EN 13782:2026
(Main)Temporary structure - Tents - Safety
- Abstract
This document specifies safety requirements which need to be observed at design, calculation, manufacture, installation, maintenance, of mobile, temporary installed tents with more than 50 m2 ground area.
This document applies also to multiple small tents which are normally not covered by this document and will be installed close together and exceed 50 m2 in sum.
NOTE Information is given in Annex C on examination and approval.
- Status
- Not Published
- Publication Date
- 17-Nov-2026
- Technical Committee
- CEN/TC 152 - Fairground and amusement park machinery and structures - Safety
- Drafting Committee
- CEN/TC 152/WG 2 - Tents
- Current Stage
- 6060 - Definitive text made available (DAV) - Publishing
- Start Date
- 18-Nov-2026
- Due Date
- 28-Sep-2026
- Completion Date
- 28-Sep-2026
EN 13782:2026 is a CEN European Standard for the safety of temporary structure tents. It specifies safety requirements for the design, calculation, manufacture, installation and maintenance of mobile, temporary installed tents with more than 50 m² ground area. It also applies to multiple small tents installed close together when their combined area exceeds 50 m².
What does EN 13782:2026 specify?
EN 13782:2026 specifies the safety requirements for tents used as temporary structures, including the information needed for examination and approval. It is organized as a full design-and-operation standard, not just a calculation method.
The scope covers tents that are mobile and temporarily installed. It also covers sets of smaller tents when they are arranged close together and function as one larger occupied area. Annex C gives information on examination and approval.
The document is arranged into Clauses 1 to 12 and Annexes A to E.
| Annex | What it covers |
|---|---|
| Annex A | Normative use of anti-slip mats |
| Annex B | Informative special design and manufacture criteria and operation |
| Annex C | Informative examination and approval |
| Annex D | Normative tents with extended setup duration |
| Annex E | Informative examples of design methodology for closed double curved Big top tents, non-circular Circus tents and pole tents |
What are the key requirements of EN 13782:2026?
EN 13782:2026 requires the tent to be designed, checked and documented as a complete structure, with loads, materials, stability, anchorage and operating procedures all treated together. In practice, this means the designer and operator need a full technical file, not only a strength calculation.
Clause 4 - design documents, construction description and drawings
The standard requires design documents that support verification of stability, resistance and operating safety, including the construction and operation description, stability verification and drawings. All possible configurations of the tent have to be covered, so the design must match how the tent is actually used.Clause 5 - material selection and covering materials
Structural materials need design data in European Standards, or proof that they are serviceable. Covering materials, welded or sewn joints, zips and adhesives must meet the relevant EN standards or be tested for strength and durability. This matters because the cover and its connections are part of the load path, not just weather protection.Clause 6 - numerical analysis and verification
The standard calls for verification according to the relevant Eurocode parts and requires checks for limit states, stability, deformation and overturning, sliding and lifting. If calculations are not enough for an assembly, testing by an independent body may be used instead. That gives designers a route for complex tents that cannot be proven by calculation alone.Clause 7 - design actions and load combinations
EN 13782:2026 covers permanent actions, an equivalent roof load, live loads, wind, snow and seismic forces, plus load combinations. Wind loading follows EN 1991-1-4 with tent-specific conditions, while snow can be omitted only when the tent is designed or operated so that snow cannot accumulate. For users, this means the local site and the planned operating season directly affect the design load case.Clause 8 - stability, equilibrium and membrane behaviour
The standard requires checks against overturning, sliding and lifting, with specific treatment of wind bracing, cladding forces, pre-stressing and post-tensioning. It also separates the verification of technical textiles and welded connections. This is important because a tent can fail through instability even when individual members are strong enough.Clause 9 - ground anchorages and on-site testing
Weight anchors and rod anchors are treated separately, and the standard includes calculation methods and test loadings on site. Ground conditions, soil type and anchor spacing matter to the final capacity. In practice, installers need site-specific evidence that the anchorage can resist the design loads.Clause 10 - other structural components
The standard covers ropes, chains, ratchets and similar components that affect public safety. Their design resistance must come from the relevant Eurocodes or standards, or from minimum breaking load with partial safety factors. Open hooks are not allowed in bracings, so rigging choices are controlled.Clause 11, Annex A and Annex D - manufacture, anti-slip mats and extended setup duration
Manufacture must be carried out by competent persons, with inspection of components and materials, and the load-bearing structure has to follow the EN 1090 series. Annex A sets conditions for using anti-slip mats, including surface condition and discard criteria. Annex D adds extra inspection and site requirements for tents used for an extended setup duration.
