SIST EN 54-16:2008
(Main)Fire detection and fire alarm systems - Part 16: Voice alarm control and indicating equipment
Fire detection and fire alarm systems - Part 16: Voice alarm control and indicating equipment
This European Standard specifies requirements, methods of test and performance criteria for voice alarm control and indicating equipment for use in fire detection and fire alarm systems installed in buildings, where the alarm signal is in the form of tone(s) or voice message(s), or both.
It also provides for the evaluation of conformity of the equipment to the requirements of this European Standard.
NOTE The overall requirements of a voice alarm system, especially concerning audibility and intelligibility, are not covered in this part of EN 54. The manufacturer should consider requirements of an overall system that may affect the equipment design. Such system requirements may be specified in another part of EN 54, in national legislation, codes and standards or in contractual documents.
Brandmeldeanlagen - Teil 16: Sprachalarmzentralen
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für Sprachalarm¬zentralen zur Verwendung in Brandmeldeanlagen fest, die in Gebäuden errichtet werden, bei denen das Alarmsignal in Form von Tönen oder gesprochener Meldungen oder beidem übertragen wird.
Sie ist auch eine Grundlage für die Bewertung der Konformität von Einrichtungen mit den Anforderungen dieser Europäische Norm.
ANMERKUNG Die Gesamtanforderungen einer Sprachalarmanlage, insbesondere hinsichtlich Hörbarkeit und Verständlichkeit, werden in diesem Teil von EN 54 nicht behandelt. Der Hersteller sollte Anforderungen eines Gesamtsystems berücksichtigen, das die Ausführung der Komponenten beeinflussen kann. Derartige System¬anforderungen können in einem weiteren Teil der EN 54, in der nationalen Gesetzgebung, Vorschriften und Normen oder in Vertragsunterlagen festgelegt werden.
Systèmes de détection et d'alarme incendie - Partie 16: Elément central du système d'alarme incendie vocale
La présente Norme européenne prescrit les exigences, les méthodes d'essai et les critères de performance des équipements de contrôle et de signalisation d'alarme vocale destinés à être utilisés dans les systèmes de détection et d'alarme incendie installés dans les bâtiments où le signal sonore d'alarme retentit sous la forme de tonalité(s) et/ou de message(s) vocal(aux).
Elle prescrit également l'évaluation de la conformité de l'équipement conformément aux exigences de la présente Norme européenne.
NOTE Les exigences générales d'un système d'alarme vocale, notamment celles relatives à l'audibilité et à l'intelligibilité, ne sont pas couvertes par cette partie de l'EN 54. Il convient que le constructeur prenne en compte les exigences d'un système général qui peuvent affecter la conception de l'équipement. De telles exigences de système peuvent être spécifiées dans une autre partie de l'EN 54, dans des législations, des codes et normes nationaux ou dans des documents contractuels.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 16. del: Centrala za zvočno alarmiranje in prikazovalna oprema
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
01-julij-2008
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO&HQWUDOD]D
]YRþQRDODUPLUDQMHLQSULND]RYDOQDRSUHPD
Fire detection and fire alarm systems - Part 16: Voice alarm control and indicating
equipment
Brandmeldeanlagen - Teil 16: Sprachalarmzentralen
Systèmes de détection et d'alarme incendie - Partie 16: Elément central du système
d'alarme incendie vocale
Ta slovenski standard je istoveten z: EN 54-16:2008
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 54-16
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2008
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 16: Voice alarm
control and indicating equipment
Systèmes de détection et d'alarme incendie - Partie 16: Brandmeldeanlagen - Teil 16: Sprachalarmzentralen
Élément central du système d'alarme incendie vocale
This European Standard was approved by CEN on 20 January 2008.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-16:2008: E
worldwide for CEN national Members.
