Abstract

This document specifies safety requirements which need to be observed at design, calculation, manufacture, installation, maintenance, of mobile, temporary installed tents with more than 50 m2 ground area.
This document applies also to multiple small tents which are normally not covered by this document and will be installed close together and exceed 50 m2 in sum.
NOTE   Information is given in Annex C on examination and approval.

Status
Published
Public Enquiry End Date
30-Jan-2026
Publication Date
22-Nov-2026
Technical Committee
I13 - Imaginarni 13
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
23-Nov-2026
Due Date
28-Jan-2027
Completion Date
23-Nov-2026

Buy Documents

Standard

SIST EN 13782:2027

English language (41 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 13782:2027 specifies safety requirements for mobile, temporary installed tents with more than 50 m2 ground area, and it also applies to multiple smaller tents that are installed close together and exceed 50 m2 in total. It is published by SIST and is intended for designers, manufacturers, installers, operators and inspection bodies that need to check whether a tent is safe to use.

What does SIST EN 13782:2027 specify?

SIST EN 13782:2027 sets the safety rules for tents from design through installation, maintenance and examination. The standard is organized into clauses 1 to 12 and Annexes A to E, so readers can move from the general scope to the detailed structural, material and inspection rules.

AnnexWhat it covers
AUse of anti-slip mats
BSpecial design and manufacture criteria and operation
CExamination and approval
DTents with extended setup duration
EExamples of design methodology for closed double curved Big top tents, non-circular Circus tents and pole tents

The scope is focused on temporary structures, not permanent buildings. Annex C is especially useful for anyone responsible for approval, because it explains how tents are examined before first use, after changes, and during periodic checks.

What are the key requirements of SIST EN 13782:2027?

SIST EN 13782:2027 puts the main burden on safe design documentation, correct material selection, structural verification and controlled inspection. In practice, it asks the designer and operator to show how the tent will stand up under normal use, weather actions and site conditions.

Design documents and drawings

Clause 4 requires a full set of design documents covering stability, resistance and operating safety. The documents must describe the construction and operation, show the structural system, and include drawings for all parts that could affect safety.

This matters because the tent must be checked as a complete system, including alternative installation arrangements and all relevant dimensions, materials and connectors.

Materials and textile joints

Clause 5 limits structural components to materials for which design data exist in European Standards, unless their serviceability is otherwise proven. For covering materials and joints, the standard points to appropriate EN requirements and asks for proof of weather tightness, tensile performance and durability.

This is important for buyers and manufacturers because the cover, seams, welds, zips and adhesives are treated as load-bearing or safety-relevant parts, not just finishing details.

Numerical analysis and verification

Clause 6 requires verification using the relevant Eurocode principles, including limit state checks, stability checks and, where needed, deformation checks. The design package must show the loads used, the properties of materials and components, the critical stresses and deformations, and any parts that need special inspection.

If calculations alone are not enough, testing by an independent body may be used instead. That gives a route for unusual designs, but it also means the evidence must be traceable and reviewable.

Actions on the structure

Clause 7 covers the loads to be considered: permanent actions, equivalent roof load, live loads, wind, snow and load combinations. The standard gives special rules for tents because their use and shape differ from ordinary buildings.

For example, it separates public-access areas from areas not open to the public, and it treats wind and snow in a way that reflects temporary use, supervision and the possibility of protecting or strengthening the tent. For engineering work, this is the core section that drives sizing of the frame, cladding and anchorage.

Stability, equilibrium and membrane structures

Clause 8 requires checks against overturning, sliding and lifting, and it sets rules for dead load, bracing, cladding forces, membrane tents and pole tents. It also requires verification of technical textiles and their welded or other textile connections.

This matters because many tent failures start at the interface between the fabric, the frame and the anchors. The clause also requires post-tensioning provisions where creep of the membrane must be compensated.

Ground anchorages and other components

Clause 9 deals with weight anchors, rod anchors, test loadings on site and calculation of load-bearing capacity. It also covers ground support for packing, which is relevant where ballast or packing blocks are used instead of direct anchorage.

Clause 10 covers other structural components such as synthetic fibre ropes, ratchets, chains and steel wire ropes, and it requires their resistance to be checked by standards, certificates or tests. This is the part to check when the tent uses cables, straps, turnbuckles or similar hardware.

