Lamp controlgear - Part 2-7: Particular requirements for battery supplied electronic controlgear for emergency lighting (self-contained)

NEXT Action: CCMC to make available
2019-03-06 - Sent to BT for approval of A nnex ZA/ZZ (approved=D162/C075)
2018-12-13 PeC: "Compliant" for LVD
2018-11-20 PeC: sent to BT to keep ratification pending in order to fix harmonization (approved D161/C072)
2018-11-12 PeC: submitted for HAS assessment
2017-11-21 - Negative assessment is received during CDV stage. Consultant assessment request is missing for FDIS.

Geräte für Lampen - Teil 2-7: Besondere Anforderungen an batterieversorgte elektronische Betriebsgeräte für die Notbeleuchtung (mit Einzelbatterie)

Appareillages de lampes - Partie 2-7: Règles particulières relatives aux appareillages électroniques alimentés par batterie pour l’éclairage de secours (autonome)

Stikalne naprave za sijalke - 2-7. del: Posebne zahteve za enosmerno napajane elektronske predstikalne naprave za zasilno razsvetljavo - Dopolnilo A1 (IEC 61347-2-7:2011/A1:2017)

General Information

Status
Published
Publication Date
13-Jun-2019
Withdrawal Date
30-Apr-2022
Current Stage
6060 - Document made available - Publishing
Start Date
14-Jun-2019
Completion Date
14-Jun-2019

Relations

Buy Standard

Amendment
EN 61347-2-7:2012/A1:2019
English language
17 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2019
Stikalne naprave za sijalke - 2-7. del: Posebne zahteve za enosmerno napajane
elektronske predstikalne naprave za zasilno razsvetljavo - Dopolnilo A1 (IEC 61347
-2-7:2011/A1:2017)
Lamp controlgear - Part 2-7: Particular requirements for battery supplied electronic
controlgear for emergency lighting (self-contained) (IEC 61347-2-7:2011/A1:2017)
Geräte für Lampen - Teil 2-7: Besondere Anforderungen an batterieversorgte
elektronische Betriebsgeräte für die Notbeleuchtung (mit Einzelbatterie) (IEC 61347-2-
7:2011/A1:2017)
Amendement 1 - Appareillages de lampes - Partie 2-7: Règles particulières relatives aux
appareillages électroniques alimentés par batterie pour l'éclairage de secours
(autonome) (IEC 61347-2-7:2011/A1:2017)
Ta slovenski standard je istoveten z: EN 61347-2-7:2012/A1:2019
ICS:
29.130.01 Stikalne in krmilne naprave Switchgear and controlgear
na splošno in general
29.140.99 Drugi standardi v zvezi z Other standards related to
žarnicami lamps
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN 61347-2-7:2012/A1

NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2019
ICS 29.140.99
English Version
Lamp controlgear - Part 2-7: Particular requirements for battery
supplied electronic controlgear for emergency lighting (self-
contained)
(IEC 61347-2-7:2011/A1:2017)
Appareillages de lampes - Partie 2-7: Règles particulières Geräte für Lampen - Teil 2-7: Besondere Anforderungen an
relatives aux appareillages électroniques alimentés par batterieversorgte elektronische Betriebsgeräte für die
batterie pour l'éclairage de secours (autonome) Notbeleuchtung (mit Einzelbatterie)
(IEC 61347-2-7:2011/A1:2017) (IEC 61347-2-7:2011/A1:2017)
This amendment A1 modifies the European Standard EN 61347-2-7:2012; it was approved by CENELEC on 2019-05-01. CENELEC
members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this amendment the
status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as
the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 61347-2-7:2012/A1:2019 E

