kSIST FprEN 12390-10:2026
(Main)Testing hardened concrete - Part 10: Determination of the carbonation resistance of concrete at atmospheric levels of carbon dioxide
- Abstract
This document specifies a method of determining the carbonation rate of a concrete, expressed in mm/√a.
This document establishes a procedure where a standardized climate-controlled chamber is used and where specimens are placed on a natural exposure site protected from direct rainfall. The standardized climate-controlled chamber procedure is the reference method.
These procedures are applicable for the initial testing of concrete, including that manufactured with slowly reacting binders, provided that the ages at which the carbonation depth is measured, the number of measurements required to calculate the carbonation rate, as well as the length of exposure to CO2, are appropriately selected, as described in this document.
These procedures are not applicable for factory production control.
- Status
- Not Published
- Public Enquiry End Date
- 21-Dec-2025
- Technical Committee
- BBB - Concrete, reinforced concrete and prestressed concrete
- Current Stage
- 5020 - Formal vote (FV) (Adopted Project)
- Start Date
- 27-Aug-2026
- Due Date
- 15-Oct-2026
kSIST FprEN 12390-10:2026 is a SIST draft European standard for testing hardened concrete. It specifies a method for determining the carbonation resistance of concrete at atmospheric levels of carbon dioxide, expressed as a carbonation rate in mm/√a. The document is aimed at initial testing of concrete, including concrete made with slowly reacting binders, and it gives both a climate-controlled chamber procedure and a natural exposure site procedure.
What does kSIST FprEN 12390-10:2026 specify?
kSIST FprEN 12390-10:2026 specifies how to measure the carbonation rate of concrete and how to report it. The climate-controlled chamber procedure is the reference method, while the natural exposure site procedure is an alternative that uses outdoor exposure protected from direct rainfall.
The scope is practical and specific:
- It applies to initial testing of concrete.
- It covers concrete with slowly reacting binders, provided the ages of measurement, the number of measurements, and the CO2 exposure period are chosen as described in the document.
- It is not for factory production control.
The document is organized into clauses 1 to 10, covering scope, references, terms, principle, reagents and apparatus, specimen production, carbonation depth measurements, rate calculation, test report, and precision. It also has two informative annexes.
| Annex | What it covers |
|---|---|
| Annex A | Guidance on suitable climate-controlled chambers |
| Annex B | Guidance on natural exposure sites |
What are the key requirements of kSIST FprEN 12390-10:2026?
kSIST FprEN 12390-10:2026 is built around a simple measurement chain: prepare representative specimens, expose them under controlled conditions, measure the carbonation front, and calculate a rate from depth versus time. In practice, this means the quality of the result depends on specimen selection, exposure control, and consistent reading of the colour change front.
Specimens and exposure conditions
Clause 4 requires pairs of beams from the same batch, or two cubes per test age, to be stored either in the climate-controlled chamber or at a natural exposure site. After defined exposure periods, a slice about 50 mm thick is broken off, or cubes are split in half, and carbonation depth is measured on the freshly broken surface.
Clause 5 sets the key exposure conditions and equipment. The chamber procedure uses carbon dioxide at 0.040 % by volume, temperature at 20 °C, and relative humidity at 65 %, with narrow tolerances. The natural exposure site must be sheltered from precipitation and monitored for relative humidity, temperature, and carbon dioxide concentration. For a reader, this means the environment is part of the test method, not just the location.
Specimen production and curing
Clause 6 requires representative constituents and specimens from a single batch for one test. Beams are the reference specimen type, and the document also allows cubes. It also points to EN 12390-1, EN 12390-2, and EN 12390-3 for specimen shape, curing, and compressive strength testing.
For the chamber method, specimens are wet cured, then exposed after standard curing and a short conditioning period in laboratory air. For the natural exposure site method, the carbonation specimens stay sealed until they have reached 50 % of the reference strength. This matters because the test starts only once the concrete has developed enough strength to give a meaningful carbonation comparison.
