SIST EN 54-27:2015
(Main)Fire detection and fire alarms systems - Part 27: Duct smoke detectors
Fire detection and fire alarms systems - Part 27: Duct smoke detectors
This document specifies requirements, test methods and performance criteria for fire detectors which detect smoke in air ducts in buildings as a part of a fire detection and fire alarm system or as an actuator for a fire protection system. For the testing of other types of smoke detectors, or smoke detectors working on different principles, this document can be used only for guidance. Duct smoke detectors with special characteristics and developed for specific risks are not covered by this document. NOTE Certain types of detector contain radioactive materials. The national requirements for radiation protection differ from country to country and are not specified in this standard.
Brandmeldeanlagen - Teil 27: Rauchmelder für die Überwachung von Lüftungsleitungen
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für automatische Brandmelder fest, die Rauch in Lüftungsleitungen erkennen und in Gebäuden als Bestandteil einer Brandmeldeanlage für Gebäude oder als Auslöseeinrichtung für eine automatische Brandschutzeinrichtung eingesetzt werden.
Rauchmelder für die Überwachung von Lüftungsleitungen mit besonderen Eigenschaften und für besondere Gefahren sind nicht Gegenstand dieser Norm.
ANMERKUNG Einige Meldertypen enthalten radioaktive Stoffe. Die nationalen Anforderungen für den Schutz gegen ionisierende Strahlung sind in den Mitgliedstaaten unterschiedlich und werden deshalb in der vorliegenden Norm nicht festgelegt.
Systèmes de détection et d'alarme incendie - Partie 27 : Détecteurs de fumées dans les conduits
La présente Norme européenne spécifie les exigences, les méthodes d’essai et les critères de performance pour les détecteurs d’incendie qui détectent la fumée dans les conduits d’air des bâtiments en tant que partie intégrante d’un système de détection et d’alarme incendie ou en tant qu’actionneur d’un système de protection contre l’incendie.
Les détecteurs de fumée dans les conduits possédant des caractéristiques particulières, conçus pour des risques spéciaux, ne sont pas couverts par ce document.
NOTE Certains types de détecteurs peuvent contenir des matériaux radioactifs. Les exigences nationales pour la protection contre les rayonnements varient d’un État membre à l’autre et ne sont par conséquent pas spécifiées dans la présente norme.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 27. del: Dimni javljalnik za prezračevalne kanale
Ta dokument določa zahteve, preskusne metode in merila učinkovitosti za javljalnike požara, ki zaznavajo prisotnost dima v prezračevalnih kanalih stavb kot del sistema za odkrivanje in javljanje požara ter alarmiranje ali kot sprožilo za sistem zaščite pred požarom. Pri preskušanju drugih vrst dimnih javljalnikov ali dimnih javljalnikov z drugačnim načinom delovanja se lahko ta dokument uporabi samo kot smernica. Dimni javljalniki za prezračevalne kanale s posebnimi značilnostmi, ki so razviti za posebna tveganja, niso zajeti v tem dokumentu. OPOMBA: Nekatere vrste javljalnikov vsebujejo radioaktivne materiale. Nacionalne zahteve za zaščito pred sevanjem se razlikujejo po posameznih državah in niso določene v tem standardu.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 54-27:2015
01-maj-2015
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO'LPQLMDYOMDOQLN
]DSUH]UDþHYDOQHNDQDOH
Fire detection and fire alarms systems - Part 27: Duct smoke detectors
Brandmeldeanlagen - Teil 27: Rauchmelder für die Überwachung von Lüftungsleitungen
Systèmes de détection et d'alarme incendie - Partie 27 : Détecteurs de fumées dans les
conduits
Ta slovenski standard je istoveten z: EN 54-27:2015
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 54-27:2015 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 54-27:2015
---------------------- Page: 2 ----------------------
SIST EN 54-27:2015
EUROPEAN STANDARD
EN 54-27
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2015
ICS 13.220.20
English Version
Fire detection and fire alarms systems - Part 27: Duct smoke
detectors
Systèmes de détection et d'alarme incendie - Partie 27 : Brandmeldeanlagen - Teil 27: Rauchmelder für die
Détecteurs de fumées dans les conduits Überwachung von Lüftungsleitungen
This European Standard was approved by CEN on 11 January 2015.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-27:2015 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
Contents Page
Foreword .5
Introduction .7
1 Scope .8
2 Normative references .8
3 Terms, abbreviated terms and definitions .9
3.1 Terms and definitions .9
3.2 Abbreviated terms . 10
4 Requirements . 10
4.1 General . 10
4.2 Nominal activation conditions/sensitivity . 10
4.2.1 Individual alarm indication . 10
4.2.2 Additional visual indication (option with requirement) . 10
