Reciprocating internal combustion engine driven alternating current generating sets — Part 1: Application, ratings and performance

ISO 8528-1:2005 defines various classifications for the application, rating and performance of generating sets consisting of a Reciprocating Internal Combustion (RIC) engine, Alternating Current (a.c.) generator and any associated controlgear, switchgear and auxiliary equipment. It applies to a.c. generating sets driven by RIC engines for land and marine use excluding generating sets used on aircraft or to propel land vehicles and Iocomotives. For some specific applications (e.g. essential hospital supplies, high-rise buildings), supplementary requirements may be necessary. The provisions of ISO 8528-1:2005 should be regarded as the basis for establishing any supplementary requirements. For other reciprocating-type prime movers (e.g. sewage-gas engines, steam engines), the provisions of ISO 8528-1:2005 should be used as a basis for establishing these requirements. Generating sets meeting the requirements of ISO 8528-1:2005 are used to generate electrical power for continuous, peak-load and standby applications. The classifications laid down in ISO 8528-1:2005 are intended to help understanding between manufacturer and customer.

Groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à combustion interne — Partie 1: Application, caractéristiques et performances

L'ISO 8528-1:2005 définit différentes classes pour l'application, les caractéristiques nominales et les performances de groupes électrogènes constitués d'un moteur alternatif à combustion interne, d'un alternateur ainsi que de tout appareillage de commande et de coupure et d'équipements auxiliaires associés. L'ISO 8528-1:2005 est applicable aux groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à combustion interne utilisés pour des applications terrestres et marines, à l'exclusion des groupes électrogènes utilisés à bord des aéronefs ou pour la propulsion de véhicules terrestres et de locomotives. Pour des applications particulières (par exemple alimentation principale d'hôpitaux, immeubles de grande hauteur), des exigences supplémentaires peuvent être nécessaires. Il convient alors de prendre les dispositions de l'ISO 8528-1:2005 comme base pour établir des exigences supplémentaires. Pour les autres machines d'entraînement de type alternatif (par exemple les moteurs à gaz de récupération, les moteurs à vapeur), il convient de prendre les dispositions de l'ISO 8528-1:2005 comme base pour établir ces exigences. Les groupes électrogènes conformes aux exigences de la présente Norme internationale sont utilisés pour produire de l'énergie électrique en continu, en écrêtage et en secours. La classification définie dans l'ISO 8528-1:2005 est destinée à faciliter les échanges entre constructeurs et clients.

General Information

Status
Withdrawn
Publication Date
06-Jun-2005
Withdrawal Date
06-Jun-2005
Current Stage
9599 - Withdrawal of International Standard
Completion Date
02-Feb-2018
Ref Project

Relations

Buy Standard

Standard
ISO 8528-1:2005 - Reciprocating internal combustion engine driven alternating current generating sets
English language
17 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 8528-1:2005 - Groupes électrogenes a courant alternatif entraînés par moteurs alternatifs a combustion interne
French language
18 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

INTERNATIONAL ISO
STANDARD 8528-1
Second edition
2005-06-01

Reciprocating internal combustion
engine driven alternating current
generating sets —
Part 1:
Application, ratings and performance
Groupes électrogènes à courant alternatif entraînés par moteurs
alternatifs à combustion interne —
Partie 1: Application, caractéristiques et performances




Reference number
ISO 8528-1:2005(E)
©
ISO 2005

---------------------- Page: 1 ----------------------
ISO 8528-1:2005(E)
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.


©  ISO 2005
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland

ii © ISO 2005 – All rights reserved

---------------------- Page: 2 ----------------------
ISO 8528-1:2005(E)
Contents Page
Foreword. v
1 Scope. 1
2 Normative references . 1
3 Symbols and abbreviations . 2
4 Other regulations and additional requirements. 2
5 General description . 2
5.1 Generating set . 2
5.2 Power Station . 4
6 Application criteria. 4
6.1 Modes of operation . 4
6.2 Site criteria. 5
6.3 Single and parallel operation. 5
6.4 Modes of start-up and control . 6
6.5 Start-up time . 6
7 Performance classes . 7
8 Installation features . 8
8.1 General. 8
8.2 Installation configurations . 8
8.3 Generating set configurations. 8
8.4 Mounting types. 8
8.5 Connection between the RIC engine and electrical generator. 9
8.6 Additional installation features — Weather effects. 9
9 Emissions . 10
10 Standard reference conditions . 10
11 Site conditions . 10
11.1 General. 10
11.2 Ambient temperature . 10
11.3 Altitude. 10
11.4 Humidity. 10
11.5 Air quality. 10
11.6 Marine environment. 11
11.7 Shock and imposed vibration. 11
11.8 Chemical pollution . 11
11.9 Radiation. 11
11.10 Cooling water/liquid. 11
12 Power adjustment for operating conditions. 11
13 Power rating definitions . 12
13.1 General. 12
13.2 Power ratings . 12
13.3 Power rating categories . 12
14 Operating performance . 15
14.1 Starting temperature. 15
14.2 Load acceptance . 15
14.3 Cyclic irregularity. 15
14.4 Generator temperature rise. 16
© ISO 2005 – All rights reserved iii