Measuring the carbonation depth
Clause 7 requires the ages for measurement to be defined in advance, counted from the moment the specimens are placed in the chamber or at the exposure site. The document recommends measurements after three months, six months, and one year, and it calls for longer testing if carbonation remains shallow after one year.
The carbonation front is revealed with an indicator solution, with phenolphthalein as the reference indicator. The broken surface is sprayed, and readings are taken shortly afterwards unless a fixing solution is used. Three measuring points are taken on each face, giving up to 12 readings per specimen set, and the mean value is recorded.
Clause 7 also explains how to treat dense aggregates, pores, porous aggregates, and extreme local values. This is important because the carbonation front can be interrupted or distorted by the aggregate structure, so the document tells the reader when to use a theoretical front and when to exclude high local deviations.
Calculating the rate and reporting it
Clause 8 calculates carbonation rate from average depth plotted against the square root of effective time. The slope of the regression line is the carbonation rate in mm/√a. The document also gives an alternative formula based on average depth and effective time.
Clause 9 makes the reporting requirements explicit. The report must identify the exposure method, the concrete reference, the specimen dates and curing period, the indicator used, the carbonation depths at each age, any displaced points or excluded values, the regression plot, the carbonation rate, and any nonconformity with test conditions. In practice, this gives enough traceability to compare mixtures or review a test later.
Precision
Clause 10 gives estimated precision for both the chamber test and the natural exposure site test. It also warns that reproducibility is affected by carbonation depth and by site-to-site differences in outdoor exposure. That matters when comparing results from different laboratories or different locations.
What terms does kSIST FprEN 12390-10:2026 define?
kSIST FprEN 12390-10:2026 does not list a formal terminology section, but it uses several key terms in a fixed technical way.
- Carbonation rate - the rate at which carbonation progresses through the concrete, expressed in mm/√a.
- Effective time - the time spent in the climate-controlled chamber or on the natural exposure site and used for the rate calculation.
- Reference method - the climate-controlled chamber procedure, which the document treats as the benchmark procedure.
- Natural exposure site - an outdoor exposure arrangement sheltered from direct rainfall but open to the atmosphere.
- Reference strength - the average 28-day compressive strength used to decide when natural exposure can begin.
- Phenolphthalein - the reference indicator solution used to show the carbonation front by colour change.
- CO2 - carbon dioxide, the exposure gas whose concentration is controlled in the chamber or monitored outdoors.
Who uses kSIST FprEN 12390-10:2026?
kSIST FprEN 12390-10:2026 is used by concrete testing laboratories, producers of concrete, and quality managers who need a standard way to compare carbonation resistance between mixes. It is also relevant to engineers and durability specialists who assess cover-zone performance and estimate how carbonation may affect reinforcement corrosion.
The document is especially useful for:
- initial testing of fresh concrete formulations
- comparison of mix changes, such as cement type, additions, w/c ratio, cement content, or fines content
- equivalent durability assessments for carbonation
- preparing data used in models that estimate the start of reinforcement corrosion
- classification work based on carbonation resistance
What changed in kSIST FprEN 12390-10:2026 from the previous edition?
kSIST FprEN 12390-10:2026 supersedes EN 12390-10:2018. The foreword states two notable changes: the scope has been updated to account for slowly reacting binders, and the chamber carbon dioxide concentration has been fixed at 400 ppm, which is 50 ppm higher than in the previous version.
Which standards are used with kSIST FprEN 12390-10:2026?
kSIST FprEN 12390-10:2026 cites three normative references and points readers to several related documents for context and practice.
| Standard | What it contributes |
|---|---|
| EN 12390-1 | Shape, dimensions, and other requirements for specimens and moulds |
| EN 12390-2 | Making and curing specimens for strength tests |
| EN 12390-3 | Compressive strength of test specimens |
| EN 13670 | Curing assumptions and strength-development guidance used in the natural exposure site procedure |
| EN 206 | Background on concrete composition and conformity |
| CEN/TR 16563 | Basic principles for equivalent durability procedures |
| CEN/TR 17172 | Validation context for chloride penetration and carbonation standardized test methods |
The foreword also lists the other parts of the EN 12390 series as related companion documents on hardened concrete testing.