Contents Page
Foreword.4
Introduction .6
1 Scope .7
2 Normative references .7
3 Terms, definitions and abbreviations.8
3.1 Terms and definitions .8
3.2 Abbreviations.10
4 General requirements.11
4.1 General.11
4.2 Combined VACIE and CIE.11
4.3 Power supply.11
5 General requirements for indications.11
5.1 Display and functional conditions .11
5.2 Indication display.12
5.3 Indication on alphanumeric displays.12
5.4 Indication of the supply of power .12
5.5 Additional indications .12
6 The quiescent condition .12
7 The voice alarm condition .12
7.1 Reception and processing of fire signals .12
7.2 Indication of the voice alarm condition.13
7.3 Audible warning (option with requirements) .13
7.4 Delays to entering the voice alarm condition (option with requirements) .13
7.5 Phased evacuation (option with requirements).13
7.6 Silencing of the voice alarm condition.13
7.7 Reset of the voice alarm condition .14
7.8 Output to fire alarm devices (option with requirements) .14
7.9 Voice alarm condition output (option with requirements) .14
8 Fault warning condition .14
8.1 Reception and processing of fault signals .14
8.2 Indication of faults in specified functions.15
8.3 Indication of faults related to the transmission path to the CIE (option with requirements) .16
8.4 Indication of faults related to voice alarm zones (option with requirements).16
8.5 System fault.16
8.6 Audible indication.16
8.7 Reset of fault indications .16
8.8 Transmission of the fault warning condition.16
9 Disablement condition (option with requirements).17
9.1 General requirements.17
9.2 Indication of the disabled condition .17
9.3 Indication of specific disablements.17
9.4 Disablements and their indication .17
9.5 Transmission of the disablement condition .17
10 Voice alarm manual control (option with requirements) .18
10.1 General requirements.18
10.2 Indication of the voice alarm zones in an activated condition .18
10.3 Indication of the voice alarm zones in fault condition.18
10.4 Indication of the voice alarm zones in disablement condition.18
11 Interface to external control device(s) (option with the requirements) .18
12 Emergency microphone(s) (option with requirements) .19
13 Design requirements.19
13.1 General requirements and manufacturer's declaration .19
13.2 Documentation .20
13.3 Mechanical design requirements.20
13.4 Electrical and other design requirements.21
13.5 Integrity of transmission paths.21
13.6 Accessibility of indications and controls .21
13.7 Indications by means of light emitting indicators .22
13.8 Indications on alphanumeric displays .22
13.9 Indication colours.22
13.10 Audible indications .23
13.11 Indicator testing.23
13.12 Audio performance.23
13.13 Message store(s) .25
13.14 Redundant power amplifiers (option with requirements) .25
14 Additional design requirements for software controlled VACIE .25
14.1 General requirements and manufacturer's declarations .25
14.2 Software documentation.25
14.3 Software design.26
14.4 Program monitoring (see also Annex C).26
14.5 The storage of programs and data (see also Annex C).27
14.6 Monitoring of memory contents .27
15 Marking.27
16 Tests .28
16.1 General .28
16.2 Functional tests .29
16.3 Audio performance and environmental tests.31
16.4 Output power .32
16.5 Signal-to-noise ratio.34
16.6 Frequency response of VACIE without microphone(s).35
16.7 Frequency response of VACIE with microphone(s) .36
16.8 Cold (operational).37
16.9 Damp heat, steady state (operational) .38
16.10 Damp heat, steady state (endurance).39
16.11 Impact (operational) .40
16.12 Vibration, sinusoidal (operational) .41
16.13 Vibration, sinusoidal (endurance) .42
16.14 Supply voltage variation (operational).42
16.15 Electromagnetic Compatibility (EMC), Immunity tests (operational).43
Annex A (informative) Explanation of access level.45
Annex B (informative) Optional functions with requirements and alternatives .47
Annex C (informative) Design requirements for software controlled VACIE.49
Annex D (informative) General information about voice alarm systems .50
Annex E (informative) Interface between the VACIE and the CIE .53
Annex F (informative) Common indications, controls and outputs when the VACIE and the CIE
are combined .54
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC) .56
Bibliography.65
Foreword
This document (EN 54-16:2008) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by September 2008, and conflicting national standards shall be
withdrawn at the latest by March 2011.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive, see informative Annex ZA, which is an integral part of this document.
