prEN 16905-1
(Main)Gas-fired endothermic engine driven heat pumps - Part 1: Terms and definitions
Gas-fired endothermic engine driven heat pumps - Part 1: Terms and definitions
1.1 Scope of the EN 16905 series
This part of EN 16905 specifies the terms and definitions for the rating and performance calculation of gas-fired endothermic engine driven heat pumps for heating and/or cooling mode including the engine heat recovery, to be used outdoor.
This European Standard specifies the terms and definitions.
This European Standard is to be used in conjunction with the following standards:
a) FprEN 16905-2:2022 on safety;
b) EN 16905-3:2017 on test conditions;
c) prEN 16905-4:2022 on the requirements, test conditions and test methods;
d) FprEN 16905‐5:2022 on the calculation of seasonal performances in heating and cooling mode;
e) the heat pump standards, EN 14511‐2, EN 14511-3 and EN 14825.
This European Standard only applies to appliances with a maximum heat input (based on net calorific value) not exceeding 70 kW at standard rating conditions.
This European Standard only applies to appliances under categories I2H, I2E, I2Er, I2R, I2E(S)B, I2L, I2LL, I2ELL, I2E(R)B, I2ESi, I2E(R), I3P, I3B, I3B/P, II2H3+, II2Er3+, II2H3B/P, II2L3B/P, II2E3B/P, II2ELL3B/P, II2L3P, II2H3P, II2E3P and II2Er3P according to EN 437.
This European Standard only applies to appliances having:
f) gas fired endothermic engines under the control of fully automatic control systems;
g) closed system refrigerant circuits in which the refrigerant does not come into direct contact with the fluid to be cooled or heated;
h) where the temperature of the heat transfer fluid of the heating system (heating water circuit) does not exceed 105 °C during normal operation;
i) where the maximum operating pressure in the:
1) heating water circuit (if installed) does not exceed 6 bar
2) domestic hot water circuit (if installed) does not exceed 10 bar.
This European Standard applies to GEHP appliances only when used for space heating or space cooling or for refrigeration, with or without heat recovery.
This European Standard is applicable to GEHP appliances that are intended to be type tested. Requirements for GEHP appliances that are not type tested would need to be subject to further consideration.
Gasbefeuerte endothermische Motor-Wärmepumpen - Teil 1: Begriffe
1.1 Anwendungsbereich der Normenreihe EN 16905
Dieser Teil von EN 16905 legt die Begriffe und Definitionen für die Bewertung und Leistungsberechnung von gasbefeuerten endothermischen Motor-Wärmepumpen für den Heiz- und/oder Kühlbetrieb einschließlich der Motor-Wärmerückgewinnung zur Anwendung im Freien fest.
Diese Europäische Norm legt die Begriffe und Definitionen fest.
Diese Europäische Norm ist anzuwenden in Zusammenhang mit den folgenden Normen:
a) FprEN 16905 2:2022 über Sicherheit;
b) EN 16905 3:2017 über Prüfbedingungen;
c) prEN 16905 4:2022 über die Anforderungen, Prüfbedingungen und Prüfverfahren;
d) FprEN 16905‐5:2022 über die Berechnung der saisonalen Effizienzkennzahlen im Heiz- und Kühlmodus;
e) den Wärmepumpennormen EN 14511‐2, EN 14511 3 und EN 14825.
Diese Europäische Norm gilt ausschließlich für Geräte mit einer maximalen Wärmebelastung von 70 kW (bezogen auf den Heizwert [NCV; en: net calorific value]) bei Norm-Nennbedingungen.
Diese Europäische Norm gilt entsprechend EN 437 ausschließlich für Geräte der folgenden Kategorien: I2H, I2E, I2Er, I2R, I2E(S)B, I2L, I2LL, I2ELL, I2E(R)B, I2ESi, I2E(R), I3P, I3B, I3B/P, II2H3+, II2Er3+, II2H3B/P, II2L3B/P, II2E3B/P, II2ELL3B/P, II2L3P, II2H3P, II2E3P und II2Er3P.
