Power cables having rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV with special fire performance for use in power stations

2021: CLC legacy converted by DCLab NISOSTS

Starkstromkabel mit Nennspannungen von 3,6/6 (7,2) kV bis 20,8/36 (42) kV mit verbessertem Verhalten im Brandfall für Kraftwerke

Câbles d'énergie de tension assignée de 3,6/6 (7,2) kV à 20,8/36 (42) kV inclus, ayant un comportement au feu particulier et destinés aux centrales électriques

Elektroenergetski kabli za nazivne napetosti od 3,6/6 (7,2) kV do vključno 20,8/36 (42) kV s posebnimi ognjevzdržnimi lastnostmi za uporabo v elektrarnah

General Information

Status
Published
Publication Date
11-Aug-2005
Withdrawal Date
30-Apr-2008
Technical Committee
Drafting Committee
Parallel Committee
Current Stage
6060 - Document made available - Publishing
Start Date
12-Aug-2005
Completion Date
12-Aug-2005

Relations

Buy Standard

Amendment
HD 622 S1:1998/A2:2005
English language
102 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI SIST HD 622 S1:1998/A2:2005

STANDARD
december 2005
Elektroenergetski kabli za nazivne napetosti od 3,6/6 (7,2) kV do vključno
20,8/36 (42) kV s posebnimi ognjevzdržnimi lastnostmi za uporabo v
elektrarnah
Power cables having rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36
(42) kV with special fire performance for use in power stations
ICS 29.060.20 Referenčna številka
©  Standard je založil in izdal Slovenski inštitut za standardizacijo. Razmnoževanje ali kopiranje celote ali delov tega dokumenta ni dovoljeno

HARMONIZATION DOCUMENT HD 622 S1/A2
DOCUMENT D'HARMONISATION
HARMONISIERUNGSDOKUMENT August 2005

ICS 29.060.20
English version
Power cables having rated voltages
from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV
with special fire performance for use in power stations

Câbles d'énergie de tension assignée  Starkstromkabel mit Nennspannungen
de 3,6/6 (7,2) kV à 20,8/36 (42) kV inclus, von 3,6/6 (7,2) kV bis 20,8/36 (42) kV
ayant un comportement au feu particulier mit verbessertem Verhalten im Brandfall
et destinés aux centrales électriques für Kraftwerke

This amendment A2 modifies the Harmonization Document HD 622 S1:1996; it was approved by
CENELEC on 2005-05-01. CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for implementation of this amendment on a national level.

Up-to-date lists and bibliographical references concerning such national implementation may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in one official version (English).

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2005 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. HD 622 S1:1996/A2:2005 E

Page 0-2
FOREWORD
This amendment to the Harmonization Document HD 622 S1:1996 was prepared by WG9 of the
Technical Committee CENELEC TC 20, Electric Cables.

The text of the draft was submitted to the Unique Acceptance Procedure and was approved by
CENELEC as amendment A2 to HD 622 S1:1996 on 2005-05-01.

The following dates were fixed:

– latest date by which the existence of the amendment
has to be announced at national level  (doa) 2005-11-01

– latest date by which the amendment has to be
implemented at national level by publication
of a harmonized national standard or by endorsement (dop) 2006-05-01

– latest date by which the national standards conflicting
with the amendment have to be withdrawn  (dow) 2008-05-01

Users of HD 622 should note that, in the particular sections, cross-references have only been updated
where the complete section has been re-issued. This Part 0 of HD 622 contains a list of relevant
changes to cross-references, which should be consulted in conjunction with the particular section.
National standards implementing one or more particular sections of HD 622 may update cross-
references in advance of changes to the published version of the HD.

By decision of the Technical Board (D81/139 extended by D104/118 & D114/076) this HD exists only in
English.
Page 0-3
CONTENTS
(HD 622 S1:1996 plus Amendment No. 1 and Amendment No. 2)

1) 3)
Part 1 General requirements
Part 3  Single core and three core cables containing halogenated materials

3-A (Spare)
3-B (Spare)
3-C1 Three core PVC insulated and sheathed, non-radial field cables with aluminium conductors and
metallic tape armour
3-C2 Single core XLPE insulated and PVC sheathed cables with aluminium conductors and metallic
screen
3-C3 Three core EPR insulated and CSP sheathed, non-radial field cables with aluminium conductors
and metallic screen
3-D (Spare)
3-E (Spare)
1) 4)
3-F Single and three core cables containing halogenated materials for 6, 10 and 15 kV

1) 3)
3-G Single and three core cables containing halogenated materials, circular or shaped conductors

1)
3-H Single and three core cables with halogenated materials and with aluminium or steel wire
armouring
Part 4 Single core and three core cables with halogen-free materials

4-A Single and three core cables with halogen-free materials for 12, 17,5 and 24 kV

3)
4-B Single and three core cables with halogen-free materials and aluminium laminate or copper wire
screens
4-C Single core cable or assemblies with halogen free materials

2)
4-D Single core cables with halogen free materials

4-E EPR insulated with halogen free sheath, three core armoured cables

1) 3)
4-F Single or three core cables with copper or aluminium conductors

4-G (Spare)
2)
4-H Single and three core cables with non-halogenated materials and with aluminium or steel wire
armouring
3)
4-I Single core cables with halogen free materials and with aluminium alloy wire armouring

1)
Amendment No. 1 introduces some changes to the text
2)
Amendment No. 1 completely revises the Particular Section
3)
Amendment No. 2 completely revises the Particular Section
4)
Amendment No. 2 withdraws the Particular Section