---------------------- Page: 3 ----------------------
ISO 8528-1:2005(E)
14.5 Fuel and lubricating oil characteristics and consumption .16
14.6 Minimum running hours .16
14.7 Regulation .16
Bibliography.17

iv © ISO 2005 – All rights reserved

---------------------- Page: 4 ----------------------
ISO 8528-1:2005(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 8528-1 was prepared by Technical Committee ISO/TC 70, Internal combustion engines.
This second edition cancels and replaces the first edition (ISO 8528-1:1993), which has been technically
revised.
ISO 8528 consists of the following parts, under the general title Reciprocating internal combustion engine
driven alternating current generating sets:
— Part 1: Application, ratings and performance
— Part 2: Engines
— Part 3: Alternating current generators for generating sets
— Part 4: Controlgear and switchgear
— Part 5: Generating sets
— Part 6: Test methods
— Part 7: Technical declarations for specification and design
— Part 8: Requirements and tests for low-power generating sets
— Part 9: Measurement and evaluation of mechanical vibrations
— Part 10: Measurement of airborne noise by the enveloping surface method
1)
— Part 11: Rotary uninterruptible power systems — Performance requirements and test methods
— Part 12: Emergency power supply to safety services

1) Part 11 will be published as ISO/IEC 88528-11.
© ISO 2005 – All rights reserved v

---------------------- Page: 5 ----------------------
INTERNATIONAL STANDARD ISO 8528-1:2005(E)

Reciprocating internal combustion engine driven alternating
current generating sets —
Part 1:
Application, ratings and performance
1 Scope
This part of ISO 8528 defines various classifications for the application, rating and performance of generating
sets consisting of a Reciprocating Internal Combustion (RIC) engine, Alternating Current (a.c.) generator and
any associated controlgear, switchgear and auxiliary equipment.
It applies to a.c. generating sets driven by RIC engines for land and marine use, excluding generating sets
used on aircraft or to propel land vehicles and Iocomotives.
For some specific applications (e.g. essential hospital supplies, high-rise buildings) supplementary
requirements may be necessary. The provisions of this part of ISO 8528 should be regarded as the basis for
establishing any supplementary requirements.
For other reciprocating-type prime movers (e.g. sewage-gas engines, steam engines), the provisions of this
part of ISO 8528 should be used as a basis for establishing these requirements.
Generating sets meeting the requirements of this International Standard are used to generate electrical power
for continuous, peak-load and standby applications. The classifications laid down in this part of ISO 8528 are
intended to help understanding between manufacturer and customer.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
ISO 3046-1, Reciprocating internal combustion engines — Performance — Part 1: Declarations of power, fuel
and lubricating oil consumptions, and test methods — Additional requirements for engines for general use
2)
ISO 8528-2 , Reciprocating internal combustion engine driven alternating current generating sets — Part 2:
Engines
2)
ISO 8528-3 , Reciprocating internal combustion engine driven alternating current generating sets — Part 3:
Alternating current generators for generating sets
2)
ISO 8528-4 , Reciprocating internal combustion engine driven alternating current generating sets — Part 4:
Controlgear and switchgear
2)
ISO 8528-5 , Reciprocating internal combustion engine driven alternating current generating sets — Part 5:
Generating sets

2) ISO 8528-2, 3, 4 and 5 are all under revision.
© ISO 2005 – All rights reserved 1

---------------------- Page: 6 ----------------------
ISO 8528-1:2005(E)
3 Symbols and abbreviations
An explanation of the symbols and abbreviations used in this Internationial Standard are shown in Table 1.
Table 1 — Symbols and abbreviations
Symbol or
Term Unit
abbreviation
P Power kW
P Permissible average power kW

pp
P Actual average power kW

pa
p Total barometric pressure kPa
r
T Charge air coolant temperature K
or
T Air temperature K
r
t Time s
ϕ Power factor
∅ Relative humidity %
r
a.c. Alternating current
COP Continuous power kW
PRP Prime power kW
LTP Limited-time running power kW
ESP Emergency standby power kW

4 Other regulations and additional requirements
For a.c. generating sets used onboard ships and offshore installations, which have to comply with rules of a
classification society, the additional requirements of the classification society shall be observed. The
classification society name shall be stated by the customer prior to placing the order.
For a.c. generating sets operating in non-classified equipment, any additional requirements are subject to
agreement between the manufacturer and customer.
If special requirements from any other regulatory authority (e.g. inspecting and/or legislative authorities) have
to be met, the authority name shall be stated by the customer prior to placing the order.
Any additional requirements shall be subject to agreement between the manufacturer and customer.
5 General description
5.1 Generating set
5.1.1 General
A generating set consists of one or more RIC engines used to produce mechanical energy and one or more
generators to convert the mechanical energy into electrical energy. The generating set includes any
components used for coupling the mechanical prime mover(s) and electrical generator(s) (e.g. couplings,
gearbox) and, where applicable, any load-bearing and mounting components.
2 © ISO 2005 – All rights reserved

---------------------- Page: 7 ----------------------
ISO 8528-1:2005(E)
5.1.2 Prime movers
For the purposes of this International Standard, prime movers may be of two types:
a) compression-ignition engines; and
b) spark-ignition engines.
Depending on the generating set application, the following criteria, among others, may be important in
selecting the prime mover to be used:
a) quality of fuel and fuel consumption;
b) exhaust gas and noise emission;
c) speed range;
d) mass and dimensions;
e) sudden electrical loading and frequency behaviour;
f) generator short-circuit characteristics;
g) cooling systems;
h) starting systems;
i) maintenance requirements;
j) waste heat utilization.
5.1.3 Electrical generators
For the purposes of this International Standard, electrical generators may be of two types:
a) synchronous; and
b) asynchronous.
Depending on the generating set application, the following criteria, among others, may be important in
selecting the generator to be used:
a) voltage characteristics during starting and normal operation as well as after load changes, taking into
account the electrical power factor;
b) short-circuit behaviour (electrical and mechanical);
c) efficiency;
d) generator design and enclosure type;
e) parallel-operation behaviour;
f) maintenance requirements.
5.1.4 Control and switchgear
Equipment for the control, switching, operation and monitoring of the generating set shall be part of the
associated controlgear and switchgear systems.
© ISO 2005 – All rights reserved 3