Manufacture, supply and special cases

Clause 11 requires competent manufacture, quality control and certificates for key materials and components, and it expects the design specification to be reflected in the finished tent. Clause 12 directs readers to Annex B for special design and manufacture criteria.

Annex D adds extra rules for tents that stay erected for a longer period and need regular inspections. Annex A gives the conditions for anti-slip mats, and Annex E shows example design methods for specific tent shapes.

What terms does SIST EN 13782:2027 define?

SIST EN 13782:2027 defines several tent types and lifecycle terms that matter for design and inspection.

  • Tent - a mobile, temporary installed structure enclosed with covers such as textiles or foils, or partly with rigid elements.
  • Tent with primary load-bearing structure - a tent where a main structural frame carries the loads and the enclosing elements close the space.
  • Membrane tent - a tent with a pre-stressed textile load-bearing structure of double curved shape, supported by masts or cables.
  • Pole tent - a tent with centre poles and guying used to stabilize the fabric covering.
  • Initial approval - the review, verification, examination and tests needed before a tent is allowed into operation.
  • Modification - a change that departs from the original design specification.
  • Repair - restoration of worn, damaged or decayed parts back to the original design specification.
  • Maintenance - inspection and replacement of components as needed.

These terms are important because the standard treats different tent forms and life-cycle events differently, especially for inspection and approval.

Who uses SIST EN 13782:2027?

SIST EN 13782:2027 is used by the people who design, make, approve, install and inspect temporary tents. The document itself points to civil engineers, electrical experts, welding engineers, and material and test engineers as relevant specialists during design and examination.

It is also relevant to tent manufacturers, event and fairground operators, installers, inspection bodies, and buyers who need safety requirements for marquee-type structures, circus tents, booth structures and other temporary covered spaces. In practice, these users apply it when selecting materials, checking anchorage, reviewing calculations, planning escape routes, and preparing the tent book and inspection reports.

What changed in SIST EN 13782:2027 from the previous edition?

SIST EN 13782:2027 replaces EN 13782:2015. The European foreword states these changes from the previous edition:

  • editorial revision and alignment with Eurocode spelling
  • updated normative references
  • a new term for anti-slip mat
  • movement of former Annex A into the wind-load clause
  • amendment of the sliding safety table to include anti-slip mats
  • a clearer separation between welded and non-welded textile connections
  • a new normative annex on anti-slip mats
  • a new annex for tents with extended setup duration
  • a new annex with design methodology examples for Big top tents, Circus tents and pole tents

Which standards are used with SIST EN 13782:2027?

SIST EN 13782:2027 relies on several companion standards for structural design, materials and safety equipment.

  • EN 1990 - basis for structural and geotechnical design, used for verification principles and wind tunnel testing requirements.
  • EN 1991-1-1, EN 1991-1-3, EN 1991-1-4 - actions on structures for densities, snow and wind, used for the main load model.
  • EN 1997-1 - geotechnical design, used for soil-related checks and anchor support conditions.
  • EN 15619 - coated fabrics for tents, used for covering materials and textile connection classes.
  • EN 12385 series and EN 818 series - wire ropes and chain products, used where lifting or tie components are part of the tent system.
  • EN ISO 7010 - safety signs, used for marking emergency exits.
  • EN 10204 - inspection documents for metallic products, used for material certificates.
  • ISO 2602 - statistical evaluation of test results, used for textile and connection testing.
  • VDI 2700 Part 15:2009 - source for anti-slip mat properties and acceptance criteria.
  • EN 3 series - portable fire extinguishers, referenced in Annex B for fire protection equipment.

What does the SIST EN 13782:2027 document contain?

SIST EN 13782:2027 contains design rules, load cases, verification methods, material rules, anchor checks, manufacturing requirements and examination procedures for temporary tents. It includes tables for safety factors and friction values, figures for wind-pressure coefficients and rod-anchor geometry, and formulas for structural and anchor verification.

The document also contains practical procedures for approval and inspection, including the tent book, periodic thorough examination and installation examination. The annexes add applied guidance for anti-slip mats, escape routes, burning behaviour, heating, electrical equipment, fire extinguishers and example calculations for specific tent forms.

Relations

Effective Date
22-Nov-2026
Effective Date
22-Nov-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
26-Jun-2024

Buy Documents

Standard

SIST EN 13782:2027

English language (41 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Aboma Certification B.V.

