EN 61000-3-3:1995/A1:2001
(Amendment)Electromagnetic compatibility (EMC) - Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current <= 16 A per phase and not subject to conditional connection
Electromagnetic compatibility (EMC) - Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current <= 16 A per phase and not subject to conditional connection
EN following parallel vote * Superseded by EN 61000-3-3:2008
Elektromagnetische Verträglichkeit (EMV) - Teil 3-3: Grenzwerte - Begrenzung von Spannungsänderungen, Spannungsschwankungen und Flicker in öffentlichen Niederspannungs-Versorgungsnetzen für Geräte mit einem Bemessungsstrom <= 16 A je Leiter, die keiner Sonderanschlussbedingung unterliegen
Compatibilité électromagnétique (CEM) - Partie 3-3: Limites - Limitation des variations de tension, des fluctuations de tension et du papillotement dans les réseaux publics d'alimentation basse tension, pour les matériels ayant un courant assigné <= 16 A par phase et non soumis à un raccordement conditionnel
Electromagnetic compatibility (EMC) – Part 3: Limits – Section 3: Limitation of voltage fluctuations and flicker in low-voltage supply systems – Equipment with rated current < 16 A - Amendment 1 (IEC 61000-3-3:1994/A1:2001)
General Information
Relations
Standards Content (Sample)
SLOVENSKI SIST EN 61000-3-
3:1997/A1:2002
prva izdaja
STANDARD
maj 2002
Electromagnetic compatibility (EMC) – Part 3: Limits – Section 3: Limitation of
voltage fluctuations and flicker in low-voltage supply systems – Equipment with
rated current < 16 A - Amendment 1 (IEC 61000-3-3:1994/A1:2001)
ICS 5HIHUHQþQDãWHYLOND
33.100.01
! "#$%!&!%’()*#+’
EUROPEAN STANDARD EN 61000-3-3/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM June 2001
ICS 33.100.10
English version
Electromagnetic compatibility (EMC)
Part 3-3: Limits -
Limitation of voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems, for equipment with rated current ≤ 16 A
per phase and not subject to conditional connection
(IEC 61000-3-3:1994/A1:2001)
Compatibilité électromagnétique (CEM) Elektromagnetische Verträglichkeit (EMV)
Partie 3-3: Limites - Teil 3-3: Grenzwerte -
Limitation des variations de tension, des Begrenzung von Spannungsänderungen,
fluctuations de tension et du papillotement Spannungsschwankungen und Flicker in
dans les réseaux publics d'alimentation öffentlichen Niederspannungs-
basse tension ayant un courant assigné Versorgungsnetzen für Geräte mit einem
≤ 16 A par phase et non soumis à un Bemessungsstrom ≤ 16 A je Leiter,
raccordement conditionnel die keiner Sonderanschlussbedingung
(CEI 61000-3-3:1994/A1:2001) unterliegen
(IEC 61000-3-3:1994/A1:2001)
This amendment A1 modifies the European Standard EN 61000-3-3:1995; it was approved by CENELEC
on 2001-05-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this amendment the status of a national standard without any
alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway,
Portugal, Spain, Sweden, Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2001 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61000-3-3:1995/A1:2001 E
Foreword
The text of document 77A/326/FDIS, future amendment 1 to IEC 61000-3-3:1994, prepared by
SC 77A, Low-frequency phenomena, of IEC TC 77, Electromagnetic compatibility, was submitted to
the IEC-CENELEC parallel vote and was approved by CENELEC as amendment A1 to
EN 61000-3-3:1995 on 2001-05-01.
The following dates were fixed:
– latest date by which the amendment has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2002-02-01
– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2004-05-01
Annexes designated "normative" are part of the body of the standard.
In this standard, annexes A, B and ZA are normative.
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of amendment 1:2001 to the International Standard IEC 61000-3-3:1994 was approved by
CENELEC as an amendment to the European Standard without any modification.
__________
- 3 - EN 61000-3-3:1995/A1:2001
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
Delete the reference to IEC 60335-2-7.
Add the following new footnote to the end of the normative reference to IEC 60868:
EN 60868 will be withdrawn and replaced by EN 61000-4-15. Flickermeters complying with EN 61000-4-15 may
also be used for flicker measurements associated with this part of EN 61000-3.