What does the kSIST FprEN 12390-10:2026 document contain?
kSIST FprEN 12390-10:2026 contains the complete test procedure, from apparatus and specimen preparation through to calculation, reporting, and precision. It includes a detailed method for using an indicator solution, measuring carbonation depth at defined points, and handling unusual cases such as dense aggregates, pores, and porous aggregates.
The document also contains two informative annexes with practical guidance for chamber design and outdoor exposure arrangements. Figures explain how to treat measurements when the carbonation front intersects dense or porous material, and the precision clause includes a table of repeatability and reproducibility estimates for chamber and natural exposure testing.
Relations
- Effective Date
- 09-Feb-2021
Get Certified
Connect with accredited certification bodies for this standard
DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

Aboma Certification B.V.
Specialized in construction, metal, and transport sectors.
Sponsored listings
Frequently Asked Questions
kSIST FprEN 12390-10:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Testing hardened concrete - Part 10: Determination of the carbonation resistance of concrete at atmospheric levels of carbon dioxide". This standard covers: This document specifies a method of determining the carbonation rate of a concrete, expressed in mm/√a. This document establishes a procedure where a standardized climate-controlled chamber is used and where specimens are placed on a natural exposure site protected from direct rainfall. The standardized climate-controlled chamber procedure is the reference method. These procedures are applicable for the initial testing of concrete, including that manufactured with slowly reacting binders, provided that the ages at which the carbonation depth is measured, the number of measurements required to calculate the carbonation rate, as well as the length of exposure to CO2, are appropriately selected, as described in this document. These procedures are not applicable for factory production control.
This document specifies a method of determining the carbonation rate of a concrete, expressed in mm/√a. This document establishes a procedure where a standardized climate-controlled chamber is used and where specimens are placed on a natural exposure site protected from direct rainfall. The standardized climate-controlled chamber procedure is the reference method. These procedures are applicable for the initial testing of concrete, including that manufactured with slowly reacting binders, provided that the ages at which the carbonation depth is measured, the number of measurements required to calculate the carbonation rate, as well as the length of exposure to CO2, are appropriately selected, as described in this document. These procedures are not applicable for factory production control.
kSIST FprEN 12390-10:2026 is classified under the following ICS (International Classification for Standards) categories: 91.100.30 - Concrete and concrete products. The ICS classification helps identify the subject area and facilitates finding related standards.
kSIST FprEN 12390-10:2026 has the following relationships with other standards: It is inter standard links to SIST EN 12390-10:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
kSIST FprEN 12390-10:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN 12390-10:2025
01-december-2025
Preskušanje strjenega betona - 10. del: Določanje odpornosti betona proti
karbonatizaciji pri atmosferski koncentraciji ogljikovega dioksida
Testing hardened concrete - Part 10: Determination of the carbonation resistance of
concrete at atmospheric levels of carbon dioxide
Prüfung von Festbeton - Teil 10: Bestimmung des Karbonatisierungswiderstandes von
Beton bei atmosphärischer Konzentration von Kohlenstoffdioxid
Essais pour béton durci - Partie 10 : Détermination de la résistance à la carbonatation du
béton à des niveaux atmosphériques de dioxyde de carbone
Ta slovenski standard je istoveten z: prEN 12390-10
ICS:
91.100.30 Beton in betonski izdelki Concrete and concrete
products
oSIST prEN 12390-10:2025 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
oSIST prEN 12390-10:2025
oSIST prEN 12390-10:2025
DRAFT
EUROPEAN STANDARD
prEN 12390-10
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2025
ICS 91.100.30 Will supersede EN 12390-10:2018
English Version
Testing hardened concrete - Part 10: Determination of the
carbonation resistance of concrete at atmospheric levels of
carbon dioxide
Essais pour béton durci - Partie 10 : Détermination de Prüfung von Festbeton - Teil 10: Bestimmung des
la résistance à la carbonatation du béton à des niveaux Karbonatisierungswiderstandes von Beton bei
atmosphériques de dioxyde de carbone atmosphärischer Konzentration von Kohlenstoffdioxid
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 104.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2025 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 12390-10:2025 E
worldwide for CEN national Members.