Specialized in construction, metal, and transport sectors.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

SIST EN 13782:2027 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Temporary structure - Tents - Safety". This standard covers: This document specifies safety requirements which need to be observed at design, calculation, manufacture, installation, maintenance, of mobile, temporary installed tents with more than 50 m2 ground area. This document applies also to multiple small tents which are normally not covered by this document and will be installed close together and exceed 50 m2 in sum. NOTE Information is given in Annex C on examination and approval.

This document specifies safety requirements which need to be observed at design, calculation, manufacture, installation, maintenance, of mobile, temporary installed tents with more than 50 m2 ground area. This document applies also to multiple small tents which are normally not covered by this document and will be installed close together and exceed 50 m2 in sum. NOTE Information is given in Annex C on examination and approval.

SIST EN 13782:2027 is classified under the following ICS (International Classification for Standards) categories: 91.040.99 - Other buildings. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 13782:2027 has the following relationships with other standards: It is inter standard links to SIST EN 15619:2009+A1:2011, SIST EN 17879:2024, SIST EN ISO 17635:2025, SIST EN ISO 15614-5:2024, SIST EN ISO 10855-1:2025, SIST EN ISO 10855-3:2025, SIST EN 13852-1:2025, SIST EN ISO 11970:2026, SIST EN 13782:2015. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN 13782:2027 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
01-januar-2027
Začasne konstrukcije - Šotori - Varnost
Temporary structure - Tents - Safety
Fliegende Bauten - Zelte - Sicherheit
Structure temporaire - Tentes - Sécurité
Ta slovenski standard je istoveten z: EN 13782:2026
ICS:
91.040.99 Druge stavbe Other buildings
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 13782
EUROPEAN STANDARD
NORME EUROPÉENNE
November 2026
EUROPÄISCHE NORM
ICS 91.040.99 Supersedes EN 13782:2015
English Version
Temporary structure - Tents - Safety
Structure temporaire - Tentes - Sécurité Fliegende Bauten - Zelte - Sicherheit
This European Standard was approved by CEN on 11 October 2026.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2026 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13782:2026 E
worldwide for CEN national Members.

