EN IEC 60947-5-5:2026
(Main)Low-voltage switchgear and controlgear - Part 5-5: Control circuit devices and switching elements - Electrical emergency stop device with mechanical latching function
- Abstract
IEC 60947-5-5:2026 This edition includes the following significant technical changes with respect to the previous edition: a) re-shaping the document with the clause numbers and names to be in line with other documents of the 60947 series; b) review of the test method to reasonably determine that the latch mechanism meets the requirements of the document; c) new Annex B for special requirements for illuminated push-button type emergency stop devices, including the reference to a function to distinguish between "active and inactive" by changing the colour of the push-button depending on the illumination. This part of IEC 60947-5 provides detailed specifications relating to the electrical and mechanical construction of emergency stop devices with mechanical latching function and to their testing. This document is applicable to electrical control circuit devices and switching elements which are used to initiate an emergency stop signal. Such devices can be provided with their own enclosure and will be installed according to the product documentation. This document does not apply to: – emergency stop devices for non-electrical control applications, for example hydraulic or pneumatic; – emergency stop devices without mechanical latching function. An emergency stop device conforming to this document can also be used as part of an emergency switching off means in compliance with IEC 60364-5-53. NOTE See also IEC 60204-1:2016 and IEC 60204-1:2016/AMD1:2021, 9.2.3.4. This document does not address specific requirements on acoustic noise as the noise emission of electrical emergency stop devices with mechanical latching function is not considered to be a relevant hazard. This second edition cancels and replaces the first edition published in 1997. This edition constitutes a technical revision.
- Status
- Published
- Publication Date
- 16-Jul-2026
- Technical Committee
- CLC/TC 121A - Low-voltage switchgear and controlgear
- Drafting Committee
- SC 121A - Low-voltage switchgear and controlgear
- Current Stage
- 6060 - Document made available - Publishing
- Start Date
- 17-Jul-2026
- Due Date
- 28-Jun-2024
- Completion Date
- 28-Jun-2024
EN IEC 60947-5-5:2026 is a CENELEC European Standard for electrical emergency stop devices with a mechanical latching function. It specifies the construction, marking, performance and test methods for control circuit devices and switching elements used to initiate an emergency stop signal in low-voltage switchgear and controlgear. It is identical to IEC 60947-5-5:2026 and is read with the general 60947 rules.
What does EN IEC 60947-5-5:2026 specify?
EN IEC 60947-5-5:2026 specifies detailed requirements for electrical emergency stop devices with mechanical latching function and how they are tested. It applies to electrical control circuit devices and switching elements used to start an emergency stop signal, including devices that have their own enclosure and are installed according to the product documentation.
The document is organized into the usual 60947 series structure: Scope, Normative references, Terms and definitions, Classification, Characteristics, Product information, Normal service, mounting and transport conditions, Constructional and performance requirements, and Tests. It also contains two normative annexes.
| Annex | What it covers |
|---|---|
| Annex A | Procedure to determine reliability data for electrical emergency stop devices used in functional safety applications, including durability-test based methods and Weibull modelling. |
| Annex B | Additional requirements for illuminated push-button type emergency stop devices, including active/inactive signalling by illumination. |
EN IEC 60947-5-5:2026 is focused on electrical devices with mechanical latching. It is not for non-electrical emergency stop applications such as hydraulic or pneumatic devices, and it is not for emergency stop devices without mechanical latching function. The document also notes that acoustic noise is not treated as a relevant hazard for these devices.
What are the key requirements of EN IEC 60947-5-5:2026?
EN IEC 60947-5-5:2026 concentrates on how the device is identified, how it behaves during operation, and how it survives mechanical and environmental stress. For a buyer or engineer, the most important point is that the standard tells you which device type to specify, what information must be supplied, and which tests prove the emergency stop function remains reliable.
