Abstract

IEC 62397:2022 describes the requirements for resistance temperature detectors (RTDs) suitable for applications in I&C systems important to safety of nuclear power plants. The requirements of RTDs include design, materials, manufacturing, testing, calibration, procurement, and inspection. RTDs used for safety applications in Nuclear Power Plants can be categorized into direct-immersed and thermowell-mounted RTDs.
This standard describes the requirements for the design, material selection, procurement, construction, and testing of resistance temperature detectors (RTDs) used in nuclear power plants (NPPs). These RTDs may be used in both the nuclear safety I&C systems and/or in the non-safety-related instrumentation systems.
This second edition cancels and replaces the first edition, published in 2007; it also cancels and replaces the first edition of IEC 61224:1993. This edition includes the following significant technical changes with respect to the previous edition.

Status
Published
Public Enquiry End Date
31-Dec-2025
Publication Date
18-Jun-2026
Technical Committee
I09 - Imaginarni 09
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
09-Jun-2026
Due Date
14-Aug-2026
Completion Date
19-Jun-2026

Buy Documents

Standard

SIST EN IEC 62397:2026

English language (42 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN IEC 62397:2026 is the Slovenian adoption of the European Standard EN IEC 62397:2026, which reproduces IEC 62397:2022. It specifies requirements for resistance temperature detectors (RTDs) used in instrumentation and control (I&C) important to safety in nuclear power plants (NPPs), including RTDs used in safety-related and non-safety-related instrumentation.

The document is written for people who need to design, buy, qualify, inspect, test or maintain RTDs for NPP service. In practice, it tells you what the RTD itself must meet, what the user must define for the application, and what evidence is needed before installation and during qualification.

What does SIST EN IEC 62397:2026 specify?

SIST EN IEC 62397:2026 covers the requirements for RTDs suitable for NPP I&C important to safety. It includes direct-immersed RTDs, thermowell-mounted RTDs, and RTDs with other specific designs that still fall within the document’s scope.

The standard also states what is outside its scope: the thermowell, guide tube, extension cable, temperature transmitter and resistance bridge associated with the RTD are not covered. That matters because these items may be specified elsewhere in the plant design or procurement documents.

The document is organized into:

  • Clause 1 - Scope
  • Clause 2 - Normative references
  • Clause 3 - Terms, definitions and abbreviated terms
  • Clause 4 - Design and construction requirements
  • Clause 5 - Inspection and tests
  • Clause 6 - Documentation
  • Annex A - Informative in situ response time test methods
  • Annex ZA - Normative references to international publications and the corresponding European publications
AnnexWhat it covers
AIn situ response time test methods, including LCSR, temperature-noise analysis and the self-heating method
ZANormative reference mapping for the European publication

What are the key requirements of SIST EN IEC 62397:2026?

SIST EN IEC 62397:2026 sets requirements for design, materials, connections, performance, inspection and qualification. A recurring theme is that the user must define application-specific conditions, especially for harsh environments, accident conditions, and acceptance criteria.

Design, materials and construction

Clause 4 requires the RTD design to suit the plant environment under normal operation and accident conditions, including certain design extension conditions. The RTD shall meet or exceed the document’s requirements, and its required reliability shall be derived from the reliability needed for the temperature-measurement function.

Clause 4.3 requires materials to retain their properties over the required service life. The RTD materials must also tolerate radiation conditions relevant to the installation position, including neutron exposure where applicable. This is important because the sensor has to keep its sensing function and mechanical integrity throughout plant life.

Clause 4.4 covers electrical and mechanical connections. The electrical connection may be 3-wire or 4-wire, and the connector assembly must resist moisture intrusion and maintain electrical continuity through normal and accident conditions. The document distinguishes a quick-disconnect type and a standard type, so procurement has to match the intended installation and maintenance approach.

The mechanical connection requirements link the RTD to its thermowell and mounting hardware. The user must ensure compatibility with the thermowell, connection head, extension guide tube and end fittings. After welding, non-destructive testing is required using agreed methods, which matters for verifying weld quality before service.

