Portable aerosol dispenser for fire extinguishing purposes

This draft European Standard specifies the characteristics, performance and test methods for extinguishing aerosol dispensers, in accordance with Directive 75/324/EEC for fire extinguishing purposes. Requirements in this draft Standard are specified for products containing less than 1 kg or 1 l of extinguishing media, which can be expelled by the action of internal pressure and are intended to extinguish test fires of type A + B, or type A + F, or type A + B + F classes of EN 2. These extinguishing aerosol dispensers are intended to be used by untrained persons for domestic applications. They are not intended to be used on gas fires (class C) and metal fires (class D).
Requirements are specified for minimum performance in Annex H for extinguishing test fires of type A, type B and type F classes of EN 2, as appropriate.
Annex A gives the conditioning treatment to be applied to extinguishing aerosol dispensers prior to testing as described in Annex B to Annex K.

Löschspraydose

In Übereinstimmung mit der Richtlinie 75/324/EWG werden in dem vorliegenden Europäischen Norm-Entwurf die Eigenschaften, das Feuerlöschvermögen und Prüfverfahren für Druckgaspackungen für Feuerlöschzwecke (Löschspraydosen) festgelegt. Die Anforderungen in diesem Norm-Entwurf sind für Produkte mit weniger als 1 kg oder 1 l Löschmittel festgelegt, das durch die Einwirkung des Innendrucks ausgestoßen werden kann und zum Löschen von Prüfbränden der Klassen A und B oder Klassen A und F oder Klassen A, B und F der EN 2 vorgesehen ist. Diese Löschspraydosen sind für die Verwendung durch ungeübte Personen im häuslichen Bereich vorgesehen. Die Löschspraydosen sind nicht dazu vorgesehen, bei Gasbränden (Brandklasse C) und Metallbränden (Brandklasse D) verwendet zu werden.
In Anhang H sind die Anforderungen an das Mindest-Feuerlöschvermögen von Prüfbränden der Brandklasse A, Brandklasse B und Brandklasse F nach EN 2 festgelegt, sofern zutreffend.
In Anhang A wird die Behandlung zur Konditionierung angegeben, der die Löschspraydosen vor den in Anhang B bis Anhang K beschriebenen Prüfungen zu unterziehen sind.

Générateur d'aérosol portatif pour l'extinction d'un incendie

La présente norme spécifie les caractéristiques, les performances et les méthodes d’essai relatives aux générateurs d’aérosols à fonction extinctrice, conformément à la Directive 75/324/CEE, destinés à l’extinction d’incendies. Les exigences de la présente norme sont spécifiées pour les produits contenant moins de 1 kg ou 1 litre d’agent extincteur, qui peuvent être diffusés par l’action d’une pression interne et qui sont destinés à l’extinction de foyers-types des classes A + B, ou A + F, ou A + B + F selon le classement de l’EN 2. Les générateurs d’aérosols à fonction extinctrice sont destinés à être utilisés par des personnes non formées, pour des applications domestiques. Ils ne sont pas destinés à être utilisés sur des feux de gaz (classe C) ou sur des feux de métaux (classe D).
L’Annexe H spécifie des exigences de performance minimales pour l’extinction de foyers-types des classes A, B et F de l’EN 2, suivant les cas.
L’Annexe A indique les conditions pré-requises à appliquer aux générateurs d’aérosols à fonction extinctrice avant les essais décrits dans les Annexes de B à K.