Device type, classification and product information
Clause 4 and Clause 5 classify emergency stop devices by actuation method, additional functions and mounting. The standard distinguishes at least push-button and trip wire switch types, and it also recognizes additional functions such as illumination, trigger mechanism, resetting means and locking mechanism. In practice, this helps you specify the exact device form and mounting arrangement you need.
Clause 6 requires product information that supports correct installation and use. For push-button devices, the documentation has to state the resetting or unlatching method, any trigger mechanism, and any illumination function. For trip wire switches, the documentation also has to give the maximum wire or rope length, tension setting information, support distances, straight-run guidance, and maintenance advice for pulleys and eyelets.
Marking and visual identification
Clause 6 requires the emergency stop symbol IEC 60417-5638:2002-10 where a symbol is needed for clarification. When reset is done by rotation, the unlatching direction must be identified and the identification color should match the actuator closely to avoid confusion. For trip wire switches, marker flags may be used to improve visibility.
The constructional requirements in Clause 8 also fix the usual colors: push-buttons are red with a yellow background where there is a background, ropes or wires are red, marker flags are yellow or red-and-yellow, the integral resetting actuator is blue, and setting indicators use green for rest position and yellow for actuated position. In practice, these color rules help operators recognize the device quickly in an emergency.
Operation, latching and direct opening action
Clause 8 requires direct opening action for the normally closed contact elements that generate the emergency stop signal. The device must also keep the emergency stop signal latched until it is manually reset, and it must not latch unless the emergency stop signal has actually been generated. This matters because the device has to fail in a way that still protects the machine stop function.
The standard also requires the device to operate and reset under normal service conditions, and shocks or vibrations must not cause unwanted opening, closing, latching or unlatching. For push-button devices, actuation must be possible by a one-handed continuous single motion, and reset has to be by rotation, pulling, or a key. For trip wire switches, the wire or rope has to trigger the stop below 200 N and below 400 mm deflection, withstand at least 10 times the designed tension, and any loss of tension must cause actuation.
Tests and verification
Clause 9 sets out the verification program. Type tests include robustness of the actuator, mechanical durability, conditioning, shock, vibration, opening and latching tests, actuation and resetting tests, impact tests for push-button types, and EMC tests as applicable. The durability test uses 6 050 cycles, which gives a practical check on the latch parts and contacts over repeated use.
The conditioning procedures expose devices to dry heat, damp heat, cold and salt mist before the shock, vibration and opening/latching tests. The shock and vibration tests check that contacts do not chatter and that the latching mechanism stays in the correct state. For readers responsible for validation, this means the standard is not just about initial function - it checks behavior after environmental stress and repeated operation.
Reliability data and functional safety
Clause 6.5 and Annex A address reliability data for functional safety applications. The key parameter is B10D, the number of cycles by which 10% of the device population will have failed dangerously. Annex A gives a procedure based on monitored durability testing and Weibull modelling, so the data in product documentation can support safety-related design work.
Annex B adds special requirements for illuminated push-button devices. If illumination is used to show whether the device is active or inactive, the lighting must not impair the emergency stop function, and the signalling function may need a risk assessment with a required Safety Integrity Level (SIL) or required Performance Level (PLr).
What terms does EN IEC 60947-5-5:2026 define?
EN IEC 60947-5-5:2026 defines the key terms needed to specify and test emergency stop devices consistently.
- Emergency stop function - a function intended to avert or reduce hazards and started by a single human action.
- Emergency stop device - a manually operated control circuit device used to initiate an emergency stop function.
- Actuating system - the mechanical parts that transmit the actuating force to the contact elements.
- Latching - the function or means that holds the actuating system in the actuated position until separate manual reset.
- Resetting - the manual action that returns the actuating system from the actuated position to the rest position.
- Direct opening action - contact separation caused directly by specified movement of the actuator through non-resilient members.
- Trip wire switch - an emergency stop device whose actuator is a rope, a wire or similar means.
Who uses EN IEC 60947-5-5:2026?