Contents Page
European foreword . 5
Introduction . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 7
4 General requirements for design, analysis and examination . 8
4.1 Design documents . 8
4.2 Description of construction and operation . 8
4.3 Construction drawings . 9
5 Selection of materials . 9
5.1 General . 9
5.2 Selection of covering materials . 9
5.3 Joining of covering materials . 9
6 Principles of numerical analysis . 10
6.1 General . 10
6.2 Verification . 10
7 Design actions . 10
7.1 General . 10
7.2 Permanent actions . 10
7.3 Equivalent load . 11
7.4 Variable actions . 11
7.4.1 Live loads . 11
7.4.2 Wind loads . 12
7.4.3 Snow loads . 16
7.4.4 Seismic forces . 17
7.5 Load combinations . 17
8 Verification of stability and equilibrium . 17
8.1 General . 17
8.2 Verification against overturning, sliding and lifting . 18
8.2.1 General . 18
8.2.2 Safety against overturning . 18
8.2.3 Safety against sliding . 19
8.2.4 Safety against lifting . 20
8.3 Dead load for tent covers . 20
8.4 Structures with primary load-bearing structure . 20
8.4.1 Ballast mountings for protection against wind loads . 20
8.4.2 Wind bracings . 20
8.4.3 Cladding forces on the structure due to wind . 21
8.5 Membrane and pole tent . 21
8.5.1 General . 21
8.5.2 Pre-stressing . 21
8.5.3 Design and construction details on membrane . 22
8.6 Verification of load-bearing capacity of technical textiles and their welded
connections . 22
8.6.1 General . 22
8.6.2 Load-bearing capacity of technical textiles and their welded connections . 22
8.6.3 Load-bearing capacity of other textile connections . 23
8.7 Safety margin, safeguards . 23
8.8 Post tensioning . 23
9 Ground anchorages . 23
9.1 General . 23
9.2 Load-bearing capacity of weight anchors . 24
9.3 Load-bearing capacity of rod anchors . 24
9.4 Test loadings on site . 26
9.5 Calculation of loading capacities . 27
9.6 Further requirements . 27
9.7 Ground support for packing . 28
10 Other structural components . 28
10.1 General . 28
10.2 Design resistance . 29
10.3 Synthetic fibre ropes . 29
10.4 Ratchets . 29
11 Manufacture and supply . 30
11.1 General . 30
11.2 Certificates . 30
11.3 Observation of the design specification . 30
11.4 Description of installation and operation procedures . 30
12 Special design and manufacture criteria . 30
Annex A (normative) Use of anti-slip mats . 31
A.1 General . 31
A.2 Discard maturity . 31
Annex B (informative) Special design and manufacture criteria and operation . 32
B.1 General . 32
B.2 Escape routes . 32
B.2.1 Common recommendations . 32
B.2.2 Design of emergency exits . 32
B.2.3 Layout of escape routes . 32
B.3 Stairs . 32
B.4 Burning behaviour . 33
B.5 Textile connection . 33
B.6 Heating and cooking systems . 33
B.7 Electrical equipment . 34
B.8 Fire extinguishers . 34
Annex C (informative) Examination and approval . 35
C.1 Examination . 35
C.1.1 General . 35
C.1.2 Qualification . 35
C.2 Procedures for examination, test and approval . 35
C.2.1 General . 35
C.2.2 Identification . 35
C.2.3 Initial approval of tents . 36
C.2.4 Inspection after repair, modification and accidents . 36
C.2.5 Report . 36
C.3 Tent book . 37
C.3.1 General . 37
C.3.2 Content . 37
C.4 Periodic thorough examination . 37
C.5 Installation examination . 37
C.5.1 General . 37
C.5.2 Extent of installation examination . 38
Annex D (normative) Tents with extended setup duration . 39
D.1 General . 39
D.2 Design method . 39
D.3 Requirements . 39
D.4 Regular inspections . 39
Annex E (informative) Examples of design methodology for closed double curved Big top
tents, circular Circus tents and pole tents . 40
E.1 Big top tents . 40
E.2 Double curved circular (Circus) tents . 40
E.3 Single curved pole tents . 40
Bibliography . 41
European foreword
This document (EN 13782:2026) has been prepared by Technical Committee CEN/TC 152 "Fairground
and amusement park machinery and structures - Safety", the secretariat of which is held by UNI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by May 2027, and conflicting national standards shall be
withdrawn at the latest by May 2027.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 13782:2015 [1] .
This document includes the following significant technical changes with respect to EN 13782:2015
[1] :
— the whole document was editorially revised and adjusted to the spelling of Eurocodes;
— Clause 2 updated;
— new term 3.6 "anti-slip mat" added;
— former Annex A has been moved to 7.4.2.3.3;
— Table 3 amended to include "anti-slip mats";
— In 8.6, a distinction is made between welded connections (8.6.2) and non-welded connections
(8.6.3);
— new Annex A on the use of anti-slip mats has been added;
— new Annex D on tents with extended setup durations has been added;
— new Annex E on examples of design methodology for closed double curved Big top tents, non-
circular Circus tents and pole tents has been added.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
The object of this document is to provide safety requirements for tents. The safety requirements are
aimed to safe-guard persons and objects against damage caused by design, manufacturing and operation
of these structures.
These guidelines have been drawn up according to past experience and risk analysis.
Existing national rules concerning health and safety of workers remain untouched.
1 Scope