---------------------- Page: 8 ----------------------
ISO 8528-1:2005(E)
5.1.5 Auxiliaries
Auxiliaries are items of equipment additional to those already fitted/installed on the generating set as supplied
but essential to its proper and safe operation, such as:
a) starting system;
b) air intake and exhaust gas systems;
c) cooling systems;
d) lubricating oil system;
e) fuel system (including fuel treatment where applicable);
f) auxiliary electrical power supply.
5.2 Power Station
A power station comprises an installation of one or more generating sets and their auxiliary equipment, the
associated controlgear and switchgear and, where applicable, the place of installation (e.g. a building, an
enclosure or special equipment for protection from the weather).
6 Application criteria
6.1 Modes of operation
6.1.1 General
The generating set mode of operation may affect certain important performance characteristics (e.g. its
economical and reliable operation, the intervals between maintenance and repair) and shall be taken into
account by the customer when agreeing the requirements with the manufacturer (see Clause 11).
6.1.2 Continuous operation at constant load
Continuous operation at constant load is defined as operation of a generating set without time limit taking into
account the maintenance period, where the applied electrical load is constant.
EXAMPLE Providing a base load for a combined heat and power plant.
6.1.3 Continuous operation at varying load
Continuous operation at varying load is defined as operation of a generating set without time limit, taking into
account the maintenance period, where the applied electrical load is variable.
EXAMPLE Providing electrical power where there is no utility electrical power available or the utility electrical supply
is uncertain.
6.1.4 Limited time operation at constant load
Limited time operation at constant load is defined as operation of a generating set within set time limits where
the applied electrical load is constant.
EXAMPLE Peak shaving load management where a generating set operating in parallel with a utility supply takes a
constant load during periods of peak power consumption.
4 © ISO 2005 – All rights reserved

---------------------- Page: 9 ----------------------
ISO 8528-1:2005(E)
6.1.5 Limited time operation at varying load
Limited time operation at varying load is defined as operation of a generating set within set time limits where
the applied electrical load is variable.
EXAMPLE To provide a basic support function to a building electrical supply in the event of normal utility supply
failure.
6.2 Site criteria
6.2.1 Land use
Land use applies to generating sets either fixed, transportable or mobile which are used on land.
6.2.2 Marine use
Marine use applies to generating sets used on board ships and offshore installations.
6.3 Single and parallel operation
6.3.1 General
Generating sets may have two types of operation as follows:
a) Single Operation:
This applies to generating sets, irrespective of their configuration or mode of start-up and control, which
will operate as the sole source of electrical power;
b) Parallel Operation:
This refers to the electrical connection of a generating set to another source of electrical supply with the
same voltage, frequency and phase to share the power supply demand for the connected network. The
characteristics of the normal utility electrical power supply, including voltage range and variation,
frequency, impedance of the network, etc., shall be stated by the customer.
6.3.2 Generating set parallel operation
In this type of operation, two or more generating sets are electrically connected (not mechanically connected)
after having been brought into synchronism. Generating sets with different outputs and speeds can be used.
6.3.3 Generating set operation in parallel with a utility supply
In this type of operation, one or more generating sets operating in parallel (as described in 6.3.1) are
electrically connected to a utility supply.
In the case of public utility electrical power supply, permission for parallel operation has to be obtained from
the public utility electricity authority. Protective equipment has to be provided in accordance with the public
regulations in force at the time.
NOTE This also applies to generating sets which, in order to periodically check their start-up function, have to
operate by supplying power into the normal electrical power supply system for a time period laid down by the generating
set manufacturer.
© ISO 2005 – All rights reserved 5

---------------------- Page: 10 ----------------------
ISO 8528-1:2005(E)
6.4 Modes of start-up and control
6.4.1 General
The modes of start-up and control involved in the operation of a generating set are normally:
a) starting;
b) monitoring;
c) voltage and frequency adjustment and synchronization where applicable;
d) switching;
e) stopping.
These can be fully or partly manual, or automatic (see ISO 8528-4).
6.4.2 Manual operation
Manual operation applies to generating sets which are started and controlled manually.
6.4.3 Semi-automatic operation
Semi-automatic operation applies to generating sets in which some of its functions are started and controlled
manually and the remainder automatically.
6.4.4 Automatic operation
Automatic operation applies to generating sets which are started and controlled completely automatically.
6.5 Start-up time
6.5.1 General
The start-up time is defined as the elapsed time between the instant when power is first demanded and the
instant when it is first available. The start-up time is usually specified in seconds. The start-up time shall meet
the requirement of the particular application in which the generating set is being used.
6.5.2 Generating set with no specified start-up time
This is a generating set where, due to the conditions under which it operates, the start-up time is of no
importance. Such generating sets are normally started manually.
6.5.3 Generating set with a specified start-up time
This is a generating set where the start-up time is specified. Such generating sets are normally started
automatically. Such generating sets may be further classified as follows:
6.5.3.1 Long-break
This is a generating set with a specified start-up time. The elapsed time between power supply failure and
power from the generating set becoming available is fairly long. In this case, the entire generating set is
started from the stationary condition after electrical power is demanded.
6 © ISO 2005 – All rights reserved