Prenosni aerosolni razpršilnik za gašenje požarov

General Information

Status
Not Published
Public Enquiry End Date
29-Jul-2015
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
25-Jul-2016
Due Date
30-Jul-2016
Completion Date
25-Jul-2016

Buy Standard

Draft
prEN 16856:2015 - BARVE
English language
41 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 16856:2015
01-julij-2015
Prenosni aerosolni razpršilnik za gašenje požarov
Portable aerosol dispenser for fire extinguishing purposes
Löschspraydose
Générateur d'aérosol portatif pour l'extinction d'un incendie
Ta slovenski standard je istoveten z: prEN 16856
ICS:
13.220.10 Gašenje požara Fire-fighting
oSIST prEN 16856:2015 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 16856:2015

---------------------- Page: 2 ----------------------
oSIST prEN 16856:2015

EUROPEAN STANDARD
DRAFT
prEN 16856
NORME EUROPÉENNE

EUROPÄISCHE NORM

May 2015
ICS 13.220.10
English Version
Portable aerosol dispenser for fire extinguishing purposes
Générateur aérosol à fonction extinctrice Löschspraydose
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 70.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16856:2015 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
Contents Page
Foreword . 4
1 Scope. 5
2 Normative references . 5
3 Terms and definitions . 5
4 Contents of the extinguishing aerosol dispenser . 7
4.1 Extinguishing medium. 7
4.2 Propellant . 7
5 Construction, design and prototype testing . 7
5.1 Operation . 7
5.2 Body and closure . 8
5.2.1 Body . 8
5.2.2 Closure . 8
5.3 Corrosion resistance . 9
5.3.1 External corrosion . 9
5.3.2 Internal corrosion . 9
5.3.3 Chemical and pressure stability . 9
5.4 Impact resistance . 9
5.5 Resistance to shock and mechanical damage . 9
5.6 Test pressure . 9
5.7 Burst pressure . 9
5.8 Life . 9
5.9 Dielectric test . 10
5.9.1 General . 10
5.9.2 Required performance . 10
6 Filling requirements . 10
6.1 Media tolerance . 10
6.2 Filling pressure . 10
6.3 P(T ) . 10
max
7 Performance . 10
7.1 Delay on operation . 10
7.2 Duration of discharge . 10
7.3 Minimum discharge of contents . 10
7.4 Leakage rate . 11
7.5 Retention of charge following partial discharge . 11
7.6 Fire extinguishing performance rating — Ratings . 11
7.6.1 General . 11
7.6.2 Class A rating . 11
7.6.3 Class B rating . 11
7.6.4 Class F rating . 11
7.7 Effective throw . 11
8 Production tests . 11
8.1 General . 11
8.2 Final inspection of filled extinguishing aerosol dispensers . 11
8.2.1 General . 11
8.2.2 Hot water bath method . 12
8.2.3 Alternative hot final test method . 12
2

---------------------- Page: 4 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
8.2.4 Cold final test method . 12
8.3 Burst test . 12
8.4 Crimped closures . 12
8.5 Discharge test . 13
8.6 Leak test . 13
9 Colour and marking of extinguishing aerosol dispensers . 13
9.1 Colour . 13
9.2 Marking - Primary information . 13
9.3 Marking - Secondary information . 14
Annex A (normative) Test conditions . 18
A.1 General . 18
A.2 Storing and temperature . 18
Annex B (normative) Corrosion test . 19
B.1 External corrosion . 19
B.2 Internal corrosion . 19
Annex C (normative) Impact test . 20
Annex D (normative) Mechanical drop test . 21
Annex E (normative) Pressure tests for bodies . 22
E.1 Test for resistance to pressure . 22
E.2 Minimum burst test . 22
Annex F (normative) Force to open valve . 23
Annex G (normative) Discharge tests . 24
G.1 Duration of discharge and minimum discharge of contents . 24
G.2 Intermittent discharge and minimum discharge of contents . 25
G.3 Effective throw . 25
Annex H (normative) Test for retention of charge after partial discharge . 26
Annex I (normative) Fire extinguishing performance tests . 27
I.1 General . 27
I.2 Schedule for testing . 27
I.3 Class A fire test . 27
I.3.1 Characteristics of test fire . 27
I.3.2 Test conditions . 30
I.3.3 Test procedure . 31
I.4 Class B fire test . 31
I.4.1 Characteristics of test fire . 31
I.4.2 Test conditions . 32
I.4.3 Test procedure . 33
I.5 Class F fire test . 33
I.5.1 General . 33
I.5.2 Characteristics of test fire . 33
I.5.3 Test conditions . 35
I.5.4 Test procedure . 35
Annex J (normative) Dielectric test . 37
J.1 Apparatus . 37
J.2 Test procedure . 37
Annex K (normative) Chemical and pressure stability test . 39
Annex L (informative) Example of breakdown and order of tests . 40
Bibliography . 41