EN IEC 60947-5-5:2026 is used by machine builders, control panel builders, emergency stop device manufacturers, and switchgear and controlgear designers. It is also used by test laboratories, certification bodies, quality managers and buyers who need to check that a device type, marking, test result or reliability declaration fits the intended application. In practice, it supports selection, product design, testing, documentation and conformity assessment for machinery and low-voltage control equipment.
What changed in EN IEC 60947-5-5:2026 from the previous edition?
EN IEC 60947-5-5:2026 is the second edition and it cancels and replaces the 1997 edition and its amendments. The significant technical changes stated in the document are:
- the clause numbers and names have been reshaped to align with the rest of the 60947 series;
- the test method has been reviewed so the latch mechanism can be determined more appropriately against the document requirements;
- Annex B has been added for illuminated push-button type emergency stop devices, including active/inactive signalling by color change.
Which standards are used with EN IEC 60947-5-5:2026?
EN IEC 60947-5-5:2026 is read with EN IEC 60947-1 and EN IEC 60947-5-1, which supply the general rules and the shared requirements for electromechanical control circuit devices. Its normative references also include:
- IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-6, IEC 60068-2-11, IEC 60068-2-27, IEC 60068-2-30 and IEC 60068-2-75 - environmental test methods used for cold, dry heat, vibration, salt mist, shock, damp heat and hammer testing.
- IEC 60417 - graphical symbols, including the emergency stop symbol used in the standard.
- ISO 13850:2015 - principles for the emergency stop function of machinery.
- IEC 60364-5-53 - emergency switching off means in low-voltage electrical installations.
- IEC 62061:2021 and IEC 62061:2021/AMD1:2024 - functional safety, including the reliability-data context for B10D and SIL.
- ISO 13849-1:2023 - safety-related parts of control systems and the PLr context.
What does the EN IEC 60947-5-5:2026 document contain?
EN IEC 60947-5-5:2026 contains the symbol for emergency stop, the classification framework for push-button and trip wire switches, and the product-information rules that manufacturers have to publish. It also includes the test equipment and test sequences for actuator robustness, durability, shock, vibration, opening and latching behavior, resetting, impact and EMC. Annex A adds a reliability-data procedure with durability testing and examples, while Annex B sets out the extra requirements for illuminated push-button devices.
Relations
- Effective Date
- 23-Jan-2023
- Effective Date
- 23-Jan-2023
- Effective Date
- 07-Jun-2022
- Effective Date
- 07-Jun-2022
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 16-Jun-2026
- Effective Date
- 21-Jul-2026
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
EN IEC 60947-5-5:2026 is a standard published by CLC. Its full title is "Low-voltage switchgear and controlgear - Part 5-5: Control circuit devices and switching elements - Electrical emergency stop device with mechanical latching function". This standard covers: IEC 60947-5-5:2026 This edition includes the following significant technical changes with respect to the previous edition: a) re-shaping the document with the clause numbers and names to be in line with other documents of the 60947 series; b) review of the test method to reasonably determine that the latch mechanism meets the requirements of the document; c) new Annex B for special requirements for illuminated push-button type emergency stop devices, including the reference to a function to distinguish between "active and inactive" by changing the colour of the push-button depending on the illumination. This part of IEC 60947-5 provides detailed specifications relating to the electrical and mechanical construction of emergency stop devices with mechanical latching function and to their testing. This document is applicable to electrical control circuit devices and switching elements which are used to initiate an emergency stop signal. Such devices can be provided with their own enclosure and will be installed according to the product documentation. This document does not apply to: – emergency stop devices for non-electrical control applications, for example hydraulic or pneumatic; – emergency stop devices without mechanical latching function. An emergency stop device conforming to this document can also be used as part of an emergency switching off means in compliance with IEC 60364-5-53. NOTE See also IEC 60204-1:2016 and IEC 60204-1:2016/AMD1:2021, 9.2.3.4. This document does not address specific requirements on acoustic noise as the noise emission of electrical emergency stop devices with mechanical latching function is not considered to be a relevant hazard. This second edition cancels and replaces the first edition published in 1997. This edition constitutes a technical revision.