What terms does EN 13782:2026 define?
EN 13782:2026 defines the main tent types and the approval and maintenance terms used throughout the standard.
- tent - a mobile, temporarily installed structure enclosed with covers such as textiles or foils, or partly with rigid elements.
- tent with primary load-bearing structure - a tent whose load-bearing structure supports enclosing elements such as roofs, frameworks or post-and-beam systems.
- membrane tent - a tent with a pre-stressed textile load-bearing structure of double-curved shape, supported by masts or cables.
- pole tent - a tent with centre poles where guying stabilizes the fabric covering.
- initial approval - the design review, verification, examination and testing needed before a tent can be put into operation.
- modification - any change that departs from the original design specification.
- repair - restoration of worn, damaged or decayed parts back to the original design specification.
- maintenance - inspection and replacement of components as necessary.
Who uses EN 13782:2026?
EN 13782:2026 is used by tent designers, structural engineers, manufacturers, installers, maintenance teams, inspection bodies and operators. It is also relevant to safety managers, event organisers, venue owners and buyers who need to specify or check the technical basis for a tent system.
In practice, these users apply the standard when they design load-bearing parts, choose fabrics and ropes, verify anchors, prepare installation documents, carry out inspections and manage periodic examinations. It is especially useful where the tent will be occupied by the public and where wind, snow or ground conditions must be assessed site by site.
What changed in EN 13782:2026 from the previous edition?
EN 13782:2026 supersedes EN 13782:2015. The foreword states these significant changes:
- the text was editorially revised and aligned with Eurocode spelling;
- normative references were updated;
- the new term anti-slip mat was added;
- the former Annex A was moved into 7.4.2.3.3;
- Table 3 was amended to include anti-slip mats;
- Clause 8.6 now distinguishes welded connections from non-welded connections;
- a new Annex A on anti-slip mats was added;
- a new Annex D on tents with extended setup duration was added;
- a new Annex E with design-method examples for Big top tents, Circus tents and pole tents was added.
Which standards are used with EN 13782:2026?
| Standard | What it contributes |
|---|---|
| ISO 2602 | Statistical treatment of test results and confidence intervals |
| EN 818-1 to EN 818-7 | Acceptance, use and maintenance information for short link chain and chain slings |
| EN ISO 1141 | Polyester fibre ropes |
| EN ISO 1346 | Polypropylene fibre ropes |
| EN ISO 1969 | Polyethylene fibre ropes |
| EN 1990 | Basis of structural and geotechnical design |
| EN 1991-1-1 | Densities, self-weight and imposed loads |
| EN 1991-1-2 | Actions on structures exposed to fire |
| EN 1991-1-3 | Snow loads |
| EN 1991-1-4 and EN 1991-1-4:2005/AC | Wind actions |
| EN 1991-1-5 | Thermal actions |
| EN 1991-1-6 | Actions during execution |
| EN 1991-1-7 | Accidental actions |
| EN 1991-1-9 | Atmospheric icing |
| EN 1991-2 | Traffic loads on bridges and other civil engineering works |
| EN 1991-3 | Actions induced by cranes and machinery |
| EN 1991-4 | Silos and tanks |
| EN 1997-1 | Geotechnical design rules |
| EN ISO 7010 | Registered safety signs used for marking escape routes and exits |
| EN 12385-1 to EN 12385-4 | Safety requirements and information for steel wire ropes |
| EN 15619 | Coated fabrics for tents and related structures |
| Execution of steel structures and aluminium structures | Manufacture of load-bearing steel and aluminium parts |
| VDI 2700 Part 15:2009 | Slip-inhibiting material used for anti-slip mats |
What does the EN 13782:2026 document contain?
