prEN IEC 61621:2026
(Main)Dry, solid insulating materials - Resistance test to high-voltage, low-current arc discharges
- Status
- Not Published
- Publication Date
- 07-Nov-2027
- Current Stage
- 4060 - Enquiry results established and sent to TC, SR, BTTF - Enquiry
- Start Date
- 21-Aug-2026
- Due Date
- 21-Aug-2026
- Completion Date
- 21-Aug-2026
prEN IEC 61621:2026 is a CLC draft standard for testing dry, solid insulating materials against high-voltage, low-current arc discharges. It specifies a laboratory method for measuring arc resistance and classifying materials by time to failure, mainly for preliminary screening, formulation changes, and quality control.
What does prEN IEC 61621:2026 specify?
prEN IEC 61621:2026 specifies a test method for comparing similar insulating materials when arcs occur close to their surfaces. The method is meant to show how quickly a material is damaged by repeated arc exposure, and it is most useful for screening and quality control rather than predicting every service condition.
The scope also warns that the results are not a general ranking for all arc types. It notes that the behavior can differ from wet tracking tests and from service exposure, and it reports that the method has given acceptable reproducibility with thermoset materials while thermoplastics can show much larger scatter.
The document is organized into these main parts:
- Clause 1 - Scope
- Clause 2 - Normative references
- Clause 3 - Terms and definitions
- Clause 4 - Apparatus
- Clause 5 - Specimens
- Clause 6 - Procedure and failure recognition
- Clause 7 - Results
- Clause 8 - Report
- Annex A - Informative guidance on failure recognition by measurement
What are the key requirements of prEN IEC 61621:2026?
prEN IEC 61621:2026 requires a controlled arc test setup, defined specimen preparation, a staged increase in arc severity, and a result reported as time to failure in seconds. In practice, that means a laboratory cannot simply apply a spark and watch for damage - the spacing, current steps, specimen condition, and failure recognition all have to be controlled.
Apparatus and calibration
Clause 4 defines the test circuit, electrodes, chamber, and calibration checks. The circuit uses a transformer, variable autotransformer, voltmeter, milliammeter, current control resistors, suppressing resistor, air core inductors, breaker, and timer, and it calls for suppressing parasitic high-frequency effects so the arc remains stable.
The electrode system is tightly specified because the arc shape depends on it. The electrodes are tungsten rods with a defined tip geometry, mounted so both electrodes rest on the specimen with a set force and spacing; the practical effect is that the test measures material behavior, not accidental setup differences.
The chamber must prevent air drafts and allow safe observation and venting after the test. The document also requires calibration of the open-circuit operating voltage and adjustment of the secondary current before testing, so each test starts from a known electrical condition.
Specimens and conditioning
Clause 5 requires prepared specimens with a defined thickness for standard comparison, and it calls for at least five tests per material. Thin materials may be stacked to reach the target thickness, and any non-standard thickness has to be reported, which matters when comparing molded parts, laminates, or samples from different production lots.
Specimens must be clean, free from visible surface defects, and conditioned in a standard atmosphere based on IEC 60212:2010 before testing. In practice, this reduces the chance that moisture, fingerprints, or handling residue distort the arc resistance result.
Procedure and failure recognition
Clause 6 applies the test in stages. The early part of the test uses interrupted arcs, then the severity is increased step by step until failure occurs; this staged approach is what makes the method useful for comparing materials with different endurance levels.
Failure recognition is based mainly on visual and acoustic observation. A specimen fails when a conducting path forms and the arc disappears, or when burning continues after the arc is interrupted; this matters because the operator must distinguish true failure from glow, scintillation, or brief burning that does not persist.
The document also notes that failure often occurs just after a change in severity step, so time at the transition between steps is especially informative. For comparison work, that means small differences in elapsed time around a step change can be more significant than the same number of seconds inside one step.
Results and classification
Clause 7 states that the result is the time to failure, called arc resistance. The material is then classified using the lowest measured result from the five specimens, with an extension rule that allows five additional tests if only one of the first five falls into a class; this helps avoid over-interpreting one borderline specimen.
The classification runs from class 0 upward in bands of increasing arc resistance. For a buyer, engineer, or quality team, this means the document does not just give a pass/fail outcome - it provides a comparative class that can be used to distinguish candidate insulating materials.
Report content
Clause 8 requires the test report to identify the material, specimen thickness, fabrication, dimensions, cleaning and conditioning details, solvent used, any surface treatment, composite orientation, central/minimum/maximum arc resistance times, and notable observations such as burning or softening. That report content is important because arc resistance results can be strongly affected by preparation and specimen history.
What terms does prEN IEC 61621:2026 define?
- Failure - A specimen fails when a conducting path forms in the material, or when arc-related burning continues after the arc is interrupted.
- Arc resistance - The total elapsed time in seconds from the start of the test until specimen failure.
- Tracking - Progressive surface degradation caused by local discharges that form conducting or partially conducting paths.
- Conducting path - The continuous current-carrying route that marks specimen failure in this test method.
