Explosive atmospheres - Part 14: Electrical installations design, selection and erection

This part of IEC 60079 contains the specific requirements for the design, selection and erection of electrical installations in hazardous areas associated with explosive atmospheres. Where the equipment is required to meet other environmental conditions, for example, protection against ingress of water and resistance to corrosion, additional methods of protection may be necessary. The method used should not adversely affect the integrity of the enclosure. The requirements of this standard apply only to the use of equipment under normal or near normal atmospheric conditions. The significant technical changes with respect to the previous edition are: Equipment Protection Levels (EPLs) have been introduced and are explained in the new Annex I and dust requirements included from IEC 61241 14, Ed. 1.0.

Explosionsfähige Atmosphäre - Teil 14: Projektierung, Auswahl und Errichtung elektrischer Anlagen

Atmosphères explosives - Partie 14: Conception, sélection et construction des installations électriques

La présente partie de la CEI 60079 établit les exigences particulières de conception, de sélection et de montage applicables aux installations électriques situées dans des emplacements dangereux en relation avec des atmosphères explosives. Lorsqu'il est exigé que le matériel soit conforme à d'autres conditions environnementales, par exemple la protection contre la pénétration de l'eau et la résistance à la corrosion, des méthodes complémentaires de protection peuvent être nécessaires. Il convient que la méthode utilisée ne dégrade pas l'intégrité de l'enveloppe. Les exigences de la présente norme s'appliquent uniquement à l'utilisation de matériels dans des conditions atmosphériques normales ou proches de la normale. Les modifications techniques significatives par rapport à l'édition précédente sont les suivantes: Les niveaux de protection de matériel (EPLs pour ' Equipment Protection Levels ') ont été introduits et ils sont expliqués dans une nouvelle Annexe I et les exigences pour les poussières issues de la CEI 61241-14, ed 1.0.

Eksplozivne atmosfere - 14. del: Načrtovanje, izbira in namestitev električnih inštalacij (IEC 60079-14:2007)

General Information

Status
Withdrawn
Publication Date
30-Oct-2008
Withdrawal Date
30-Jun-2011
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
02-Jan-2017
Completion Date
02-Jan-2017

Relations

Buy Standard

Standard
EN 60079-14:2009
English language
100 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Explosionsfähige Atmosphäre -- Teil 14: Projektierung, Auswahl und Errichtung elektrischer AnlagenAtmosphères explosives -- Partie 14: Conception, sélection et construction des installations électriquesExplosive atmospheres -- Part 14: Electrical installations design, selection and erection91.140.50Sistemi za oskrbo z elektrikoElectricity supply systems29.260.20Electrical apparatus for explosive atmospheresICS:Ta slovenski standard je istoveten z:EN 60079-14:2008SIST EN 60079-14:2009en,fr,de01-januar-2009SIST EN 60079-14:2009SLOVENSKI
STANDARDSIST EN 61241-14:2005SIST EN 60079-14:20031DGRPHãþD