4.2.3 Alarm resetting for stand-alone systems (option with requirement) . 11
4.2.4 Connection of ancillary devices (option with requirement) . 11
4.2.5 Response to slowly developing fires. 11
4.2.6 Dazzling . 11
4.3 Operational reliability . 11
4.3.1 Repeatability . 11
4.3.2 Reproducibility . 11
4.3.3 On-site adjustment of response behaviour . 11
4.3.4 Manufacturer's adjustments . 12
4.3.5 Monitoring of detachable detectors . 12
4.3.6 Software controlled detectors (when provided) . 12
4.4 Tolerance to supply voltage — Variation in supply parameters . 13
4.5 Performance parameters under fire conditions — Fire sensitivity . 13
4.6 Durability of Nominal activation conditions/sensitivity . 13
4.6.1 Temperature resistance . 13
4.6.2 Humidity resistance . 14
4.6.3 Corrosion resistance — Sulfur dioxide (SO ) corrosion (endurance) . 14
2
4.6.4 Shock and vibration resistance . 14
4.6.5 Electrical stability — EMC, immunity tests (operational) . 14
4.6.6 Air leakage . 14
5 Testing, assessment and sampling methods . 15
5.1 General . 15
5.1.1 Atmospheric conditions for tests . 15
5.1.2 Operating conditions for tests . 15
5.1.3 Mounting arrangements . 15
5.1.4 Tolerances . 15
5.1.5 Response threshold value . 16
5.1.6 Provision for tests . 16
5.1.7 Reduced function tests . 17
5.1.8 Test schedule . 17
5.2 Nominal activation conditions/sensitivity . 18
5.2.1 Individual alarm indication . 18
5.2.2 Additional visual indication (when provided) . 18
5.2.3 Alarm resetting for stand-alone system (when provided) . 18
5.2.4 Connection of ancillary devices (when provided) . 18
2
---------------------- Page: 4 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
5.2.5 Response to slowly developing fires . 18
5.2.6 Dazzling . 18
5.3 Operational reliability . 19
5.3.1 Repeatability . 19
5.3.2 Reproducibility . 20
5.3.3 On-site adjustment of response behaviour . 20
5.3.4 Manufacturer's adjustments . 20
5.3.5 Monitoring of detachable detectors . 20
5.3.6 Software controlled devices . 20
5.4 Tolerance to supply voltage . 20
5.4.1 Variation in supply parameters . 20
5.5 Performance parameters under fire conditions . 21
5.5.1 Fire sensitivity . 21
5.6 Durability of Nominal activation conditions/sensitivity . 23
5.6.1 Temperature resistance . 23
5.6.2 Humidity resistance . 25
5.6.3 Corrosion resistance — Sulfur dioxide (SO ) corrosion (endurance) . 27
2
5.6.4 Shock and vibration resistance . 28
5.6.5 Electrical stability . 32
5.6.6 Air leakage . 33
6 Assessment and verification of constancy of performance (AVCP) . 34
6.1 General . 34
6.2 Type testing . 34
6.2.1 General . 34
6.2.2 Test samples, testing and compliance criteria . 35
6.2.3 Test reports . 35
6.3 Factory production control (FPC) . 35
6.3.1 General . 35
6.3.2 Requirements . 36
6.3.3 Product specific requirements . 38
6.3.4 Initial inspection of factory and FPC . 39
6.3.5 Continuous surveillance of FPC . 39
6.3.6 Procedure for modifications. 40
6.3.7 One-off products, pre-production products, (e.g. prototypes) and products produced in
very low quantities . 40
7 Classification . 40
8 Marking, labelling and packaging . 41
9 Data . 41
Annex A (normative) Aerosol tunnel arrangement for response measurements . 42
Annex B (normative) Test aerosol for response threshold value measurements . 43
Annex C (normative) Smoke measuring instruments . 44
Annex D (normative) Apparatus for dazzling test . 48
Annex E (normative) Fire test room and working volume arrangements for fire tests . 49
Annex F (normative) Smouldering (pyrolysis) wood fire (TF2D) . 51
Annex G (normative) Flaming plastics (polyurethane) fire (TF4D) . 54
Annex H (normative) Low temperature black smoke (decaline) liquid fire (TF8D) . 56
Annex I (informative) Information concerning the construction of the tunnel for fire tests . 59
Annex J (informative) Information concerning the construction of the measuring ionization
chamber . 61
3
---------------------- Page: 5 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
Annex K (informative) Information about DSD used as a stand-alone system. 64
Annex L (informative) Power supply . 65
Annex M (informative) Information concerning test procedures and requirements for the
response to slowly developing fires . 66
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Regulation . 70
ZA.1 Scope and relevant characteristics . 70
ZA.2 Procedure for assessment and verification of constancy of performance (AVCP) of duct
smoke detectors . 72
ZA.2.1 System of AVCP . 72
ZA.2.2 Declaration of performance (DoP) . 73
ZA.3 CE marking and labelling . 78
Bibliography . 81
4
---------------------- Page: 6 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
Foreword
This document (EN 54-27:2015) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by September 2015 and conflicting national standards shall be withdrawn
at the latest by March 2019.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports basic requirements of EU Regulation 305/2011.