Diese Europäische Norm gilt ausschließlich für Geräte mit:
f) endothermischen Gasmotoren, die durch vollständig automatisierte Regelungen gesteuert werden;
g) geschlossenen Kühlkreislaufsystemen, in denen das Kühlmittel nicht direkt mit der zu kühlenden oder zu erwärmenden Flüssigkeit in Berührung kommt;
h) einer Temperatur des Wärmeübertragungsmediums im Heizsystem (Heizungswasserkreislauf), die im Normalbetrieb 105 °C nicht überschreitet;
i) einem höchsten Betriebsdruck im:
1) Heizungswasserkreislauf (falls installiert), der 6 bar nicht überschreitet;
2) Warmwasserbereitungskreislauf für Nutzwasser (falls installiert), der 10 bar nicht überschreitet.
Diese Europäische Norm gilt ausschließlich für GEHP-Systeme, die zur Raumbeheizung oder kühlung oder zur Kälteerzeugung mit oder ohne Wärmerückgewinnung angewendet werden.
Diese Europäische Norm gilt für GEHP-Systeme, die einer Typprüfung zu unterziehen sind. Anforderungen an nicht typgeprüfte GEHP-Systeme wären ein Thema für weitere Überlegungen.
Pompes à chaleur à moteur endothermique alimenté au gaz - Partie 1 : Termes et définitions
1.1 Domaine d'application de la série EN 16905
La présente partie de l'EN 16905 spécifie les termes et définitions relatifs aux calculs des caractéristiques et des performances des pompes à chaleur à moteur endothermique alimenté au gaz pour le mode chauffage et/ou refroidissement, y compris la récupération de chaleur du moteur, qui doivent être utilisées en extérieur.
La présente Norme européenne spécifie les termes et définitions.
La présente Norme européenne est à utiliser conjointement avec les normes suivantes :
a) FprEN 16905-2:2022 relative à la sécurité ;
b) EN 16905-3:2017 relative aux conditions d'essai ;
c) prEN 16905-4:2022 relative aux exigences, aux conditions d'essai et aux méthodes d'essai ;
d) FprEN 16905‐5:2022 relative au calcul des performances saisonnières en modes chauffage et refroidissement ;
e) les normes relatives aux pompes à chaleur, EN 14511‐2, EN 14511-3 et EN 14825.
La présente Norme européenne s'applique uniquement aux appareils dont le débit calorifique maximal (dérivé du pouvoir calorifique inférieur) ne dépasse pas 70 kW dans les conditions de performance nominale.
La présente Norme européenne se limite également aux appareils classés dans les catégories I2H, I2E, I2Er, I2R, I2E(S)B, I2L, I2LL, I2ELL, I2E(R)B, I2ESi, I2E(R), I3P, I3B, I3B/P, II2H3, II2Er3, II2H3B/P, II2L3B/P, II2E3B/P, II2ELL3B/P, II2L3P, II2H3P, II2E3P et II2Er3P de l'EN 437.
La présente Norme européenne norme ne s'applique qu'aux appareils :
f) équipés de moteurs endothermiques alimentés au gaz régulés par des systèmes de régulation entièrement automatisés ;
g) comportant des circuits fermés de réfrigérant dans lesquels le réfrigérant n'entre pas en contact direct avec le fluide à refroidir ou à chauffer ;
h) dans lesquels la température du fluide caloporteur du système de chauffage (circuit d'eau de chauffage) ne dépasse pas 105 °C dans les conditions normales de fonctionnement ;
i) dans lesquels la pression maximale de fonctionnement :
1) ne dépasse pas 6 bar dans le circuit d'eau de chauffage (le cas échéant) ; et
2) ne dépasse pas 10 bar dans le circuit d'eau chaude sanitaire (le cas échéant).
La présente Norme européenne s'applique aux appareils GEHP utilisés uniquement pour le chauffage de locaux, le refroidissement de locaux ou la réfrigération, avec ou sans récupération de chaleur.
La présente Norme européenne s'applique aux appareils GEHP destinés à être soumis à des essais de type. Les exigences relatives aux appareils GEHP non soumis à des essais de type pourraient être assujetties à des considérations supplémentaires.