This document specifies safety requirements for the design, calculation, manufacture, installation, and
maintenance of mobile, temporary installed tents with more than 50 m ground area.
This document also applies to multiple small tents installed close together and exceed 50 m in sum.
NOTE Information is given in Annex C on examination and approval.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
ISO 2602, Statistical interpretation of test results — Estimation of the mean — Confidence interval
EN 1990, Eurocode - Basis of structural and geotechnical design
EN 1991-1-1, Eurocode 1: Actions on structures - Part 1-1: General actions - Densities, self-weight, imposed
loads for buildings
EN 1991-1-3, Eurocode 1 - Actions on structures - Part 1-3: General actions - Snow loads
EN 1991-1-4, Eurocode 1: Actions on structures - Part 1-4: General actions - Wind actions
EN 1997-1, Eurocode 7 - Geotechnical design - Part 1: General rules
EN ISO 7010, Graphical symbols - Safety colours and safety signs - Registered safety signs (ISO 7010:2019,
Corrected version 2020-06)
EN 10204:2004, Metallic products - Types of inspection documents
EN 12385-1, Steel wire ropes - Safety - Part 1: General requirements
EN 12385-2, Steel wire ropes - Safety - Part 2: Definitions, designation and classification
EN 12385-3, Steel wire ropes - Safety - Part 3: Information for use and maintenance
EN 12385-4, Steel wire ropes - Safety - Part 4: Stranded ropes for general lifting applications
EN 15619, Rubber or plastic coated fabrics - Safety of temporary structures (tents) - Specification for
coated fabrics intended for tents and related structures
EN 818 (all parts), Short link chain for lifting purposes - Safety
EN 1090 (all parts), Execution of steel structures and aluminium structures
VDI 2700 Part 15:2009, Securing of loads on road vehicles - Slip-inhibiting materials
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
• ISO Online browsing platform: available at http://www.iso.org/obp
• IEC Electropedia: available at http://www.electropedia.org/
3.1
tent
mobile, temporary installed structure enclosed with covers (textiles, foils) or partly with rigid elements
Note 1 to entry: It can be built as an enclosed or open building i.e. marquee, tent-hall, booth.
3.1.1
tent with primary load-bearing structure
load-bearing structure with enclosing elements
EXAMPLE        Structures with primary load-bearing structure can be roofs, frameworks, post-and-beam system.
3.1.2
membrane tent
tent (3.1) with a load-bearing pre-stressed textile structure with double curved shape, supported by
masts and/or cables
3.1.3
pole tent
tent (3.1) with centre poles, where guying is used to stabilize the fabric covering
3.2
initial approval
design and calculation review, verification, examinations and tests necessary for tent (3.1) operation
3.3
modification
alteration of a tent (3.1) which results in a deviation from the original design specification
3.4
repair
restorations of worn, damaged or decayed parts back to the original design specification
3.5
maintenance
inspection and replacement of components as necessary
3.6
anti-slip mat
slip-inhibiting material with a specific friction coefficient of μ = 0,60
[SOURCE: Adapted from VDI 2700 Part 15:2009 [2]]
4 General requirements for design, analysis and examination
4.1 Design documents
The design documents shall include information for the verification of the stability, resistance and
operating safety, especially a description of the construction and operation, the stability verification
and design drawings as well as relevant documents concerning the burning behaviour.
The documents shall include all the possible configurations of the tent.
4.2 Description of construction and operation
The tent (3.1), in particular its design, intended use and its static system shall be explained in this
description.
The description shall include details of the particular features of the tent and of any alternative modes
of installation, also details of the main dimensions, limitations, design particulars and materials.
4.3 Construction drawings
Construction drawings shall exist for all sub-assemblies and individual components, the fracture or
failure of which might endanger the stability or operating safety of the tent.
The construction drawings shall feature all the dimensions and cross-section values required for testing
and approval, also details of materials, structural components, fasteners and connectors.
The construction plans shall comprise the following:
— general drawings in plan view, elevation and sections, to one of the following scales, i.e. 1:100, 1:50
or 1:20. If clearness and readability does not suffice other scales shall be used;
— detail drawings relating to all the structural sub-assemblies not clearly discernible on the general
drawings, also detail plans of connections and of individual items of structural nature that are likely
to affect the safety of the tent and of its operation, drawn to a larger scale.
5 Selection of materials
5.1 General
Structural components shall be manufactured from materials whose properties are specified in
European Standards.
Other materials may only be used on condition that proof of their serviceability has been established.
The designer shall give special consideration to structural joints which are to be welded and the