EN 13782:2026 contains load tables, pressure coefficients, friction values, anchor design methods, connection classes and inspection procedures. It uses formulas for load combinations, resistance checks and rod-anchor capacity, so it is a working document for design and verification rather than a general description.
It also includes figures for wind loading on gable roofs, round tents and membrane structures, plus examples for Big top tents, Circus tents and pole tents in Annex E. Annex C gives the examination, approval, tent book and periodic inspection workflow, which supports certification and operational control.
The document is therefore used for design review, testing, approval, installation checks and ongoing inspection of temporary tents.
Relations
- Effective Date
- 26-Jun-2024
- Effective Date
- 22-Nov-2026
- Effective Date
- 22-Nov-2026
- Effective Date
- 28-Jan-2026
- Effective Date
- 28-Jan-2026
- Effective Date
- 28-Jan-2026
- Effective Date
- 28-Jan-2026
- Effective Date
- 28-Jan-2026
- Effective Date
- 28-Jan-2026
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

Aboma Certification B.V.
Specialized in construction, metal, and transport sectors.
Sponsored listings
Frequently Asked Questions
EN 13782:2026 is a standard published by the European Committee for Standardization (CEN). Its full title is "Temporary structure - Tents - Safety". This standard covers: This document specifies safety requirements which need to be observed at design, calculation, manufacture, installation, maintenance, of mobile, temporary installed tents with more than 50 m2 ground area. This document applies also to multiple small tents which are normally not covered by this document and will be installed close together and exceed 50 m2 in sum. NOTE Information is given in Annex C on examination and approval.
This document specifies safety requirements which need to be observed at design, calculation, manufacture, installation, maintenance, of mobile, temporary installed tents with more than 50 m2 ground area. This document applies also to multiple small tents which are normally not covered by this document and will be installed close together and exceed 50 m2 in sum. NOTE Information is given in Annex C on examination and approval.
EN 13782:2026 is classified under the following ICS (International Classification for Standards) categories: 91.040.99 - Other buildings. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 13782:2026 has the following relationships with other standards: It is inter standard links to EN 13782:2015, EN 15619:2008+A1:2010, EN 17879:2023, EN ISO 11970:2025, EN ISO 10855-3:2024, EN ISO 17635:2025, EN ISO 15614-5:2024, EN ISO 10855-1:2024, EN 13852-1:2025. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 13782:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 tent
- 3.1.1 tent with primary load-bearing structure
- 3.1.2 membrane tent
- 3.1.3 pole tent
- 3.2 initial approval
- 3.3 modification
- 3.4 repair
- 3.5 maintenance
- 3.6 anti-slip mat
- 4 General requirements for design, analysis and examination
- 4.1 Design documents
- 4.2 Description of construction and operation
- 4.3 Construction drawings
- 5 Selection of materials
- 5.1 General
- 5.2 Selection of covering materials
- 5.3 Joining of covering materials
- 6 Principles of numerical analysis
- 6.1 General
- 6.2 Verification
- 7 Design actions
- 7.1 General
- 7.2 Permanent actions
- 7.3 Equivalent load
- 7.4 Variable actions
- 7.5 Load combinations
- 8 Verification of stability and equilibrium
- 8.1 General
- 8.2 Verification against overturning, sliding and lifting
- 8.3 Dead load for tent covers
- 8.4 Structures with primary load-bearing structure
- 8.5 Membrane and pole tent
- 8.6 Verification of load-bearing capacity of technical textiles and their welded
- 8.7 Safety margin, safeguards
- 8.8 Post tensioning
- 9 Ground anchorages
- 9.1 General
- 9.2 Load-bearing capacity of weight anchors
- 9.3 Load-bearing capacity of rod anchors
- 9.4 Test loadings on site
- 9.5 Calculation of loading capacities
- 9.6 Further requirements
- 9.7 Ground support for packing
- 10 Other structural components
- 10.1 General
- 10.2 Design resistance
- 10.3 Synthetic fibre ropes
- 10.4 Ratchets
- 11 Manufacture and supply
- 11.1 General
- 11.2 Certificates
- 11.3 Observation of the design specification
- 11.4 Description of installation and operation procedures
- 12 Special design and manufacture criteria
- Annex A
- Annex B
- Annex C
- Annex D
- Annex E
- Bibliography
Introduction
The object of this document is to provide safety requirements for tents. The safety requirements are aimed to safe-guard persons and objects against damage caused by design, manufacturing and operation of these structures.