For relationship with EU Regulation(s), see informative Annex ZA, which is an integral part of this document.
Information on the relationship between this European Standard and other standards of the EN 54 series is
given in EN 54-1.
EN 54, Fire detection and fire alarm systems, consists of the following parts:
— Part 1: Introduction;
— Part 2: Control and indicating equipment;
— Part 3: Fire alarm devices — Sounders;
— Part 4: Power supply equipment;
— Part 5: Heat detectors — Point detectors;
— Part 7: Smoke detectors — Point detectors using scattered light, transmitted light or ionization;
— Part 10: Flame detector — Point detectors;
— Part 11: Manual call points;
— Part 12: Smoke detectors — Line detectors using an optical light beam;
— Part 13: Compatibility assessment of system components;
— Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance [CEN
Technical specification];
— Part 16: Voice alarm control and indicating equipment;
— Part 17: Short circuit isolators;
— Part 18: Input/output devices;
— Part 20: Aspirating smoke detectors;
— Part 21: Alarm transmission and fault warning routing equipment;
5
---------------------- Page: 7 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
— Part 22: Resettable line type heat detectors;
— Part 23 Fire alarm devices — Visual alarm devices;
— Part 24: Components of voice alarm systems — Loudspeakers;
— Part 25: Components using radio links;
— Part 26: Point fire detectors using carbon monoxide sensors;
— Part 27: Duct smoke detectors [the present document];
— Part 28: Non-resettable line type heat detectors;
— Part 29: Multi-sensor fire detectors — Point detectors using a combination of smoke and heat sensors;
— Part 30: Multi-sensor fire detectors — Point detectors using a combination of carbon monoxide and heat
sensors;
— Part 31: Multi-sensor fire detectors — Point detectors using a combination of smoke, carbon monoxide
and optionally heat sensors.
NOTE This list includes standards that are in preparation and other standards may be added. For current status of
published standards refer to www.cen.eu.
According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
6
---------------------- Page: 8 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
Introduction
Duct smoke detectors (DSD) are used as part of a fire detection and fire alarm system or as a stand-alone
actuator for a fire protection system to sample the air within air ducts of a building. Detection of smoke can be
used as a signal to the connected control and indicating equipment and can be used as a signal to an air-
handling system to prevent the spread of smoke within the building.
A DSD is required to function satisfactorily not only in the event of a fire, but also in the conditions likely to be
met in practice such as corrosion, vibration, direct impact, indirect shock and electromagnetic interference.
Some tests specified are intended to assess the performance of the DSD under such conditions.
The performance of DSD is assessed from results obtained in specific tests. This document is not intended to
place any other restrictions on the design and construction of such equipment.
An example for a stand-alone system is given in Figure K.1. The configuration of a fire detection and fire alarm
system is given in EN 54-1.
Annex L gives information on power supply. These requirements are system requirements or requirements on
other components respectively and do not concern the product requirements of the DSD.
7
---------------------- Page: 9 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
1 Scope
This European Standard specifies requirements, test methods and performance criteria for fire detectors
which detect smoke in air ducts in buildings as a part of a fire detection and fire alarm system or as an
actuator for a fire protection system.
Duct smoke detectors with special characteristics and developed for specific risks are not covered by this
document.