Performance and calibration

Clause 4.7 sets the RTD performance topics that matter in operation: accuracy, resistance-temperature calibration, self-heating error, thermal response time, interchangeability, insulation resistance, vibration behavior, steam resistance, thermal cycling, dielectric inspection, hydraulic strength and in situ response time.

The standard treats calibration as a traceable comparison against a known standard, and it requires the RTD accuracy to be established that way. It also includes the Callendar formula for platinum resistance thermometers in the resistance-temperature calibration clause, so the document is not just about sensor hardware - it also defines how the sensor’s resistance should be interpreted as temperature.

Response time is handled in a practical way. The document distinguishes laboratory plunge testing from in situ response time testing in the installed plant configuration, because the installed thermowell and process conditions can change the result significantly. That distinction matters when a plant needs real operational response time, not just bench data.

Inspection, tests and qualification

Clause 5 requires testing to prove conformance. Routine production tests are required for every RTD, while qualification tests are applied to samples of each design and range. The manufacturer must also keep inspection and test records for the relevant plant or RTD life.

Clause 5.4 provides the detailed test methods. It includes assembly and appearance checks, calibration procedure, self-heating testing, thermal response time testing, insulation resistance testing, repeatability after thermal shock, vibration testing, steam testing, thermal cycling, dielectric inspection, hydraulic testing, in situ response time testing and cross-calibration testing.

Clause 5.6 ties qualification to IEC/IEEE 60780-323 and IEC/IEEE 60980-344, or to relevant national guides and regulations. It also allows additional tests such as LOCA simulation, seismic testing and irradiation testing when the application requires them. In practice, this means qualification is not fixed once and for all - it must match the reactor type, the plant environment and the sensor’s safety role.

What terms does SIST EN IEC 62397:2026 define?

  • Resistance temperature detector (RTD) - A temperature detector whose resistance changes with temperature and is used here for NPP temperature measurement.
  • Calibration - A traceable operation that establishes the relationship between indication and measurement result under specified conditions.
  • Cross-calibration / cross-validation - A comparison of redundant instruments to identify outliers or calibration changes.
  • Drift - A slow change in indication that is not caused by a change in the measurand.
  • In situ measurement - Measurement of RTD performance while the RTD remains installed in its normal service configuration.
  • Response time - The time needed for the component to reach a specified output state after a signal or temperature change.
  • Self-heating error - The apparent temperature rise caused by power dissipated in the sensor during measurement.
  • Thermowell - A protective jacket that shields the sensor and allows replacement.

Abbreviations used in the document include RTD, NPP, I&C, LCSR, SHI and QA. LCSR means loop current step response, and SHI means self-heating index.

Who uses SIST EN IEC 62397:2026?

SIST EN IEC 62397:2026 is used by NPP designers, instrumentation engineers, manufacturers, purchasers, quality assurance staff, inspection teams and qualification laboratories. It is especially relevant when a project needs to specify, procure, test or qualify RTDs for safety-related temperature measurement.

Plant operators and maintenance teams use it when they need documentation, installation compatibility, response-time verification or cross-calibration of installed RTDs. Buyers and suppliers use it to align technical specifications, acceptance criteria and factory testing before delivery.

What changed in SIST EN IEC 62397:2026 from the previous edition?

This second edition replaces the first edition published in 2007 and also replaces IEC 61224:1993. The revision merges content from both documents into one standard for RTDs in NPP service.

The main changes stated in the document include:

  • incorporation of definitions, references and test methods from IEC 61224
  • added in situ response time test methods
  • updated and expanded terms and definitions, including cross-calibration and SHI
  • revised design, materials, connection and manufacturing requirements
  • more detailed performance and test requirements, including cross-calibration testing
  • updated references to IEC 60751, IEC/IEEE 60780-323 and IEC/IEEE 60980-344
  • added informative Annex A for in situ response time methods

Which standards are used with SIST EN IEC 62397:2026?

Clause 2 names these normative references:

  • IEC 60068-2-6 - used for vibration testing of RTDs
  • IEC 60068-2-30 - used for damp-heat cyclic testing and thermal cycling where applied
  • IEC 60751 - used for platinum resistance thermometers, calibration-related content and RTD characteristics
  • IEC/IEEE 60780-323 - used for qualification of electrical equipment important to safety
  • IEC/IEEE 60980-344 - used for seismic qualification of equipment important to safety

Annex ZA maps these references to the corresponding European publications. The document also cites related standards and bodies of work in its bibliography and introduction, including IEC 61298-2, IEC 62385, IEC 62765-2 and IAEA nuclear safety publications, to place RTD practice in the wider nuclear instrumentation framework.