EN 54 Fire detection and fire alarm systems consists of the following parts:
Part 1: Introduction
Part 2: Control and indicating equipment
Part 3: Fire alarm devices – Sounders
Part 4: Power supply equipment
Part 5: Heat detectors – Point detectors
Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
Part 10: Flame detectors – Point detectors
Part 11: Manual call points
Part 12: Smoke detectors – Line detectors using an optical light beam
Part 13: Compatibility assessment of system components
Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
Part 15: Point detectors using a combination of detected phenomena
Part 16: Voice alarm control and indicating equipment
Part 17: Short-circuit isolators
Part 18: Input/output devices
Part 20: Aspirating smoke detectors
Part 21: Alarm transmission and fault warning routine equipment
Part 22: Line-type heat detectors
Part 23: Fire alarm devices – Visual alarms
Part 24: Components of voice alarm systems – Loudspeakers
Part 25: Components using radio links
1)
Part 26: Point fire detectors using carbon monoxide sensors
1)
Part 27: Duct smoke detectors
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
1) Under preparation.
Introduction
A voice alarm system used in a fire detection and fire alarm system provides, manually and/or automatically,
an audible fire alarm signal within the building.
Such a fire alarm voice alarm system will require voice alarm control and indicating equipment (VACIE) (see
3.1.1) to control the alarm signal(s) and the fire alarm voice message(s). The voice alarm control and
indicating equipment may be a separate unit or may be physically combined with the fire detection and fire
alarm control and indicating equipment (CIE as referenced in EN 54-2).
This part of EN 54 follows closely the format and requirements of EN 54-2 and is drafted on the basis of
mandatory functions which are to be provided on all voice alarm control and indicating equipment, and
optional functions (with requirements) which may be provided. It is intended that the options be used for
specific applications, as recommended in application guidelines.
This European Standard does not specify requirements for components of the VACIE as separate parts; they
are tested as part of the voice alarm control and indicating equipment as a whole.
Each optional function is included as a separate entity, with its own set of associated requirements, in order to
permit voice alarm control and indicating equipment with many different combinations of functions to comply
with this European Standard. Other functions associated with fire detection and fire alarm may also be
provided, even if not specified in this European Standard.
Although this European Standard does not cover emergency alarm systems for non-fire applications, it may
be used as a basis for the assessment of the control and indication equipment for such systems.
1 Scope
This European Standard specifies requirements, methods of test and performance criteria for voice alarm
control and indicating equipment for use in fire detection and fire alarm systems installed in buildings, where
the alarm signal is in the form of tone(s) or voice message(s), or both.
It also provides for the evaluation of conformity of the equipment to the requirements of this European
Standard.
NOTE The overall requirements of a voice alarm system, especially concerning audibility and intelligibility, are not
covered in this part of EN 54. The manufacturer should consider requirements of an overall system that may affect the
equipment design. Such system requirements may be specified in another part of EN 54, in national legislation, codes and
standards or in contractual documents.