NOTE Certain types of detector contain radioactive materials. The national requirements for radiation protection differ
from one member state to another and are not specified in this standard.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 54-1:2011, Fire detection and fire alarm systems - Part 1: Introduction
1)
EN 54-7:2000, Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors using
scattered light, transmitted light or ionization
EN 54-13:2005, Fire detection and fire alarm systems - Part 13: Compatibility assessment of system
components
2)
EN 54-20:2006, Fire detection and fire alarm systems - Part 20: Aspirating smoke detectors
EN 50130-4:2011, Alarm systems - Part 4: Electromagnetic compatibility - Product family standard: Immunity
requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems
EN 60068-1:2014, Environmental testing - Part 1: General and guidance (IEC 60068-1:1988)
EN 60068-2-1:2007, Environmental testing - Part 2-1: Tests - Test A: Cold (IEC 60068-2-1:2007)
EN 60068-2-2:2007, Environmental testing - Part 2-2: Tests - Test B: Dry heat (IEC 60068-2-2:2007)
EN 60068-2-6:2008, Environmental testing - Part 2-6: Tests - Test Fc: Vibration (sinusoidal)(IEC 60068-2-
6:2007)
EN 60068-2-27:2009, Environmental testing - Part 2-27: Tests - Test Ea and guidance: Shock (IEC 60068-2-
27:2008)
EN 60068-2-42:2003, Environmental testing - Part 2-42: Tests - Test Kc: Sulphur dioxide test for contacts and
connections (IEC 60068-2-42:2003)
EN 60068-2-75:2014, Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests (IEC 60068-2-
75:2014)
1 ) EN 54-7:2000 is currently impacted by the stand-alone amendments EN 54-7:2000/A1:2002 and EN 54-
7:2000/A2:2006.
2) EN 54-20:2006 is currently impacted by the corrigendum EN 54-20:2006/AC:2008.
8
---------------------- Page: 10 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
EN 60068-2-78:2013, Environmental testing - Part 2-78: Tests - Test Cab: Damp heat, steady state
(IEC 60068-2-78:2012)
3 Terms, abbreviated terms and definitions
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1:2011, EN 54-13:2005 and the
following apply.
3.1.1
duct smoke detector
fire detector that monitors the air in an air duct to detect smoke
Note 1 to entry: The combination with additional sensors for different fire phenomena is possible.
3.1.2
response threshold value
aerosol concentration within the duct in the proximity of the specimen at the moment that it generates an
alarm signal
Note 1 to entry: The response threshold value can depend on signal processing in the detector and in the control and
indicating equipment.
3.1.3
type 1 DSD
point smoke detector mounted inside the duct
3.1.4
type 2 DSD
point smoke detector mounted inside the duct with additional electrical components
Note 1 to entry: Additional electrical components, e.g. visual indicators are not covered by EN 54 standards. Their
functions are described e.g. in 4.2.1, 4.2.2, and 4.2.3.
3.1.5
type 3 DSD
point smoke detector mounted outside the duct with additional mechanical means to sample the air
3.1.6
type 4 DSD
point smoke detector mounted outside the duct with additional mechanical means to sample the air and with
additional electrical components
Note 1 to entry: Additional electrical components, e.g. visual indicators are not covered by EN 54 standards. Their
functions are described e.g. in 4.2.1, 4.2.2, and 4.2.3.
3.1.7
type 5 DSD
aspirating smoke detector with all sampling points inside the duct
3.1.8
type 6 DSD
other types of DSD not complying with type 1 to type 5
Note 1 to entry: This type 6 DSD includes detectors based on EN 54–7 or EN 54–20 with modified sensitivity settings.
9
---------------------- Page: 11 ----------------------
SIST EN 54-27:2015
EN 54-27:2015 (E)
3.2 Abbreviated terms
ASD Aspirating smoke detector
CIE Control and indicating equipment
DSD Duct smoke detector
FDAS Fire detection and fire alarm system
FPC Factory production control
FPS Fire protection system
4 Requirements
4.1 General
4.1.1 Duct smoke detectors shall incorporate at least one smoke sensor. The combination with additional
sensors for different fire phenomena can be used.
If additional fire sensors for different fire phenomena are implemented in a DSD, these sensors shall be
approved in accordance with the corresponding EN 54 standards.
The manufacturer shall specify whether the DSD can directly be used as an actuator for fire protection
systems, i.e. stand-alone system or as a part of a FDAS.
The requirements of this clause shall be applied for all six types of DSD. The relevant tests for the different
types of DSD are described in Clause 5.
For type 1 DSD to type 4 DSD, the point smoke detector shall be approved to EN 54-7. Otherwise the DSD
shall be assessed like a type 6 DSD.
For type 5 DSD, the ASD shall be approved to EN 54-20; otherwise the DSD shall be assessed like a
type 6 DSD.
4.1.2 Compliance:
To comply with this standard the DSD shall meet the requirements of Clause 4 which shall be verified by
visual inspection or engineering assessment and shall be tested as described in Clause 5 and shall meet the
requirements of the tests.
4.2 Nominal activation conditions/sensitivity
4.2.1 Individual alarm indication
Each DSD shall be provided with a red visual indicator, by which the DSD can be identified when the
assoc
...