---------------------- Page: 11 ----------------------
ISO 8528-1:2005(E)
6.5.3.2 Short-break
This is a generating set operating with rotating electrical machines where the electrical power supply is
interrupted for a specific time (usually defined in milliseconds) while the necessary electrical transfer takes
place. A source of stored mechanical energy is used to supply power to the rotating electrical machines for a
short period and, where necessary, to start and accelerate the RIC engine.
6.5.3.3 No-break
This is a generating set operating with continuously running electrical machines so as to ensure an
uninterrupted supply of electrical power in the event of utility failure. A source of stored mechanical energy is
used to supply power to the connected equipment for a short period and, where necessary, to start and
accelerate the RIC engine. As the drive is transferred from one power source to another, there may be a
temporary deviation in frequency.
NOTE It is essential that the size of the permitted deviation in frequency during the transfer is agreed between the
customer and manufacturer.
7 Performance classes
Four performance classes are defined in order to cover the various requirements of the supplied electrical
systems as follows:
a) Class G1
This applies to generating set applications where the connected loads are such that only basic
parameters of voltage and frequency need to be specified.
EXAMPLE General-purpose applications (lighting and other simple electrical loads).
b) Class G2
This applies to generating set applications where its voltage characteristics are very similar to those for
the commercial public utility electrical power system with which it operates. When load changes occur,
there may be temporary but acceptable deviations of voltage and frequency.
EXAMPLE Lighting systems, pumps, fans and hoists.
c) Class G3
This applies to applications where the connected equipment makes severe demands on the stability and
level of the frequency, voltage and waveform characteristics of the electrical power supplied by the
generating set.
EXAMPLE Telecommunications and thyristor-controlled loads. It should be remembered that both rectifier and
thyristor-controlled loads may need special consideration with respect to their effect on generator-voltage waveform.
d) Class G4
This applies to applications where the demands made on the stability and level of the frequency, voltage
and waveform characteristics of the electrical power supplied by the generating set are exceptionally
severe.
EXAMPLE Data-processing equipment or computer systems.
© ISO 2005 – All rights reserved 7

---------------------- Page: 12 ----------------------
ISO 8528-1:2005(E)
8 Installation features
8.1 General
Requirements to meet local regulations may affect the design and installation of the generating set and shall
be taken into account by the customer and manufacturer in addition to the requirements shown in 8.2 to 8.6.
8.2 Installation configurations
8.2.1 General
The installation configurations in 8.2.2 to 8.2.4 may or may not have all the necessary generating set auxiliary
equipment integrally mounted.
8.2.2 Fixed
This configuration applies to generating sets which are permanently installed.
8.2.3 Transportable
This configuration applies to generating sets which are not permanently installed or are mobile.
8.2.4 Mobile
This configuration applies to generating sets which have an integral chassis fitted with wheels whereby the
generating set can be moved from one location to another.
8.3 Generating set configurations
In order to simplify the contractual information required for specifying RIC engine driven generating set
applications, application configurations are as follows:
 A: without baseframe;
 B: with baseframe;
 C: with baseframe, integrally mounted controlgear, switchgear and auxiliaries;
 D: configuration as given in C with enclosure (see Clause 9);
 E: configuration as given in C having an integral set of wheels or mounted on a trailer (see 8.2.4).
8.4 Mounting types
The type of mounting to be used for the generating set shall be agreed between the customer and the
generating set manufacturer. Some typical types of mounting are:
a) Rigid:
In this type of installation, the generating set is installed on inflexible mounts. If foundations for mounting
the generating set are installed on substrates of low elasticity (e.g. cork tiles) with no resilient layers
inserted, the method of mounting is considered to be rigid.
b) Resilient:
In this type of installation, the generating set is installed on resilient mountings that are able to, depending
upon their characteristics, partially insulate it from vibration. For special applications (e.g. marine or
mobile) restrained resilient mountings may be required.
8 © ISO 2005 – All rights reserved

---------------------- Page: 13 ----------------------
ISO 8528-1:2005(E)
1) Fully resilient:
In this type of installation, the generating set is mounted on a baseframe or
...

NORME ISO
INTERNATIONALE 8528-1
Deuxième édition
2005-06-01


Groupes électrogènes à courant alternatif
entraînés par moteurs alternatifs
à combustion interne —
Partie 1:
Application, caractéristiques
et performances
Reciprocating internal combustion engine driven alternating current
generating sets —
Part 1: Application, ratings and performance




Numéro de référence
ISO 8528-1:2005(F)
©
ISO 2005

---------------------- Page: 1 ----------------------
ISO 8528-1:2005(F)
PDF – Exonération de responsabilité
Le présent fichier PDF peut contenir des polices de caractères intégrées. Conformément aux conditions de licence d'Adobe, ce fichier
peut être imprimé ou visualisé, mais ne doit pas être modifié à moins que l'ordinateur employé à cet effet ne bénéficie d'une licence
autorisant l'utilisation de ces polices et que celles-ci y soient installées. Lors du téléchargement de ce fichier, les parties concernées
acceptent de fait la responsabilité de ne pas enfreindre les conditions de licence d'Adobe. Le Secrétariat central de l'ISO décline toute
responsabilité en la matière.
Adobe est une marque déposée d'Adobe Systems Incorporated.
Les détails relatifs aux produits logiciels utilisés pour la création du présent fichier PDF sont disponibles dans la rubrique General Info
du fichier; les paramètres de création PDF ont été optimisés pour l'impression. Toutes les mesures ont été prises pour garantir
l'exploitation de ce fichier par les comités membres de l'ISO. Dans le cas peu probable où surviendrait un problème d'utilisation,
veuillez en informer le Secrétariat central à l'adresse donnée ci-dessous.


