This specification covers annealed and intermediate tempered round aluminum wires suitable for electrical purposes like stranding into conductors or for solid single conductors, either bare or insulated. The tempers covered here are 1350-O, 1350-H12 or 1350-H22, 1350-H14 or 1350-H24, 1350-H16 or 1350-H26, and 1350-H142 or 1350-H242. Materials shall be made from drawing stock in which the manufacturer shall have the option of producing the intermediate tempers by either strain-hardening only, by strain-hardening and partial annealing. The wires shall adhere to standard nominal diameters, cross-sectional areas, masses per unit length, and densities. Wires shall also be tested to evaluate their conformance to specified values of tensile strength and electrical resistivity.
SCOPE
1.1 This specification covers aluminum 1350-O (annealed), 1350-H12 or -H22 (¼ hard), 1350-H14 or -H24 (½ hard), 1350-H16 or -H26 (¾ hard) and 1350-H142 or -H242 (½ hard), suitable for stranding into conductors or for solid single conductors, either bare or insulated (see Table 1 or Table 2).
1.2 The values stated in inch-pound units or SI units are to be regarded separately as standard. The values in each system are not exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification.
1.2.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.
Note 1—Prior to 1975, aluminum 1350 was designated as EC-aluminum.
Note 2—The aluminum and temper designations conform to ANSI H35.1. Aluminum 1350 corresponds to Unified Numbering System A91350 in accordance with Practice E527.  
TABLE 1 Standard Nominal Diameters, Cross-Sectional Areas, and Mass Per Unit Length of Solid Round Aluminum Wires and Conductors at 20°C AWG or cmil Sizes
Note—Metric values listed as follows represent a soft conversion and as such they may not be the same as those metric mass per unit length which are calculated from the basic metric density.
Conversion factors:
1 lb/1000 ft = 1.488 ft + 00 kg/km
1 in. = 25.4 mm
   Size cmil
or AWG DiameterCross-Sectional AreaMass Per Unit Length milsmmcmilin.2mm2 lb/1000 ftkg/km 500 000707.117.960500 0000.3927253.3459.4 683.7 450 000670.817.040450 0000.3534228.0413.5 615.3 400 000632.516.070400 0000.3142202.7367.6 547.0 350 000591.615.030350 0000.2749177.3321.6 478.6  300 000547.713.910300 0000.2356152.0275.7 410.2 250 000500.012.700250 0000.1963126.7229.7 341.8   0000460.0 11.680211 6000.1662 107.2194.4289.3  000409.6 10.4000167 8000.1318 85.01154.2229.4  00364.89.2660133 1000.1045 67.43122.3182.0  0324.98.2520105 600 0.0829153.4997.00144.3  1289.37.348083 6900.0657342.4176.91114.4  2257.66.543066 3600.0521233.6260.9890.73   3229.45.827052 6200.0413326.6748.3671.96  4204.35.189041 7400.0327821.1538.3557.07  5181.94.620033 0900.0259916.7730.4045.24  6162.04.115026 2400.0206113.3024.1235.88  7144.33.665020 8200.0163510.5519.1328.47  8128.53.264016 5100.012978.6715.1722.58   9114.42.906013 0900.010286.63112.0317.89  10101.92.588010 3800.0084555.2619.54214.20  1190.72.30408 2260.0064614.1687.55911.25  1280.82.05206 5290.0051283.3085.9998.927  1372.01.82905 1840.0040722.6274.7647.088  1464.11.62804 1090.0032272.0823.7765.618   1557.11.45003 2600.0025611.6522.9964.458  1650.81.29002 5810.0020271.3082.3713.529  1745.31.15102 0520.0016121.0401.8862.806  1840.31.02401 6240.0012760.82291.4922.221  1935.9 0.91191 2890.001012 0.6531 1.1841.762  2032.0 0.81281 0240.00080420.51890.94101.400   2128.5 0.7239812.20.00063790.41160.74641.111  2225.3 0.6426640.10.00050270.32430.58820.8752  2322.60.5740510.80.00040110.25880.46930.6984  2420.1 0.5105404.00.00031730.20470.37130.5542  2517.90.4547320.40.00025160.16240.29440.4381  2615.9 0.4039252.80.00019860.12810.23230.3457   2714.2 0.3607201.60.00015890.10220.18530.2757  28 12.60.3200158.80.0001247 0.08045 0.14590.2171  2...