These guidelines have been drawn up according to past experience and risk analysis. Existing national rules concerning health and safety of workers remain untouched.
SIST EN 13782:2027 EN 13782:2026 (E)
1 Scope
This document specifies safety requirements for the design, calculation, manufacture, installation, and
maintenance of mobile, temporary installed tents with more than 50 m ground area.
This document also applies to multiple small tents installed close together and exceed 50 m in sum. NOTE Information is given in Annex C on examination and approval.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 2602, Statistical interpretation of test results — Estimation of the mean — Confidence interval EN 1990, Eurocode - Basis of structural and geotechnical design EN 1991-1-1, Eurocode 1: Actions on structures - Part 1-1: General actions - Densities, self-weight, imposed loads for buildings EN 1991-1-3, Eurocode 1 - Actions on structures - Part 1-3: General actions - Snow loads EN 1991-1-4, Eurocode 1: Actions on structures - Part 1-4: General actions - Wind actions EN 1997-1, Eurocode 7 - Geotechnical design - Part 1: General rules EN ISO 7010, Graphical symbols - Safety colours and safety signs - Registered safety signs (ISO 7010:2019, Corrected version 2020-06) EN 10204:2004, Metallic products - Types of inspection documents EN 12385-1, Steel wire ropes - Safety - Part 1: General requirements EN 12385-2, Steel wire ropes - Safety - Part 2: Definitions, designation and classification EN 12385-3, Steel wire ropes - Safety - Part 3: Information for use and maintenance EN 12385-4, Steel wire ropes - Safety - Part 4: Stranded ropes for general lifting applications EN 15619, Rubber or plastic coated fabrics - Safety of temporary structures (tents) - Specification for coated fabrics intended for tents and related structures EN 818 (all parts), Short link chain for lifting purposes - Safety EN 1090 (all parts), Execution of steel structures and aluminium structures VDI 2700 Part 15:2009, Securing of loads on road vehicles - Slip-inhibiting materials
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply. - ISO Online browsing platform: available at http://www.iso.org/obp - IEC Electropedia: available at http://www.electropedia.org/
SIST EN 13782:2027 EN 13782:2026 (E)
3.1 tent
mobile, temporary installed structure enclosed with covers (textiles, foils) or partly with rigid elements Note 1 to entry: It can be built as an enclosed or open building i.e. marquee, tent-hall, booth.
3.1.1 tent with primary load-bearing structure
load-bearing structure with enclosing elements EXAMPLE Structures with primary load-bearing structure can be roofs, frameworks, post-and-beam system.
3.1.2 membrane tent
tent (3.1) with a load-bearing pre-stressed textile structure with double curved shape, supported by masts and/or cables
3.1.3 pole tent
tent (3.1) with centre poles, where guying is used to stabilize the fabric covering
3.2 initial approval
design and calculation review, verification, examinations and tests necessary for tent (3.1) operation
3.3 modification
alteration of a tent (3.1) which results in a deviation from the original design specification
3.4 repair
restorations of worn, damaged or decayed parts back to the original design specification
3.5 maintenance
inspection and replacement of components as necessary
3.6 anti-slip mat
slip-inhibiting material with a specific friction coefficient of μ = 0,60 [SOURCE: Adapted from VDI 2700 Part 15:2009 [2]]
4 General requirements for design, analysis and examination
4.1 Design documents
The design documents shall include information for the verification of the stability, resistance and operating safety, especially a description of the construction and operation, the stability verification and design drawings as well as relevant documents concerning the burning behaviour. The documents shall include all the possible configurations of the tent.
4.2 Description of construction and operation
The tent (3.1), in particular its design, intended use and its static system shall be explained in this description.
The description shall include details of the particular features of the tent and of any alternative modes of installation, also details of the main dimensions, limitations, design particulars and materials.
