Fire-fighting pumps - Fire-fighting centrifugal pumps without primer - Part 1: Classification, general and safety requirements

This document applies to centrifugal pumps without priming devices for fire-fighting use designed as
 floating pumps (FPN-F),
 submersible pumps (FPN-S) or
 boosted pumps (FPN-B).
Fire-fighting centrifugal pumps without primer are defined as terminated by their inlet and outlet connections as
well as by their shaft ends.
This document applies for fire-fighting centrifugal pumps without priming devices for use under ambient
temperatures between -15 °C and 40 °C.
NOTE 1 For special conditions, -30 °C; see 6.11.
This document does not apply to fire-fighting centrifugal pumps without primer of which the only power source is
directly applied manual effort.
This document does not apply to fire-fighting centrifugal pumps without primer, intended to be used as
interchangeable equipment (i.e. combined by the user with another machine or vehicle acting as a driver).
This document does not apply to fire-fighting centrifugal pumps without primer with a nominal delivery
pressure pN above 15 bar.
NOTE 2 High pressure pumps with primer are dealt with in EN 1028-1 and EN 1028-2.
This document specifies the classification and general requirements for fire-fighting centrifugal pumps without
priming devices with a nominal delivery rate of up to 6 000 l/min.
This document deals with significant hazards listed in Clause 4, hazardous situations and events during the
commissioning, operation and maintenance of fire-fighting centrifugal pumps without priming devices, used as
intended and under the conditions foreseen by the manufacturer.
This document does not deal with the detailed verification of general and safety requirements and/or protective
measures. These are covered in EN 14710-2 "Verification of general and safety requirements".
This document does not deal with noise.

Feuerlöschpumpen - Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung - Teil 1: Klassifizierung, allgemeine Anforderungen und Sicherheitsanforderungen

Dieses Dokument gilt für Kreiselpumpen ohne Entlüftungseinrichtungen für Feuerlöschzwecke, die als
⎯ Schwimmpumpen (FPN-F),
⎯ Tauchpumpen (FPN-S) oder
⎯ gespeiste Pumpen (FPN-B)
ausgeführt sind.
Die Grenzen von Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung sind durch ihre Eintritts- und
Austrittsanschlüsse sowie durch ihre Wellenenden festgelegt.
Dieses Dokument gilt für Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung, die in einem Umgebungstemperaturbereich
zwischen − 15 °C und 40 °C eingesetzt werden.
ANMERKUNG 1 Bei besonderen Bedingungen, − 30 °C, siehe 6.11.
Dieses Dokument gilt nicht für Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung, deren einzige
Kraftquelle die direkt aufgebrachte menschliche Arbeitskraft ist.
Dieses Dokument gilt nicht für Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung, die als auswechselbare
Ausrüstungen vorgesehen sind (z. B. durch den Anwender als Antrieb mit einer anderen Maschine oder
einem anderen Fahrzeug kombiniert).
Dieses Dokument gilt nicht für Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung mit einem Nennförderdruck,
pN, von mehr als 15 bar.
ANMERKUNG 2 Hochdruckpumpen mit Entlüftungseinrichtung sind Gegenstand von EN 1028-1 und 1028-2.
Dieses Dokument legt die Klassifizierung und die allgemeinen Anforderungen für Feuerlöschkreiselpumpen
ohne Entlüftungseinrichtung mit einem Nennförderstrom bis 6 000 l/min fest.
Dieses Dokument behandelt sämtliche in Abschnitt 4 aufgeführten signifikanten Gefährdungen, Gefährdungssituationen
und -ereignisse bei Inbetriebnahme, Betrieb und Instandhaltung von Feuerlösch-kreiselpumpen
ohne Entlüftungseinrichtung, wenn sie bestimmungsgemäß und unter den vom Hersteller vorhersehbaren
Bedingungen eingesetzt werden.
Dieses Dokument behandelt nicht die detaillierte Feststellung der Übereinstimmung mit den allgemeinen und
Sicherheitsanforderungen und/oder Schutzmaßnahmen. Diese werden in EN 14710-2 „Feststellung der
Überei

Pompes à usage incendie - Pompes centrifuges à usage incendie sans dispositif d'amorçage - Partie 1: Classification, prescriptions générales et de sécurité