3

---------------------- Page: 5 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
Foreword
This document (prEN 16856:2015) has been prepared by Technical Committee CEN/TC 70 “Manual
means of fire fighting equipment”, the secretariat of which is held by AFNOR.
This document is currently submitted to the CEN Enquiry.
It specifies the requirements for non-refillable portable aerosol dispensers for fire extinguishing
purposes.
This draft standard has been written with the aim of producing a specification for relatively
inexpensive small disposable, aerosol dispensers for fire extinguishing purposes with an acceptable
minimum level of performance. This type of product is intended for use only in situations where fires of
limited proportions are anticipated because of the nature of some process or activity, where the
possibility of fire spreading to other materials is remote, or where people are present at the likely
times of risk. The standard therefore is unlikely to meet the requirements of the various specifying
authorities for more comprehensive protection. These products are not intended to supplant
extinguishers that comply with EN 3 (all parts), which should still be regarded as the principal type to
meet the needs of various authorities.
Special attention is drawn to Directive 75/324/EEC of 20 May 1975, on the approximation of the laws
of the member states relating to Aerosol Dispensers, Directive 2008/47/EC and Commission Directive
94/1/EC of 6 January 1994 adapting some technicalities of Council Directive 75/324/EEC on the
approximation of the laws of the Member States relating to aerosol dispensers.
4

---------------------- Page: 6 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
1 Scope
This draft European Standard specifies the characteristics, performance and test methods for
extinguishing aerosol dispensers, in accordance with Directive 75/324/EEC for fire extinguishing
purposes. Requirements in this draft Standard are specified for products containing less than 1 kg or
1 l of extinguishing media, which can be expelled by the action of internal pressure and are intended
to extinguish test fires of type A + B, or type A + F, or type A + B + F classes of EN 2. These
extinguishing aerosol dispensers are intended to be used by untrained persons for domestic
applications. They are not intended to be used on gas fires (class C) and metal fires (class D).
Requirements are specified for minimum performance in Annex H for extinguishing test fires of type A,
type B and type F classes of EN 2, as appropriate.
Annex A gives the conditioning treatment to be applied to extinguishing aerosol dispensers prior to
testing as described in Annex B to Annex K.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 615, Fire protection — Fire extinguishing media — Specifications for powders (other than class D
powders)
EN ISO 9227, Corrosion tests in artificial atmospheres — Salt spray tests (ISO 9227)
ISO 657-14, Hot-rolled steel sections — Part 14: Hot-finished structural hollow sections —
Dimensions and sectional properties
ISO 4470, Sawn timber — Determination of the average moisture content of a lot
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
aerosol dispenser for fire extinguishing purposes
non-refillable metallic container intended for a single use, which holds a compressed gas and liquid,
paste or powder extinguishing media, equipped with a valve allowing a controlled discharge of the
contents
Note 1 to entry: Extinguishing aerosol dispensers are designed to be discarded after any use and are bound
not to be refilled.
3.2
batch
definite quantity of products or components produced at one time under conditions that are presumed
uniform
Note 1 to entry: The circumstances under which the conditions can be presumed cannot be generally stated;
for example, a change in the material or tool used in an interruption in the manufacturing process can give rise to
different conditions, see ISO 3534-2.
5