weldability of the selected metals in accordance with European Standards.
5.2 Selection of covering materials
For rubber and plastic coated fabrics, EN 15619 shall be applied. The supplier certification shall be
provided.
For other fabric materials and cladding elements of:
— cotton fabrics;
— synthetic fabrics;
— solid covering and sheeting such as sectional metal sheets, wood or plastic panels and multi
components elements,
the following requirements shall be regarded:
— fabric materials designated for structural use shall conform to EN standards or, in absence, to
agreement by the parties involved;
— it shall be ensured that the material and the connections specified provides sufficient weather-
tightness, tensile strength to ensure safe and durable performance of the textile cover. The partial
safety factors for structural use of fabrics shall be according to 8.6;
— standards for textile, membrane and inflatable structures.
5.3 Joining of covering materials
Joints by sewing, welding and by adhesives and zips shall conform to the relevant EN standards or shall
be tested for their ultimate tear and shear properties. The ageing and environmental influences shall
be taken into account by the application of additional partial safety factors.
Zips shall be tested for their strength to withstand the calculated loads of the structure. Effects of wearing
out and influence of UV light on plastic shall be considered.
If suitable structural strength cannot be verified, they shall only be used in non-safety critical
applications.
6 Principles of numerical analysis
6.1 General
If subsequently not determined differently, the verification shall follow the relevant part of the Eurocode
and shall comprise:
st nd
—
limit states analysis (according to theory of 1 or 2 order);
— stability limit states analysis, i.e. bar buckling, plate and shell buckling;
— if required, verification of deformation limit states;
— verification of safety against overturning, sliding and uplift.
6.2 Verification
The verification shall include the following details, amongst others:
— design loads, taking into account the possible operating conditions or installations alternatives.
Special loads imposed during erection should be recognized;
— information concerning material and components;
— main dimensions and cross-section values of all load-bearing structural components;
— determination of the most unfavourable stresses and details relating to the strength of the load-
bearing structural components and of the fasteners;
— if calculations are insufficient to evaluate limit states of assemblies the analysis may be substituted
by testing at an independent testing body. There, the testing body shall commit the appropriate
number of tests, samples, the testing procedure, the reporting etc., according to the relevant
EN standards or in absence of the relevant EN standards by agreement with the parties involved;
— details of deformations (flexure, torsion), in as much as such details affect the serviceability or
operating safety of the tent;
— details of those components which require special examination and inspection.
7 Design actions
7.1 General
All the applicable actions shall be taken into account according to EN 1991-1-1, EN 1991-1-3 and
EN 1991-1-4.
Adaptations due to the specific use of tents are stated below.
7.2 Permanent actions
For tents a very precise assumption of the permanent actions is possible. As far as variation can occur
the values G and G shall be taken into account for assessing the applicable structural response.
k,sup k,inf
Elsewhere a single characteristic value G is sufficient:
k
G characteristic value of permanent action;
k
G upper characteristic value of permanent action;
k,sup
G lower characteristic value of permanent action.
k,inf
Included in the above category are the dead loads of the load-bearing structure, accessories, and
technical equipment required for operation as well as claddings, decorations, and similar items. The
influence of dry or wet material conditions shall be recognized (G , G ).
k,sup k,inf
7.3 Equivalent load
The equivalent load is a vertical uniformly distributed load of q = 0,1   kN/m on the roof, which
el
considers additional structural effects. This load shall be applied on the primary structural components.
This load shall only be combined with dead load (including pre-tension, if applicable).
The equivalent load shall not be converted to a live load.
7.4 Variable actions
7.4.1 Live loads
7.4.1.1 Vertical loads for areas with universal, public access
The following vertical imposed loads shall be applied for:
— floors and their stairs, landings, ramps, entrances, exits and similar areas in facilities (tents,
booths):
q  = 3,50 kN/m ;
k
— raised floors, platforms and their stairs or, if particularly dense crowds are anticipated for the
above mentioned category:
q  = 5,00 kN/m ;
k
— stairs, an area load in accordance with the items above or:
Q  = 1,00 kN per step in unfavourable position, whichever is more unfavourable;
k
— seat boards of rows of seats per seat run and for floors between fixed rows of seats, unless higher
loads results from the application of area loads (q  = 3,5 kN/m ):
k
q = 1,50 kN/m.
k
7.4.1.2 Vertical loads for areas not open for public access
