HD 603 S1:1994/A3:2007
(Amendment)Distribution cables of rated voltage 0,6/1 kV
Distribution cables of rated voltage 0,6/1 kV
Merged with HD 603 S1:1994/AA (pr=20605) for publication as one single document
Energieverteilungskabel mit Nennspannungen 0,6/1 kV
Câbles de distribution de tension nominale 0,6/1 kV
Distribucijski kabli za naznačeno napetost 0,6/1 kV
Opomba: Standard SIST HD 603 S1:1998/A3:2007 se uporablja, dokler ga ne razveljavi in nadomesti novi standard. Predviden datum razveljavitve HD 603 S1:1994/A3:2007 je bil 28.2.2017.
Nanaša se na kable za naznačeno napetost 0,6/1,0 kV, ki se uporabljajo v podzemnih distribucijskih sistemih. Posebne vrste kablov so označene v posebnih delih.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2007
'LVWULEXFLMVNLNDEOL]DQD]QDþHQRQDSHWRVWN9
Distribution cables of rated voltage 0,6/1 kV
Energieverteilungskabel mit Nennspannungen 0,6/1 kV
Câbles de distribution de tension nominale 0,6/1 kV
Ta slovenski standard je istoveten z: HD 603 S1:1994/A3:2007
ICS:
29.060.20 Kabli Cables
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
HARMONIZATION DOCUMENT
HD 603 S1/A3
DOCUMENT D'HARMONISATION
April 2007
HARMONISIERUNGSDOKUMENT
ICS 29.060.20
English version
Distribution cables of rated voltage 0,6/1 kV
Câbles de distribution Energieverteilungskabel
de tension nominale 0,6/1 kV mit Nennspannungen 0,6/1 kV
This amendment A3 modifies the Harmonization Document HD 603 S1:1994; it was approved by CENELEC on
2006-11-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for implementation of this amendment at national level.
Up-to-date lists and bibliographical references concerning such national implementations may be obtained on
application to the Central Secretariat or to any CENELEC member.
This amendment exists in one official version (English).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2007 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 603 S1:1994/A3:2007 E
Page 0-2
Foreword
This amendment to the Harmonization Document HD 603 S1:1994 has been prepared by WG9 of Technical
Committee CENELEC TC 20, Electric cables.
Part 1 has been revised, especially to include a Guide to use and selection of cables. A list of additions and
amendments to the particular sections of Parts 3 to 8 is given in this Part 0.
Users of HD 603 should note that, in the particular sections, cross-references have only been updated where
the complete section has been re-issued. This Part 0 of HD 603 contains a list of relevant changes to cross-
references which should be consulted in conjunction with the particular section. National standards
implementing one or more particular sections of HD 603 may update cross-references in advance of changes
to the published version of the HD.
The text of the draft, including a correction circulated as prAA, was submitted to the Unique Acceptance
Procedure and was approved by CENELEC as amendment A3 to HD 603 S1:1994 on 2006-11-01.
The following dates were fixed:
– latest date by which the existence of the amendment
has to be announced at national level (doa) 2007-05-01
– latest date by which the amendment has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2007-11-01
– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2009-11-01
By decision of the Technical Board (D81/139 extended by D104/118 & D114/076) this HD exists only in
English.