SIST EN 13782:2027 EN 13782:2026 (E)
4.3 Construction drawings
Construction drawings shall exist for all sub-assemblies and individual components, the fracture or failure of which might endanger the stability or operating safety of the tent. The construction drawings shall feature all the dimensions and cross-section values required for testing and approval, also details of materials, structural components, fasteners and connectors. The construction plans shall comprise the following:
- general drawings in plan view, elevation and sections, to one of the following scales, i.e. 1:100, 1:50 or 1:20. If clearness and readability does not suffice other scales shall be used;
- detail drawings relating to all the structural sub-assemblies not clearly discernible on the general drawings, also detail plans of connections and of individual items of structural nature that are likely to affect the safety of the tent and of its operation, drawn to a larger scale.
5 Selection of materials
5.1 General
Structural components shall be manufactured from materials whose properties are specified in European Standards.
Other materials may only be used on condition that proof of their serviceability has been established. The designer shall give special consideration to structural joints which are to be welded and the weldability of the selected metals in accordance with European Standards.
5.2 Selection of covering materials
For rubber and plastic coated fabrics, EN 15619 shall be applied. The supplier certification shall be provided.
For other fabric materials and cladding elements of:
- cotton fabrics;
- synthetic fabrics;
- solid covering and sheeting such as sectional metal sheets, wood or plastic panels and multi components elements, the following requirements shall be regarded:
- fabric materials designated for structural use shall conform to EN standards or, in absence, to agreement by the parties involved;
- it shall be ensured that the material and the connections specified provides sufficient weathertightness, tensile strength to ensure safe and durable performance of the textile cover. The partial safety factors for structural use of fabrics shall be according to 8.6;
- standards for textile, membrane and inflatable structures.
5.3 Joining of covering materials
Joints by sewing, welding and by adhesives and zips shall conform to the relevant EN standards or shall be tested for their ultimate tear and shear properties. The ageing and environmental influences shall be taken into account by the application of additional partial safety factors.
SIST EN 13782:2027 EN 13782:2026 (E) Zips shall be tested for their strength to withstand the calculated loads of the structure. Effects of wearing out and influence of UV light on plastic shall be considered.
If suitable structural strength cannot be verified, they shall only be used in non-safety critical applications.
6 Principles of numerical analysis
6.1 General
If subsequently not determined differently, the verification shall follow the relevant part of the Eurocode and shall comprise:
st nd
limit states analysis (according to theory of 1 or 2 order); - stability limit states analysis, i.e. bar buckling, plate and shell buckling; - if required, verification of deformation limit states; - verification of safety against overturning, sliding and uplift.
6.2 Verification
The verification shall include the following details, amongst others:
- design loads, taking into account the possible operating conditions or installations alternatives. Special loads imposed during erection should be recognized;
- information concerning material and components;
- main dimensions and cross-section values of all load-bearing structural components;
- determination of the most unfavourable stresses and details relating to the strength of the loadbearing structural components and of the fasteners;
- if calculations are insufficient to evaluate limit states of assemblies the analysis may be substituted by testing at an independent testing body. There, the testing body shall commit the appropriate number of tests, samples, the testing procedure, the reporting etc., according to the relevant EN standards or in absence of the relevant EN standards by agreement with the parties involved;
- details of deformations (flexure, torsion), in as much as such details affect the serviceability or operating safety of the tent;
- details of those components which require special examination and inspection.
7 Design actions
7.1 General
All the applicable actions shall be taken into account according to EN 1991-1-1, EN 1991-1-3 and EN 1991-1-4.
Adaptations due to the specific use of tents are stated below.
7.2 Permanent actions
For tents a very precise assumption of the permanent actions is possible. As far as variation can occur the values G and G shall be taken into account for assessing the applicable structural response. k,sup k,inf Elsewhere a single characteristic value G is sufficient:
k
SIST EN 13782:2027 EN 13782:2026 (E) G characteristic value of permanent action; k G upper characteristic value of permanent action; k,sup G lower characteristic value of permanent action.
k,inf Included in the above category are the dead loads of the load-bearing structure, accessories, and technical equipment required for operation as well as claddings, decorations, and similar items. The influence of dry or wet material conditions shall be recognized (G , G ). k,sup k,inf
7.3 Equivalent load
The equivalent load is a vertical uniformly distributed load of q = 0,1 kN/m on the roof, which el considers additional structural effects. This load shall be applied on the primary structural components. This load shall only be combined with dead load (including pre-tension, if applicable). The equivalent load shall not be converted to a live load.
