Standard Test Method for Performance Testing of Excess Flow Valves

SIGNIFICANCE AND USE
5.1 This test method is intended to be used for the evaluation of EFVs manufactured for use on residential and small commercial thermoplastic natural gas service lines. Possible applications of the test include product design and quality control testing by a manufacturer and product acceptance testing by a natural gas utility.  
5.2 The user of this test method should be aware that the flows and pressures measured in the test apparatus may not correlate well with those measured in a field installation. Therefore, the user should conduct sufficient tests to ensure that any specific EFV will carry out its intended function in the actual field installation used.
SCOPE
1.1 This test method covers a standardized method to determine the performance of excess flow valves (EFVs) designed to limit flow or stop flow in thermoplastic natural gas service lines.2  
1.2 All tests are intended to be performed using air as the test fluid. Unless otherwise stated, all flow rates are reported in standard cubic feet per hour of 0.6 relative density natural gas.  
1.3 The test method recognizes two types of EFV. One type, an excess flow valve-bypass (EFVB), allows a small amount of gas to bleed through (bypass) after it has tripped, usually as a means of automatically resetting the device. The second type, an excess flow valve-non bypass (EFVNB), is intended to trip shut forming an essentially gas tight seal.  
1.4 The performance characteristics covered in this test method include flow at trip point, pressure drop across the EFV, bypass flow rate of the EFVB or leak rate through the EFVNB after trip, and verification that the EFV can be reset.  
1.4.1 Gas distribution systems may contain condensates and particulates such as organic matter, sand, dirt, and iron compounds. Field experience has shown that the operating characteristics of some EFVs may be affected by accumulations of these materials. The tests of Section 11 were developed to provide a simple, inexpensive, reproducible test that quantifies the effect, if any, of a uniform coating of kerosene and of kerosene contaminated with a specified amount of ferric oxide powder on an EFV's operating characteristics.  
1.5 Excess flow valves covered by this test method will normally have the following characteristics: a pressure rating of up to 125 psig (0.86 MPa); a trip flow of between 200 ft3/h and 2500 ft3/h (5.66 m3/h and 70.8 m3/h) at 10 psig (0.07 MPa); a minimum temperature rating of 0°F(–18°C), and a maximum temperature rating of 100 °F (38 °C).  
1.6 The EFVs covered by this test method shall be constructed to fit piping systems no smaller than 1/2 CTS and no larger than 11/4 IPS, including both pipe and tubing sizes.  
1.7 Tests will be performed at 67 °F ± 10 °F (19.4 °C ± 5.5 °C). Alternative optional test temperatures are 100 °F ± 10 °F (37.7 °C ± 5.5 °C) and 0 ± 10°F (–18 ± 5.5°C). All flow rates must be corrected to standard conditions.  
1.8 This test method was written for EFVs installed in thermoplastic piping systems. However, it is expected that the test method may also be used for similar devices in other piping systems.  
1.9 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautions, see Section 8.  
1.11 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the...