Toplotna črpalka s plinsko gnanim motorjem z notranjim zgorevanjem - 1. del: Izrazi in definicije
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN 16905-1:2023
01-januar-2023
Toplotna črpalka s plinsko gnanim motorjem z notranjim zgorevanjem - 1. del:
Izrazi in definicije
Gas-fired endothermic engine driven heat pumps - Part 1: Terms and definitions
Gasbefeuerte endothermische Motor-Wärmepumpen - Teil 1: Begriffe
Pompes à chaleur à moteur endothermique alimenté en gaz - Partie 1 : Termes et
définitions
Ta slovenski standard je istoveten z: prEN 16905-1
ICS:
01.040.27 Prenos energije in toplote Energy and heat transfer
(Slovarji) engineering (Vocabularies)
27.080 Toplotne črpalke Heat pumps
oSIST prEN 16905-1:2023 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------oSIST prEN 16905-1:2023
---------------------- Page: 2 ----------------------
oSIST prEN 16905-1:2023
DRAFT
EUROPEAN STANDARD
prEN 16905-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
December 2022
ICS 01.040.27; 27.080 Will supersede EN 16905-1:2017
English Version
Gas-fired endothermic engine driven heat pumps - Part 1:
Terms and definitions
Pompes à chaleur à moteur endothermique alimenté Gasbefeuerte endothermische Motor-Wärmepumpen -
en gaz - Partie 1 : Termes et définitions Teil 1: BegriffeThis draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 299.If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16905-1:2022 E
worldwide for CEN national Members.---------------------- Page: 3 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
Contents Page
European foreword ...................................................................................................................................................... 3
Introduction .................................................................................................................................................................... 4
1 Scope .................................................................................................................................................................... 5
1.1 Scope of the EN 16905 series ...................................................................................................................... 5
2 Normative references .................................................................................................................................... 5
3 Terms and definitions ................................................................................................................................... 6
3.1 Appliance and its constituents ................................................................................................................... 6
3.2 Combustion products circuit .................................................................................................................... 10
3.3 Adjusting, monitoring, control and safety devices ........................................................................... 10
3.4 Operation of the GEHP appliance ............................................................................................................ 13
3.5 Gases .................................................................................................................................................................. 16
3.6 Conditions of operation, measurement and calculations .............................................................. 17
4 Denomination................................................................................................................................................. 41
Bibliography ................................................................................................................................................................. 42
Index ............................................................................................................................................................................. 43
---------------------- Page: 4 ----------------------oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
European foreword
This document (prEN 16905-1:2022) has been prepared by Technical Committee CEN/TC 299 “Gas-
fired sorption appliances, indirect fired sorption appliances, gas-fired endothermic engine heat pumps
and domestic gas-fired washing and drying appliances”, the secretariat of which is held by UNI.
This document is currently submitted to the CEN Enquiry.This document will supersede EN 16905-1:2017.
This document includes the following significant technical changes with respect to EN 16905-1:2017:
— new definitions added in subclause 3.1, 3.4, 3.5 and 3.6;— modifications of existing definitions in subclause 3.6.
---------------------- Page: 5 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
Introduction
The GEHP appliances having their condenser cooled by air and by the evaporation of external additional
water are not covered by this European Standard.Single split and multisplit systems are covered by this European Standard.
The GEHP appliances can have one or more primary or secondary functions.
This European Standard specifies the requirements, test methods and test conditions concerning, in
particular, the construction, safety, fitness for purpose, and rational use of energy, for the rating and
performance calculation of air conditioners and heat pumps using either air, water or brine as heat
transfer media, with gas-fired endothermic engine driven compressors when used for space heating,
cooling and refrigeration, hereafter referred to as “GEHP appliance”.The EN 16905 series comprises the following parts under the general title Gas‐fired endothermic engine
driven heat pumps:— Part 1: Terms and definitions;
— Part 2: Safety;
— Part 3: Tests conditions;
— Part 4: Tests methods;
— Part 5: Calculation of seasonal performances in heating and cooling mode.
This document has been prepared to address the definitions used in all parts.
prEN 16905-1:2022, FprEN 16905-2:2022, EN 16905-3:2017, prEN 16905-4:2022 and FprEN 16905-
5:2022 are linked to the Energy Related Products Directive (2009/125/EC) in terms of tests conditions,
tests methods and seasonal performances calculation methods under Mandate M/535; (see EN 16905-
3:2017, Annex ZA, prEN 16905-4:2022, Annex ZA, FprEN 16905-5:2022, Annex ZA and FprEN 16905-
2:2022, Annexes ZB and ZC).These documents will be reviewed whenever new mandates could apply.