7.4 Variable actions
7.4.1 Live loads
7.4.1.1 Vertical loads for areas with universal, public access
The following vertical imposed loads shall be applied for:
- floors and their stairs, landings, ramps, entrances, exits and similar areas in facilities (tents, booths):
q = 3,50 kN/m ; k - raised floors, platforms and their stairs or, if particularly dense crowds are anticipated for the above mentioned category:
q = 5,00 kN/m ; k - stairs, an area load in accordance with the items above or:
Q = 1,00 kN per step in unfavourable position, whichever is more unfavourable; k - seat boards of rows of seats per seat run and for floors between fixed rows of seats, unless higher
loads results from the application of area loads (q = 3,5 kN/m ):
k q = 1,50 kN/m.
k
7.4.1.2 Vertical loads for areas not open for public access
The following vertical imposed loads shall be applied for:
- all floors, platforms, ramps, stairs, catwalks and the like which are walked over by individual persons, whatever is more unfavourable:
q = 1,50 kN/m k or Q = 1,50 kN individual load k
SIST EN 13782:2027 EN 13782:2026 (E)
7.4.1.3 Horizontal imposed loads
The following horizontal imposed loads shall be applied for parapets, fences, railings, wall panels etc.
When bounding floors with public access designed for q = 3,50 kN/m :
k - q = 0,50 kN/m at hand rail height; k - q = 0,10 kN/m at intermediate rail height.
k
When bounding floors with public access designed for q = 5,00 kN/m :
k - q = 1,00 kN/m at hand rail height; k - q = 0,15 kN/m at intermediate rail height.
k
When bounding floors without public access designed for q = 1,50 kN/m :
k - q = 0,30 kN/m at hand rail height; k - q = 0,10 kN/m at intermediate rail height.
k In order to achieve an adequate longitudinal and transverse stiffness in the case of raised floors and platforms in tents, a horizontal load acting at every floor level in the most unfavourable direction in each case simultaneously shall be entered in the calculation in addition to any eventual wind force in accordance with 7.4.2. This horizontal load component shall be taken as 1/20th of the vertical imposed load according to 7.4.1.1 and 7.4.1.2.
NOTE This horizontal component load (1/20th) does not consider structures subject to dynamic horizontal imposed loading due to synchronized movement.
7.4.2 Wind loads
7.4.2.1 General
The wind loads shall be based on EN 1991-1-4, assuming that the special nature of the textile covers is taken into account and regarding:
- location;
- duration and period of installation;
- use under supervision of an operator;
- possibilities of protecting and strengthening.
7.4.2.2 Minimum loads
For locations where the fundamental value of the basic wind velocity v > 28 m/s, calculations shall b,0 be provided for the tent verifying the stability and resistance with the local conditions. For the determination of the necessary peak velocity pressure q (z ) EN 1991-1-4 shall apply in conjunction p e with the requirements of the national annexes. The values obtained may be reduced by the factor 0,7. For locations where the fundamental value of the basic wind velocity v ≤ 28 m/s, the wind load per b,0 unit may be evaluated applying the following minimum values.
The wind pressure acting on the external surfaces, w , should be obtained from Formula (1) and applied e according to Figure 1:
w = q z ·c (1) e p e pe
SIST EN 13782:2027 EN 13782:2026 (E) where is the peak velocity pressure (as a function of the reference height for the external q z p e
pressure), in kN/m ; z is the reference height for the external pressure, in m; e c is the pressure coefficient for the external pressure.