What does the SIST EN IEC 62397:2026 document contain?

The document contains the RTD design and construction rules, the performance clauses, the inspection and qualification test methods, and the documentation that should accompany the RTD. It also includes a detailed annex on in situ response-time methods.

The body of the standard includes figures for RTD forms, electrical connection types and mechanical connection arrangements. It also includes a Callendar formula section for resistance-temperature calibration and separate procedures for calibration, self-heating, thermal response time, vibration, steam, thermal cycling, dielectric inspection, hydraulic testing and cross-calibration.

Annex A gives three in situ response time methods: loop current step response, temperature-noise analysis and the self-heating method. That annex is useful when a plant needs installed-performance data rather than laboratory data alone.

Relations

Effective Date
03-Feb-2026
Effective Date
03-Feb-2026
Effective Date
03-Feb-2026
Effective Date
03-Feb-2026
Effective Date
03-Feb-2026

Buy Documents

Standard

SIST EN IEC 62397:2026

English language (42 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DNV

DNV is an independent assurance and risk management provider.

NA Norway Verified

Lloyd's Register

Lloyd's Register is a global professional services organisation specialising in engineering and technology.

UKAS United Kingdom Verified

DNV Energy Systems

Energy and renewable energy certification.

NA Norway Verified

Sponsored listings

Frequently Asked Questions

SIST EN IEC 62397:2026 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Nuclear power plants - Instrumentation and control important to safety - Resistance temperature detectors (IEC 62397:2022)". This standard covers: IEC 62397:2022 describes the requirements for resistance temperature detectors (RTDs) suitable for applications in I&C systems important to safety of nuclear power plants. The requirements of RTDs include design, materials, manufacturing, testing, calibration, procurement, and inspection. RTDs used for safety applications in Nuclear Power Plants can be categorized into direct-immersed and thermowell-mounted RTDs. This standard describes the requirements for the design, material selection, procurement, construction, and testing of resistance temperature detectors (RTDs) used in nuclear power plants (NPPs). These RTDs may be used in both the nuclear safety I&C systems and/or in the non-safety-related instrumentation systems. This second edition cancels and replaces the first edition, published in 2007; it also cancels and replaces the first edition of IEC 61224:1993. This edition includes the following significant technical changes with respect to the previous edition.

IEC 62397:2022 describes the requirements for resistance temperature detectors (RTDs) suitable for applications in I&C systems important to safety of nuclear power plants. The requirements of RTDs include design, materials, manufacturing, testing, calibration, procurement, and inspection. RTDs used for safety applications in Nuclear Power Plants can be categorized into direct-immersed and thermowell-mounted RTDs. This standard describes the requirements for the design, material selection, procurement, construction, and testing of resistance temperature detectors (RTDs) used in nuclear power plants (NPPs). These RTDs may be used in both the nuclear safety I&C systems and/or in the non-safety-related instrumentation systems. This second edition cancels and replaces the first edition, published in 2007; it also cancels and replaces the first edition of IEC 61224:1993. This edition includes the following significant technical changes with respect to the previous edition.