Who uses prEN IEC 61621:2026?
prEN IEC 61621:2026 is used by laboratories that test electrical insulating materials, by manufacturers developing or reformulating those materials, and by quality control teams that need a repeatable comparative arc test. It is also relevant to engineers and buyers evaluating dry, solid insulating materials for applications where surface arcing may be a concern.
The document is especially relevant to teams working on electrical insulation and systems qualification. Its scope also makes it useful where the aim is to detect changes in formulation or to compare similar materials during production control.
Which standards are used with prEN IEC 61621:2026?
The document cites several standards that support the test method:
- IEC 60112:2025 - Comparative tracking index testing for solid insulating materials, used as a comparison point for tracking behavior.
- IEC 60212:2010 - Standard conditioning atmosphere for solid electrical insulating materials before and during testing.
- IEC 60587:2022 - Test methods for tracking and erosion under severe ambient conditions, used for comparison with arc-related behavior.
- IEC 61302:1995 - Rotating wheel dip test for tracking and erosion resistance.
- EN 50191:2000 - Safety requirements for erection and operation of electrical test equipment.
- EN IEC 60112:2020 - European adoption of the comparative tracking index method, also used for comparison.
What does the prEN IEC 61621:2026 document contain?
prEN IEC 61621:2026 contains a complete laboratory test method, starting with the electrical apparatus and the electrode geometry, then moving to specimen preparation, test execution, failure recognition, and reporting. It includes an example electrical circuit, an example electrode mount, an example electrode assembly, and figures showing arc appearance before and after failure.
The document also includes a timing table for the staged current sequence used during the test and an informative annex on measurement-based approaches to failure recognition. Annex A discusses temperature, voltage, and current measurements as possible objective indicators, which can help laboratories develop or validate more consistent failure detection methods.
Relations
- Effective Date
- 08-Nov-2022
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
prEN IEC 61621:2026 is a draft published by CLC. Its full title is "Dry, solid insulating materials - Resistance test to high-voltage, low-current arc discharges". This standard covers: Dry, solid insulating materials - Resistance test to high-voltage, low-current arc discharges
Dry, solid insulating materials - Resistance test to high-voltage, low-current arc discharges
prEN IEC 61621:2026 is classified under the following ICS (International Classification for Standards) categories: 17.220.99 - Other standards related to electricity and magnetism; 29.035.01 - Insulating materials in general. The ICS classification helps identify the subject area and facilitates finding related standards.
prEN IEC 61621:2026 has the following relationships with other standards: It is inter standard links to EN 61621:1997. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
prEN IEC 61621:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 failure
- 3.2 arc resistance
- 3.3 tracking
- 4 Apparatus
- 4.1 Test circuit
- 4.2 Electrodes and electrode assembly
- 4.3 Test chamber
- 4.4 Calibration
- 5 Specimens
- 5.1 Specimen geometry
- 5.2 Cleaning and conditioning
- 6 Procedure and failure recognition
- 6.1 Test procedure
- 6.2 Failure and failure recognition
- 7 Results
- 8 Report
- Annex A
- Bibliography
1 Scope
This International Standard describes a test method which can provide preliminary differentiation between similar insulating materials, with respect to their resistance to damage when exposed to high-voltage, low-current arc discharges, occurring close to their surfaces. The discharges cause localized thermal and chemical decomposition and erosion and eventually a conductive path forms across the insulating material. The severity of the test conditions is gradually increased: in the early stages a low-current arc discharge is repeatedly interrupted, whereas in the later stages, the arc current is raised in successive steps. Because of its convenience and because of the short time required for testing, the test method is applicable for preliminary screening of materials, for detecting the effects of changes in formulation and for quality control testing.
Previous experience with this test, showed acceptable reproducibility with thermoset materials. Using thermoplastics, some testing laboratories report unacceptably large variation in test results which lead to the recommendation not to use the test for thermoplastics. NOTE Attempts are being made to reduce the variability of the results of tests on thermoplastics by controlling the electrode pressure and depth of penetration into the material during the test. Without such electrode control, tests on many thermoplastics may not be sufficiently meaningful to be performed. This test method will not, in general, permit conclusions to be drawn concerning the relative arc resistance rankings of materials which may be subjected to other types of arcs. The ranking of materials may differ from what is found in wet tracking tests (e.g. IEC 60112:2025, IEC 60587:2022 and IEC 61302:1995) and from their performance in service, where the intensity, recurrence frequency and time of exposure to arc discharges ar e very different.Nevertheless, a certain correlation with the Inclined-Plane-Test according to IEC 60587:2022 was found within one material group (e.g. silicone elastomers). [1][2]
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60112:2025, Method for the determination of the proof and the comparative tracking indices of solid insulating materials IEC 60212:2010, Standard conditions for use prior to and during the testing of solid electrical insulating materials IEC 60587:2022, Electrical insulating materials used under severe ambient conditions - Test methods for evaluating resistance to tracking and erosion IEC 61302:1995, Electrical insulating materials - Method to evaluate the resistance to tracking and erosion - Rotating wheel dip test EN 50191:2000, Erection and operation of electrical test equipment EN IEC 60112:2020, Method for the determination of the proof and the comparative tracking indices of solid insulating materials
oSIST prEN IEC 61621:2026
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:
- IEC Electropedia: available at http://www.electropedia.org/
- ISO Online browsing platform: available at http://www.iso.org/obp
3.1 failure
failure is considered to have occurred when a conducting path is formed in the material; failure is also considered to have occurred if the arc causes a material to burn and the burning continues when the arc is interrupted
3.2 arc resistance
total elapsed time in seconds from the start of test until specimen failure
3.3 tracking
the progressive degradation of the surface of a solid insulating material by local discharges to form conducting or partially conducting paths
[SOURCE: EV ref 442-01-41 [IEC 60050-442-01-4]]
4 Apparatus
4.1 Test circuit
The principal components of the electrical circuit for the apparatus are shown in Figure 1.