Add:
Publication Year Title EN/HD Year
1) 2)
IEC 61000-3-2 Electromagnetic compatibility (EMC) EN 61000-3-2 2000
(mod) Part 3-2: Limits - Limits for harmonic
current emissions (equipment input
current up to and including 16 A per
phase)
1) 2)
IEC 61000-3-11 Part 3-11: Limits - Limitation of voltage EN 61000-3-11 2000
changes, voltage fluctuations and flicker
in public low-voltage supply systems -
Equipment with rated current ≤ 75 A and
subject to conditional connection
1) 2)
IEC 60974-1 Arc welding equipment EN 60974-1 1998
Part 1: Welding power sources
1)
undated reference.
2)
valid edition at date of issue.
NORME CEI
INTERNATIONALE IEC
61000-3-3
INTERNATIONAL
STANDARD
AMENDEMENT 1
AMENDMENT 1
2001-01
Amendement 1
Compatibilité électromagnétique (CEM) –
Partie 3-3:
Limites – Limitation des variations de tension,
des fluctuations de tension et du papillotement
dans les réseaux publics d'alimentation basse
tension, pour les matériels ayant un courant
assigné ≤16 A par phase et non soumis à un
raccordement conditionnel
Amendment 1
Electromagnetic compatibility (EMC) –
Part 3-3:
Limits – Limitation of voltage changes, voltage
fluctuations and flicker in public low-voltage
supply systems, for equipment with rated
current ≤16 A per phase and not subject to
conditional connection
IEC 2001 Droits de reproduction réservés Copyright - all rights reserved
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
M
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
61000-3-3 Amend. 1 IEC:2001 – 3 –
FOREWORD
This amendment has been prepared by subcommittee 77A: Low frequency phenomena, of IEC
technical committee 77: Electromagnetic compatibility.
The text of this amendment is based on the following documents:
FDIS Report on voting
77A/326/FDIS 77A/328/RVD
Full information on the voting for the approval of this amendment can be found in the report on
voting indicated in the above table.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until 2005. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
__________
Title
Replace the title of this standard on the cover page, the title page and on pages 7 and 11 as
follows:
ELECTROMAGNETIC COMPATIBILITY (EMC) –
Part 3-3: Limits –
Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems, for equipment with rated current ≤16 A per phase and not subject to
conditional connection
Page 3
CONTENTS
Replace the title of clause 4 by the following title:
4 Assessment of voltage changes, voltage fluctuations and flicker
Add the title of the new annex B as follows:
Annex B (normative) Test conditions and procedures for measuring d voltage changes
max
caused by manual switching
61000-3-3 Amend. 1 IEC:2001 – 5 –
Page 7
FOREWORD
Replace the last paragraph by
Annexes A and B form an integral part of this standard.
Page 9
INTRODUCTION
Add the following new paragraph at the end of the introduction:
The limits in this standard relate to the voltage changes experienced by consumers connected
at the interface between the public supply low-voltage network and the equipment user’s
installation. Consequently, if the actual impedance of the supply at the supply terminals of
equipment connected within the equipment user’s installation exceeds the test impedance, it is
possible that supply disturbance exceeding the limits may occur.
Page 11
1 Scope
Replace, in the first paragraph, “This section of IEC 1000-3” by “This part of IEC 61000”.
Throughout the text replace all references to “section” by “part”.
Replace the third paragraph by the following:
This part of IEC 61000 is applicable to electrical and electronic equipment having an input
current equal to or less than 16 A per phase, intended to be connected to public low-voltage
distribution systems of between 220 V and 250 V line to neutral at 50 Hz, and not subject to
conditional connection.
Add the following new paragraph after the third paragraph:
Equipment which does not comply with the limits of this part of IEC 61000 when tested with the
reference impedance Z of 6.4, and which therefore cannot be declared compliant with this
ref
part, may be retested or evaluated to show conformity with IEC 61000-3-11. Part 3-11 is
applicable to equipment with rated input current ≤75 A per phase and subject to conditional
connection.
Replace notes 1 and 2 by the following note:
NOTE The limits in this part of IEC 61000 are based mainly on the subjective severity of flicker imposed on the
light from 230 V/60 W coiled-coil filament lamps by fluctuations of the supply voltage. For systems with nominal
voltage less than 220 V line to neutral and/or frequency of 60 Hz, the limits and reference circuit values are under
consideration.
61000-3-3 Amend. 1 IEC:2001 – 7 –
2 Normative references
Delete the reference to IEC 60335-2-7.