IEC 60947-5-5:2026 This edition includes the following significant technical changes with respect to the previous edition: a) re-shaping the document with the clause numbers and names to be in line with other documents of the 60947 series; b) review of the test method to reasonably determine that the latch mechanism meets the requirements of the document; c) new Annex B for special requirements for illuminated push-button type emergency stop devices, including the reference to a function to distinguish between "active and inactive" by changing the colour of the push-button depending on the illumination. This part of IEC 60947-5 provides detailed specifications relating to the electrical and mechanical construction of emergency stop devices with mechanical latching function and to their testing. This document is applicable to electrical control circuit devices and switching elements which are used to initiate an emergency stop signal. Such devices can be provided with their own enclosure and will be installed according to the product documentation. This document does not apply to: – emergency stop devices for non-electrical control applications, for example hydraulic or pneumatic; – emergency stop devices without mechanical latching function. An emergency stop device conforming to this document can also be used as part of an emergency switching off means in compliance with IEC 60364-5-53. NOTE See also IEC 60204-1:2016 and IEC 60204-1:2016/AMD1:2021, 9.2.3.4. This document does not address specific requirements on acoustic noise as the noise emission of electrical emergency stop devices with mechanical latching function is not considered to be a relevant hazard. This second edition cancels and replaces the first edition published in 1997. This edition constitutes a technical revision.
EN IEC 60947-5-5:2026 is classified under the following ICS (International Classification for Standards) categories: 29.120.99 - Other electrical accessories; 29.130.20 - Low voltage switchgear and controlgear. The ICS classification helps identify the subject area and facilitates finding related standards.
EN IEC 60947-5-5:2026 has the following relationships with other standards: It is inter standard links to EN 60947-5-5:1997/A11:2013, EN 60947-5-5:1997, EN 60947-5-5:1997/A2:2017, EN 60947-5-5:1997/A1:2005, EN 60068-2-75:2014, EN IEC 60947-1:2021, EN 60417-2:1999, EN IEC 60068-2-30:2025, EN IEC 60068-2-1:2025, EN 60068-2-6:2008, EN IEC 60068-2-11:2021, EN 60068-2-27:2009, EN IEC 60068-2-2:2025, EN IEC 60947-5-1:2025, EN 15954-1:2013. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN IEC 60947-5-5:2026 is associated with the following European legislation: EU Directives/Regulations: 2006/42/EC, 2014/35/EU, 2023/1230; Standardization Mandates: M/396, M/511, M/605. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
EN IEC 60947-5-5:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 emergency stop function
- 3.2 emergency stop device
- 3.3 emergency stop signal
- 3.4 actuating system
- 3.5 actuator
- 3.6 rest position
- 3.7 actuated position
- 3.8 latching
- 3.9 resetting
- 3.10 direct opening action
- 3.11 push-button type emergency stop device
- 3.12 trigger mechanism
- 3.13 trip wire switch
- 4 Classification
- 4.1 Contact elements
- 4.2 Means of actuation
- 4.3 Additional functions
- 4.4 Emergency stop device mounting
- 5 Characteristics
- 5.1 Summary of characteristics
- 5.2 Type of emergency stop device
- 5.3 Rated and limiting values for switching elements
- 5.4 Utilization categories for switching elements
- 6 Product information
- 6.1 Nature of information
- 6.2 Marking
- 6.3 Instructions for installation, operation and maintenance, decommissioning and
- 6.4 Environmental information
- 6.5 Reliability data
- 7 Normal service, mounting and transport conditions
- 8 Constructional and performance requirements
- 8.1 Constructional requirements
- 8.2 Performance requirements
- 8.3 Electromagnetic compatibility (EMC)
- 8.4 Special requirements
- 9 Tests
- 9.1 Kinds of tests
- 9.2 Compliance with constructional requirements
- 9.3 Performance
- 9.4 Tests for EMC
- Annex A
- Annex B
- Bibliography
INTRODUCTION This document deals specifically with electrical emergency stop devices with mechanical latching function and gives additional electrical and mechanical requirements to those given in the following International Standards:
- ISO 13850, giving requirements for the emergency stop function of a machine, whatever be the energy used;
- IEC 60204-1, giving additional requirements for an emergency stop function realized by the electrical equipment of a machine;
- IEC 60947-5-1, specifying electrical characteristics of electromechanical control circuit devices.