---------------------- Page: 6 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
1 Scope
1.1 Scope of the EN 16905 series
This part of EN 16905 specifies the terms and definitions for the rating and performance calculation of
gas-fired endothermic engine driven heat pumps for heating and/or cooling mode including the engine
heat recovery, to be used outdoor.This European Standard specifies the terms and definitions.
This European Standard is to be used in conjunction with the following standards:
a) FprEN 16905-2:2022 on safety;b) EN 16905-3:2017 on test conditions;
c) prEN 16905-4:2022 on the requirements, test conditions and test methods;
d) FprEN 16905-5:2022 on the calculation of seasonal performances in heating and cooling mode;
e) the heat pump standards, EN 14511-2, EN 14511-3 and EN 14825.This European Standard only applies to appliances with a maximum heat input (based on net calorific
value) not exceeding 70 kW at standard rating conditions.This European Standard only applies to appliances under categories I , I , I , I , I , I , I ,
2H 2E 2Er 2R 2E(S)B 2L 2LLI , I , I , I , I , I , I , II , II , II , II , II , II , II ,
2ELL 2E(R)B 2ESi 2E(R) 3P 3B 3B/P 2H3+ 2Er3+ 2H3B/P 2L3B/P 2E3B/P 2ELL3B/P 2L3P
II , II and II according to EN 437.
2H3P 2E3P 2Er3P
This European Standard only applies to appliances having:
f) gas fired endothermic engines under the control of fully automatic control systems;
g) closed system refrigerant circuits in which the refrigerant does not come into direct contact with
the fluid to be cooled or heated;h) where the temperature of the heat transfer fluid of the heating system (heating water circuit) does
not exceed 105 °C during normal operation;i) where the maximum operating pressure in the:
1) heating water circuit (if installed) does not exceed 6 bar
2) domestic hot water circuit (if installed) does not exceed 10 bar.
This European Standard applies to GEHP appliances only when used for space heating or space cooling
or for refrigeration, with or without heat recovery.This European Standard is applicable to GEHP appliances that are intended to be type tested.
Requirements for GEHP appliances that are not type tested would need to be subject to further
consideration.2 Normative references
There are no normative references in this document.
---------------------- Page: 7 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp— IEC Electropedia: available at https://www.electropedia.org/
3.1 Appliance and its constituents
3.1.1
air conditioner
encased assembly or assemblies designed as a unit to provide delivery of conditioned air to an enclosed
space (room for instance) or zoneNote 1 to entry: It includes a refrigeration system for cooling and possibly dehumidifying the air.
Note 2 to entry: It can have means for heating, circulating, cleaning and humidifying the air. If the unit provides
heating by reversing the refrigerating cycle, then it is a heat pump.3.1.2
close control air conditioner
air conditioner to satisfy the requirements of the process carried out in the air conditioned room
3.1.3control cabinet air conditioner
air conditioner to satisfy the requirements of the control cabinet
3.1.4
double-duct air conditioner
air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is
introduced from the outdoor environment to the unit by a duct and rejected to the outdoor
environment by a second duct, and which is placed wholly inside the place to be conditioned, near a
wall3.1.5
engine heat recovery
recovery of residual heat energy from the engine by means of a heat exchanger
3.1.6
engine heat recovery heat exchanger
heat exchanger assembly which is designed to transfer the residual heat energy to the engine heat
recovery medium3.1.7
exhaust air
air from the air conditioned space entering the outdoor heat exchanger
3.1.8
brine
heat transfer medium that has a freezing point lower than the freezing point of water
---------------------- Page: 8 ----------------------oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.1.9
gas carrying circuit
assembly of parts of the GEHP appliance that carry or contain supplied gas or process gas
Note 1 to entry: This circuit includes the gas circuit.3.1.10
gas circuit
assembly of parts of the GEHP appliance that carry or contain the supplied gas between the gas inlet
connection and the outlet of the safety shut-off valves3.1.11
gas inlet connection
part of the GEHP appliance intended to be connected to the gas supply
3.1.12
gas rate adjuster
component allowing the gas rate of a gas mixture equipment to be brought to a predetermined value
according to the supply conditionsNote 1 to entry: The action of operating this device is called “adjustment of the gas rate”.
Note 2 to entry: e.g. gas mixer.3.1.13
GEHP appliance
gas-fired endothermic engine driven heat pump
3.1.14
heat pump
encased assembly or assemblies designed as a unit to provide delivery of heat
Note 1 to entry: It includes a refrigeration system for heating.