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
Contents Page
European foreword . 3
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 Principle . 6
5 Reagents and apparatus . 7
6 Production of specimens . 7
6.1 General . 7
6.2 Procedure when using climate controlled chamber . 8
6.3 Procedure when using a natural exposure site . 8
7 Carbonation depth measurements . 9
7.1 Testing age and generation of colour change . 9
7.2 Determination of the carbonation depth . 10
7.2.1 General . 10
7.2.2 Measuring the depth of carbonation . 10
7.2.3 Appreciation of dense aggregates . 10
7.2.4 Appreciation of pores and porous aggregates and extreme values . 10
8 Determination of the rate of carbonation . 10
9 Test report . 11
10 Precision . 12
Annex A (informative) Guidance on suitable climate controlled chambers . 14
Annex B (informative) Guidance on natural exposure sites . 18
Bibliography . 20
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
European foreword
This document (prEN 12390-10:2025) has been prepared by Technical Committee CEN/TC 104
“Concrete and related products”,”, the secretariat of which is held by SN.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 12390-10:2018.
prEN 12390-10:2025 includes the following significant technical changes with respect to
EN 12390-10:2018:
— The scope has been updated in order to account for slowly reacting binders.
The EN 12390 series, under the general title Testing hardened concrete, consists of the following parts:
— Part 1: Shape, dimensions and other requirements for specimens and moulds
— Part 2: Making and curing specimens for strength tests
— Part 3: Compressive strength of test specimens
— Part 4: Compressive strength - Specification for testing machines
— Part 5: Flexural strength of test specimens
— Part 6: Tensile splitting strength of test specimens
— Part 7: Density of hardened concrete
— Part 8: Depth of penetration of water under pressure
— Part 9: Freeze–thaw resistance with de-icing salts - Scaling (Technical Specification)
— Part 10: Determination of the carbonation resistance of concrete at atmospheric levels of carbon
dioxide
— Part 11: Determination of the chloride resistance of concrete, unidirectional diffusion
— Pert 12: Determination of the carbonation resistance of concrete – Accelerated carbonation method
— Part 13: Determination of the secant modulus of elasticity in compression
— Part 14: Semi-adiabatic method for the determination of heat released by concrete during its
hardening process
— Part 15: Adiabatic method for the determination of heat released by concrete during its hardening
process
— Part 16: Determination of the shrinkage of concrete
— Part 17: Determination of creep of concrete in compression
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
— Part 18: Determination of the chloride migration coefficient
— Part 19: Determination of electrical resistivity
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
Introduction
In reinforced and prestressed concrete structures, a sufficient concrete cover protects conventional
steel reinforcement from corrosion and contributes to ensure that the intended working life is achieved.
Reinforcement corrosion induced by carbonation can play a significant role in a structure’s
serviceability and consequently carbonation resistance of concrete, in particular of the cover zone, is an
important property to be quantified.
This document describes a test method for the quantification of the carbonation rate of any freshly cast
concrete. This document quantifies concrete behaviour in the conditions of carbonation at natural
levels of carbon dioxide. For standardization purposes, the carbon dioxide concentration in the climate
controlled chamber is fixed at 400 ppm, which is an increase of 50 ppm over the value used in the
previous version of this document. However, atmospheric levels of carbon dioxide are not constant in
location or time, and in some urban and industrial areas, carbon dioxide concentration exceeds
400 ppm.
From a European perspective, it makes sense to have common test procedures and common assessment
procedures, but with various possible purposes.