SIST EN IEC 62397:2026 is classified under the following ICS (International Classification for Standards) categories: 27.120.20 - Nuclear power plants. Safety. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN IEC 62397:2026 has the following relationships with other standards: It is inter standard links to SIST EN 60068-2-30:2006, SIST EN IEC 60751:2022, SIST EN 60780-323:2017, SIST EN IEC/IEEE 60980-344:2021, SIST EN 60068-2-6:2008. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN IEC 62397:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions and abbreviated terms
  • 3.1 Terms and definitions
  • 3.1.1 calibration
  • 3.1.2 cross-calibration
  • 3.1.3 drift
  • 3.1.4 in situ measurement
  • 3.1.5 protective tube
  • 3.1.6 resistance temperature detector
  • 3.1.7 response time
  • 3.1.8 self-heating error
  • 3.1.9 self-heating index
  • 3.1.10 thermowell
  • 3.1.11 tolerance of RTD
  • 3.2 Abbreviated terms
  • 4 Design and construction requirements
  • 4.1 General
  • 4.2 Reliability
  • 4.3 Materials
  • 4.4 Connections
  • 4.5 Manufacturing quality
  • 4.6 Ambient conditions (normal and accident operations) and qualification
  • 4.7 RTD performance
  • 4.8 Identification
  • 4.9 Failure mode and effects analysis
  • 5 Inspection and tests
  • 5.1 General
  • 5.2 Inspection and test failure
  • 5.3 Inspection and test reports
  • 5.4 Test method
  • Annex A describes the techniques which can be used for the in situ measurement of RTD
  • 5.5 Production test
  • 5.6 Qualification test
  • 6 Documentation
  • Annex A
  • Bibliography

INTRODUCTION a) Technical background, main issues and organisation of the standard This standard describes the requirements for the design, material selection, procurement, construction, and testing of resistance temperature detectors (RTDs) used in nuclear power plants (NPPs). These RTDs may be used in both the nuclear safety I&C systems and/or in the non-safety-related instrumentation systems.

This standard is a revision merger of IEC 62397 and IEC 61224 and was initiated in November 2019.

b) Situation of the current standard in the structure of the SC 45A standard series IEC 62397 is not directly referenced by IEC 61513 and is a third-level SC 45A document tackling the issue of RTDs.

For more details on the structure of the SC 45A series of standards, see item d) of this introduction.

c) Recommendations and limitations regarding the application of this standard There is no particular recommendation or limitation regarding the application of this standard. d) Description of the structure of the IEC SC45A standard series and relationships with other IEC documents and other bodies documents (IAEA, ISO) The IEC SC 45A standard series comprises a hierarchy of four levels. The top-level documents of the IEC SC 45A standard series are IEC 61513 and IEC 63046. IEC 61513 provides general requirements for instrumentation and control (I&C) systems and equipment that are used to perform functions important to safety in nuclear power plants (NPPs). IEC 63046 provides general requirements for electrical power systems of NPPs; it covers power supply systems including the supply systems of the I&C systems. IEC 61513 and IEC 63046 are to be considered in conjunction and at the same level. IEC 61513 and IEC 63046 structure the IEC SC 45A standard series and shape a complete framework establishing general requirements for instrumentation, control and electrical power systems for nuclear power plants.

IEC 61513 and IEC 63046 refer directly to other IEC SC 45A standards for general requirements for specific topics, such as categorization of functions and classification of systems, qualification, separation, defence against common cause failure, control room design, electromagnetic compatibility, human factors engineering, cybersecurity, software and hardware aspects for programmable digital systems, coordination of safety and security requirements and management of ageing. The standards referenced directly at this second level should be considered together with IEC 61513 and IEC 63046 as a consistent document set. At a third level, IEC SC 45A standards not directly referenced by IEC 61513 or by IEC 63046 are standards related to specific requirements for specific equipment, technical methods, or activities. Usually these documents, which make reference to second-level documents for general requirements, can be used on their own.

A fourth level extending the IEC SC 45 standard series, corresponds to the Technical Reports which are not normative.

SIST EN IEC 62397:2026

The IEC SC 45A standards series consistently implements and details the safety and security principles and basic aspects provided in the relevant IAEA safety standards and in the relevant documents of the IAEA nuclear security series (NSS). In particular this includes the IAEA requirements SSR-2/1 , establishing safety requirements related to the design of nuclear power plants (NPPs), the IAEA safety guide SSG-30 dealing with the safety classification of structures, systems and components in NPPs, the IAEA safety guide SSG-39 dealing with the design of instrumentation and control systems for NPPs, the IAEA safety guide SSG-34 dealing with the design of electrical power systems for NPPs, the IAEA safety guide SSG-51 dealing with human factors engineering in the design of NPPs and the implementing guide NSS17 for computer security at nuclear facilities. The safety and security terminology and definitions used by the SC 45A standards are consistent with those used by the IAEA.