Le présent document s’applique aux pompes centrifuges à usage incendie sans dispositif d’amorçage,
utilisées comme :
— pompes flottantes (FPN-F) ;
— pompes immergées (FPN-S) ; ou
— pompes suralimentées (FPN-B).
Les pompes centrifuges à usage incendie sans dispositif d’amorçage sont définies comme étant terminées par leurs
orifices d’entrée et de sortie ainsi que par leurs extrémités d’axe.
Le présent document s’applique aux pompes centrifuges à usage incendie sans dispositif d’amorçage pour une utilisation
à une température ambiante pouvant varier entre – 15 °C et + 40 °C.
NOTE 1 Pour les conditions spéciales à – 30 °C, voir 6.11.
Le présent document ne s’applique pas aux pompes centrifuges à usage incendie sans dispositif d’amorçage pour
lesquelles la seule source d’énergie est la force humaine employée directement.
Le présent document ne s’applique pas aux pompes centrifuges à usage incendie sans dispositif d’amorçage
destinées à être utilisées comme équipement interchangeable (c'est-à-dire, combiné par l'utilisateur avec une autre
machine ou un véhicule agissant comme actionneur).
Le présent document ne s’applique pas aux pompes centrifuges à usage incendie sans dispositif d’amorçage ayant
une pression nominale de refoulement pN supérieure à 15 bar.
NOTE 2 Les pompes haute pression avec dispositif d'amorçage font l’objet de la norme EN 1028-1 et EN 1028-2.
Le présent document spécifie la classification et les prescriptions générales relatives aux pompes centrifuges à usage
incendie sans dispositif d’amorçage d’un débit nominal de refoulement pouvant aller jusqu'à 6 000 l/min.
Le présent document traite des phénomènes dangereux significatifs listés à l’Article 4, des situations et des
événements dangereux pendant la mise en service, le fonctionnement et l’entretien des pompes centrifuges à usage
d’incendie sans dispositif d’amorçage, quand elles sont utilisées comme prévu et, dans les conditions prévues par le
fabricant.

Gasilske črpalke - Gasilske centrifugalne črpalke brez sesalne naprave - 1. del: Klasifikacija, splošne in varnostne zahteve

General Information

Status
Withdrawn
Publication Date
08-Jul-2008
Withdrawal Date
16-Dec-2008
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
17-Dec-2008
Completion Date
17-Dec-2008

Relations

Buy Standard

Standard
EN 14710-1:2005+A1:2008
English language
29 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2008
*DVLOVNHþUSDONH*DVLOVNHFHQWULIXJDOQHþUSDONHEUH]VHVDOQHQDSUDYHGHO
.ODVLILNDFLMDVSORãQHLQYDUQRVWQH]DKWHYH
Fire-fighting pumps - Fire-fighting centrifugal pumps without primer - Part 1:
Classification, general and safety requirements
Feuerlöschpumpen - Feuerlöschkreiselpumpen ohne Entlüftungseinrichtung - Teil 1:
Klassifizierung, allgemeine Anforderungen und Sicherheitsanforderungen
Pompes à usage incendie - Pompes centrifuges à usage incendie sans dispositif
d'amorçage - Partie 1: Classification, prescriptions générales et de sécurité
Ta slovenski standard je istoveten z: EN 14710-1:2005+A1:2008
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 14710-1:2005+A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2008
ICS 13.220.10 Supersedes EN 14710-1:2005
English Version
Fire-fighting pumps - Fire-fighting centrifugal pumps without
primer - Part 1: Classification, general and safety requirements
Pompes à usage incendie - Pompes centrifuges à usage Feuerlöschpumpen - Feuerlöschkreiselpumpen ohne
incendie sans dispositif d'amorçage - Partie 1: Entlüftungseinrichtung - Teil 1: Klassifizierung, allgemeine
Classification, prescriptions générales et de sécurité Anforderungen und Sicherheitsanforderungen
This European Standard was approved by CEN on 17 December 2004 and includes Amendment 1 approved by CEN on 6 June 2008.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14710-1:2005+A1:2008: E
worldwide for CEN national Members.

Contents
Page
Foreword.3
0 Introduction.4
1 Scope .5
2 Normative references .6
3 Terms and definitions .7
4 List of significant hazards .12
5 Safety requirements and/or protective measures.14
6 General and performance requirements .17
7 Verification of the safety requirements and/or protective measures.18
8 Verification of the general and performance requirements .18
9 Classification and brief designation.19
10 Designation .21
11 Information for use .21
Annex ZA (informative) Relationship between this European Standard and the Essential
Requirements of EU Directive 98/37/EC .27
Annex ZB (informative) !!!!Relationship between this European Standard and the Essential
Requirements of EU Directive 2006/42/EC"""".28
Bibliography .29

Figures
Figure 1 — Characteristic curve for the pressure in the outlet section p (principle) . 10
a
Figure 2 — General warning sign ISO 7010-W001 . 22

Tables
Table 1 — List of significant hazards. 13
Table 2 — Fire-fighting centrifugal pumps with nominal delivery pressures of 6 bar. 20
Table 3 — Fire-fighting centrifugal pumps with nominal delivery pressures of 10 bar. 20
Table 4 — Fire-fighting centrifugal pumps with nominal delivery pressures of 15 bar. 20