Page 0-4
List of updated cross-references

Original Ref Original title New Ref New title
HD 48 Impulse tests on cables and their accessories EN 60230 Impulse tests on cables and their accessories
HD 186 Marking by inscription for the identification of cores of electric EN 50334 Marking by inscription for the identification of cores of electric
cables having more than 5 cores cables
HD 383 Conductors of electric cables EN 60228 Conductors of electric cables
HD 405.1 Tests on electric cables under fire conditions – Part 1: Test EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
on a single vertical insulated wire or cable Part 1-2: Test for vertical flame propagation for a single
insulated wire or cable – Procedure for 1 kW pre-mixed flame
HD 405.3 Tests on electric cables under fire conditions – Part 3: Tests EN 50266 Common test methods for cables under fire conditions – Test
on bunched wires or cables (series) for vertical flame spread of vertically-mounted bunched wires
or cables
HD 505 Common test methods for insulating and sheathing materials EN 60811 Insulating and sheathing materials of electric cables –
(series) of electric cables (series) Common test methods
HD 602 Test on gases evolved during combustion of materials from EN 50267-2-2 Common test methods for cables under fire conditions – Test
cables – Determination of degree of acidity (corrosivity) of on gases evolved during combustion of materials from cables –
gases by measuring pH and conductivity Part 2-2: Procedures – Determination of degree of acidity of
gases for materials by measuring pH and conductivity
HD 606 Measurement of smoke density of electric cables burning EN 50268 Common test methods for cables under fire conditions –
(series) under defined conditions (series) Measurement of smoke density of cables burning under
defined conditions
IEC 502 Extruded solid dielectric insulated power cables for rated IEC 60502-2 Power cables with extruded insulation and their accessories for
voltages from 1 kV to 30 kV rated voltages from 1 kV (U = 1,2 kV) up to 30 kV (U = 36
m m
kV) – Part 2: Cables for rated voltages from 6 kV (U = 7,2 kV)
m
up to 30 kV (U = 36 kV)
m
IEC 754-1 Test on gases evolved during combustion of electric cables. EN 50267-2-1 Common test methods for cables under fire conditions – Tests
Part 1: determination of the amount of halogen acid gas on gases evolved during combustion of materials from cables –
evolved during the combustion of polymeric materials taken Part 2-1: Procedures – Determination of the amount of halogen
from cables acid gas
EN 50265-2-1 Common test methods for cables under fire conditions – Test EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
for resistance to vertical flame propagation for a single Part 1-2: Test for vertical flame propagation for a single
insulated conductor or cable – Part 2-1: Procedures – 1 kW insulated wire or cable – Procedure for 1 kW pre-mixed flame
pre-mixed flame
Page 1-0
Part 1
PART 1: GENERAL REQUIREMENTS
Replace the complete part by the following

Page 1-1
Part 1
POWER CABLES HAVING RATED VOLTAGE FROM
3,6/6 (7,2) kV UP TO AND INCLUDING 20,8/36 (42) kV
WITH SPECIAL FIRE PERFORMANCE FOR USE IN POWER STATIONS

PART 1: GENERAL REQUIREMENTS
Page 1-2
Part 1
CONTENTS
1 General.1-4
1.1 Scope.1-4
1.2 Object.1-4
2 Definitions.1-4
2.1 Definitions relating to insulating and sheathing compounds .1-4
2.2 Definitions relating to the tests .1-5
2.3 Rated voltage.1-5
3 Marking.1-6
3.1 Indication of origin.1-6
3.2 Additional marking.1-6
3.3 Durability.1-6
3.4 Legibility.1-7
3.5 Common marking.1-7
3.6 Use of the name CENELEC.1-7
4 Core identification.1-7
5 General requirements for the construction of cables .1-7
5.1 Conductors.1-7
5.2 Conductor screening.1-8
5.3 Insulation.1-8
5.4 Assembly of cores and fillers and binder tape.1-9
5.5 Inner covering (bedding).1-9
5.6 Inner sheath.1-9
5.7 Metallic coverings.1-10
5.8 Outer sheath.1-10
5.9 Non-metallic components of halogen free cables.1-11
6 Tests on completed cables .1-11
7 (Spare).1-11
8 (Spare).1-11
9 Guide to use and selection of cables .1-11

Page 1-3
Part 1
References
Part 1 of HD 622 S1 incorporates by dated or undated reference, provisions from other publications.
These references are cited at the appropriate places in the text and the publications are listed hereafter.
For dated references, subsequent amendments to or revisions of any of these publications apply to
Part 1 of HD 622 S1 only when incorporated in it by amendment or revision. For undated references the
latest edition of the publication referred to applies.

EN 50266 (series) Common test methods for cables under fire conditions – Test for vertical flame
spread of vertically-mounted bunched wires or cables.

EN 50267 (series) Common test methods for cables under fire conditions - Tests on gases evolved
during combustion of materials from cables.

EN 50268 (series) Measurement of smoke density of electric cables burning under defined
conditions.
EN 50334 Marking by inscription for the identification of cores of electric cables

EN 60228 Conductors of insulated cables

EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for
vertical flame propagation for a single insulated wire or cable – Procedure for 1
kW pre-mixed flame
EN 60811 (series) Insulating and sheathing materials of electric cables - Common test methods

HD 21 Cables of rated voltages up to and including 450/750 V
and having thermoplastic insulation

HD 22 Cables of rated voltages up to and including 450/750 V and having crosslinked
insulation
HD 605 Electric cables – Additional test metho
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.