2 Normative references
The following referenced documents are indispensable for the application of this standard. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction
EN 54-2:1997, Fire detection and fire alarm systems — Part 2: Control and indicating equipment
EN 54-2:1997/A1:2006, Fire detection and fire alarm systems — Part 2: Control and indicating equipment
EN 54-4:1997, Fire detection and fire alarm systems — Part 4: Power supply equipment
EN 54-4:1997/A1:2002, Fire detection and fire alarm systems — Part 4: Power supply equipment
EN 54-4:1997/A2:2006, Fire detection and fire alarm systems — Part 4: Power supply equipment
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard:
Immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A1:1998, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A2:2003, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: immunity requirements for components of fire, intruder and social alarm systems
EN 60068-1:1994, Environmental testing — Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum
1988 + A1:1992)
EN 60068-2-1:2007, Environmental testing — Part 2-1: Tests — Test A: Cold (IEC 60068-2-1:2007)
EN 60068-2-6:1995, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal)
(IEC 60068-2-6:1995 + Corrigendum 1995)
EN 60068-2-47:2005, Environmental testing — Part 2-47: Tests — Mounting of specimens for vibration,
impact and similar dynamic tests (IEC 60068-2-47:2005)
EN 60068-2-75:1997, Environmental testing — Part 2-75: Tests — Test Eh: Hammer tests
(IEC 60068-2-75:1997)
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state (IEC
60068-2-78:2001)
EN 60268-4:2004, Sound system equipment — Part 4: Microphones (IEC 60268-4:2004)
EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989)
EN 60529:1991/A1:2000, Degrees of protection provided by enclosures (IP code) – Amendment A1
(IEC 60529:1989/A1:1999)
EN 60721-3-3:1995, Classification of environmental conditions — Part 3: Classification of groups of
environmental parameters and their severities — Section 3: Stationary use at wheatherprotected locations
(IEC 60721-3-3:1994)
EN 60721-3-3:1995/A2:1997, Classification of environmental conditions — Part 3: Classification of groups of
environmental parameters and their severities — Section 3: Stationary use at wheatherprotected locations –
Amendment A2 (IEC 60721-3-3:1994/A2:1996)
EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000)
IEC 60268-1, Sound system equipment — Part 1: General
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1:1996 and the following apply.
3.1.1
access level
one of several states of a VACIE in which selected:
controls can be operated,
manual operations can be carried out,
indications are visible and/or
information can be obtained
NOTE Further information on access level is given in Annex A.
3.1.2
alphanumeric display
indicator that is capable of giving information by displaying messages consisting of text and/or numeric
characters
3.1.3
cabinet
housing which affords the degree of protection and robustness required by this standard to its constituent
parts and sub-assemblies (see 13.3)
3.1.4
earth fault
unwanted connection between earth potential and any part of the VACIE, transmission paths to the VACIE, or
transmission paths between parts of the VACIE
3.1.5
emergency microphone
microphone for use by the fire service or other responsible persons as part of a voice alarm system
3.1.6
emergency microphone control
manual control which activates an emergency microphone
NOTE Often called a "push to talk" control (PTT).
3.1.7
field
sub-division of a window of an alphanumeric display
3.1.8
functional condition
condition of the VACIE characterized by its indication at the VACIE
NOTE The functional conditions recognized in this European Standard are:
the voice alarm condition (see 3.1.25),
the fault warning condition, when a fault is indicated,
the disabled condition, when the disablement of functions is indicated,
the quiescent condition, when the VACIE is powered by a power supply conforming to EN 54-4 and no
other functional condition is indicated.
3.1.9
indicator
device which can change its state to give information
3.1.10
mandatory
adjective used to describe:
functions which shall be provided on all VACIEs and the requirements of these functions and
the requirements of optional functions with requirements, if these are provided
3.1.11
non-volatile memory
memory elements that do not require the presence of an energy source for the retention of their contents
3.1.12
octave
frequency band as defined in EN 61260
3.1.13
output power
maximum squared RMS output voltage divided by the minimum load resistance that can be maintained for a
1 kHz sinusoidal signal of specified duration, for a specified THD
3.1.14
program
software necessary for a VACIE to comply with at least the requirements of this European Standard, including
initialising data, reset and interrupt vectors, operating code and variables
3.1.15
reset
operation capable of terminating the voice alarm condition and/or the fault warning condition
3.1.16
running data
alterable data subject to temporary modification during operation, either automatically or by manual controls
3.1.17
silencing
switching off an audible signal of a sounding device that is capable of being re-sounded by a new event
3.1.18
site specific data
alterable data required for the VACIE to operate in a defined system configuration
3.1.19
voice alarm transmission path
physical connection, external to the cabinet of the VACIE, for the transmission of information and/or power
between parts of a VACIE contained in different cabinets and between the VACIE and other components of a
voice alarm system, as defined in EN 54-1
3.1.20
voice alarm condition
when any fire alarm signal, recorded or live, is broadcast in at least one voice alarm zone
3.1.21
voice alarm output control
manual control which can be used to cause a voice alarm zone or group of voice alarm zones to sound an
audible voice alarm signal
3.1.22
voice alarm control and indicating equipment
component of a voice alarm system that generates and transmits voice alarm signals to loudspeaker circuit(s)
when it receives alarm signal(s) from a fire detection and alarm system and/or manual controls
NOTE See Annex D for further information.