EUROPEAN STANDARD EN 60079-14 NORME EUROPÉENNE
EUROPÄISCHE NORM October 2008
CENELEC European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2008 CENELEC -
All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60079-14:2008 E
ICS 29.260.20 Supersedes EN 60079-14:2003
English version
Explosive atmospheres -
Part 14: Electrical installations design,
selection and erection (IEC 60079-14:2007)
Atmosphères explosives -
Partie 14: Conception,
sélection et construction
des installations électriques (CEI 60079-14:2007)
Explosionsfähige Atmosphäre -
Teil 14: Projektierung,
Auswahl und Errichtung
elektrischer Anlagen (IEC 60079-14:2007)
This European Standard was approved by CENELEC on 2008-07-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom.
2008-07-01. This European Standard supersedes EN 60079-14:2003. It constitutes a technical revision with respect to gases and vapours and incorporates the requirements for dusts from EN 61241-14:2004. The incorporation of requirements for dust is without technical change. The significant technical changes with respect to EN 60079-14:2003 are as follows: – knowledge, skills and competencies of "Responsible Persons”, “Operatives" and "Designers" are explained in Annex F; – Equipment Protection Levels (EPLs) have been introduced and are explained in the new Annex I; – dust requirements included from EN 61241-14:2004. NOTE Dust requirements are included as an interim presentation for the purpose of EN 60079-14:2008 and will be refined in a next edition with other required technical changes. The following dates were fixed: – latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement
(dop)
2009-05-01 – latest date by which the national standards conflicting
with the EN have to be withdrawn
(dow)
2011-07-01 Annexes ZA and ZB have been added by CENELEC. __________ Endorsement notice The text of the International Standard IEC 60079-14:2007 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following notes have to be added for the standards indicated: IEC/TS 60034-17 NOTE Harmonized as CLC/TS 60034-17:2004 (not modified).IEC/TS 60034-25 NOTE Harmonized as CLC/TS 60034-25:2005 (not modified).IEC 60332-2-2 NOTE Harmonized as EN 60332-2-2:2004 (not modified) IEC 60742 NOTE Harmonized as EN 60742:1995 (modified).
Superseded by EN 61558 series (partially modified) IEC 61008-1 NOTE Harmonized as EN 61008-1:2004 (modified) IEC 61010-1 NOTE Harmonized as EN 61010-1:2001 (not modified) IEC 61024-1 NOTE Superseded by IEC 62305-3, which is harmonized as EN 62305-3:2006 (modified) __________
– 3 – EN 60079-14:2008
Annex ZA
(normative)
Normative references to international publications with their corresponding European publications
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
NOTE
When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies.
Publication Year Title EN/HD Year
IEC 60034-1 – 1) Rotating electrical machines -
Part 1: Rating and performance EN 60034-1 2004 2)
IEC 60034-5
– 1) Rotating electrical machines -
Part 5: Degrees of protection provided by the integral design of rotating electrical machines (IP code) - Classification EN 60034-5 2001 2)
IEC 60050-826 – 1) International Electrotechnical Vocabulary (IEV) -
Part 826: Electrical installations – –
IEC 60060-1 – 1) High-voltage test techniques - Part 1: General definitions and test requirements HD 588.1 S1 1991 2)
IEC 60079 Series Explosive atmospheres
EN 60079 Series
IEC 60079-0 (mod) – 1) Explosive atmospheres -
Part 0: Equipment – General requirements EN 60079-0 2006 2)
IEC 60079-1 – 1) Explosive atmospheres -
Part 1: Equipment protection by flameproof enclosures "d" EN 60079-1 2007 2)
IEC 60079-2 – 1) Explosive atmospheres -
Part 2: Equipment protection by pressurized enclosure "p"
EN 60079-2 2007 2)
IEC 60079-5 – 1) Explosive atmospheres -
Part 5: Equipment protection by powder filling "q" EN 60079-5 2007 2)
IEC 60079-6 – 1) Explosive atmospheres -
Part 6: Equipment protection by oil immersion "o" EN 60079-6 2007 2)
IEC 60079-7 – 1) Explosive atmospheres -
Part 7: Equipment protection by increased safety "e" EN 60079-7 2007 2)
IEC 60079-11
– 1) Explosive atmospheres -
Part 11: Equipment protection by intrinsic safety "i" EN 60079-11 2007 2)
IEC/TR 60079-13 – 1) Electrical apparatus for explosive gas atmospheres -
Part 13: Construction and use of rooms or buildings protected by pressurization – –
1) Undated reference.
2) Valid edition at date of issue.
IEC 60079-15 – 1) Electrical apparatus for explosive gas atmospheres -
Part 15: Construction, test and marking of type of protection "n" electrical apparatus EN 60079-15 2005 2)
IEC/TR 60079-16 – 1) Electrical apparatus for explosive gas atmospheres -
Part 16: Artificial ventilation for the protection of analyzer(s) houses – –
IEC 60079-18 – 1) Electrical apparatus for explosive gas atmospheres -
Part 18: Construction, test and marking of type of protection encapsulation "m" electrical apparatus EN 60079-18 + corr. April
2004 2)2006
IEC 60079-19 – 1) Explosive atmospheres -
Part 19: Equipment repair, overhaul and reclamation EN 60079-19 2007 2)