oSIST prEN IEC 61621:2026
Figure 1 – Example for electrical circuit NOTE 1 In the secondary circuit wiring the stray capacitance should be less than 40 pF. Large stray capacitance may disturb the arc shape and influence the test results.
NOTE 2 Due to electrical hazards, the appliance should be equipped with state-of-the-art safety technology to prevent contact with live parts (e.g. EN 50191:2000)
4.1.1 Transformer, T
A transformer with a rated secondary potential (on open circuit) of 15 kV, and a rated secondary current (on short circuit) of 60 mA, line frequency (48 Hz to 62 Hz).
4.1.2 Variable autotransformer, T
Rated 1 kVA and suitable for the line voltage.
NOTE A constant primary voltage supply ±2 % is recommended.
4.1.3 Voltmeter, V
L AC voltmeter with an accuracy of ±0,5 %, capable of reading line voltage +10−20%. Voltage on the secondary side shall be regularly controlled by a reference measurement. Alternatively, measurement of the voltage in the secondary circuit can be done, but a high capacity is to be avoided (see 4.1, Note 1).
oSIST prEN IEC 61621:2026
4.1.4 Milliammeter, A
A true r.m.s. a.c. milliammeter capable of reading 10 mA to 40 mA with an accuracy of ±5 %. Since this milliammeter is used only when setting up or making changes in the circuit, it may be shorted out by a bypass switch when not in use.
NOTE 1 Although provision has been made for the suppression of radio frequency components of current in the arc, it may be desirable to check for their presence when the apparatus is first constructed. This is best done by use of a suitable thermocouple type r.f. milliammeter temporarily inserted in series with the milliammeter. NOTE 2 A milliampmeter of moving-iron type is recommended for current measurement. Other milliampmeter e.g. “Rectifier-type” might be affected by superposition of high frequency components of current indicating a larger value.
4.1.5 Current control resistors, R , R , R and R and switches S , S , S , S
10 20 30 40 2 3 4 5 Four resistors are required in series with the primary of T . These resistors must be adjustable,
to some extent, to permit exact settings of the currents during calibration. R is always in the
circuit to provide a 10 mA current. The switch S – S are used the select the test current while 2 5 testing.
4.1.6 Suppressing resistor, R
Rated at 15 kΩ and at least 24 W. This resistor, along with the inductors (see 4.1.7) is used to suppress parasitic high frequency in the arc circuit.
4.1.7 Air core inductors, Xs
An inductance totalling from 1.2 H to 1.5 H with an insulating non-metallic core used to suppress parasitic high frequency in the arc circuit.
NOTE A single coil of this inductance is not practical. A satisfactory inductor may be constructed by connecting in series eight coils of 3 000 to 5 000 turns of wire wound on insulating non-metallic cores of about 12.7 mm diameter and 15.9 mm inside length.
4.1.8 Breaker, B
Motor driven or electronically operated interrupter used to give the required cycles for the three lower steps of the test by opening and closing the primary circuit according to the schedule in Table 1, with an accuracy of ±0.008 s.
4.1.9 Timer, TT
A timer that allows the arc resistance to be measured with an accuracy of ±1 s.
4.2 Electrodes and electrode assembly
4.2.1 Electrode geometry
The electrodes are made from 2.4 mm ±0.05 mm diameter tungsten rod which is free from cracks, pits or rough spots. The free electrode length shall be a minimum of 20 mm. It is recommended that the electrodes are mounted in a shank which allows correct orie ntation of the electrode tip after sharpening. The electrode tip shall be ground and polished to produce an angle of 30° ±1° to the axis, to achieve a flat elliptical face. As an example, Figure 2 shows the electrodes mounted in a suitable shank.
oSIST prEN IEC 61621:2026
NOTE ① Shank ② Electrode Dimensions in millimetres Figure 2 – Electrode mounted in a shank (example) NOTE 1 Tungsten welding rods have been found to be suitable for use as electrodes. NOTE 2 A steel jig for securing the electrodes during sharpening to ensure finishing the pointed tips to the proper geometry is helpful.
...