pe Table 1 — Peak velocity pressure q (z ) p e Reference height Peak velocity pressure q (z ) z p e e
m kN/m z ≤ 5 0,50 e 5 < z ≤ 10 0,60 e 10 < z ≤ 15 0,66 e 15 < z ≤ 20 0,71 e 20 < z ≤ 25 0,76 e Contrary to the pressures specified in Table 1, a reduced peak velocity pressure of
may be applied to tents with a width of 10 m or less and a height of 5 m or less. q z = 0,30 kN/m p e Dimensions in metres Key z reference height for the external pressure e peak velocity pressure (as a function of the reference height for the external pressure) q z p e Figure 1 — Reference height z and the corresponding peak velocity pressure profile q (z ) e p e
7.4.2.3 Pressure coefficients
7.4.2.3.1 General In general, the pressure coefficients for various structures and structural members shall be taken from EN 1991-1-4. The c values given in Figure 2 and Figure 3 are for closed structures only. p 7.4.2.3.2 Gable roof structures On the basis of past experience with tents of conventional design, the aerodynamic pressure coefficient for gable roof structures of the type illustrated in Figure 2 may be determined with the aid of the external pressure coefficients, c , given there. The internal pressure coefficient, c , need not be taken into pe pi account for closed structures.
SIST EN 13782:2027 EN 13782:2026 (E) Key 1 direction of wind α angle of the roof pitch c external pressure coefficient pe Figure 2 — External pressure coefficient c for closed tents of gable roof shape pe 7.4.2.3.3 Closed tents of round shape For round shape tents of conventional design according to Figure 3 the pressure coefficients according to Figure 4 may be used.
NOTE In general, Figure 3 is used for standard circus tents.
Key 1 direction of wind φ peripheral angle α angle of the pitch (45° or 22° or 90° (wall)) Figure 3 — Round shape tent
SIST EN 13782:2027 EN 13782:2026 (E) Key c pressure coefficient p φ peripheral angle α angle of the pitch (45° or 22° or 90° (wall)) Figure 4 — Pressure coefficients c for round shape tents p The pressure coefficients, c , given in Figure 4 include a constant internal pressure coefficient, p c =‐0,25.
pi The pressure coefficient, c , may be limited to 1,0 for the transverse loading of the perimeter poles. p
7.4.2.4 Wind on the membrane load-bearing structure
The pressure coefficients may be taken according to EN 1991-1-4 [3], or to wind tunnel test. Wind tunnel testing shall be done by an experienced laboratory in accordance with EN 1990. Pressure coefficients are presented in Figure 5.
SIST EN 13782:2027 EN 13782:2026 (E) Key 1 upwards 2 downwards c pressure coefficient p Figure 5 — Pressure coefficient c p
7.4.3 Snow loads
Snow loads shall be applied in accordance with EN 1991-1-3.
Snow loads need not to be taken into account for tents:
- where by design snow settling on the tent is prevented; or
- erected in areas, where there is no likelihood of snow; or
- operated at a time of the year, where the likelihood of snow can be discounted; or
- where pre-planned operation action or operating conditions prevents snow from settling on the tent.
This last condition may be achieved by ensuring that:
- sufficient heating equipment is installed and is ready for use; and
- heating is started prior to snow fall; and
- tent is heated in such a way, that the whole roof cladding has an outside air temperature of more than +2 °C; and
- cladding is made and tensioned in such a way, that ponding of melt water or any other deformations of the cladding cannot take place.
If a snow height not exceeding 8 cm is ensured by removing snow, a reduced snow load for tents may
be applied with q = 0,20 kN/m on the overall roof area.
k
SIST EN 13782:2027 EN 13782:2026 (E)
7.4.4 Seismic forces
Seismic forces generally do not need to be considered because of the flexibility and the light weight of the tent.
7.5 Load combinations
Load combinations shall be applied in accordance with EN 1990. The design values of the actions may be simplified with the following combinations and partial safety factors:
γ G +γ Q G k Q,1 k,1 E = γ G +γ Q (2) G k Q,i k,i d γ G +γ Q G k Q,el k,el where E is the design value of effect of actions; d γ = 1,35 is the partial safety factor for unfavourable permanent actions; G γ = 1,00 is the partial safety factor for favourable permanent actions; G γ = 1,50 is the partial safety factor for only one variable action; Q,1 γ = 1,35 is the partial safety factor for more variable actions; Q,i γ = 1,35 is the partial safety factor for equivalent load; Q,el G is the characteristic value of permanent action; k Q is the characteristic value for only one of the variable actions; k,1 Q is the characteristic value for more variable actions; k,i Q is the characteristic value of vertical equivalent load according to 7.3. k,el
...