One of the intended applications of this document is the comparison of concrete mixtures, and in
particular the assessment of the impact of a change of constituent, e.g. cement type, addition, or the
impact of a change in mix proportions, e.g. w/c ratio, cement content, fines content. Such a comparison,
is also carried out when assessing the durability performance, and more precisely the ‘equivalent
durability’ with respect to carbonation, of a concrete, with unknown carbonation resistance or of a
concrete with one or more unfamiliar constituents. CEN/TR 16563 sets out basic principles to be
followed by 'equivalent durability' procedures.
In addition, this document provides parameters used in the classification of concrete on the basis of its
carbonation resistance.
Moreover, the rate of carbonation, as determined by the described test procedure, is used in some
models that estimate the start of reinforcement corrosion.
As this document provides test procedures, it only describes the production of standardized test
results; how these test results are used is not within the scope of this document.
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
1 Scope
This document specifies a method of determining the carbonation rate of a concrete, expressed in
mm/√a.
This document establishes a procedure where a standardized climate controlled chamber is used and
where specimens are placed on a natural exposure site protected from direct rainfall. The standardized
climate controlled chamber procedure is the reference method.
These procedures are applicable for the initial testing of concrete, including those manufactured with
slowly reacting binders, provided that the ages at which the carbonation depth is measured, the number
of measurements required to calculate the carbonation rate, as well as the length of exposure to CO , are
appropriately selected, as described in this document.
These procedures are not applicable for factory production control.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12390-1, Testing hardened concrete — Part 1: Shape, dimensions and other requirements for
specimens and moulds
EN 12390-2, Testing hardened concrete — Part 2: Making and curing specimens for strength tests
EN 12390-3, Testing hardened concrete — Part 3: Compressive strength of test specimens
3 Terms and definitions
No terms and definitions are listed in this document.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— IEC Electropedia: available at https://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
4 Principle
Pairs of beams of concrete (or two cubes per test age) from the same batch of concrete are stored in a
climate controlled chamber as specified in 5.4 or on a natural exposure site as specified in 5.5. After
defined periods of exposure, an approximately 50 mm thick slice of the beam is broken off at each test
age and tested for its carbonation depth. If cubes are being used, they are broken in half and one half of
each cube is used to measure the carbonation depth, the other half being discarded.
The carbonation depth is measured at three locations on each face of each beam/cube giving a potential
total of 12 measurements per specimen and potentially 24 measurements for the two specimens. The
mean carbonation depth of all measurements is calculated. The remains of the beams are returned to
the climate controlled chamber for testing at other pre-defined ages. Using at least three sets of
measurements taken at 3 months, 6 months and 1 year, the rate of carbonation expressed as mm/√a is
determined.
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
5 Reagents and apparatus
5.1 A solution of 1 g of phenolphthalein powder dissolved in a solution of 70 ml ethanol and 30 ml of
deionized water. Phenolphthalein is the reference method but an alternative indicator giving a colour
change in the range pH 8 to pH 11 that gives a sufficiently clear colour change in concrete to
differentiate the neutralized zone may be used, e.g. thymolphthalein, flavonoids, curcumine, or
antocianines.
WARNING — Phenolphthalein is listed on the REACH candidate list of substances of very high concern
for authorization. Phenolphthalein powder should be handled with the greatest care using safety gloves
in a fume cupboard fitted with an extractor.
5.2 Where used, a fixing solution to permanently fix the colour change in the concrete specimen (see
7.1).
NOTE Suppliers of some indicator solutions also provide a fixing solution that permanently fixes the colour
change.
5.3 A magnifier and a gauge to measure the depth of carbonation perpendicular to the exposed
concrete surface which ensure a precision of the measurement of 0,5 mm.
5.4 A climate controlled chamber controlling the average over the test duration carbon dioxide
concentration at (0,040 ± 0,001) % by volume with no variation outside (0,040 ± 0,005) %, temperature
at (20 ± 2) °C and a relative humidity at (65 ± 2) % (see Annex A for details of a suitable chamber).