©  ISO 2005
Droits de reproduction réservés. Sauf prescription différente, aucune partie de cette publication ne peut être reproduite ni utilisée sous
quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les microfilms, sans l'accord écrit
de l'ISO à l'adresse ci-après ou du comité membre de l'ISO dans le pays du demandeur.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax. + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Publié en Suisse

ii © ISO 2005 – Tous droits réservés

---------------------- Page: 2 ----------------------
ISO 8528-1:2005(F)
Sommaire Page
Avant-propos. v
1 Domaine d'application. 1
2 Références normatives . 1
3 Symboles et abréviations . 2
4 Autres règlements et exigences supplémentaires. 2
5 Descriptions générales . 3
5.1 Groupe électrogène. 3
5.2 Centrale de puissance. 4
6 Critères d'application . 4
6.1 Modes de fonctionnement . 4
6.2 Critères d'utilisation sur site . 5
6.3 Fonctionnement en solo ou couplé . 5
6.4 Modes d'intervention et de commande . 6
6.5 Délai d'intervention. 6
7 Classes de performance . 7
8 Caractéristiques d'installation. 8
8.1 Généralités . 8
8.2 Types d'installations . 8
8.3 Configurations du groupe électrogène . 8
8.4 Types de montage . 9
8.5 Liaison entre le moteur alternatif à combustion interne et la génératrice. 9
8.6 Autres caractéristiques d'installation — Effet des intempéries . 10
9 Émissions . 10
10 Conditions normales de référence. 10
11 Conditions de site. 10
11.1 Généralités . 10
11.2 Température ambiante . 11
11.3 Altitude. 11
11.4 Humidité. 11
11.5 Qualité de l'air . 11
11.6 Environnement marin. 11
11.7 Choc et vibrations. 11
11.8 Pollution chimique. 11
11.9 Radiations. 11
11.10 Refroidissement par eau/liquide . 11
12 Réglage de puissance pour les conditions de fonctionnement . 12
13 Définitions des classes de puissance . 12
13.1 Généralités . 12
13.2 Puissance . 12
13.3 Types de puissances. 12
14 Performances de fonctionnement. 16
14.1 Température de démarrage . 16
14.2 Prise de charge . 16
14.3 Irrégularité cyclique. 16
14.4 Élévation de température de la génératrice . 17
© ISO 2005 – Tous droits réservés iii

---------------------- Page: 3 ----------------------
ISO 8528-1:2005(F)
14.5 Caractéristiques et consommation de carburant et de lubrifiant . 17
14.6 Autonomie minimale de fonctionnement . 17
14.7 Régulation. 17
Bibliographie . 18

iv © ISO 2005 – Tous droits réservés

---------------------- Page: 4 ----------------------
ISO 8528-1:2005(F)
Avant-propos
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes nationaux de
normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est en général confiée
aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude a le droit de faire partie du
comité technique créé à cet effet. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec l'ISO participent également aux travaux. L'ISO collabore étroitement avec
la Commission électrotechnique internationale (CEI) en ce qui concerne la normalisation électrotechnique.
Les Normes internationales sont rédigées conformément aux règles données dans les Directives ISO/CEI,
Partie 2.
La tâche principale des comités techniques est d'élaborer les Normes internationales. Les projets de Normes
internationales adoptés par les comités techniques sont soumis aux comités membres pour vote. Leur
publication comme Normes internationales requiert l'approbation de 75 % au moins des comités membres
votants.
L'attention est appelée sur le fait que certains des éléments du présent document peuvent faire l'objet de
droits de propriété intellectuelle ou de droits analogues. L'ISO ne saurait être tenue pour responsable de ne
pas avoir identifié de tels droits de propriété et averti de leur existence.
L'ISO 8528-1 a été élaborée par le comité technique ISO/TC 70, Moteurs à combustion interne.
Cette deuxième édition annule et remplace la première édition (ISO 8528-1:1993), qui a fait l'objet d'une
révision technique.
L'ISO 8528 comprend les parties suivantes, présentées sous le titre général Groupes électrogènes à courant
alternatif entraînés par moteurs alternatifs à combustion interne:
— Partie 1: Application, caractéristiques et performances
— Partie 2: Moteurs
— Partie 3: Alternateurs pour groupes électrogènes
— Partie 4: Appareillage de commande et de coupure
— Partie 5: Groupes électrogènes
— Partie 6: Méthodes d'essai
— Partie 7: Déclarations techniques pour la spécification et la conception
— Partie 8: Prescriptions et essais pour groupes électrogènes de faible puissance
— Partie 9: Mesurage et évaluation des vibrations mécaniques
— Partie 10: Mesurage du bruit aérien par la méthode de la surface enveloppe
— Partie 11: Systèmes électriques alternatifs sans interruption — Exigences de performance et méthodes
1)
d'essai
— Partie 12: Alimentation électrique de secours de services de sécurité

1) L'ISO 8528-11 fera l'objet de la publication ISO/CEI 88528-11.
© ISO 2005 – Tous droits réservés v

---------------------- Page: 5 ----------------------
NORME INTERNATIONALE ISO 8528-1:2005(F)