__________
Page 0-3
CONTENTS
(HD 603 S1:1994 with A1, A2 and A3)
1) 5) 11)
Part 1 GENERAL REQUIREMENTS
Part 3 PVC INSULATED CABLES - UNARMOURED
1) 11)
3A Cables with (type 3A-1) and without (type 3A-2) concentric conductor
11)
3B Cables without concentric conductor (type 3B-1)
3C Cables (type 3C-1) with concentric conductor, PVC sheath
3D Cables (type 3D-1) without concentric conductor, PE sheath
3E Cables (type 3E-1) without concentric conductor, PVC sheath
1) 4) 11)
3F Cables with (type 3F-1)and without (type 3F-2)concentric conductor
1) 5) 11)
3G Cables with (type 3G-1) and without (type 3G-2) concentric conductor
3H Cables with (type 3H-1)and without (type 3H-2) concentric conductor
1) 5) 10)
3I Cables with (type 3I-1) and without (types 3I-2 and 3I-3) concentric conductor
1) 11)
3J Cables with concentric conductor (type 3J-1)
3K Withdrawn
1) 5) 11)
3L Cables with concentric conductor (type 3L-1)
2) 11)
3M Unarmoured cables (type 3M-1)
5) 10)
3N Unarmoured cables (type 3N)
11)
3O Cables without (type 3O-1) concentric conductor
Part 4 PVC INSULATED CABLES - ARMOURED
1) 11)
4A Cables with concentric conductor (screen) (type 4A)
1) 5) 10)
4B Cables with braided (type 4B-1) or helically applied (type 4B-2) armour
2) 11)
4C Cables without concentric conductor (type 4C)
1) 11)
4D Armoured cables without (type 4D-1) concentric conductor
11)
4E Armoured cables with (type 4E-1) or without (type 4E-2) concentric copper
conductor or screen
Part 5 XLPE INSULATED CABLES - UNARMOURED
11)
5A Cables without concentric conductor (type 5A)
5B Cables (type 5B) without concentric conductor, PE sheath
5C Cables (type 5C) without concentric conductor, PVC sheath
1) 4) 11)
5D Cables with and without concentric conductor (types 5D-1 and 5D-2)
1) 11)
5E Cables (for energy boards) with concentric conductor (type 5E)
1) 11)
5F Cables with concentric screen and uninsulated neutral (type 5F)
1) 5) 11)
5G Cables with (type 5G-1) and without (type 5G-2) concentric conductor
5H Cables without concentric conductor (type 5H)
1) 5) 10)
5I Cables without concentric conductor (type 5I)
1) 11)
5J Cables with concentric conductor (type 5J)
1) 11)
5K Cables with concentric screen (type 5K)
1) 11)
5L Cables with concentric screen (type 5L)
1) 11)
5M Cables without concentric conductor (type 5M)
1) 9)
5N Cables without concentric conductor (type 5N)
5) 11)
5O Cables without concentric conductor, PVC sheath (type 5O)
1) 5) 11)
5P Cables with concentric conductor, PVC or PE sheath (type 5P-1 and 5P-2)
5Q Withdrawn
1) 5) 10)
5R CNE cables with concentric waveform neutral/earth conductor (type 5R)
1) 5) 10)
5S Service cables with concentric conductor (type 5S)
1) 11)
5T Cables with (type 5T-1) and without (type 5T-2) concentric conductor
11)
5U Cables with (type 5TU1) concentric waveform neutral conductor
3) 11)
5V Unarmoured cables (type 5V)
3) 13)
5W Cables with concentric conductor (type 5W)
12)
5X Cables without concentric conductor (type 5X)
Page 0-4
Part 6 XLPE INSULATED CABLES - ARMOURED
1) 5) 10)
6A Cables with braided (type 6A-1) or helically applied (type 6A-2) armour
6B Withdrawn
1) 11)
6C Armoured cables with (type 6C-1) and without (type 6C-2) concentric conductor
3) 11)
6D Steel tape armoured cables (type 6D)
11)
6E Cables without concentric conductor (screen) (type 6E)
Part 7 EPR INSULATED CABLES - UNARMOURED
5) 9)
7A Cables with and without concentric conductor (type 7A)
5) 9)
7B Pre-assembled cables without concentric conductor (type 7B)
1) 13)
7C Cables without concentric conductor (type 7C)
7D Withdrawn
1) 11)
7E Cables with (type 7E-1) and without (type 7E-2) concentric conductor
Part 8 EPR INSULATED CABLES - ARMOURED
8A Withdrawn
1) 11)
8B Armoured cables with (type 8B-1) and without (type 8B-2) concentric conductor
1)
Amendment A1 introduces some changes to the text.
2)
Amendment A1 completely revises the particular section.
3)
New section introduced by amendment A1.
4)
Amendment A2 introduces some changes to the text.
5)
Amendment A2 completely revises the particular section.
6)
Amendment A1 withdraws the section.
7)
Amendment A2 withdraws the section.
8)
Amendment A3 introduces some changes to the text.