The following vertical imposed loads shall be applied for:
— all floors, platforms, ramps, stairs, catwalks and the like which are walked over by individual
persons, whatever is more unfavourable:
q  = 1,50 kN/m
k
or
Q  = 1,50 kN individual load
k
7.4.1.3 Horizontal imposed loads
The following horizontal imposed loads shall be applied for parapets, fences, railings, wall panels etc.
When bounding floors with public access designed for q  = 3,50 kN/m :
k
— q  = 0,50 kN/m at hand rail height;
k
— q  = 0,10 kN/m at intermediate rail height.
k
When bounding floors with public access designed for q  = 5,00 kN/m :
k
— q  = 1,00 kN/m at hand rail height;
k
— q  = 0,15 kN/m at intermediate rail height.
k
When bounding floors without public access designed for q  = 1,50 kN/m :
k
— q  = 0,30 kN/m at hand rail height;
k
— q  = 0,10 kN/m at intermediate rail height.
k
In order to achieve an adequate longitudinal and transverse stiffness in the case of raised floors and
platforms in tents, a horizontal load acting at every floor level in the most unfavourable direction in
each case simultaneously shall be entered in the calculation in addition to any eventual wind force in
accordance with 7.4.2. This horizontal load component shall be taken as 1/20th of the vertical imposed
load according to 7.4.1.1 and 7.4.1.2.
NOTE This horizontal component load (1/20th) does not consider structures subject to dynamic horizontal
imposed loading due to synchronized movement.
7.4.2 Wind loads
7.4.2.1 General
The wind loads shall be based on EN 1991-1-4, assuming that the special nature of the textile covers is
taken into account and regarding:
— location;
— duration and period of installation;
— use under supervision of an operator;
— possibilities of protecting and strengthening.
7.4.2.2 Minimum loads
For locations where the fundamental value of the basic wind velocity v > 28 m/s, calculations shall
b,0
be provided for the tent verifying the stability and resistance with the local conditions. For the
determination of the necessary peak velocity pressure q (z ) EN 1991-1-4 shall apply in conjunction
p e
with the requirements of the national annexes. The values obtained may be reduced by the factor 0,7.
For locations where the fundamental value of the basic wind velocity v  ≤ 28 m/s, the wind load per
b,0
unit may be evaluated applying the following minimum values.
The wind pressure acting on the external surfaces, w , should be obtained from Formula (1) and applied
e
according to Figure 1:
w = q z ·c
(1)
e p e pe
where
is the peak velocity pressure (as a function of the reference height for the external
q z
p e
pressure), in kN/m ;
z is the reference height for the external pressure, in m;
e
c is the pressure coefficient for the external pressure.
pe
Table 1 — Peak velocity pressure q (z )
p e
Reference height Peak velocity pressure
q (z )
z
p e
e
m
kN/m
z  ≤ 5 0,50
e
5 < z  ≤ 10 0,60
e
10 < z  ≤ 15 0,66
e
15 < z  ≤ 20 0,71
e
20 < z  ≤ 25 0,76
e
Contrary to the pressures specified in Table 1, a reduced peak velocity pressure of
may be applied to tents with a width of 10 m or less and a height of 5 m or less.
q z = 0,30   kN/m
p e
Dimensions in metres
Key
z reference height for the external pressure
e
peak velocity pressure (as a function of the reference height for the external pressure)
q z
p e
Figure 1 — Reference height z and the corresponding peak velocity pressure profile q (z )
e p e
7.4.2.3 Pressure coefficients
7.4.2.3.1 General
In general, the pressure coefficients for various structures and structural members shall be taken from
EN 1991-1-4. The c values given in Figure 2 and Figure 3 are for closed structures only.
p
7.4.2.3.2 Gable roof structures
On the basis of past experience with tents of conventional design, the aerodynamic pressure coefficient
for gable roof structures of the type illustrated in Figure 2 may be determined with the aid of the external
pressure coefficients, c , given there. The internal pressure coefficient, c , need not be taken into
pe pi
account for closed structures.
Key
1 direction of wind
α angle of the roof pitch
c external pressure coefficient
pe
Figure 2 — External pressure coefficient c for closed tents of gable roof shape
pe
7.4.2.3.3 Closed tents of round shape
For round shape tents of conventional design according to Figure 3 the pressure coefficients according
to Figure 4 may be used.
NOTE In general, Figure 3 is used for standard circus tents.
Key
1 direction of wind
φ peripheral angle
α angle of the pitch (45° or 22° or 90° (wall))
Figure 3 — Round shape tent
Key
c pressure coefficient
p
φ peripheral angle
α angle of the pitch (45° or 22° or 90° (wall))
Figure 4 — Pressure coefficients c for round shape tents
p
The pressure coefficients, c , given in Figure 4 include a constant internal pressure coefficient,
p
c =‐0,25.
pi
The pressure coefficient, c , may be limited to 1,0 for the transverse loading of the perimeter poles.
p
7.4.2.4 Wind on the membrane load-bearing structure
The pressure coefficients may be taken according to EN 1991-1-4 [3], or to wind tunnel test.
Wind tunnel testing shall be done by an experienced laboratory in accordance with EN 1990.
Pressure coefficients are presented in Figure 5.
Key
1 upwards
2 downwards
c pressure coefficient
p
Figure 5 — Pressure coefficient c
p