---------------------- Page: 7 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
3.3
body
seamless metallic container of the extinguishing aerosol dispenser not fitted with its accessories, such
as valves, having a maximum total capacity of 1 000 ml
3.4
valve
self-closing release device allowing the discharge of the extinguishing media to be discontinuous
3.5
charge of an extinguishing aerosol dispenser
mass or volume of the extinguishing medium contained in the extinguishing aerosol dispenser
3.6
maximum pressure at maximum operating temperature P
T
max
pressure within the extinguishing aerosol dispenser when filled with the quantity of solid, liquid and
gaseous content to the maximum upper tolerance specified under production conditions, at a
temperature of 50 °C
3.7
burst pressure
maximum pressure achieved during a burst test
3.8
test pressure
pressure, when applied, shows no visible permanent deformation
3.9
working pressure
pressure declared by the manufacturer as the pressure within the extinguishing aerosol dispenser,
when filled with quantities of solid, liquid and gaseous content at 20 °C
3.10
extinguishing medium
substance including any additive, such as corrosion inhibitor, freezing point depressant or blowing
agent, contained in the extinguishing aerosol dispenser that causes extinction of a fire
3.11
protective cap
cover over the valve of the extinguishing aerosol dispenser
3.12
propellant
compressed gas held in the container, which allows the required pressure for the discharge of the
extinguishing medium
3.13
fire rating
designation of the largest test fire that has been extinguished when tested in accordance with 7.6.2,
7.6.3 and 7.6.4
3.14
domestic
premises occupied as a private dwelling, including any garden, yard, garage, outhouse, or
appurtenance of such premises, which is not used in common by the occupants of more than one
such dwelling
6

---------------------- Page: 8 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
3.15
safety device
part that needs to be broken or removed before the extinguishing aerosol dispenser, and be activated
3.16
security seal
part that is broken when removing the safety device and once broken cannot be replaced
3.17
minimum operating temperature
T
min
minimum temperature declared by the manufacturer at which the extinguishing aerosol dispenser will
operate
4 Contents of the extinguishing aerosol dispenser
4.1 Extinguishing medium
The extinguishing medium shall be one of the following:
— water based, including additives conforming to the physical characteristics declared by the
manufacturer;
— powder conforming to EN 615.
4.2 Propellant
Only propellants listed in Table 1 or mixtures thereof shall be used. The maximum water content shall
be as specified in Table 1, except when used in a water-based extinguishing aerosol dispenser.
Tracers may be added to the propellant to facilitate leakage detection, but the content shall not
exceed a mass fraction of 10 % of the propellant content.
Table 1 — Permitted propellants
 Propellant Maximum water content
  mass fraction, %
Air  0,006
Argon  0,006
Helium  0,006
Nitrogen  0,006
5 Construction, design and prototype testing
5.1 Operation
5.1.1 The extinguishing aerosol dispenser shall be operated by activating the valve. The method of
activation shall be readily apparent. It shall not be necessary for any movement of the actuating
mechanism to be repeated in order to initiate discharge.
5.1.2 The construction of the extinguishing aerosol dispenser shall ensure no parts can be
removed, excluding items in 5.1.5 and 5.1.6.
7

---------------------- Page: 9 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
5.1.3 The design of the extinguishing aerosol dispenser shall allow rapid identification of whether or
not it has been used.
5.1.4 The extinguishing aerosol dispenser shall operate without inversion.
5.1.5 The extinguishing aerosol dispenser shall incorporate a safety device to prevent inadvertent
operation, which shall be so constructed that any unaided manual attempt to initiate discharge will not
deform or break any part in a way that would prevent the subsequent discharge of the extinguishing
aerosol dispenser.
5.1.6 The extinguishing aerosol dispenser shall have a security seal, which shall be broken by the
removal of the safety device. The force required to remove the safety device and break the security
seal shall be between 20 and 100 N, see Annex F. This security seal shall be such that it will not be
broken or damaged in normal service and cannot be replaced after operation.
5.1.7 The extinguishing aerosol dispenser shall incorporate a valve to enable the discharge to be
interrupted. The force required to actuate the device shall not exceed 75 N, see Annex F.
5.2 Body and closure
5.2.1 Body
The body shall be a metallic seamless container and shall have a maximum total capacity of 1000 ml.
5.2.2 Closure
The closure shall be crimped under the neck ring of the body. The crimping diameter and the crimping
depth shall be determined by the manufacturer, see Figure 1.