Groupes électrogènes à courant alternatif entraînés par
moteurs alternatifs à combustion interne —
Partie 1:
Application, caractéristiques et performances
1 Domaine d'application
La présente partie de l'ISO 8528 définit différentes classes pour l'application, les caractéristiques nominales et
les performances de groupes électrogènes constitués d'un moteur alternatif à combustion interne, d'un
alternateur ainsi que de tout appareillage de commande et de coupure et d'équipements auxiliaires associés.
Elle est applicable aux groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à
combustion interne utilisés pour des applications terrestres et marines, à l'exclusion des groupes électrogènes
utilisés à bord des aéronefs ou pour la propulsion de véhicules terrestres et de locomotives.
Pour des applications particulières (par exemple alimentation principale d'hôpitaux, immeubles de grande
hauteur), des exigences supplémentaires peuvent être nécessaires. Il convient alors de prendre les
dispositions de la présente partie de l'ISO 8528 comme base pour établir des exigences supplémentaires.
Pour les autres machines d'entraînement de type alternatif (par exemple les moteurs à gaz de récupération,
les moteurs à vapeur), il convient de prendre les dispositions de la présente partie de l'ISO 8528 comme base
pour établir ces exigences.
Les groupes électrogènes conformes aux exigences de la présente Norme internationale sont utilisés pour
produire de l'énergie électrique en continu, en écrêtage et en secours. La classification définie dans la
présente partie de l'ISO 8528 est destinée à faciliter les échanges entre constructeurs et clients.
2 Références normatives
Les documents référencés ci-dessous sont indispensables à l'application du présent document. Pour les
références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition du
document référencé (y compris les amendements) s'applique.
ISO 3046-1, Moteurs alternatifs à combustion interne — Performances — Partie 1: Déclaration de la
puissance et de la consommation de carburant et d'huile de lubrification, et méthodes d'essai — Exigences
supplémentaires pour les moteurs d'usage général
2)
ISO 8528-2 , Groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à combustion
interne — Partie 2: Moteurs
2)
ISO 8528-3 , Groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à combustion
interne — Partie 3: Alternateurs pour groupes électrogènes
2)
ISO 8528-4 , Groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à combustion
interne — Partie 4: Appareillage de commande et de coupure

2) L'ISO 8528-2, l'ISO 8528-3, l'ISO 8528-4 et l'ISO 8528-5 sont en cours de révision.
© ISO 2005 – Tous droits réservés 1

---------------------- Page: 6 ----------------------
ISO 8528-1:2005(F)
2)
ISO 8528-5 , Groupes électrogènes à courant alternatif entraînés par moteurs alternatifs à combustion
interne — Partie 5: Groupes électrogènes
3 Symboles et abréviations
Le Tableau 1 fournit une explication des symboles et des abréviations utilisés dans la présente Norme
internationale.
Tableau 1 — Symboles et abréviations
Symboles et
Terme Unité
abréviations
P Puissance kW
P Puissance moyenne admissible kW

pp
P Puissance réelle moyenne kW

pa
p Pression barométrique totale kPa
r
T Température du fluide de refroidissement de K
or
l'air de suralimentation
T Température de l'air K
r
t Temps s
ϕ Facteur de puissance
∅ Humidité relative %
r
c.a. Courant alternatif
COP Puissance continue kW
PRP Puissance principale kW
LTP Puissance pour utilisation limitée kW
ESP Puissance de secours d'urgence kW

4 Autres règlements et exigences supplémentaires
Pour les groupes électrogènes à courant alternatif utilisés à bord des navires et des installations au large qui
doivent satisfaire aux règles d'une société de classification, les exigences supplémentaires de la société de
classification doivent être satisfaites. Le nom de la société de classification doit être déclaré par le client avant
la passation de la commande.
Pour les groupes électrogènes à courant alternatif fonctionnant sur des équipements non classés, toute
exigence supplémentaire doit faire l'objet d'un accord entre le constructeur et le client.
Lorsque des exigences particulières émanant d'autres autorités de réglementation (par exemple d'organismes
de contrôle et/ou d'agences gouvernementales) doivent être satisfaites, le nom de l'autorité correspondante
doit être déclaré par le client avant la passation de la commande.
Toute exigence supplémentaire doit faire l'objet d'un accord entre le constructeur et le client.
2 © ISO 2005 – Tous droits réservés

---------------------- Page: 7 ----------------------
ISO 8528-1:2005(F)
5 Description générale
5.1 Groupe électrogène
5.1.1 Généralités
Un groupe électrogène est constitué d'un ou de plusieurs moteurs alternatifs à combustion interne produisant
de l'énergie mécanique et d'une ou de plusieurs génératrices convertissant l'énergie mécanique en énergie
électrique. Le groupe électrogène comprend des éléments destinés à assurer l'accouplement de(s)
machine(s) d'entraînement mécanique(s) et de(s) génératrice(s) électrique(s) (par exemple accouplement
réducteur ou multiplicateur, boîte d'engrenage) et, le cas échéant, d'éléments de montage et de support.
5.1.2 Machines d'entraînement
Pour les besoins de la présente Norme internationale, les machines d'entraînement peuvent être de deux
types:
a) à moteurs à allumage par compression, ou
b) à moteurs à allumage par étincelle.
En fonction de l'application du groupe électrogène, les critères suivants, entre autres, peuvent revêtir de
l'importance pour le choix de la machine d'entraînement à utiliser:
a) la qualité du carburant et la consommation;
b) les gaz d'échappement et l'émission du bruit;
c) la plage de vitesses;
d) la masse et les dimensions;
e) la prise de charge électrique instantanée et la tenue en fréquence;
f) les caractéristiques de court-circuit de la génératrice;
g) les systèmes de refroidissement;
h) les systèmes de démarrage;
i) les exigences relatives à la maintenance;
j) la récupération de la chaleur dissipée.
5.1.3 Génératrices électriques
Pour les besoins de la présente Norme internationale, les génératrices électriques peuvent être de deux
types:
a) synchrone, ou
b) asynchrone.
En fonction de l'application du groupe électrogène, les critères suivants, entre autres, peuvent revêtir de
l'importance pour le choix de la génératrice à utiliser:
a) les caractéristiques de tension au démarrage et en fonctionnement normal ainsi qu'après des variations
de charge en tenant compte du facteur de puissance électrique;
© ISO 2005 – Tous droits réservés 3

