core: 1.5 mm² to 630 mm²
- 2‑ and 5‑core: 1.0 mm² to 25 mm²
- 3‑ and 4‑core: 1.0 mm² to 300 mm²
- Fire and safety performance:
- Low smoke measurement according to EN 61034‑2 (minimum 60% light transmittance).
- Absence of halogens / low corrosive gas emission checked per EN 50525‑1 (Annex B).
- Vertical flame propagation tests: EN 60332‑1‑2 (single cable) and EN 60332‑3‑24 (bunched cables).
- Testing and verification:
- Annex A lists mandatory electrical, mechanical, material and fire tests (EN 50395, EN 50396, EN 60811 series).
- Compatibility, thermal ageing and low‑temperature impact tests are specified.
- Marking: Cable marking to comply with EN 50525‑1; use the H07ZZ‑F code.
Applications and who uses this standard
- Practical uses: specification and procurement of flexible power cables where halogen‑free, low‑smoke behavior is required - for safe equipment and machinery connections in industrial and commercial installations.
- Primary users:
- Cable manufacturers and material suppliers
- OEMs, machine builders and panel producers
- Electrical designers, specifiers and consultants
- Installers, testing laboratories and compliance officers
- Safety and facility managers assessing fire performance of cabling
Related standards
- EN 50525‑1 - General requirements for low voltage energy cables (must be read in conjunction)
- EN 50363‑5 / EN 50363‑6 - Material specifications for halogen‑free cross‑linked compounds
- EN 60332‑1‑2, EN 60332‑3‑24 - Flame propagation tests
- EN 61034‑2 - Smoke density measurement
- EN 60228 - Conductor class definitions
- EN 60811 series - Common cable test methods
EN 50525‑3‑21 helps ensure flexible low‑voltage cables meet harmonized European requirements for fire safety, material performance and testing - important for specifying reliable, low‑smoke halogen‑free cabling solutions.
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2011
(OHNWULþQLNDEOL1L]NRQDSHWRVWQLHQHUJHWVNLNDEOL]QD]QDþHQRQDSHWRVWMRGR
YNOMXþQR988GHO.DEOLVSRVHEQLPLRJQMHYDUQLPLODVWQRVWPL
=YLMDYLNDEOL]]DPUHåHQRL]RODFLMREUH]KDORJHQRYLQ]QL]NRHPLVLMRGLPD
Electric cables - Low voltage energy cables of rated voltages up to and including 450/750
V (U0/U) - Part 3-21: Cables with special fire performance - Flexible cables with halogen-
free crosslinked insulation, and low emission of smoke
Kabel und Leitungen - Starkstromleitungen mit Nennspannungen bis 450/750 V (U0/U) -
Teil 3-21: Leitungen mit verbessertem Verhalten im Brandfall - Flexible halogenfreie,
raucharme Leitungen mit vernetzter Isolierung
Câbles électriques - Câbles d’énergie basse tension de tension assignée au plus égale à
450/750 V (U0/U) - Partie 3-21: Câbles à performances spéciales au feu - Câbles
souples isolés en matériau élastomère réticulé sans halogène, à faible dégagement de
fumée
Ta slovenski standard je istoveten z: EN 50525-3-21:2011
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
29.060.20 Kabli Cables
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 50525-3-21
NORME EUROPÉENNE
May 2011
EUROPÄISCHE NORM
ICS 29.060.20 Supersedes HD 22.13 S2:2007
English version
Electric cables -
Low voltage energy cables of rated voltages up to and including 450/750 V
(U /U) -
Part 3-21: Cables with special fire performance -
Flexible cables with halogen-free crosslinked insulation, and low emission
of smoke
Câbles électriques - Kabel und Leitungen -
Câbles d’énergie basse tension de tension Starkstromleitungen mit Nennspannungen
assignée au plus égale à 450/750 V bis 450/750 V (U /U) -
(U /U) - Teil 3-21: Starkstromleitungen mit
Partie 3-21: Câbles à performances verbessertem Verhalten im Brandfall -
spéciales au feu - Flexible halogenfreie, raucharme
Câbles souples isolés en matériau Leitungen mit vernetzter Isolierung
élastomère réticulé sans halogène, à
faible dégagement de fumée
This European Standard was approved by CENELEC on 2011-01-17. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50525-3-21:2011 E
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric
cables.
The text of the draft was submitted to the formal vote and was approved by CENELEC as
EN 50525-3-21 on 2011-01-17.
This document, which is one of a multipart series, supersedes HD 22.13 S2:2007.
Attention is drawn to the possibility that some of the elements of this document may be the
subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any
or all such patent rights.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-01-17
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2014-01-17
___________
- 3 - EN 50525-3-21:2011
Contents
Page
1 Scope . 4
2 Normative references . 4
3 Terms and definitions . 5
4 Heat resistant cables (90 °C) . 5
4.1 Heavy duty cables – H07ZZ-F . 5
4.2 Heavy duty multicore cables – H07ZZ-F . 6
Annex A (normative) Tests for cables to EN 50525-3-21 . 8
Annex B (normative) General data . 9
Annex C (normative) Requirements for compatibility test . 13
C.1 Test conditions . 13
C.2 Requirements . 13
Bibliography . 14
Tables
Table A.1 . 8
Table B.1 . 9
Table B.2 . 12
Table C.1 − Requirements . 13
1 Scope
EN 50525-3-21 applies to flexible cables, insulated and sheathed with halogen-free
crosslinked compound and having low emission of smoke and corrosive gases when exposed
to fire.
NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as
part of the check for absence of halogens (see Annex B of EN 50525-1).