Key
1 crimp depth
2 crimp diameter
3 neck ring
Figure 1 — Crimp diameter and depth
8

---------------------- Page: 10 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
5.3 Corrosion resistance
5.3.1 External corrosion
After testing in accordance with B.1, the extinguishing aerosol dispenser shall show no signs of
progressive corrosion or other chemical degradation, no pressure shall be released and shall operate
as intended. The discharge time shall be equal to or greater than the manufacturer’s specified
minimum.
5.3.2 Internal corrosion
After storage in accordance with B.2, the extinguishing aerosol dispenser shall operate as intended.
The discharge time shall be equal to or greater than the manufacturer’s specified minimum. After
being discharged, the extinguishing aerosol dispenser shall be checked internally for corrosion. There
shall be no signs of progressive corrosion, however uniform oxidation may occur.
5.3.3 Chemical and pressure stability
The contents shall not generate pressure by reacting with the body or any lining. The complete
assembly shall be chemically stable. Small increases are permitted, but the total pressure may
increase by a maximum of 10 % of the working pressure during the test, but shall be stable by the end
of the test. It shall be tested in accordance with Annex K.
5.4 Impact resistance
The extinguishing aerosol dispenser (with protective cap if used) correctly charged and equipped with
all the fittings that are subject to internal pressure in normal operation, may leak but the body shall not
rupture, when tested in accordance with Annex C. To ensure any leak does not affect the
performance of the extinguishing aerosol dispenser, it shall operate as intended and be tested within
5 min of being subjected to the tests in Annex C. The discharge time shall be + 15 % of the actual
time measured in 7.2 and the minimum discharge shall be in accordance with 7.3.
5.5 Resistance to shock and mechanical damage
The extinguishing aerosol dispenser shall show no detectable leakage resulting in loss of pressure
when tested in accordance with Annex D. The extinguishing aerosol dispenser shall operate as
intended. The discharge time shall be + 15 % of the actual time measured in 7.2 and the minimum
discharge shall be in accordance with 7.3.
5.6 Test pressure
The body shall withstand an internal pressure of 10 bar or 1,5 times the P(T ), whichever is the
max
greater, without visible permanent deformation when tested in accordance with E.1.
5.7 Burst pressure
The minimum burst pressure of the body, fitted with all pressure retaining parts, shall be 18 bar or at
least 1,2 times test pressure, whichever is the greater, when tested in accordance with E.2. The body
shall not fragment or eject any parts.
5.8 Life
An extinguishing aerosol dispenser has a maximum life of 39 months from the date of manufacture.
9

---------------------- Page: 11 ----------------------
oSIST prEN 16856:2015
prEN 16856:2015 (E)
5.9 Dielectric test
5.9.1 General
The dielectric test is designed to determine the electrical conductivity of the extinguishing aerosol
dispenser during the test when performed in accordance with Annex G.
5.9.2 Required performance
When the extinguishing aerosol dispenser is in operation and the metallic plate is live, the current
between the handle and earth, and between the nozzle and earth, shall not be more than 0,5 mA at
any time during the complete discharge of the extinguishing aerosol dispenser. The test shall be
carried out in accordance with Annex J.
6 Filling requirements
6.1 Media tolerance
The filling tolerance of the gross contents shall be + 5 % for powder extinguishing media and + 0/-3 %
for all other extinguishing media.
The filling tolerance for each individual constituent of the gross content shall be + 2 %.
6.2 Filling pressure
The filling pressure shall be + 0,5 bar of the working pressure at 20 °C.
6.3 P(T )
max
The filling pressure, when filled to the upper tolerance, shall be such that the maximum developed
pressure at 50 °C shall not exceed 13,2 bar.
7 Performance
7.1 Delay on operation
Not more than 2 s shall elapse between activation of the valve and commencement of the discharge
when tested in accordance with G.1.
7.2 Duration of discharge
The duration of effective discharge shall be not less than 6 s when tested in accordance with G.1
(continuous discharge).
7.3 Minimum discharge of contents