SIST EN IEC 60947-5-5:2026
1 Scope
This part of IEC 60947-5 provides detailed specifications relating to the electrical and mechanical construction of emergency stop devices with mechanical latching function and to their testing.
This document is applicable to electrical control circuit devices and switching elements which are used to initiate an emergency stop signal. Such devices can be provided with their own enclosure and will be installed according to the product documentation. This document does not apply to:
- emergency stop devices for non-electrical control applications, for example hydraulic or pneumatic; - emergency stop devices without mechanical latching function. An emergency stop device conforming to this document can also be used as part of an emergency switching off means in compliance with IEC 60364-5-53. NOTE See also IEC 60204-1:2016 and IEC 60204-1:2016/AMD1:2021, 9.2.3.4. This document does not address specific requirements on acoustic noise as the noise emission of electrical emergency stop devices with mechanical latching function is not considered to be a relevant hazard.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60068-2-1, Environmental testing - Part 2-1: Tests - Test A: Cold IEC 60068-2-2, Environmental testing - Part 2-2: Tests - Test B: Dry heat IEC 60068-2-6, Environmental testing - Part 2-6: Tests - Test Fc: Vibration (sinusoidal) IEC 60068-2-11, Environmental testing - Part 2-11: Tests - Test Ka: Salt mist IEC 60068-2-27, Environmental testing - Part 2-27: Tests - Test Ea and guidance: Shock IEC 60068-2-30, Environmental testing - Part 2-30: Tests - Test Db: Damp heat, cyclic (12 h + 12 h cycle) IEC 60068-2-75, Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests IEC 60417, Graphical symbols for use on equipment, available at https://www.graphicalsymbols.info/equipment IEC 60947-1:2020, Low-voltage switchgear and controlgear - Part 1: General rules IEC 60947-5-1:2024, Low-voltage switchgear and controlgear - Part 5-1: Control circuit devices and switching elements - Electromechanical control circuit devices
SIST EN IEC 60947-5-5:2026
ISO 13850:2015, Safety of machinery - Emergency stop function - Principles for design
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60947-1, IEC 60947-5-1 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- IEC Electropedia: available at https://www.electropedia.org/
- ISO Online browsing platform: available at https://www.iso.org/obp
3.1 emergency stop function
function which is intended to:
- avert or to reduce hazards to persons, damage to machinery or to work in progress;
- be initiated by a single human action.
[SOURCE: ISO 12100:2010, 3.40, modified – the first preferred term "emergency stop" has been removed.]
3.2 emergency stop device
manually operated control circuit device used to initiate an emergency stop function Note 1 to entry: An emergency stop device can also provide auxiliary functions, for example for redundancy or for signalling through additional contact element(s), or both. Such additional contact(s) can be normally open or normally closed, or both.
3.3 emergency stop signal
signal, which is generated by an emergency stop device contact, used to initiate an emergency stop function
3.4 actuating system
<of an emergency stop device> mechanical parts which transmit the actuating force to the contact elements [SOURCE: IEC 60050-441:1984, 441-15-21, modified – restricted to electromechanical emergency stop devices; the note is not relevant anymore.]