Foreword
This document (EN 14710-1:2005+A1:2008) has been prepared by Technical Committee CEN/TC 192 “Fire
service equipment”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by January 2009, and conflicting national standards shall be withdrawn at
the latest by January 2009.
This document includes Amendment 1, approved by CEN on 2008-06-06.
This document supersedes EN 14710-1:2005.
The start and finish of text introduced or altered by amendment is indicated in the text by tags ! ".
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
!For relationship with EU Directive(s), see informative Annexes ZA and ZB, which are integral parts of this
document."
This document is intended to be used in conjunction with part 2 of EN 14710 “Verification of general and
safety requirements”.
EN 14710 "Fire-fighting pumps – Fire-fighting centrifugal pumps without primer" comprises two parts:
 Part 1: Classification, general and safety requirements;
 Part 2: Verification of general and safety requirements.
For relationship with EN 1028 see EN 14710-2:2005, 4.1.
This document includes a Bibliography.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and United Kingdom.
0 Introduction
This document is a type C standard as stated in EN ISO 12100-1.
The machinery concerned and the extent to which hazards, hazardous situations and events are covered are
indicated in the scope of this document.
Where provisions of this type C standard are different from those which are stated in type A or B standards, the
provisions of this type C standard take precedence over the provisions of the other standards, for machines that
have been designed and built in accordance with the provisions of this type C standard.
While producing this document it was assumed that:
a) only trained persons operate the machine;
b) the original characteristics are maintained provided components are kept in good repair and working
order.
1 Scope
This document applies to centrifugal pumps without priming devices for fire-fighting use designed as
 floating pumps (FPN-F),
 submersible pumps (FPN-S) or
 boosted pumps (FPN-B).
Fire-fighting centrifugal pumps without primer are defined as terminated by their inlet and outlet connections as
well as by their shaft ends.
This document applies for fire-fighting centrifugal pumps without priming devices for use under ambient
temperatures between -15 °C and 40 °C.
NOTE 1 For special conditions, -30 °C; see 6.11.
This document does not apply to fire-fighting centrifugal pumps without primer of which the only power source is
directly applied manual effort.
This document does not apply to fire-fighting centrifugal pumps without primer, intended to be used as
interchangeable equipment (i.e. combined by the user with another machine or vehicle acting as a driver).
This document does not apply to fire-fighting centrifugal pumps without primer with a nominal delivery
pressure p above 15 bar.
N
NOTE 2 High pressure pumps with primer are dealt with in EN 1028-1 and EN 1028-2.
This document specifies the classification and general requirements for fire-fighting centrifugal pumps without
priming devices with a nominal delivery rate of up to 6 000 l/min.
This document deals with significant hazards listed in Clause 4, hazardous situations and events during the
commissioning, operation and maintenance of fire-fighting centrifugal pumps without priming devices, used as
intended and under the conditions foreseen by the manufacturer.
This document does not deal with the detailed verification of general and safety requirements and/or protective
measures. These are covered in EN 14710-2 "Verification of general and safety requirements".
This document does not deal with noise.
This document does not deal with the technical safety requirements for the design or manufacture of drivers or of
additional equipment intended to be fitted to inlet and outlet connections. It does not cover risks directly arising
from means provided for the portability, transportability, and mobility of pump units during or between periods of
operation, or requirements for power transmission devices. In addition, this document does not cover:
 hazards occurring due to decommissioning;
 hazards during use due to a specific environment (e.g. traffic during use on public roads, potentially
explosive atmospheres).
This document does not apply to fire-fighting centrifugal pumps without primer that are manufactured before the
date of publication by CEN of this document.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 294, Safety of machinery — Safety distance to prevent danger zones being reached by the upper limbs.
EN 349, Safety of machinery — Minimum gaps to avoid crushing of parts of the human body.
EN 547-2, Safety of machinery — Human body measurements — Part 2: Principles for determining the
dimensions required for access openings.
EN 547-3, Safety of machinery — Human body measurements — Part 3: Anthropometric data.
EN 563, Safety of machinery — Temperatures of touchable surfaces — Ergonomics data to establish
temperature limit values for hot surfaces.
EN 842, Safety of machinery — Visual danger signals — General requirements, design and testing.
EN 894-1, Safety of machinery — Ergonomics requirements for the design of displays and control actuators —
Part 1: General principles for human interactions with displays and control actuators.
EN 894-2, Safety of machinery — Ergonomics requirements for the design of displays and control actuators —-
Part 2: Displays.
EN 894-3, Safety of machinery — Ergonomics requirements for the design of displays and control actuators —
Part 3: Control actuators.
EN 953, Safety of machinery — Guards — General requirements for the design and construction of fixed and
movable guards.
EN 1050:1996, Safety of machinery — Principles for risk assessment.
EN 13202, Ergonomics of the thermal environment — Temperatures of touchable hot surfaces — Guidance
for establishing surface temperature limit values in production standards with the aid of EN 563.
EN 14710-2:2005, Fire-fighting pumps — Fire-fighting centrifugal pumps without primer — Part 2: Verification
of general and safety requirements.
EN 60204-1:1997, Safety of machinery — Electrical equipment of machines — Part 1: General requirements
(IEC 60204-1:1997).
EN 60529, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989).
EN 61310-1, Safety of machinery — Indication, marking and actuation — Part 1: Requirements for visual,
auditory and tactile signals (IEC 61310-1:1995).
EN 61310-2, Safety of machinery — Indication, marking and actuation — Part 2: Requirements for marking
(IEC 61310-2:1995).
EN 62079, Preparation of instructions — Structuring, content and presentation (IEC 62079:2001).
EN ISO 5199, Technical specifications for centrifugal pumps — Class II (ISO 5199:2002).
EN ISO 9905, Technical specifications for centrifugal pumps — Class I (ISO 9905:1994).
EN ISO 9908, Tec
...