5.5 Alternatively to climate controlled chamber, a natural exposure site where specimens are
protected from direct precipitation such as rain, hail and snow (see Annex B for details of a suitable
arrangement). The site shall be equipped with instruments to measure relative humidity, temperature
and carbon dioxide concentration at least 4 times per day. If this is not possible, local meteorological
data can be used.
5.6 Apparatus for recording the relative humidity, which ensures a precision of the measurement
of ± 1,0 %, and the temperature with a precision of ± 0,5 °C.
5.7 Apparatus for recording CO concentration with a precision of ± 0,001 % by volume. If a climate
controlled chamber is being used, it shall be fitted with an audible/visual/electronic alarm to signify
breaching of limits.
5.8 Fan to provide a homogeneous CO concentration in the air. Type, dimensions and power of the
fan shall be adapted to the dimension of the chamber.
6 Production of specimens
6.1 General
Representative samples of the constituents, e.g. cement, aggregates, shall be used for making the test
specimens. Either a sample of concrete is taken from the concrete production plant or the concrete
mixes shall be produced using the laboratory’s standard procedures. The specimens for one test, which
include specimens for the carbonation test and compressive strength tests, shall be cast from a single
batch of concrete.
For laboratory production, a minimum batch volume of 50 l is recommended.
oSIST prEN 12390-10:2025
prEN 12390-10:2025 (E)
Each test shall comprise at least two prismatic beams each being at least 350 mm long and the other
dimensions at least three times the maximum aggregate size or two cubes per test age with a side
length of at least three times the maximum aggregate size. Beams are the reference specimens.
Avoid or minimize the use of mould release agents on the moulds as they may influence the carbonation
depth.
All compressive strength specimens, either cubes or cylinders, shall be made and cured in accordance
with EN 12390-1 and EN 12390-2 and tested in accordance with EN 12390-3.
6.2 Procedure when using climate controlled chamber
After moulding the test specimens, cover the exposed concrete surface with polythene or similar
impermeable sheeting to prevent drying. After (24 ± 2) h, the moulds shall be stripped and the test
specimens transferred without delay into the standard curing condition according to EN 12390-2. After
27 days of standard curing, the test specimens shall be exposed to laboratory air, T = (20 ± 2) °C,
RH = (65 ± 5) % for (16 ± 2) h and then they are placed in the climate controlled chamber.
NOTE 1 The reason for the 27 day wet curing is to allow cements to hydrate prior to carbonation testing as
further hydration is hindered by the carbonation test conditions.
NOTE 2 In climate controlled chambers that do not have the facility to reduce the relative humidity, if the test
specimens are placed immediately in the climate controlled chamber, the rate of carbonation decreases when the
relative humidity is too high and (temporarily) exceeds the limit. If the climate controlled chamber is fitted with
facilities to reduce the relative humidity (not the normal situation), the test specimens can be placed directly in
the climate controlled chamber.
The test specimens shall be positioned in the climate controlled chamber in a way that permits air to
circulate freely around all the four faces to be tested. This is either by horizontal storage or vertical
storage, but ensuring a 50 mm gap between adjacent specimens. The temperature shall be measured at
least once per day at a constant time.
The relative humidity and carbon dioxide concentration shall be measured and recorded at least once
every two hours. The average carbon dioxide concentration in the climate controlled chamber over the
duration of the test shall be (0,040 ± 0,001) % with no variation outside (0,040 ± 0,005) %.
6.3 Procedure when using a natural exposure site
For each concrete mix, cast at least two beams or at least six cubes for carbonation testing and at least 2
or if the strength development is not known, at least 5 compressive strength specimens from a single
batch of concrete. The test specimens shall be cast horizontally in accordance with EN 12390-2. After
finishing the test specimens, cover the exposed surface with polythene or similar impermeable sheeting
to prevent drying.
After (24 ± 2) h, the moulds shall be stripped and the carbonation test specimens transferred without
delay into close-fitting, sealed polythene bags or similar storage material and stored at (20 ± 2) °C until
they have reached 50 % of the reference strength. If the temperature range is from 15 °C to 25 °C, 50 %
of the reference strength
...