Note 2 to entry: It can have means for cooling, circulating, cleaning and dehumidifying the air. The cooling is by
means of reversing the refrigerating cycle.3.1.15
heat recovery
recovery of heat rejected by the unit whose primary control is in the cooling mode by means of either
an additional heat exchanger (e.g. a liquid chiller with an additional condenser) or by transferring the
heat through the refrigerating system for use by units whose primary control remains in heating mode
(e.g. variable refrigerant flow with simultaneous cooling and heating operation)3.1.16
heat recovery heat exchanger
heat exchanger assembly which is designed to transfer heat to the heat recovery medium
3.1.17heat transfer medium
medium (water, air …) used for the transfer of the heat without changing the state
---------------------- Page: 9 ----------------------oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.1.18
ignition device
means (e.g. electrical, etc.) used to ignite the gas admitted to the internal combustion engine
3.1.19indoor heat exchanger
heat exchanger which is designed to transfer heat between the refrigerant and the indoor heat transfer
mediumNote 1 to entry: In the case of an air conditioner operating in the cooling mode, this is the evaporator. In the case
of an air conditioner operating in heating mode, this is the condenser.Note 2 to entry: In case the indoor heat transfer is water or brine, the indoor heat exchanger is also placeable at
outdoor.3.1.20
injector
component that admits gas into an internal combustion engine
3.1.21
internal combustion engine
mechanism delivering shaft power by the combustion of fuel in one or more cylinders in which working
pistons reciprocate3.1.22
multi-split system
split system incorporating more than one indoor units, one or more refrigerant circuits, one or more
compressors, and one or more outdoor unitsNote 1 to entry: The indoor units can be individually controlled or not.
3.1.23
outdoor heat exchanger
heat exchanger which is designed to transfer heat between any available heat source and the
refrigerantNote 1 to entry: In the case of an air conditioner operating in the cooling mode, this is the condenser. In the case
of an air conditioner operating in heating mode, this is the evaporator.3.1.24
primary function
main purpose for which the GEHP appliance is designed
Note 1 to entry: Both the heating and cooling functions of the GEHP appliance are classed as primary functions if
they satisfy the rational use of energy requirements for those functions.3.1.25
range-rating device
component on the GEHP appliance intended to be used by the installer to adjust the nominal heat input
(value of the heat input at standard rating condition) of the GEHP appliance within the range of
maximum and minimum heat inputs stated in the technical specifications/instructions, to suit the actual
heat requirements of the installation---------------------- Page: 10 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.1.26
recycled air
air from the air conditioned space entering the indoor heat exchanger
3.1.27
sealing an adjuster or control device
arrangements made to make evident any attempt to change the set adjustment (e.g. breakage of the
device or the sealing material)Note 1 to entry: A sealed adjuster or control device is considered to be non-existent.
3.1.28secondary function
optional function of the GEHP appliance, such as heating or cooling, which is not expected to satisfy the
rational use of energy requirements of a primary function3.1.29
single-duct air conditioner
air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is
introduced from the space containing the unit and discharged outside this space3.1.30
single split unit
factory assembly of components of refrigeration system fixed on two mountings to form a discrete
matched functional unit3.1.31
simultaneously heating and cooling mode multi-split system
split system air conditioner or heat pump incorporating a single refrigerant circuit, at least one variable
speed compressor or an alternate compressor combination for varying the capacity of the system by
three or more steps, multiple indoor units, each capable of being individually controlled and one or
more outdoor unitsNote 1 to entry: This system is capable of operating as a heat pump where recovered heat from the indoor units
operating in the cooling mode can be transferred to one or more units operating in the heating mode.
Note 2 to entry: This may be achieved by a gas/liquid separator or a third line in the refrigeration circuit.