---------------------- Page: 8 ----------------------
ISO 8528-1:2005(F)
b) les comportements en court-circuit (électrique et mécanique);
c) le rendement;
d) la conception de la génératrice ainsi que le type d'enveloppe;
e) le comportement en fonctionnement en parallèle;
f) les exigences relatives à la maintenance.
5.1.4 Appareillage de commande et de coupure
L'équipement assurant les fonctions de commande, de coupure et de contrôle nécessaires au fonctionnement
du groupe électrogène doit faire partie intégrante de l'appareillage de commande et de coupure associé.
5.1.5 Auxiliaires
Les équipements complémentaires à ceux déjà intégrés/installés sur le groupe électrogène fourni mais qui
sont nécessaires à son bon fonctionnement en toute sécurité, tels que:
a) dispositif de mise en marche;
b) circuits d'aspiration d'air et d'échappement de gaz;
c) systèmes de refroidissement;
d) système de lubrification;
e) circuits d'alimentation en carburant (y compris les dispositifs de traitement du carburant, le cas échéant);
f) alimentation électrique auxiliaire.
5.2 Centrale de puissance
Une centrale de puissance comprend un ensemble constitué d'un ou de plusieurs groupes électrogènes avec
leurs équipements auxiliaires, de l'appareillage de commande et de coupure associé et, le cas échant, de
l'environnement de l'installation (par exemple un bâtiment, une enceinte bâtie autour ou un équipement
spécial de protection contre les intempéries).
6 Critères d'application
6.1 Modes de fonctionnement
6.1.1 Généralités
Certaines caractéristiques importantes de performance du groupe électrogène (par exemple son
fonctionnement économique et fiable, les intervalles de temps entre les opérations de maintenance et de
réparation) peuvent être influencées par son mode de fonctionnement et doivent être prises en compte par le
client lorsqu'il convient des exigences avec le constructeur (voir Article 11).
6.1.2 Fonctionnement continu sous charge constante
Un groupe électrogène a un fonctionnement continu sous charge constante s'il fonctionne sans limitation de
temps en tenant compte de la période de maintenance, lorsque la charge électrique appliquée est constante.
EXEMPLE Fournir une charge de base à une centrale combinée chaleur-électricité.
4 © ISO 2005 – Tous droits réservés

---------------------- Page: 9 ----------------------
ISO 8528-1:2005(F)
6.1.3 Fonctionnement continu sous charge variable
Un groupe électrogène a un fonctionnement continu sous charge variable s'il fonctionne sans limitation de
temps en tenant compte de la période de maintenance, lorsque la charge électrique appliquée est variable.
EXEMPLE Fournir de l'énergie électrique en cas d'indisponibilité ou de défaillance de l'énergie électrique réseau.
6.1.4 Fonctionnement limité sous charge constante
Un groupe électrogène a un fonctionnement limité sous charge constante s'il fonctionne pendant un temps
limité, lorsque la charge électrique appliquée est constante.
EXEMPLE Gestion de la charge d'écrêtage lorsqu'un groupe électrogène en fonctionnement couplé avec une
alimentation réseau est soumis à une charge constante pendant des périodes de pointe de consommation.
6.1.5 Fonctionnement limité sous charge variable
Un groupe électrogène a un fonctionnement limité sous charge variable s'il fonctionne pendant un temps
limité, lorsque la charge électrique appliquée est variable.
EXEMPLE Assurer une fonction de soutien de base à l'alimentation électrique d'un bâtiment en cas de défaillance
de l'alimentation réseau normale.
6.2 Critères d'utilisation sur site
6.2.1 Utilisation terrestre
L'utilisation terrestre s'applique aux groupes électrogènes fixes, transportables ou mobiles qui sont utilisés à
terre.
6.2.2 Utilisation marine
L'utilisation marine s'applique aux groupes électrogènes utilisés à bord de navires ou dans des installations au
large.
6.3 Fonctionnement en solo ou couplé
6.3.1 Généralités
Les groupes électrogènes peuvent avoir les deux types de fonctionnement suivants:
a) fonctionnement en solo;
Le fonctionnement en solo s'applique aux groupes électrogènes qui, indépendamment de leur
configuration ou de leur mode d'intervention et de commande, fonctionnent en source unique de
puissance électrique;
b) fonctionnement couplé.
Le fonctionnement couplé se rapporte au raccordement électrique d'un groupe électrogène à une autre
source d'énergie électrique, de mêmes tension, fréquence et en correspondance de phase, pour répartir
l'alimentation du réseau connecté. Les caractéristiques de l'alimentation par le réseau, y compris les
plages et les variations de tension, de fréquence et d'impédance du réseau, etc., doivent être spécifiées
par le client.
6.3.2 Fonctionnement couplé de groupes électrogènes
Dans ce type de fonctionnement, deux groupes électrogènes ou plus sont raccordés électriquement (pas
mécaniquement) après avoir été amenés au synchronisme. Des groupes électrogènes de différentes
puissances et vitesses peuvent être utilisés.
© ISO 2005 – Tous droits réservés 5