3.1.23
voice alarm signal
audible fire alarm signal within the building, comprising a tone and/or a voice message
3.1.24
voice alarm zone
distinct geographic area containing a group of voice alarm loudspeakers intended to give the same voice
alarm signal
3.1.25
volatile memory
memory elements that require the presence of an energy source for the retention of their contents
3.1.26
window
area of the alphanumeric display used for information relating to one functional condition at a given time
3.2 Abbreviations
For the purpose of this document, the following abbreviations apply.
CIE control and indicating equipment (item B of Figure 1 in EN 54-1:1996)
PSE power supply equipment (item L of Figure 1 in EN 54-1:1996)
RMS root mean square (e.g. of a signal)
S/N signal-to-noise ratio
THD total harmonic distortion
VACIE voice alarm control and indicating equipment
4 General requirements
4.1 General
4.1.1 If an optional function with requirements is included in the VACIE, then all the corresponding
requirements shall be met. Annex B gives an overview of these optional functions with requirements.
4.1.2 If functions other than those specified in this European Standard are provided for the VACIE, they
shall not jeopardize compliance with any requirements of this European Standard.
4.2 Combined VACIE and CIE
When the VACIE and CIE are combined they may share common indications, manual controls and outputs
(see Annex F). In this case, the following shall apply:
a) a single fault in the CIE shall not adversely affect the mandatory functions of the VACIE;
b) indication(s) and manual control(s) of the voice alarm condition shall be clearly identifiable, with the
exception of the optional audible warning.
4.3 Power supply
Power supply equipment, external or included in the VACIE, shall comply with the requirements of EN 54-4.
NOTE The power supply may be shared with that of the fire detection and fire alarm system.
5 General requirements for indications
5.1 Display and functional conditions
5.1.1 The VACIE shall be capable of unambiguously indicating the following functional conditions, as
described in Clauses 6 to 9:
quiescent condition;
voice alarm condition;
fault warning condition;
disablement condition (option with requirements).
5.1.2 The VACIE shall be capable of being simultaneously in any combination of the following functional
conditions on different voice alarm zones:
voice alarm condition;
fault warning condition;
disablement condition (option with requirements).
5.2 Indication display
All mandatory indications shall be clearly identifiable, except where otherwise specified in this European
Standard.
5.3 Indication on alphanumeric displays
Where an alphanumeric display is used to display indications relating to different functional conditions these
may be displayed at the same time. However, for each functional condition there shall be only one window, in
which all of the information relating to that functional condition is grouped.
5.4 Indication of the supply of power
5.4.1 A visible indication shall be given by means of a separate discrete light emitting indicator while the
VACIE is supplied with power.
5.4.2 Where the VACIE is distributed in more than one cabinet, an indication of supply of power to the
cabinet shall be given on each distributed cabinet.
5.5 Additional indications
Where additional indications are provided, they shall be clearly identifiable and shall not override the primary
indication of the VACIE.
6 The quiescent condition
Any kind of system information may be displayed during the quiescent condition. However, no indications shall
be given which could be confused with indications used in:
the voice alarm condition, or
the fault warning condition, or
the disablement condition (option with requirements).
7 The voice alarm condition
7.1 Reception and processing of fire signals
7.1.1 The VACIE shall be capable of receiving and processing alarm signals from the CIE or from manual
control on the VACIE or both, and causing the appropriate voice alarm outputs to be activated within 3 s or on
expiry of any delay period (see 7.4).
NOTE See Annex E for additional information relating to the interface between the VACIE and the CIE.
7.1.2 The mandatory indications and/or outputs shall not be falsified by multiple alarm signals received
simultaneously from the CIE and/or manual controls.
7.1.3 Where the VACIE and CIE are in separate cabinets, failure of the transmission path between the CIE
and the VACIE shall not result in any loss of control or any change of state of the VACIE, unless option 8.3 is
used.