General Information

Status
Historical
Publication Date
31-Mar-2012
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM B609/B609M-12 - Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM B609/B609M-12 - Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:B609/B609M −12
StandardSpecification for
Aluminum 1350 Round Wire, Annealed and Intermediate
1
Tempers, for Electrical Purposes
This standard is issued under the fixed designation B609/B609M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope B682 SpecificationforMetricSizesofElectricalConductors
B830 Specification for Uniform Test Methods and Fre-
1.1 This specification covers aluminum 1350-O (annealed),
quency
1 1
1350-H12 or -H22 ( ⁄4 hard), 1350-H14 or -H24 ( ⁄2 hard),
E29 Practice for Using Significant Digits in Test Data to
3 1
1350-H16 or -H26 ( ⁄4 hard) and 1350-H142 or -H242 ( ⁄2
Determine Conformance with Specifications
hard), suitable for stranding into conductors or for solid single
E527 Practice for Numbering Metals and Alloys in the
conductors, either bare or insulated (see Table 1 or Table 2).
Unified Numbering System (UNS)
1.2 The values stated in inch-pound units or SI units are to 3
2.3 ANSI Standard:
be regarded separately as standard. The values in each system
ANSI H35.1 American National Standard for Alloy and
are not exact equivalents; therefore, each system shall be used
Temper Designation Systems for Aluminum
independently of the other. Combining values from the two
ANSI H35.1[M] American National Standard for Alloy and
systems may result in nonconformance with the specification.
Temper Designation Systems for Aluminum
1.2.1 For density, resistivity, and temperature, the values
4
2.4 NIST Standards:
stated in SI units are to be regarded as standard.
NBS Handbook 100—Copper Wire Tables of the National
NOTE 1—Prior to 1975, aluminum 1350 was designated as EC- Bureau of Standards
aluminum.
NBS Handbook 109—Aluminum Wire Tables of the Na-
NOTE 2—The aluminum and temper designations conform to ANSI
tional Bureau of Standards
H35.1. Aluminum 1350 corresponds to Unified Numbering System
A91350 in accordance with Practice E527.
3. Terminology
3.1 Definitions of Terms Specific to This Standard:
2. Referenced Documents
3.1.1 lot, n—a group of production units, up to 30 000 lb of
2.1 The following documents of the issue in effect on date
mass, of one type and size of wire, which was produced during
of material purchase form a part of this specification to the
the same time period, under similar production conditions, and
extent referenced herein.
is presented for acceptance at the same time (Explanatory
2
2.2 ASTM Standards:
Notes 1 and 2).
B193 Test Method for Resistivity of Electrical Conductor
3.1.2 production unit, n—a coil, reel, spool, or other pack-
Materials
age of wire that represents a single usable length.
B233 Specification for Aluminum 1350 Drawing Stock for
3.1.3 sample, n—the production unit or units from which a
Electrical Purposes
test specimen or specimens has been removed, and which is
B354 Terminology Relating to Uninsulated Metallic Electri-
considered to have properties representative of the lot.
cal Conductors
B557 Test Methods for Tension Testing Wrought and Cast
3.1.4 specimen, n—a length of wire removed for test pur-
Aluminum- and Magnesium-Alloy Products
poses.
4. Ordering Information
1
This specification is under the jurisdiction of ASTM Committee B01 on
4.1 Orders for material under this specification shall include
Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on
the following information:
Conductors of Light Metals.
4.1.1 Quantity of each size,
Current edition approved April 1, 2012. Published May 2012. Originally
approved in 1977. Last previous edition approved in 2010 as B609/
B609M – 99 (2010). DOI: 10.1520/B0609_B0609M-12.
2 3
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from American National Standards Institute (ANSI), 25 W. 43rd St.,
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM 4th Floor, New York, NY 10036, http://www.ansi.org.