3.5 actuator
<of an emergency stop device> part of the actuating system which is operated by a part of the human body Note 1 to entry: Examples of an actuator include: a push-button, a wire, or a rope. [SOURCE: IEC 60050-441:1984, 441-15-22, modified – actuation is intended to be achieved by human only, the domain has been added and the note has been revised.]
SIST EN IEC 60947-5-5:2026
3.6 rest position
position of an emergency stop device, or of a part of it, which has not been actuated Note 1 to entry: In rest position, the normally closed contacts are closed and the machine (or equipment) can work.
3.7 actuated position
position of an emergency stop device, or of a part of it, after it has been operated Note 1 to entry: In the actuated position of the emergency stop device, the normally closed contacts remain open.
3.8 latching
<of an emergency stop device> function or means which engage and maintain the actuating system in the actuated position until reset by a separate manual action
3.9 resetting
disengaging <of an emergency stop device> manual action to return the actuating system of the emergency stop device from the actuated position to the rest position Note 1 to entry: Examples of resetting include the rotation of a key or the actuator, pulling the actuator or pushing or rotating a dedicated reset button.
3.10 direct opening action
DEPRECATED: positive opening action <of a contact element> achievement of contact separation as a direct result of a specified movement of the switch actuator through non-resilient members (e.g. non dependent upon springs) [SOURCE: IEC 60947-5-1:2024, 3.1.15.2, modified – addition of a deprecated term.]
3.11 push-button type emergency stop device
emergency stop device with a button type as actuator
3.12 trigger mechanism
positive latching safety lock mechanism mechanical means ensuring that when operated, latching occurs at the point where the emergency stop signal is generated
3.13 trip wire switch
rope pull switch emergency stop device in which the actuator is a rope, a wire or similar means
SIST EN IEC 60947-5-5:2026
4 Classification
4.1 Contact elements
Subclause 4.1 of IEC 60947-5-1:2024 applies.
4.2 Means of actuation
Emergency stop devices can be classified according to the means of actuation, for example push-button, trip wire switch.
4.3 Additional functions
Emergency stop devices can be classified according to the additional function(s) of the device (e.g. illumination, trigger mechanism, resetting means or locking mechanism to maintain the emergency stop signal).
4.4 Emergency stop device mounting
Emergency stop devices can be classified according to the mounting of the device, for example hole size D16, D22, D30 for a push-button type.
5 Characteristics
5.1 Summary of characteristics
Subclause 5.1 of IEC 60947-5-1:2024 applies.
NOTE For information exchange in electronic format, see ACC515 and ACC522 classes of IEC 62683-1 Common Data Dictionary for trip wire switch, and emergency stop push-button respectively.
5.2 Type of emergency stop device
The kind of emergency stop device shall be stated:
- push-button;
- trip wire switch.
5.3 Rated and limiting values for switching elements
Subclause 5.3 of IEC 60947-5-1:2024 applies.
5.4 Utilization categories for switching elements
For emergency stop contact elements with direct opening action, the utilization categories shall be one or more categories specified in IEC 60947-5-1:2024, K.5.4. For additional contact elements for auxiliary functions, the utilization categories shall be one or more categories selected from IEC 60947-5-1:2024, Table 1.
SIST EN IEC 60947-5-5:2026
6 Product information
6.1 Nature of information
Subclause 6.1 and Clause K.6 of IEC 60947-5-1:2024 apply with the following addition. For push-button switches, information provided in the product documentation shall include:
- resetting/unlatching method;
- trigger mechanism, if applicable;
- illumination function, if applicable.
For trip wire switches, information provided in the product documentation shall include:
- resetting/unlatching method;
- the maximum length of wire or rope;
- information to establish correct tension of wire or rope;
- the distances between supports;
- recommendation to use only straight runs of wire or rope;
- if applicable, guidance on maintenance for pulleys and eyelets, and the measures necessary to ensure that the wire or rope remains in proper position.