IEC 61513 and IEC 63046 have adopted a presentation format similar to the basic safety publication IEC 61508 with an overall life-cycle framework and a system life-cycle framework. Regarding nuclear safety, IEC 61513 and IEC 63046 provide the interpretation of the general requirements of IEC 61508-1, IEC 61508-2 and IEC 61508-4, for the nuclear application sector. In this framework, IEC 60880, IEC 62138 and IEC 62566 correspond to IEC 61508-3 for the nuclear application sector.

IEC 61513 and IEC 63046 refer to ISO 9001 as well as to IAEA GSR part 2 and IAEA GS-G-3.1 and IAEA GS-G-3.5 for topics related to quality assurance (QA). At level 2, regarding nuclear security, IEC 62645 is the entry document for the IEC/SC 45A security standards. It builds upon the valid high level principles and main concepts of the generic security standards, in particular ISO/IEC 27001 and ISO/IEC 27002; it adapts them and completes them to fit the nuclear context and coordinates with the IEC 62443 series. At level 2, IEC 60964 is the entry document for the IEC/SC 45A control rooms standards, IEC 63351 is the entry document for the human factors engineering standards and IEC 62342 is the entry document for the ageing management standards.

NOTE 1 It is assumed that for the design of I&C systems in NPPs that implement conventional safety functions (e.g. to address worker safety, asset protection, chemical hazards, process energy hazards) international or national standards would be applied.

NOTE 2 IEC TR 64000 provides a more comprehensive description of the overall structure of the IEC SC 45A standards series and of its relationship with other standards bodies and standards.

SIST EN IEC 62397:2026

NUCLEAR POWER PLANTS – INSTRUMENTATION AND CONTROL IMPORTANT TO SAFETY – RESISTANCE TEMPERATURE DETECTORS

1 Scope

This document describes the requirements for resistance temperature detectors (RTDs) suitable for applications in I&C systems important to safety of nuclear power plants. The requirements of RTDs include design, materials, manufacturing, testing, calibration, procurement, and inspection. RTDs used for safety applications in Nuclear Power Plants can be categorized into direct-immersed and thermowell-mounted RTDs. Furthermore, there are RTDs with specific design which cannot be assigned to the categories mentioned above. However, they are also covered by the requirements stated in this document. This document does not cover the design, material selection, and construction of the thermowell, the guide tube, the extension cable, and the temperature transmitter or resistance bridge which may be associated with the RTD.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60068-2-6:2007, Environmental testing – Part 2-6: Tests – Test Fc: Vibration (sinusoidal) IEC 60068-2-30:2005, Environmental testing – Part 2-30: Tests – Test Db: Damp heat, cyclic (12 h + 12 h cycle) IEC 60751:2022, Industrial platinum resistance thermometers and platinum temperature sensors IEC/IEEE 60780-323:2016, Nuclear facilities – Electrical equipment important to safety – Qualification IEC/IEEE 60980-344:2020, Nuclear facilities – Equipment important to safety – Seismic qualification

3 Terms, definitions and abbreviated terms

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

SIST EN IEC 62397:2026

3.1 Terms and definitions

3.1.1 calibration

set of operations that establishes, by referring to standards, the relationship which exists under specified conditions between an indication and a result of a measurement Note 1 to entry: This term is based on the "uncertainty" approach. Note 2 to entry: The relationship between the indications and measurement results can be expressed, in principle, using a calibration diagram.

3.1.2 cross-calibration

cross-validation procedure of intercomparing the indications of redundant instruments (e.g., temperature sensors) to identify outlier sensors as a means of verifying calibration or identifying calibration changes. A more appropriate term for this definition is "cross-validation," but, cross-calibration is more commonly used Note 1 to entry: A calibration test of temperature sensors in some NPPs can be different from this definition mainly because an adjustment of the temperature channel during cross calibration may be allowed within a predetermined allowable value.