IEC 60079-25 – 1) Electrical apparatus for explosive gas atmospheres -
Part 25: Intrinsically safe systems EN 60079-25 + corr. April
2004 2)2006
IEC 60079-26 – 1) Explosive atmospheres -
Part 26: Equipment with equipment protection level (EPL) Ga EN 60079-26 2007 2)
IEC 60079-27 – 1) Explosive atmospheres -
Part 27: Fieldbus intrinsically safe concept (FISCO) EN 60079-27 2008 2)
IEC 60079-28 – 1) Explosive atmospheres - Part 28: Protection of equipment and transmission systems using optical radiation EN 60079-28 2007 2)
IEC 60079-29-1 (mod) – 1) Explosive atmospheres -
Part 29-1: Gas detectors - Performance requirements of detectors for flammable gases EN 60079-29-1 2007 2)
IEC 60079-29-2 – 1) Explosive atmospheres -
Part 29-2: Gas detectors - Selection, installation, use and maintenance of detectors for flammable gases and oxygen EN 60079-29-2 + corr. December
2007 2)2007
IEC 60079-31 – 3) Explosive Atmospheres -
Part 31: Equipment dust ignition protection by enclosure "tD" EN 60079-31 – 3)
IEC 60243-1 – 1) Electrical strength of insulating materials - Test methods -
Part 1: Tests at power frequencies EN 60243-1 1998 2)
IEC 60332-1-2 – 1) Tests on electric and optical fibre cables under fire conditions -
Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame EN 60332-1-2 2004 2)
IEC 60364 (mod) Series Low-voltage electrical installations
HD 60364/ HD 384 Series
3) To be published.
– 5 – EN 60079-14:2008 Publication Year Title EN/HD Year
IEC 60364-4-41 (mod) – 1) Low-voltage electrical installations -
Part 4-41: Protection for safety - Protection against electric shock HD 60364-4-41 + corr. July
2007 2)2007
IEC 60529 – 1) Degrees of protection provided by
enclosures (IP Code) EN 60529 + corr. May
1991 2)1993
IEC 60950 (mod) Series Information technology equipment - Safety
EN 60950 Series
IEC 61010-1
– 1) Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements EN 61010-1 + corr. June
2001 2)2002
IEC 61241 Series Electrical apparatus for use in the
presence of combustible dust
EN 61241
Series
IEC 61241-0 (mod)
– 1) Electrical apparatus for use in the presence of combustible dust -
Part 0: General requirements EN 61241-0 2006 2)
IEC 61241-1 – 1) Electrical apparatus for use in the
presence of combustible dust -
Part 1: Protection by enclosures "tD" EN 61241-1 + corr. December
2004 2)2006
IEC 61241-2-1 – 1) Electrical apparatus for use in the presence of combustible dust -
Part 2: Test methods -
Section 1: Methods for determining the minimum ignition temperatures of dust – –
IEC 61241-4 – 1) Electrical apparatus for use in the
presence of combustible dust -
Part 4: Type of protection 'pD' EN 61241-4 2006 2)
IEC 61241-10 – 1) Electrical apparatus for use in the presence of combustible dust -
Part 10: Classification of areas where combustible dusts are or may be present EN 61241-10 2004 2)
IEC 61241-11
– 1) Electrical apparatus for use in the
presence of combustible dust -
Part 11: Protection by intrinsic safety 'iD' EN 61241-11 2006 2)
IEC 61285 – 1) Industrial-process control - Safety of analyser houses EN 61285 2004 2)
IEC 61558-2-6 – 1) Safety of power transformers, power supply units and similar -
Part 2-6: Particular requirements for safety isolating transformers for general use EN 61558-2-6 1997 2)
IEC 62305-3 (mod) – 1) Protection against lightning -
Part 3: Physical damage to structures and life hazard EN 62305-3 + corr. September
2006 2)2008
ISO 10807 – 1) Pipework - Corrugated flexible metallic hose assemblies for the protection of electric cables in explosive atmospheres EN ISO 10807 1996 2)
ATEX Categories and Equipment Protection Levels (EPLs) This European Standard has been written to incorporate the concept of Equipment Protection Levels (EPLs). EPLs are analogous to the ATEX Categories, indeed the definitions are identical. Wherever there is a reference to an EPL in the text it should be equated with the corresponding ATEX Category: - EPL ‘Ga’ equates to ATEX Category 1G; - EPL ‘Gb’ equates to ATEX Category 2G; - EPL ‘Gc’ equates to ATEX Category 3G; - EPL ‘Da’ equates to ATEX Category 1D; - EPL ‘Db’ equates to ATEX Category 2D; - EPL ‘Dc’ equates to ATEX Category 3D.
IEC 60079-14Edition 4.0 2007-12INTERNATIONAL STANDARD NORME INTERNATIONALEExplosive atmospheres –
Part 14: Electrical installations design, selection and erection
Atmosphères explosives –
Partie 14: Conception, sélection et construction des installations électriques
INTERNATIONAL ELECTROTECHNICAL COMMISSION COMMISSION ELECTROTECHNIQUE INTERNATIONALE XDICS 29.260.20 PRICE CODECODE PRIXISBN 2-8318-9491-3
– 2 – 60079-14 © IEC:2007 CONTENTS FOREWORD.8 INTRODUCTION.10
1 Scope.13 2 Normative references.13 3 Terms and definitions.16 3.1 General.16 3.2 Hazardous areas.16 3.3 Flameproof enclosure.17 3.4 Increased safety.17 3.5 Intrinsic safety - General.18 3.6 Intrinsic safety parameters.19 3.7 Pressurization.19 3.8 Type of protection 'n'.19 3.13 Electrical supply systems.20 3.14 Equipment.21 4 General.21 4.1 General requirements.21 4.2 Documentation.22 4.3 Assurance of
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.