7.4.3 Snow loads
Snow loads shall be applied in accordance with EN 1991-1-3.
Snow loads need not to be taken into account for tents:
— where by design snow settling on the tent is prevented; or
— erected in areas, where there is no likelihood of snow; or
— operated at a time of the year, where the likelihood of snow can be discounted; or
— where pre-planned operation action or operating conditions prevents snow from settling on the
tent.
This last condition may be achieved by ensuring that:
— sufficient heating equipment is installed and is ready for use; and
— heating is started prior to snow fall; and
— tent is heated in such a way, that the whole roof cladding has an outside air temperature of more
than +2 °C; and
— cladding is made and tensioned in such a way, that ponding of melt water or any other deformations
of the cladding cannot take place.
If a snow height not exceeding 8 cm is ensured by removing snow, a reduced snow load for tents may
be applied with q  = 0,20 kN/m on the overall roof area.
k
7.4.4 Seismic forces
Seismic forces generally do not need to be considered because of the flexibility and the light weight of
the tent.
7.5 Load combinations
Load combinations shall be applied in accordance with EN 1990.
The design values of the actions may be simplified with the following combinations and partial safety
factors:
γ G +γ Q
G k Q,1 k,1
E = γ G +γ Q  (2)
G k Q,i k,i
d
γ G +γ Q
G k Q,el k,el
where
E is the design value of effect of actions;
d
γ  = 1,35 is the partial safety factor for unfavourable permanent actions;
G
γ  = 1,00 is the partial safety factor for favourable permanent actions;
G
γ  = 1,50 is the partial safety factor for only one variable action;
Q,1
γ  = 1,35 is the partial safety factor for more variable actions;
Q,i
γ  = 1,35 is the partial safety factor for equivalent load;
Q,el
G is the characteristic value of permanent action;
k
Q is the characteristic value for only one of the variable actions;
k,1
Q is the characteristic value for more variable actions;
k,i
Q is the characteristic value of vertical equivalent load according to 7.3.
k,el
8 Verification of stability and equilibrium
8.1 General
The limit states due to all different actions shall be determined separately for the individual actions of
Clause 7. The limit states due to the combinations of actions shall be calculated. It shall be verified that
the design value of internal forces or moments does not exceed the corresponding design resistance of
the respective part and the ultimate or serviceability limit state is not exceeded.
Special consideration shall be given to the limit state verification regarding deformation and stability,
nd
as the deformation limit can be a decisive value. Any favourable effect resulting from the 2 order theory
may be taken into account.
All verifications shall be performed for the most unfavourable loading. In this connection, the
permanent, variable and accidental actions shall always be assumed to have the position and magnitude
which result in the most unfavourable limit states for the structural and mechanical components to be
calculated. For structural and mechanical components and items of equipment which are not permanent
fixtures, it shall also be ascertained whether more unfavourable conditions are likely to arise when such
items are displaced or removed.
Non-standard formula shall be recorded in writing with the symbols in accordance with European
Standards or International Standards. The sources of such formula shall be stated, if this source is
accessible to everyone. In other cases, the derivation of the formula shall be presented to such an extent
that their correctness can be verified.
If computer processing for calculation is used, special consideration shall be given to the requirements
for the review of computer calculations during the design approval. Clear information concerning the
software, formula, units etc. shall be submitted. Input and output data shall be thoroughly documented.
The correctness of the input assumptions and the output shall be comprehensively reviewed during
design approval.
The design value of the resistance, R , shall be evaluated in accordance with Formula (3):
d
R
k
R =  (3)
d
γ
M
where
R is the characteristic value of the resistance;
k
γ is the partial safety factor for a material property.
M
The values stated in the respective European Standard shall be taken into account.
8.2 Verification against overturning, sliding and lifting
8.2.1 General
Safety against overturning, sliding and lifting shall be calculated.
Favourably acting permanent actions shall be taken into account with their lower value only.
If sufficient safety cannot be guaranteed by virtue of the dead load of a structure alone, then further
additional steps shall be taken to ensure it, such as counterweights, anchorages and buttresses for
example.
As the weight of tents can be determined accurately, the following minimum partial safety factors shall
be applied:
Table 2 — Partial safety factor γ against overturning, sliding and lifting
Loading γ
1 favourably acting proportions of the 1,0
dead load
2 unfavourably acting proportions of 1,1
the dead load
3 unfavourably acting wind loads 1,2
4 unfavourably acting proportions of 1,3
loads other than the loads listed in
items 2 and 3
8.2
...