The cables are of rated voltage U /U 450/750 V.
The cables are intended for the connection of equipment and machinery to the fixed supply.
The maximum conductor operating temperature for each of the cables in this standard is
90 °C.
NOTE 2 HD 516 contains extensive guidance on the safe use of cables in this standard.
This EN 50525-3-21 should be read in conjunction with EN 50525-1, which specifies general
requirements.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
NOTE One or more references to the standards below are in respect of a specific sub-division of that standard,
for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times,
the latest version applies.
EN 50363-5 Insulating, sheathing and covering materials for low voltage energy
cables - Part 5: Halogen-free, cross-linked insulating compounds
EN 50363-6 Insulating, sheathing and covering materials for low voltage energy
cables - Part 6: Halogen-free, cross-linked sheathing compounds
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non electrical test methods for low voltage energy cables
EN 50525-1 Electric cables - Low voltage energy cables of rated voltages up to
and including 450/750 V (U /U) - Part 1: General requirements
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
Part 1-2: Test for vertical flame propagation for a single insulated
wire or cable - Procedure for 1 kW pre-mixed flame (IEC 60332-1-2)
EN 60332-3-24 Tests on electric and optical fibre cables under fire conditions –
Part 3-24: Test for vertical flame spread of vertically-mounted
bunched wires or cables - Category C (IEC 60332-3-24)
EN 60811-1-2 Insulating and sheathing materials of electric and optical cables -
Common test methods - Part 1-2: General application - Thermal
ageing methods (IEC 60811-1-2)
EN 60811-1-4 Insulating and sheathing materials of electric and optical cables -
Common test methods - Part 1-4: General application - Tests at low
temperature (IEC 60811-1-4)
EN 61034-2 Measurement of smoke density of cables burning under defined
conditions - Part 2: Test procedure and requirements (IEC 61034-2)
- 5 - EN 50525-3-21:2011
3 Terms and definitions
For the purposes of this document the terms and definitions given in Clause 3 of EN 50525-1
apply.
4 Heat resistant cables (90 °C)
4.1 Heavy duty cables – H07ZZ-F
4.1.1 Construction
4.1.1.1 Conductor
The conductor shall be class 5, according to EN 60228.
4.1.1.2 Sizes of cable
The sizes of cable shall be:
2 2
- single core – 1,5 mm to 630 mm ;
2 2
- 2 and 5 core – 1,0 mm to 25 mm ;
2 2
- 3 and 4 core – 1,0 mm to 300 mm .
4.1.1.3 Insulation
The insulation shall be a cross-linked compound, Type EI 8 to EN 50363-5, applied around
each conductor.
4.1.1.4 Assembly
The cores of cables having two to five cores shall be twisted together.
NOTE 1 A centre filler may be used.
NOTE 2 A tape may be applied around the core assembly before application of the sheath.
4.1.1.5 Sheath
The cores shall be covered with a sheath.
a) For cables with a specified sheath thickness up to and including 2,4 mm:
1) sheath in a single layer, cross-linked compound of type EM 8 to EN 50363-6.
b) For cables with a specified sheath thickness greater than 2,4 mm:
1) sheath either in a single layer, cross-linked compound of type EM 8 to EN 50363-6;
2) or in two layers, with the inner layer made of one of the cross-linked compounds
type EM 8 or EM 10 to EN 50363-6 and the outer layer of the cross-linked
compound type EM 8 to EN 50363-6.
The sheath applied in a single layer or the inner layer of the sheath in two layers shall, for
cables with two to five cores, fill the spaces between the cores. Where a tape of suitable
material is applied around the core assembly (see NOTE 2 to 4.1.1.4) this requirement shall
not apply, provided that the finished cables shall not have any substantial cavity in the outer
interstices between the cores.
4.1.1.6 Marking
The cable shall be marked with the CENELEC code H07ZZ-F. The marking shall comply with
Clause 6 of EN 50525-1.
4.1.2 Requirements
Each cable shall comply with the appropriate requirements given in EN 50525-1, and the
particular requirements of this Part.
Testing shall be in accordance with Annex A.
The dimensions of the cables shall conform to Table B.1 for the relevant size.
The requirements to be met for the compatibility test shall be as given in Annex C.
When tested in accordance with the method and p
...
Frequently Asked Questions
EN 50525-3-21:2011 is a standard published by CLC. Its full title is "Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-21: Cables with special fire performance - Flexible cables with halogen-free crosslinked insulation, and low emission of smoke". This standard covers: EN 50525-3-21 applies to flexible cables, insulated and sheathed with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltage U0/U 450/750 V. The cables are intended for the connection of equipment and machinery to the fixed supply. The maximum conductor operating temperature for each of the cables in this standard is 90 °C. NOTE 2 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-21 should be read in conjunction with EN 50525-1, which specifies general requirements.
EN 50525-3-21 applies to flexible cables, insulated and sheathed with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltage U0/U 450/750 V. The cables are intended for the connection of equipment and machinery to the fixed supply. The maximum conductor operating temperature for each of the cables in this standard is 90 °C. NOTE 2 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-21 should be read in conjunction with EN 50525-1, which specifies general requirements.
EN 50525-3-21:2011 is classified under the following ICS (International Classification for Standards) categories: 29.060.20 - Cables. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 50525-3-21:2011 has the following relationships with other standards: It is inter standard links to HD 22.13 S2:2007, EN 50525-3-21:2011/AC:2013. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 50525-3-21:2011 is associated with the following European legislation: EU Directives/Regulations: 2006/95/EC, 2014/35/EU, 2014/53/EU. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
You can purchase EN 50525-3-21:2011 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CLC standards.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...