[SOURCE: IEC 62385:2007, 3.6]

3.1.3 drift

change in the indication of a measuring instrument, generally slow, continuous, not necessarily in the same direction and not related to a change in the measurand [SOURCE: IEC 60050-311:2001, 311-06-13]

3.1.4 in situ measurement

measurement of RTD performance (calibration or response time) while the RTD remains installed in normal configuration for service

3.1.5 protective tube

tubular material used to protect one or more sensing resistors and inner leads assembly from environmental impact

3.1.6 resistance temperature detector

RTD detector generally made up of a stainless steel cylindrical barrel protecting a platinum resistor whose resistance varies with temperature. This detector is placed in the piping containing the fluid whose temperature is measured in this way. It can be directly immersed in the fluid or protected by an intermediate casing called the thermowell Note 1 to entry: Mounting means or connection heads may be included. The temperature-sensing resistor can be made of platinum, nickel tungsten, copper, or other metals. However, a platinum sensor is commonly used in the RTD in an NPP; therefore, a platinum resistance thermometer is referred to in this document. Note 2 to entry: In this document, the term "sensor" describes the RTD unit with all its associated protection, for example, barrel or thermowell. For most applications of measuring process fluid temperature in an NPP, the platinum resistor sensor is installed inside a stainless steel thermowell, and the thermowell is mounted on a pipe or container by means of external threads or welding. For air temperature measurement, a direct sensor may be used.

SIST EN IEC 62397:2026

3.1.7 response time

period of time necessary for a component to achieve a specified output state from the time that it receives a signal requiring it to assume that output state Note 1 to entry: Thermal response time used in this document is the time required for the temperature detector to reach 63,2 % of the total change in resistance for a step change in temperature. [SOURCE: IAEA Safety Glossary, 2018]

3.1.8 self-heating error

rise in the indicated temperature due to the power dissipated in the sensor by the measurement

3.1.9 self-heating index

self-heating coefficient SHI coefficient with the dimension °C/mW is characteristic for a resistor/thermometer and describes the temperature increase of the resistor per unit power dissipated. This coefficient is evaluated under specified operating conditions of the resistor or thermometer. The medium, its flow conditions and temperature should be specified [SOURCE: IEC 60751:2008, 3.9]

3.1.10 thermowell

protective jacket for RTDs, thermocouples, and other temperature sensors. The thermowell is also used to facilitate replacement of the temperature sensor [SOURCE: IEC 62385:2007, 3.19]

3.1.11 tolerance of RTD

initial maximum allowable deviation expressed as temperature in °C from nominal temperature/resistance relationship in RTD [SOURCE: IEC 62765-2:2019, 3.19]

3.2 Abbreviated terms

HELB High-energy Line Break ITS-90 The International Temperature Scale of 1990 (Temperature units in this document are in terms of International Temperature Scale-1990) LCSR Loop Current Step Response LOCA Loss of Coolant Accident M&TE Measurement and Test Equipment NPP Nuclear Power Plant PRT Platinum Resistance Thermometer RTD Resistance Temperature Detector SHI Self-heating index of RTD QA Quality Assurance

SIST EN IEC 62397:2026

4 Design and construction requirements

4.1 General

RTDs can be supplied with different internal constructions, which depend on the manufacture, qualifications, and applications. For RTD being used in an NPP, the design and structure of the RTD should consider the environmental conditions in which the detector is being used under normal operating and under design basis accident conditions and certain design extension

conditions, as well as the qualification tests specified by the user . The RTD shall meet or exceed the requirements specified in this document.

4.2 Reliability

The design philosophy for RTDs that are used in NPPs requires a device which is capable of continuous successful operation at rated service conditions throughout its specified design life. The required reliability of the RTD shall be derived from the overall reliability specified for the temperature measurement function.

RTDs that operate as part of a safety system should have their design lives defined. The features of the RTD that are necessary to fulfill safety functions shall be ensured for the complete service life of the equipment, except for parts which have a short design life and can be replaced periodically. The preservation of these features should be ensured by appropriate maintenance and testing strategies. Arrangements shall be made for the RTD to be replaced or re-assessed before its design life is reached.

4.3 Materials

4.3.1 General

With the exception of parts which have a lower design life, all materials within the construction of the RTD shall retain their required features, attributes and design parameters for the required service life of the RTD.

4.3.2 Radiation dose to materials

The total integrated radiation dose shall be derived from postulated environmental conditions during normal operation and postulated accidents.