7.2 Indication of the voice alarm condition
7.2.1 The presence of a voice alarm condition shall be indicated on the VACIE, without prior manual
intervention, by:
a) a visible indication by means of a separate discrete light emitting indicator (the General Voice Alarm
Activated indicator) and
b) a visible indication for each activated voice alarm zone where manual controls are provided (see 10.2);
NOTE This may be by means of separate discrete indicators or an alphanumeric display as specified in 13.8.
c) an optional audible indication, as specified in 7.3.
7.2.2 The audible warning shall be capable of being silenced at access level 1 or 2.
7.3 Audible warning (option with requirements)
The audible warning of the voice alarm condition (see 7.2.1 c)) may be the same as that for the fault warning
condition. If they are different, the voice alarm condition warning shall have priority.
7.4 Delays to entering the voice alarm condition (option with requirements)
The VACIE may be provided with a facility to introduce a delay before entering the voice alarm condition. In
this case:
a) the operation of the delay shall be selectable at access level 3;
b) the operation of the delay shall be in increments not exceeding 1 min up to a maximum of 10 min;
c) the delay to one output signal shall not affect the delay to other outputs;
d) it shall be possible to override the delay by a manual operation at access level 1;
e) there shall be provision to switch on and switch off delays by means of a manual operation at access
level 2 (see Annex A for information on access levels);
f) there may be provision to automatically switch on and/or switch off delays by means of a programmable
timer which shall be configurable at access level 3;
g) a separate discrete light emitting indicator and/or a field on the alphanumeric display shall be visible when
a fire signal is received and the delay activated. This indication shall be suppressed when the VACIE
enters the voice alarm condition.
7.5 Phased evacuation (option with requirements)
The VACIE may have a provision to phase the warning signals to the emergency loudspeaker zones. The
facility shall be configurable at access level 3. There may be provision to switch on and switch off the phased
evacuation sequence by means of a manual operation at access level 2 (see Annex A for information on
access levels).
7.6 Silencing of the voice alarm condition
7.6.1 Silencing of the voice alarm condition from the CIE
7.6.1.1 Where the voice alarm condition has been triggered from the CIE, the VACIE shall respond
appropriately to a silence instruction from the CIE.
7.6.1.2 The silencing procedure may allow for the completion of messages in the process of being
broadcast.
7.6.2 Manual silencing of the voice alarm condition (option with requirements)
It may be possible to manually silence the voice alarm message from the VACIE at access level 2. In this case,
following manual silencing, it shall be possible to re-activate the voice alarm message at access level 2.
7.7 Reset of the voice alarm condition
7.7.1 Reset of the voice alarm condition from the CIE
Where the voice alarm condition has been triggered from the CIE, the VACIE shall respond appropriately to a
reset instruction from the CIE.
7.7.2 Manual reset of the voice alarm condition (option with requirements)
7.7.2.1 It may be possible to reset the voice alarm condition from the VACIE at access level 2 by means
of a separate manual control. In this case, this control shall be used only for reset and may be the same as
that used for reset from the fault warning condition.
7.7.2.2 Following a manual reset operation, the indication of the correct functional condition
corresponding to any received signals shall either remain or be re-established within 20 s.
7.8 Output to fire alarm devices (option with requirements)
In addition to the voice alarm outputs the VACIE may have provision for the automatic transmission of fire
alarm signals to fire alarm devices such as beacons and vibrating devices. In this case, the following shall
apply:
a) it shall be possible to de-activate the fire alarm devices at access level 2;
b) following de-activation, it shall be possible to re-activate the fire alarm devices at access level 2;
c) the fire alarm devices shall not be de-activated automatically;
d) it shall be possible to configure the VACIE at access level 3 to automatically reactivate the fire alarm
devices if an alarm is reported in an other zone.
7.9 Voice alarm condition output (option with requirements)
The VACIE may have provision for transmitting a signal that it is in the voice alarm condition. In this case, it
shall activate the output only in the voice alarm condition.