9)
Amendment A3 introduces new Guide to use (Annex A).
10)
Amendment A3 introduces some changes to the text and new Guide to use (Annex A).
11)
Amendment A3 completely revises the particular section and introduces new Guide to use (Annex A).
12)
New section introduced by amendment A3.
13)
Amendment A3 withdraws the section.
Page 0-5
List of updated cross-references
Original Ref Original title New Ref New title
HD 186 Marking by inscription for the EN 50334 Marking by inscription for the
identification of cores of electric identification of cores of electric cables
cables having more than five cores
HD 383 Conductors of insulated cables EN 60228 Conductors of insulated cables
HD 405 Test on electric cables under fire EN 50265 Common test methods for cables under
(series) condition (series) fire conditions – Test for resistance to
vertical flame propagation for a single
insulated conductor or cable.
HD 405.1 Tests on electric cables under fire EN 50265-2-1 Common test methods for cables under
conditions – Part 1: Test on a single fire conditions – Test for resistance to
vertical insulated wire or cable vertical flame propagation for a single
insulated conductor or cable – Part 2-1:
Procedure – 1 kW pre-mixed flame
HD 405.3 Tests on electric cables under fire EN 50266 Common test methods for cables under
conditions – Part 3: Tests on bunched (series) fire conditions – Test for vertical flame
wires or cables spread of vertically-mounted bunched
wires or cables
HD 505 Common test methods for insulating EN 60811 Insulating and sheathing materials of
(series) and sheathing materials of electric (series) electric cables – Common test methods
cables
HD 606 Measurement of smoke density of EN 50268 Common test methods for cables under
(series) electric cables burning under defined (series) fire conditions – Measurement of
conditions smoke density of cables burning under
defined conditions
EN 50265-2-1 Common test methods for cables EN 60332-1-2 Tests on electric and optical fibre
under fire conditions – Test for cables under fire conditions
resistance to vertical flame Part 1-2: Test for vertical flame
propagation for a single insulated propagation for a single insulated wire
conductor or cable or cable - Procedure for 1 kW pre-
Part 2-1: Procedures – 1 kW pre- mixed flame
mixed flame
EN 61034 Measurement of smoke density of
EN 50268 Common test methods for cables
(series) cables burning under defined
(series) under fire conditions – Test for
conditions
vertical flame spread of vertically-
mounted bunched wires or cables
IEC 183 Guide to the selection of high-voltage IEC 60183 Guide of the selection of high-voltage
cables cables
IEC 60502 Extruded solid dielectric insulated IEC 60502-1 Power cables with extruded insulation
power cables for rated voltages from and their accessories for rated voltages
1 kV to 30 kV from 1 kV (U = 1,2 kV) up to 30 kV
m
(U = 36 kV) – Part 1: Cables for rated
m
voltages of 1 kV (U = 1,2 kV) and 3 kV
m
(U = 3,6 kV)
m
IEC 754-1 Tests on gases evolved during EN 50267-2-1 Common test methods for cables under
combustion of materials from cables – fire conditions – Tests on gases
Part 1: Determination of the amount evolved during combustion of materials
of halogen acid gas from cables – Part 2-1: Procedures –
Determination of the amount of halogen
acid gas
Page 0-6
BLANK PAGE
Page 1-0
Part 1
PART 1: GENERAL REQUIREMENTS
Replace the complete part by the following:
Page 1-1
Part 1
DISTRIBUTION CABLES OF RATED VOLTAGE 0,6/1 KV
PART 1: GENERAL REQUIREMENTS
Page 1-2
Part 1
CONTENTS
1 General. 4
1.1 Scope . 4
1.2 Object . 4
2 Definitions. 4
2.1 Definitions concerning the insulating and sheathing compounds. 4
2.2 Definitions relating to the tests . 5
2.3 Rated voltage.6
3 Marking. 6
3.1 Indication of origin.6
3.2 Additional marking . 7
3.3 Durability. 7
3.4 Legibility. 7
3.5 Common marking. 7
3.6 Use of the name CENELEC . 7
4 Core identification. 7
5 General requirements for the construction of cables .
...