General Information

Status
Published
Publication Date
31-Jan-2022
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM F1802-22 - Standard Test Method for Performance Testing of Excess Flow Valves
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM F1802-22 - Standard Test Method for Performance Testing of Excess Flow Valves
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: F1802 − 22
Standard Test Method for
1
Performance Testing of Excess Flow Valves
This standard is issued under the fixed designation F1802; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
3 3 3
1. Scope* and 2500 ft /h (5.66 m /h and 70.8 m /h) at 10 psig (0.07
MPa); a minimum temperature rating of 0°F(–18°C), and a
1.1 This test method covers a standardized method to
maximum temperature rating of 100 °F (38 °C).
determine the performance of excess flow valves (EFVs)
designed to limit flow or stop flow in thermoplastic natural gas 1.6 The EFVs covered by this test method shall be con-
2
1
service lines. structed to fit piping systems no smaller than ⁄2 CTS and no
1
larger than 1 ⁄4 IPS, including both pipe and tubing sizes.
1.2 All tests are intended to be performed using air as the
test fluid. Unless otherwise stated, all flow rates are reported in 1.7 Tests will be performed at 67 °F 6 10 °F (19.4 °C 6
standard cubic feet per hour of 0.6 relative density natural gas. 5.5 °C). Alternative optional test temperatures are 100 °F 6
10 °F (37.7 °C 6 5.5 °C) and 0 6 10°F (–18 6 5.5°C). All
1.3 The test method recognizes two types of EFV. One type,
flow rates must be corrected to standard conditions.
anexcessflowvalve-bypass(EFVB),allowsasmallamountof
gas to bleed through (bypass) after it has tripped, usually as a 1.8 This test method was written for EFVs installed in
means of automatically resetting the device. The second type, thermoplastic piping systems. However, it is expected that the
an excess flow valve-non bypass (EFVNB), is intended to trip test method may also be used for similar devices in other
shut forming an essentially gas tight seal. piping systems.
1.4 The performance characteristics covered in this test 1.9 The values stated in inch-pound units are to be regarded
method include flow at trip point, pressure drop across the as standard. The values given in parentheses are mathematical
EFV, bypass flow rate of the EFVB or leak rate through the conversions to SI units that are provided for information only
EFVNB after trip, and verification that the EFV can be reset. and are not considered standard.
1.4.1 Gas distribution systems may contain condensates and
1.10 This standard does not purport to address all of the
particulates such as organic matter, sand, dirt, and iron com-
safety concerns, if any, associated with its use. It is the
pounds. Field experience has shown that the operating charac-
responsibility of the user of this standard to establish appro-
teristics of some EFVs may be affected by accumulations of
priate safety, health, and environmental practices and deter-
these materials. The tests of Section 11 were developed to
mine the applicability of regulatory limitations prior to use.
provide a simple, inexpensive, reproducible test that quantifies
For specific precautions, see Section 8.
the effect, if any, of a uniform coating of kerosene and of
1.11 This international standard was developed in accor-
kerosene contaminated with a specified amount of ferric oxide
dance with internationally recognized principles on standard-
powder on an EFV’s operating characteristics.
ization established in the Decision on Principles for the
Development of International Standards, Guides and Recom-
1.5 Excess flow valves covered by this test method will
mendations issued by the World Trade Organization Technical
normally have the following characteristics: a pressure rating
3
Barriers to Trade (TBT) Committee.
of up to 125 psig (0.86 MPa); a trip flow of between 200 ft /h
2. Referenced Documents
3
1
This test method is under the jurisdiction of ASTM Committee F17 on Plastic 2.1 ASTM Standards:
Piping Systems and is the direct responsibility of Subcommittee F17.40 on Test
D1600 TerminologyforAbbreviatedTermsRelatingtoPlas-
Methods.
tics
Current edition approved Feb. 1, 2022. Published April 2022. Originally
E177 Practice for Use of the Terms Precision and Bias in
approved in 1995 as PS 13–95. Last previous edition approved in 2015 as
F1802–15. DOI: 10.1520/F1802-22.
ASTM Test Methods
2
This contamination test procedure may be utilized to determine the effect, if
any, of contaminants from a specific gas distribution system on the operational
characteristics of an EFV under consideration for use in that system. Condensates,
3
oils and particulates removed from that distribution system could be substituted for For referenced ASTM standards, visit
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F1802 − 15 F1802 − 22
Standard Test Method for
1
Performance Testing of Excess Flow Valves
This standard is issued under the fixed designation F1802; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope Scope*
1.1 This test method covers a standardized method to determine the performance of excess flow valves (EFVs) designed to limit
2
flow or stop flow in thermoplastic natural gas service lines.
1.2 All tests are intended to be performed using air as the test fluid. Unless otherwise stated, all flow rates are reported in standard
cubic feet per hour of 0.6 relative density natural gas.
1.3 The test method recognizes two types of EFV. One type, an excess flow valve-bypass (EFVB), allows a small amount of gas
to bleed through (bypass) after it has tripped, usually as a means of automatically resetting the device. The second type, an excess
flow valve-non bypass (EFVNB), is intended to trip shut forming an essentially gas tight seal.
1.4 The performance characteristics covered in this test method include flow at trip point, pressure drop across the EFV, bypass
flow rate of the EFVB or leak rate through the EFVNB after trip, and verification that the EFV can be reset.
1.4.1 Gas distribution systems may contain condensates and particulates such as organic matter, sand, dirt, and iron compounds.
Field experience has shown that the operating characteristics of some EFVs may be affected by accumulations of these materials.
The tests of Section 11 were developed to provide a simple, inexpensive, reproducible test that quantifies the effect, if any, of a
uniform coating of kerosene and of kerosene contaminated with a specified amount of ferric oxide powder on an EFV’s operating
characteristics.
1.5 Excess flow valves covered by this test method will normally have the following characteristics: a pressure rating of up to 125
3 3 3 3
psig (0.86 MPa); a trip flow of between 200200 ft /h and 2500 ft /h (5.66(5.66 m /h and 70.8 m /h) at 10 psig (0.07 MPa); a
minimum temperature rating of 0°F(–18°C), and a maximum temperature rating of 100°F (38°C).100 °F (38 °C).
1
1.6 The EFVs covered by this test method shall be constructed to fit piping systems no smaller than ⁄2 CTS and no larger than
1
1 ⁄4 IPS, including both pipe and tubing sizes.
1.7 Tests will be performed at 6767 °F 6 10°F (19.410 °F (19.4 °C 6 5.5°C).5.5 °C). Alternative optional test temperatures are
100 6 10°F (37.7 6 5.5°C) 100 °F 6 10 °F (37.7 °C 6 5.5 °C) and 0 6 10°F (–18 6 5.5°C). All flow rates must be corrected
to standard conditions.
1
This test method is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.40 on Test Methods.
Current edition approved Nov. 1, 2015Feb. 1, 2022. Published May 2016April 2022. Originally approved in 1995 as PS 13–95. Last previous edition approved in 20102015
as F1802–04(2010).F1802–15. DOI: 10.1520/F1802-15.10.1520/F1802-22.
2
This contamination test procedure may be utilized to determine the effect, if any, of contaminants from a specific gas distribution system on the operational characteristics
of an EFV under consideration for use in that system. Condensates, oils and particulates removed from that distribution system could be substituted for kerosene and iron
oxide. Results obtained from using reagents or contaminants other than those specified in this test method must not be used in comparison with results obtained using the
reagents specified in this test method.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F1802 − 22
1.8 This test method was written for EFVs installed in thermoplastic piping systems. However, it is expected that the test method
may also be used for similar devices in other piping systems.
1.9 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of thi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.