3.1.32water loop
closed circuit of water maintained with a temperature range on which the units in cooling mode reject
heat and the units in heating mode take heat---------------------- Page: 11 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.2 Combustion products circuit
3.2.1
air supply and combustion products evacuation ducts
means for transporting combustion air to the internal combustion engine and the combustion products
to the terminal or fitting pieceNote 1 to entry: It is necessary to distinguish between:
— completely surrounded ducts: the combustion products evacuation duct is surrounded by combustion air
throughout its length,— separate ducts: the combustion products evacuation duct and the combustion air supply duct are neither
concentric nor completely surrounded ducts.3.2.2
backflow valve
valve to prevent flue gas backflow
3.2.3
combustion chamber
enclosure inside which combustion of the air-gas mixture takes place
3.2.4
combustion circuit
circuit including the air supply duct and the combustion products circuit
3.2.5
combustion products circuit
circuit including the combustion chamber, the heat exchanger, the combustion products evacuation
duct and either the fitting piece or the connection to the terminal, if any3.2.6
terminal
part of the combustion circuit fitted external to the building which has the function of the air supply
inlet and/or combustion products outlet of the appliance3.2.7
terminal guard
device that protects the terminal from physical damage from outside influences
3.3 Adjusting, monitoring, control and safety devices
3.3.1
adjustable pressure regulator
pressure regulator fitted with a means of adjusting the downstream pressure
Note 1 to entry: This means is considered as an “adjusting device”.
3.3.2
adjustable control thermostat
control thermostat that permits the user to obtain setting temperatures between a minimum and a
maximum value---------------------- Page: 12 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.3.3
air proving device
device intended to cause safety shutdown in the event of abnormal conditions of air admission or of
combustion products evacuation3.3.4
automatic engine control system
system that comprises a programming unit and the combustion detection function
Note 1 to entry: All the functions of an automatic control system are assembled in one or more housings.
3.3.5automatic shut-off valve
device that automatically opens, closes or varies a rate on a signal from the engine control system
Note 1 to entry: Automatic valves are classified in accordance with EN 161 into classes A, B, C, D and J.
3.3.6breather hole
orifice that allows atmospheric pressure to be maintained in a compartment of variable volume
3.3.7closure member
movable part of the valve or the thermoelectric device that opens, varies or shuts off the gas path
3.3.8control knob
component intended to be moved by hand in order to act on an appliance control (e.g. tap, thermostat,
etc.)3.3.9
control thermostat
device enabling the water temperature to be kept automatically within a given range at a
predetermined value3.3.10
diaphragm
flexible component that operates a valve by means of a force resulting from a pressure difference
3.3.11external soundness
soundness, with respect to the atmosphere, of an enclosure containing gas
3.3.12
fault tolerating time
time between the occurrence of a fault and the shut-down of the internal combustion engine which is
tolerated by the application without creating a hazardous situation3.3.13
gas/air ratio control
device that automatically adapts the combustion air rate to the gas rate or vice versa
---------------------- Page: 13 ----------------------oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.3.14
frost protection system
system that actively protects the water in the GEHP appliance against freezing
Note 1 to entry: An anti-freeze solution is not considered as an active frost protective system.
3.3.15ignition safety time
TSA
time elapsing between the start and the stop of the gas supply to internal combustion engine in the
event of ignition not taking place3.3.16
internal soundness
soundness of a closure member in the closed position and isolating an enclosure containing gas from
another enclosure or from the outlet of the valve3.3.17
limit thermostat
device that causes a shut off of the gas supply when a limit value of the temperature is reached, and
automatically enables a new start-up sequence when the temperature returns below the fixed limit
3.3.18maximum allowable working temperature
temperature that the material can withstand over a long period of time under working condition
3.3.19multifunctional control
device which has two or more controls and/or control function(s) whereby the functional parts cannot
operate if separated3.3.20
overheat cut-off device
device that causes safety shutdown and non-volatile lockout before the GEHP appliance is damaged
and/or before safety is put in question3.3.21
pressure regulator
device which maintains the downstream pressure constant to within fixed limits independent of
variations within a given range of the upstream pressure and the gas rate3.3.22
programme
sequence of control operations determined by the programming unit, involving switching on,
supervising and switching off the internal combustion engine3.3.23
programming unit
device that reacts to impulses from control and safety systems, gives control commands, controls the
start-up programme, supervises the internal combustion engine operation and causes controlled
shutdown, safety shutdown or lockout, if necessary and follows a predetermined sequence of actions