European foreword
The text of document 34C/1354/FDIS future edition 1 of IEC 61347-2-7/A1, prepared by SC 34C
"Auxiliaries for lamps" of IEC/TC 34 "Lamps and related equipment" was submitted to the IEC-
CENELEC parallel vote and approved by CENELEC as EN 61347-2-7:2012/A1:2019.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2020-02-01
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2022-05-01
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association, and supports essential requirements of EU Directive(s).
For the relationship with EU Directive(s), see informative Annex ZZ, which is an integral part of this
document.
Endorsement notice
The text of the International Standard IEC 61347-2-7:2011/A1:2017 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated:
IEC 61347-2-13 NOTE Harmonized as EN 61347-2-13
Replace Annex ZA of EN 61347-2-7:2012 by the following one:
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60081 - Double-capped fluorescent lamps - EN 60081 1998
Performance specifications
EN 60081:1998/A1 2002
EN 60081:1998/A2 2003
EN 60081:1998/A3 2005
EN 60081:1998/A4 2010
EN 60081:1998/A5 2013
EN 60081:1998/A6 2017
+A11 2018
IEC 60598-2-22 - Luminaires - Part 2-22: Particular EN 60598-2-22 2014
requirements - Luminaires for
emergency lighting
+AC 2015
EN 60598-2-22/FprA1 2017
IEC 60901 - Single-capped fluorescent lamps - EN 60901 1996
Performance specifications
EN 60901:1996/A1 1997
EN 60901:1996/A2 2000
EN 60901:1996/A3 2004
EN 60901:1996/A4 2008
EN 60901:1996/A5 2012
EN 60901:1996/A6 2017
Publication Year Title EN/HD Year
IEC 60921 Ballasts for tubular fluorescent lamps - EN 60921 2004
Performance requirements
EN 60921:2004/A1 2006
IEC 60929 - AC and/or DC-supplied electronic EN 60929 2011
control gear for tubular fluorescent
lamps - Performance requirements
+AC 2011
EN 60929:2011/A1 2016
IEC 61347-1 - Lamp controlgear - Part 1: General EN 61347-1 2015
and safety requirements
IEC 61347-2-3 - Lamp control gear - Part 2-3: EN 61347-2-3 2011
Particular requirements for a.c. and/or
d.c. supplied electronic control gear
for fluorescent lamps
+AC 2011
+A1 2017
IEC 61558-1 2005 Safety of power transformers, power EN 61558-1 2005
supplies, reactors and similar products
-- Part 1: General requirements and
tests
+A1 2009  +A1 2009
IEC 61558-2-1 2007 Safety of power transformers, power EN 61558-2-1 2007
supplies, reactors and similar products
- Part 2-1: Particular requirements and
tests for separating transformers and
power supplies incorporating
separating transformers for general
applications
IEC 61558-2-6 2009 Safety of transformers, reactors, EN 61558-2-6 2009
power supply units and similar
products for supply voltages up to 1
100 V - Part 2-6: Particular
requirements and tests for safety
isolating transformers and power
supply units incorporating safety
isolating transformers
IEC 61558-2-16 2009 Safety of transformers, reactors, EN 61558-2-16 2009
power supply units and similar
products for supply voltages up to 1
100 V - Part 2-16: Particular
requirements and tests for switch
mode power supply units and
transformers for switch mode power
supply units
IEC 62034 Automatic test systems for battery EN 62034 2012
powered emergency escape lighting
Annex ZZ
(informative)
Relationship between this European Standard and the safety objectives of
Directive 2014/35/EU [2014 OJ L96] aimed to be covered
This European Standard has been prepared under a Commission’s standardization request relating to
harmonized standards in the field of the Low Voltage Directive, M/511, to provide one voluntary means
of conforming to safety objectives of Directive 2014/35/EU of the European Parliament and of the
Council of 26 February 2014 on the harmonization of the laws of the Member States relating to the
making available on the market of electrical equipment designed for use within certain voltage limits
[2014 OJ L96].
Once this standard is cited in the Official Journal of the European Union under that Directive,
compliance with the normative clauses of this standard given in Table ZZ.1 confers, within the limits of
the scope of this standard, a presumption of conformity with the corresponding safety objectives of
that Directive, and associated EFTA regulations.
Table ZZ.1 – Correspondence between this European Standard
and Annex I of Directive 2014/35/EU [2014 OJ L96]
Safety objectives of Clause(s) / sub-clause(s) Remarks / Notes
Directive 2014/35/EU of this EN
(1)(a) Clause 7 None
(1)(b) Clause 4 None
(1)(c) See items 2 and 3 of this table None
(2)(a) Clause 8, 9, 10, 11, 12, 16, 17, EMF is not covered in this
18,19, 22, 23, 28, 29, 30, 31, 32 standard.

EMF for lighting equipment is
covered by EN 62493.
(2)(b) Clause 9, 22, 23, 28, 31, 32 None
(2)(c) Clause 9, 22, 23, 28, 31, 32 None
(2)(d) Clause 8, 9, 10, 11, 12, 16, 17, None
18, 19, 22, 23, 28, 31, 32
(3)(a) Clause 4 None
(3)(b) Clause 4 None
(3)(c) Clause 9, 14, 29, 30, 31, 32, 33 None.
WARNING 1 — Presumption of conformity stays valid only as long as a reference to this European
Standard is maintained in the list published in the Official Journal of the European Union. Users of this
standard should consult frequently the latest list published in the Official Journal of the European
Union.
WARNING 2 — Other Union legislation may be applicable to the product(s) falling within the scope of
this standard.
IEC 61347-2-7 ®
Edition 3.0 2017-10
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
A MENDMENT 1
AM ENDEMENT 1
Lamp controlgear –
Part 2-7: Particular requirements for battery supplied electronic controlgear for

emergency lighting (self-contained)

Appareillages de lampes –
Partie 2-7: Règles particulières relatives aux appareillages électroniques

alimentés par batterie pour l’éclairage de secours (autonome)

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.140.99 ISBN 978-2-8322-4819-5

– 2 – IEC 61347-2-7:2011/AMD1:2017
© IEC 2017
FOREWORD
This amendment has been prepared by subcommittee 34C: Auxiliaries for lamps, of IEC
technical committee 34: Lamps and related equipment.
The text of this amendment is based on the following documents:
FDIS Report on voting
34C/1354/FDIS 34C/1359/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC website under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
_____________
IEC 61347-2-7:2011/AMD1:2017 – 3 –
© IEC 2017
INTRODUCTION to Amendment 1
EBLF is the ratio of the light output of a light source in emergency mode to the rated light
output under normal conditions. EBLF is controlled by the output characteristics (current,
voltage, power) of the controlgear with which the light source is operated.
For conventional lamps like fluorescent lamps, the EBLF is defined by the light output ratio of
the lamp operated at 100 % and in emergency mode.
EBLF = Φ / Φ
emergency 100 %
For this measurement no special lamp is required, it is expected that all lamps of the same
type show a very similar light output ratio independent of its manufacturer. The measurement
is done at an ambient temperature of 25 °C. Due to the same dimensions and the identical
cooling system (free air) the thermal conditions are identical for all lamps. The result is fully
reproducible without any additional condition.
Special requirements for LED light sources
The light output of LED light sources depends also on the temperature at which they are
operated. Typically the temperature is controlled by a heat sink on which it is mounted (e.g.
luminaire surface).
This amendment describes a test method to evaluate the EBLF via an output factor (EOF )
X
taking into account that the ratio of the forward current of the LED controlgear is directly
proportional to the LED light output. Any non-linearity due to the increased efficacy at lower
operation temperature leads to an increased tolerance of the light output in the emergency
mode but always positive.
Controlgear, which operates the LED light source in normal operation as well as in emergency
operation can be marked directly with the output factor. Controlgear, operating the LED
module in emerge
...

Questions, Comments and Discussion