8 Fault warning condition
8.1 Reception and processing of fault signals
8.1.1 The VACIE shall enter the fault warning condition when signals are received which, after any
necessary processing, are interpreted as a fault.
8.1.2 The VACIE shall be capable of simultaneously recognizing all of the faults specified in 8.2 and, if
provided, in 8.3 unless this is prevented by:
the presence of an alarm output signal in the same voice alarm zone and/or
the disablement of the corresponding voice alarm zone or function.
8.1.3 The VACIE shall enter the fault warning condition within 100 s of the occurrence of the fault, or the
reception of a fault signal or within another time as specified in this European Standard or in other parts of
EN 54.
8.2 Indication of faults in specified functions
8.2.1 The presence of faults in specified functions shall be indicated on the VACIE without prior manual
intervention. The fault warning condition is established when the following are present:
a) a visible indication by means of a separate light emitting indicator (the general fault warning indicator),
b) a visible indication for each recognised fault as specified in 8.2.3, 8.2.4, 8.3 (if provided), 8.4 (if provided),
and 8.5 and
c) an audible indication, as specified in 8.6.
8.2.2 If the indication is on an alphanumeric display, which cannot simultaneously indicate all of the faults
because of its limited capacity, at least the following shall apply:
a) the presence of fault indications which have been suppressed shall be indicated;
b) suppressed fault indications shall be capable of being displayed by means of a manual operation at
access level 1 or 2 which interrogates only fault indications.
8.2.3 The following faults shall be indicated by means of separate light emitting indicators and/or an
alphanumeric display:
a) an indication at least common to any power supply fault resulting from:
1) a short circuit or an interruption in a transmission path to a power supply (item L of Figure 1 of
EN 54-1:1996), where the power supply is contained in a different cabinet from that of the VACIE and
2) the power supply faults as specified in EN 54-4;
b) an indication at least common to any earth fault of less than 50 kΏ which is capable of affecting a
mandatory function, and which is not otherwise indicated as a fault of a supervised function;
c) an indication of the rupture of any fuse within the VACIE, or the operation of any protective device within
the VACIE which is capable of affecting a mandatory function in the fire alarm condition;
d) an indication of any short circuit or interruption, at least common to all transmission paths between parts
of the VACIE contained in more than one cabinet, which is capable of affecting a mandatory function and
which is not otherwise indicated as a fault of a supervised function.
NOTE These indications may be suppressed during the fire alarm condition.
8.2.4 The following faults shall be indicated at least by means of the general fault warning indicator:
a) any short circuit or interruption in a voice alarm transmission path between parts of the VACIE contained
in more than one cabinet even where the fault does not affect a mandatory function;
b) any short circuit or interruption in the voice alarm transmission path to the emergency microphone
capsule, if provided;
c) any short circuit or interruption in the voice alarm transmission path between the VACIE and loudspeakers
even where the fault does not affect the operation of loudspeakers;
d) any short circuit or interruption in the transmission path between the VACIE and fire alarm devices when
used (see 7.8);
e) failure of any power amplifier.
8.3 Indication of faults related to the transmission path to the CIE (option with requirements)
The VACIE may have provision for an indication of faults related to the voice alarm transmission path to the
CIE. In this case, the short circuit or interruption of the transmission path to the CIE shall be indicated by
means of a separate light emitting indicator and/or an alphanumeric display.
8.4 Indication of faults related to voice alarm zones (option with requirements)
The VACIE may have provision for an indication of faults related to voice alarm zones. In this case the short
circuit or interruption of a voice alarm transmission path between the VACIE and the loudspeakers in that
zone shall be indicated by means of a separate light emitting indicator per zone and/or an alphanumeric
display.
8.5 System fault
A system fault is a fault as specified in 14.4 or 14.6 in the case of software controlled VACIE. A system fault
may prevent requirements of this European Standard, other than those specified below, from being fulfilled. In
the event of a system fault at least the following shall apply:
a) a system fault shall be visibly indicated by means of the general fault warning indicator and a separate
light emitting indicator on the VACIE. These indications shall not be suppressed by any other functional
condition of the VACIE and shall remain until a manua
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...