If neutron radiation is expected at the installation position of the RTD, the neutron fluence shall be taken into consideration when selecting the design and materials of the RTD. Material changes due to activation or fast neutron damage shall not affect adversely the safety function of the equipment. Some devices may be exposed to beta radiation in a severe accident. Beta and gamma radiation cause different types of damage.

4.3.3 Resistance element material

In addition to meeting the required temperature characteristics (including accuracy, repeatability, response time and reliability) the resistance element material shall be selected to meet the following material property requirements:

  • high resistance to corrosion and chemical attack;
  • high resistance to radiation damage;

1 The user corresponds to the party or the company that uses the RTD in an NPP for measuring the temperature in a safety or a non-safety system. The term user may also refer to the purchaser or the buyer, or the operator of the RTD.

SIST EN IEC 62397:2026

  • suitable strength and mechanical stability throughout the required temperature range and design life.

Because of its outstanding properties, the resistance element may consist of platinum. Other materials may be used if these requirements are met.

The sensing wire shall be mounted so as to be almost free of strains to avoid the strain gauge effect from causing extraneous changes in resistance. Furthermore, the thermometer shall be manufactured with the resistance element free of contaminants.

4.3.4 Seals and adhesives

The RTD shall be hermetically sealed. RTDs used in a harsh environment, such as under hightemperature and/or radiation areas, may be designed without organic material. The tightness of the insulating termination shall be tested according to an adequate and proven procedure. All cements, adhesives, or seals used internally in the device shall be capable of withstanding the service conditions without functional deterioration and without emitting gases. All nonmetallic materials, when used for seals, protective finishes, and so forth, shall be moisture- and flame-resistant. These non-metallic materials shall not support fungus growth and shall not be adversely affected by the ambient environments specified in the performance requirements of this standard.

4.4 Connections

4.4.1 Structural type

RTDs shall have lead wires terminated through a qualified hermetic seal. There are two common types of electrical connections used in an NPP. Figure 1 provides the general form and dimensions of an RTD without any thermowell. Figure 2 is a rigid RTD with a quick disconnector and is referred to as Type I (quick disconnect). Figure 3 and Figure 4 are rigid RTDs without quick disconnectors, and are referred to as Type II (standard) with long insertion and short insertion, respectively. A user may specify any other form of RTD and construction, depending on its particular applications.

For resistance thermometer with connector, the spring gap, as part of the dust cover, should completely cover the end of the extension tube.

Dimensions in millimetres

Figure 1 – Form and dimensions of an RTD

SIST EN IEC 62397:2026

Figure 2 – Installation of a rigid RTD (Type I)

Figure 3 – Installation of a rigid RTD (Type II) long insertion

Figure 4 – Installation of a rigid RTD (Type II) short insertion

4.4.2 Electrical connection
4.4.2.1 General

The electrical connectors of resistance thermometers shall meet the following requirements:

  • The electrical connectors configuration can be 3-wire or 4-wire, see IEC 60751 for details.
  • The electrical connectors of resistance thermometers shall have a qualified leak tightness.

SIST EN IEC 62397:2026

  • The connector assembly shall prevent moisture intrusion that may result in a leakage current, thus deteriorating the signal and producing a false temperature indication. The cable connector assembly shall also provide mechanical protection for the connections, thus preventing mechanical stresses from rendering the circuit susceptible to the effects of moisture intrusion, or breaking off the connections completely.
  • All circuits shall maintain electrical continuity throughout the normal and accident operating conditions.
4.4.2.2 Type of connection

There are two kinds of electrical connectors commonly used in resistance thermometers in nuclear power plants:

Type I (Quick disconnect, Figure 2) The electrical connection is achieved by using a multi-pin connector. The connector shall be splash-proof and water-proof when mated and shall meet the insulation resistance requirements in 4.7.7. The contact resistance between each pit of the mated connector shall be as low as possible, and shall not affect adversely the required accuracy of the complete sensor (sensor and connection interface/connector). For high accuracy applications, the user may consider gold or silver plating for the pins and sockets of the connector. The temperature rating of the connector shall be in accordance with the requirements of the nuclear power plant at the planned installation location. For harsh environment purposes a lower limit of 150 °C should be considered, or the accident temperature specified by the user.

Unless otherwise specified, the manufacturer shall supply the mating connector half with the RTD.

...