4
Standards volume information, refer to the standard’s Document Summary page on Available from National Technical Information Service (NTIS), 5301 Shawnee
the ASTM website. Rd., Alexandria, VA 22312, http://www.ntis.gov.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
B609/B609M−12
TABLE 1 Standard Nominal Diameters, Cross-Sectional Areas, and Mass Per Unit Length of Solid Round Aluminum Wires and
Conductors at 20°C AWG or cmil Sizes
NOTE 1—Metric values listed as follows represent a soft conversion and as such they may not be the same as those metric mass per unit length which
are calculated from
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:B609/B609M–99 (Reapproved 2010) Designation: B609/B609M – 12
Standard Specification for
Aluminum 1350 Round Wire, Annealed and Intermediate
1
Tempers, for Electrical Purposes
This standard is issued under the fixed designation B609/B609M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1 1
1.1 This specification covers aluminum 1350-O (annealed), 1350-H12 or -H22 ( ⁄4 hard), 1350-H14 or -H24 ( ⁄2 hard),
3 1
1350-H16 or -H26 ( ⁄4 hard) and 1350-H142 or -H242 ( ⁄2 hard), suitable for stranding into conductors or for solid single
conductors, either bare or insulated (see Table 1 or Table 2).
1.2 The values stated in inch-pound units or SI units are to be regarded separately as standard. The values in each system are
not exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems
may result in nonconformance with the specification.
1.2.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.
NOTE 1—Prior to 1975, aluminum 1350 was designated as EC-aluminum.
NOTE 2—The aluminum and temper designations conform to ANSI H35.1. Aluminum 1350 corresponds to Unified Numbering System A91350 in
accordance with Practice E527.
2. Referenced Documents
2.1 The following documents of the issue in effect on date of material purchase form a part of this specification to the extent
referenced herein.
2
2.2 ASTM Standards:
B193 Test Method for Resistivity of Electrical Conductor Materials
B233 Specification for Aluminum 1350 Drawing Stock for Electrical Purposes
B354 Terminology Relating to Uninsulated Metallic Electrical Conductors
B557 Test Methods for Tension Testing Wrought and Cast Aluminum- and Magnesium-Alloy Products
B682 Specification for Metric Sizes of Electrical Conductors
B830 Specification for Uniform Test Methods and Frequency
E29 Practice for Using Significant Digits in Test Data to Determine Conformance with Specifications
E527 Practice for Numbering Metals and Alloys in the Unified Numbering System (UNS)
3
2.3 ANSI Standard:
ANSI H35.1 American National Standard for Alloy and Temper Designation Systems for Aluminum
ANSI H35.1[M] American National Standard for Alloy and Temper Designation Systems for Aluminum
4
2.4 NIST Standards:
NBS Handbook 100—Copper Wire Tables of the National Bureau of Standards
NBS Handbook 109—Aluminum Wire Tables of the National Bureau of Standards
3. Terminology
3.1 Definitions of Terms Specific to This Standard:
3.1.1 lotlot, n—a group of production units, up to 30 000 lb of mass, of one type and size of wire, which was produced during
1
This specification is under the jurisdiction of ASTM Committee B01 on Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on Conductors
of Light Metals.
Current edition approved Oct. 1, 2010. Published December 2010. Originally approved in 1977. Last previous edition approved in 2004 as B609/B609M–99 (Reapproved
2004). DOI: 10.1520/B0609_B0609M-99R10.
Current edition approved April 1, 2012. Published May 2012. Originally approved in 1977. Last previous edition approved in 2010 as B609/B609M – 99 (2010). DOI:
10.1520/B0609_B0609M-12.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036, http://www.ansi.org.
4
Available from National Technical Information Service (NTIS), U.S. Department of Commerce, 5285 Port Royal Rd., Springfield, VA 22161.
4
Available from National Technical Information Service (NTIS), 5301 Shawnee Rd., Alexandria, VA 22312, http://www.ntis.gov.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
B609/B609M – 12
TABLE 1 Standard Nominal Diameters, Cross-Sectional Areas, and Mass Per Unit Length of Solid Round Aluminum Wires and
Conductors at 20°C AWG or cmil Sizes
NOTE 1—Metric values listed as follows represent a soft conversion and as such they may not be the same as those metric mass per uni
...

Questions, Comments and Discussion