---------------------- Page: 10 ----------------------
ISO 8528-1:2005(F)
6.3.3 Fonctionnement couplé avec le réseau
Dans ce type de fonctionnement, un ou plusieurs groupes électrogènes fonctionnant couplés, tel que décrit en
6.3.1, sont raccordés électriquement au réseau.
Le fonctionnement couplé avec le réseau public nécessite l'autorisation du distributeur public d'électricité. Les
dispositifs de protection doivent satisfaire aux règlements publics en vigueur.
NOTE Ceci s'applique également aux groupes électrogènes qui, lors des vérifications périodiques de démarrage,
fonctionnent en fournissant de l'énergie au réseau pendant une période définie par le constructeur du groupe électrogène.
6.4 Modes d'intervention et de commande
6.4.1 Généralités
Les modes d'intervention et de commande impliqués dans le fonctionnement d'un groupe électrogène sont
généralement
a) le démarrage,
b) la surveillance,
c) le réglage de la tension et de la fréquence et la synchronisation, le cas échéant,
d) la commutation,
e) l'arrêt.
Ceux-ci peuvent être entièrement ou partiellement manuels ou automatiques conformément à l'ISO 8528-4.
6.4.2 Fonctionnement manuel
Le fonctionnement manuel s'applique aux groupes électrogènes qui sont démarrés et commandés
manuellement.
6.4.3 Fonctionnement semi-automatique
Le fonctionnement semi-automatique s'applique aux groupes électrogènes dont une partie des fonctions est
démarrée et commandée manuellement et l'autre partie automatiquement.
6.4.4 Fonctionnement automatique
Le fonctionnement automatique s'applique aux groupes électrogènes qui sont démarrés et commandés de
manière totalement automatique.
6.5 Délai d'intervention
6.5.1 Généralités
Le délai d'intervention est le temps écoulé à partir de l'instant où l'énergie est réclamée jusqu'à celui où elle
est fournie. Le délai d'intervention est généralement spécifié en secondes. Il doit satisfaire aux exigences de
l'application particulière pour laquelle le groupe électrogène est utilisé.
6.5.2 Groupes électrogènes à délai d'intervention non spécifié
Les groupes électrogènes à délai d'intervention non spécifié sont des groupes électrogènes dont le délai
d'intervention n'a pas d'importance, compte tenu des conditions dans lesquelles ces groupes électrogènes
fonctionnent. De tels groupes électrogènes sont généralement démarrés manuellement.
6 © ISO 2005 – Tous droits réservés

---------------------- Page: 11 ----------------------
ISO 8528-1:2005(F)
6.5.3 Groupes électrogènes à délai d'intervention spécifié
Les groupes électrogènes à délai d'intervention spécifié sont des groupes électrogènes dont le délai
d'intervention est imposé et dont le démarrage est généralement automatique. De tels groupes électrogènes
peuvent être classés comme suit:
6.5.3.1 Groupes à longue coupure
Les groupes à longue coupure sont des groupes électrogènes à délai d'intervention spécifié. La fourniture de
puissance est interrompue pendant un temps assez long après chaque coupure. Dans ce cas, le groupe
électrogène entier est démarré de son état stationnaire après l'appel de puissance.
6.5.3.2 Groupes à courte coupure
Les groupes à courte coupure sont des groupes électrogènes dont la génératrice tourne et pour lesquels la
fourniture de puissance est interrompue durant le temps (généralement défini en millisecondes) nécessaire au
fonctionnement du dispositif de coupure. Une source d'énergie potentielle mécanique est utilisée pour
alimenter les génératrices pendant une courte période et, si nécessaire, pour démarrer et accélérer le moteur
alternatif à combustion interne.
6.5.3.3 Groupes sans coupure
Les groupes sans coupure sont des groupes électrogènes dont la génératrice tourne en continu en
garantissant une fourniture complètement ininterrompue de puissance dans l'éventualité d'une défaillance du
secteur. Une source d'énergie potentielle mécanique est utilisée pour fournir la puissance à l'équipement
raccordé pendant une courte période et, si nécessaire, pour démarrer et accélérer le moteur alternatif à
combustion interne. Comme l'entraînement est transféré d'une source d'énergie à l'autre, ceci peut créer une
fluctuation temporaire de fréquence.
NOTE Il est essentiel que l'amplitude de variation de fréquence admise pendant le transfert fasse l'objet d'un accord
entre le client et le constructeur.
7 Classes de performance
Les quatre classes de performance suivantes sont définies pour tenir compte des diverses exigences des
circuits alimentés:
a) Classe G1
Cette classe est définie pour des applications dans lesquelles les matériels alimentés sont tels que
seules des contraintes mineures de tension et de fréquence ont besoin d'être spécifiées.
EXEMPLE Usage général (éclairage et autres charges électriques simples).
b) Classe G2
Cette classe est définie pour des applications dans lesquelles les caractéristiques de tension sont
sensiblement les mêmes que celles du réseau public. Quand des variations de charge interviennent, des
fluctuations de tension et de fréquence temporaires peuvent être acceptées.
EXEMPLE Systèmes d'éclairage, pompes, ventilateurs et appareils de levage.
c) Classe G3
Cette classe est définie pour des applications dans lesquelles le matériel alimenté nécessite des
exigences sévères de stabilité et de niveau en fréquence, tension et
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.