Add the following new footnote to the end of the normative reference to IEC 60868:
IEC 60868 will be withdrawn and replaced by IEC 61000-4-15 in 2003. Flickermeters complying with IEC 61000-4-15
may also be used for flicker measurements associated with this part of IEC 61000-3.
Add the following new normative references to the existing list:
IEC 61000-3-2: Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic
current emissions (equipment input current <16 A per phase)
IEC 61000-3-11: Electromagnetic compatibility (EMC) – Part 3-11: Limits – Limitation of voltage
changes, voltage fluctuations and flicker in public low-voltage supply systems – Equipment with
rated current <75 A and subject to conditional connection
IEC 60974-1: Arc welding equipment – Part 1: Welding power sources
Page 13
3 Definitions
Replace the following existing definitions as follows:
3.1
r.m.s. voltage shape
U(t)
the time function of r.m.s. voltage, evaluated as a single value for each successive half period
between zero-crossings of the source voltage (see figure 2)
3.2
voltage change characteristic
ΔU(t)
the time function of the r.m.s. voltage change evaluated as a single value for each successive
half period between zero-crossings of the source voltage between time intervals in which the
voltage is in a steady-state condition for at least 1 s (see figure 2)
NOTE Since this characteristic is only used for assessments using calculations, the voltage in the steady-state
condition is assumed to be constant within the measurement accuracy (see 6.2).
3.3
maximum voltage change characteristic
ΔU
max
the difference between maximum and minimum r.m.s. values of a voltage change characteristic
(see figure 2)
61000-3-3 Amend. 1 IEC:2001 – 9 –
3.5
voltage fluctuation
series of changes of r.m.s. voltage evaluated as a single value for each successive half-period
between zero-crossings of the source voltage
3.10
flicker impression time
t
f
value with a time dimension which describes the flicker impression of a voltage change
characteristic
Add, on page 15, the following new definitions:
3.11
conditional connection
connection of equipment requiring the user’s supply at the interface point to have an
impedance lower than the reference impedance Z in order that the equipment emissions
ref
comply with the limits in this part.
NOTE Meeting the voltage change limits may not be the only condition for connection; emission limits for other
phenomena such as harmonics, may also have to be satisfied.
3.12
interface point
interface between a public supply network and a user’s installation
Page 15
4 Assessment of voltage fluctuations and flicker
Replace the existing title by the following new title:
4 Assessment of voltage changes, voltage fluctuations and flicker
4.1 Assessment of voltage fluctuations and flicker
Replace "waveform" in the first sentence by "characteristic".
Replace the first line of note 3 by the following:
3 For single-phase and symmetrical three-phase equipment the voltage change can, provided X is positive
(inductive), be approximated to:
Replace “waveform” by “characteristic” and “waveforms” by “characteristics” specifically in
subclauses 4.2.2, 4.2.3, 4.2.3.1, 4.2.3.2 and in table 1.
61000-3-3 Amend. 1 IEC:2001 – 11 –
Page 19
4.2.3.2 Shape factor
Replace the existing second paragraph as follows:
The relative voltage change characteristic shall be obtained from a histogram of U(t) (see
figure 3).
5 Limits
Replace the existing text of the clause by the following new text:
The limits shall be applicable to voltage fluctuations and flicker at the supply terminals of the
equipment under test, measured or calculated according to clause 4 under test conditions
described in clause 6 and annex A. Tests made to prove compliance with the limits are
considered to be type tests.
The following limits apply:
– the value of P shall not be greater than 1,0;
st
– the value of P shall not be greater than 0,65;
lt
– the value of d(t) during a voltage change shall not exceed 3,3 % for more than 500 ms;
– the relative steady-state voltage change, d , shall not exceed 3,3 %;
c
– the maximum relative voltage change d , shall not exceed
max
a) 4 % without additional conditions;
b) 6 % for equipment which is:
– switched manually, or
– switched automatically more frequently than twice per day, and also has either a
delayed restart (the delay being not less than a few tens of seconds), or manual
restart, after a power supply interruption.
NOTE The cycling frequency will be further limited by the P and P limit. For example: a d of 6 % producing a
st lt max
rectangular voltage change characteristic twice per hour will give a P of about 0,65.
lt
c) 7 % for equipment which is
– attended whilst in use (for example: hair dryers, vacuum cleaners, kitchen
equipment such as mixers, garden equipment such as lawn mowers, portable tools
such as electric drills), or
– switched on automatically, or is intended to be sw
...
Questions, Comments and Discussion