6.2 Marking
6.2.1 General
Subclause 6.2 of IEC 60947-5-1:2024, with the exception of 6.2.4, applies with the following additions.
6.2.2 Push-button type emergency stop devices
Where a symbol is necessary for clarification, the symbol IEC 60417-5638:2002-10 shall be used (see Figure 1).
Figure 1 – Symbol (IEC 60417-5638:2002-10) for emergency stop The direction of unlatching shall be identified when resetting is achieved by rotation of the button. The identification of the direction of unlatching shall have the same or nearly the same colour as the actuator in order to avoid misinterpretation.
NOTE 1 Compliance with this requirement fulfils ISO 13850:2015, 4.3.7. NOTE 2 See also IEC 60073 and ISO 3864 series for general information concerning identification and safety colours.
6.2.3 Trip wire switches
Marker flags may be attached to trip wires or ropes for improved visibility. See 8.1.3. Where a symbol is necessary for clarification on the marker flag, the symbol IEC 60417-5638:2002-10 shall be used (see Figure 1).
SIST EN IEC 60947-5-5:2026
6.3 Instructions for installation, operation and maintenance, decommissioning and
dismantling Subclause 6.3 of IEC 60947-5-1:2024 applies.
6.4 Environmental information
Subclause 6.4 of IEC 60947-5-1:2024 applies.
6.5 Reliability data
According to IEC 62061:2021 and IEC 62061:2021/AMD1:2024, Annex C and ISO 13849-1:2023, Annex O, the main functional safety parameter characterizing an emergency stop device is B .
10D B for an emergency stop device is the number of cycles by which 10 % of the device 10D population will have failed dangerously, which means the normally closed contact failed to open. for an emergency stop device shall be established in accordance with Annex A. B 10D For information exchange in electronic format, the ACC007 class and ACE056 property (defined in the IEC 62683 domain of IEC CDD) should be used.
7 Normal service, mounting and transport conditions
Clause 7 of IEC 60947-5-1:2024 applies with the following addition. Additional tests for shock and vibration are defined in 9.3.8 and 9.3.9.
8 Constructional and performance requirements
8.1 Constructional requirements
8.1.1 General
Subclause 8.1 of IEC 60947-5-1:2024 applies with the following additions. Means shall be provided to enable the emergency stop device to be securely installed in its intended mounting position.
Verification of the applicable constructional requirements in 8.1.2 or 8.1.3 shall be conducted in accordance with 9.2.
8.1.2 Additional requirements for push-button type emergency stop devices
Push-buttons used as emergency stop device actuators shall be coloured red. When a background exists behind the actuator, it shall be coloured yellow. Additional requirements for illuminated push-button type emergency stop devices are defined in Annex B.
SIST EN IEC 60947-5-5:2026
8.1.3 Additional requirements for trip wire switches
Ropes or wires used for trip wire switches shall be coloured red. If marker flags are used to improve the visibility of wires or ropes, they shall be coloured yellow or "red and yellow" (alternating stripes or colours).
The integral resetting actuator shall be coloured blue.
When coloured indicators are provided to assist setting of a trip wire switch, green shall indicate the correct setting of the rest position and yellow shall indicate the correct setting of the actuated position.
8.2 Performance requirements
8.2.1 General
Subclause 8.2 of IEC 60947-5-1:2024 applies with the following additions.
8.2.2 Direct opening action
Emergency stop devices including all normally closed contact elements generating the emergency stop signal shall have a direct opening action in accordance with IEC 60947-5-1:2024, Annex K.
8.2.3 Operation
It shall be possible to operate and reset the emergency stop device under all normal service conditions.
For the normally closed contacts generating the emergency stop signal, vibrations or shocks, or both, shall not cause the opening of the contacts in the closed position or the closing of the contacts in the open position, nor actuation or release of the latching mechanism. The tests shall be conducted in accordance with 9.3.
...