operating in conjunction with a combustion detection device---------------------- Page: 14 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.3.24
remote control
device that performs the remote control function by wires or wireless connection, with or without line
of sight of the GEHP appliance3.3.25
remote control function
function that provides automatic and normal operation by means of a control intended to be actuated
with or without line of sight of the GEHP appliance, e.g. through:a) communication lines/protocols,
b) additional hardware and/or software,
c) ultra-sonic,
d) infrared (IR)/radio frequency (RF) transmission,
e) all kind of combinations of a) to c) via the internet, e.g. modems, portable telephones
3.3.26remote reset
device that performs a specific remote control function, being reset from lock-out to allow a restart
attempt3.3.27
safety temperature limiter
device that causes safety shutdown and non-volatile lockout so as to prevent a gas or a water
temperature exceeding a preset limit3.4 Operation of the GEHP appliance
3.4.1
backfire
mistimed explosion in the cylinder or exhaust of an engine
3.4.2
complete combustion
combustion with no more than traces of combustible constituents (hydrogen, hydrocarbons, carbon
monoxide, carbon etc.) in the combustion products3.4.3
condensing operation mode of the flue system
operation mode where, under normal operation conditions, condensate is produced in the combustion
products3.4.4
controlled shutdown
process by which a control device (on the GEHP appliance or external to it) causes the gas supply to the
internal combustion engine to be stopped immediately; the GEHP appliance returns to its start position
3.4.5domestic hot water
DHW
water delivered by the GEHP appliance, raised to a certain temperature in order to use it for domestic
needs, e.g. kitchen, bathroom, etc.---------------------- Page: 15 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.4.6
engine rpm equivalent
rpmequivalent
at standard rating conditions means the revolutions per minute of the internal combustion engine
calculated on the basis of an engine rpm at 70, 60, 40 and 20 % part load ratios for heating (or cooling if
no heating function is offered) and weighing factors of 0,15, 0,25, 0,30 and 0,30 respectively
3.4.7extinction safety time
time that elapses between extinction of the supervised flame and the order to shut off the gas supply to
internal combustion engine3.4.8
heat input
quantity of energy used in unit time corresponding to the volumetric or mass flow rates, the calorific
value used being either the net or gross calorific valueNote 1 to entry: The heat input is expressed in kilowatt (kW).
3.4.9
incomplete combustion
combustion at which at least one combustible constituent is present in significant proportions in the
combustion products3.4.10
internal cooling circuit
loop in which a fluid circulates intended to maintain the various elements of the GEHP appliance at their
operating temperature3.4.11
locking out
complete interruption of the gas supply with lockout
3.4.12
maximum water operating pressure
PMS
maximum water operating pressure at which the GEHP appliance can be used, in bars given by the
symbol PMS, followed by the equals sign, the numerical value and the unit bar3.4.13
maximum water service pressure
maximum pressure permitted in the domestic water circuit of combinations GEHP appliance, as stated
in the appliance instructions3.4.14
nominal electrical frequency
frequency stated in the technical specifications/instructions at which the GEHP appliance can operate
normally---------------------- Page: 16 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.4.15
nominal voltage
voltage or range of voltages stated in the technical specifications/instructions at which the GEHP
appliance can operate normally3.4.16
non-volatile lockout
shutdown condition such that a restart can only be accomplished by a manual reset
3.4.17pre-purge time
period during which pre-purge takes place
3.4.18
purge
mechanical introduction of air into the combustion circuit in order to displace any gas/air mixture,
which could remain thereNote 1 to entry: A distinction is made between:
— pre-purge: the purge that takes place between the start command and the ignition device being energized,
— post-purge: the purge that is carried out after burner shutdown.3.4.19
recycling
automatic process by which, after loss of combustion during operation, the gas supply is interrupted
and the full start procedure is re-initiated automatically3.4.20
safety shutdown
process which is effected immediately following the response of a protection device or the detection of
a fault and puts the internal combustion engine out of operation such as to maintain a safe condition
and avoid damage to the GEHP appliance, and through which the resulting state of the system is defined
by deactivated terminals for the shut-off valves and the ignition device3.4.21
start
action which causes the GEHP appliance to leave its prestart operation allowing the predetermined
programme to commence---------------------- Page: 17 ----------------------
oSIST prEN 16905-1:2023
prEN 16905-1:2022 (E)
3.5 Gases
3.5.1
calorific value
quantity of heat produced by the complete combustion, at a constant pressure equal to 1 013,25 mbar,
of a unit volume or mass of gas, the constituents of the combustible mixture being taken at reference
conditions and the products of combustion being brought back to the same conditions
Note 1 to entry: A distinction is made between:— the gross calorific value Hs: the water pr
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.