Low-voltage switchgear and controlgear assemblies - General requirements for low-voltage substation cable distribution boards

To be read in conjunction with EN 60439-1 * Superseded by EN 60439-5:2006

Niederspannungs-Schaltgerätekombinationen - Allgemeine Anforderungen an Niederspannungsverteilungen in Netzstationen

Ensembles d'appareillage à basse tension - Règles générales pour les tableaux de poste basse tension

Low-voltage switchgear and controlgear assemblies - General requirements for low-voltage substation cable distribution boards

General Information

Status
Withdrawn
Publication Date
15-Apr-2004
Withdrawal Date
28-Feb-2007
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
01-Sep-2009
Completion Date
01-Sep-2009

Relations

Buy Standard

Standard
EN 50300:2004
English language
25 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-junij-2004
Low-voltage switchgear and controlgear assemblies - General requirements for
low-voltage substation cable distribution boards
Low-voltage switchgear and controlgear assemblies - General requirements for low-
voltage substation cable distribution boards
Niederspannungs-Schaltgerätekombinationen - Allgemeine Anforderungen an
Niederspannungsverteilungen in Netzstationen
Ensembles d'appareillage à basse tension - Règles générales pour les tableaux de poste
basse tension
Ta slovenski standard je istoveten z: EN 50300:2004
ICS:
29.130.20 Nizkonapetostne stikalne in Low voltage switchgear and
krmilne naprave controlgear
29.240.99 'UXJDRSUHPDY]YH]L] Other equipment related to
RPUHåML]DSUHQRVLQ power transmission and
GLVWULEXFLMRHOHNWULþQHHQHUJLMH distribution networks
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN 50300
NORME EUROPÉENNE
EUROPÄISCHE NORM April 2004
ICS 29.130.20
English version
Low-voltage switchgear and controlgear assemblies –
General requirements for low-voltage
substation cable distribution boards

Ensembles d'appareillage à basse tension - Niederspannungs-
Règles générales pour les tableaux Schaltgerätekombinationen –
de poste basse tension Allgemeine Anforderungen an
Niederspannungsverteilungen in
Netzstationen
This European Standard was approved by CENELEC on 2004-03-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 50300:2004 E
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 17D, Low-voltage
switchgear and controlgear assemblies.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50300 on
2004-03-01.
This European Standard is to be used in conjunction with EN 60439-1:1999.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2005-03-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2007-03-01
__________
– 3 – EN 50300:2004
Contents
Page
Introduction.4
1 General .4
2 Definitions .5
3 Classification of ASSEMBLIES.6
4 Electrical characteristics of ASSEMBLIES .7
5 Information to be given regarding the ASSEMBLY .7
6 Service conditions.7
7 Design and construction.8
8 Test specifications .11
Annex A (normative) Cross-sections of conductors .21

Figures
Figure 101 – Typical enclosure mounting arrangements for mechanical strength tests .22
Figure 102 – Testing arrangement for the verification of resistance to static load .22
Figure 103 – Sandbag for test to verify resistance to shock load .23
Figure 104 – Diagram of test to verify resistance to shock load.23
Figure 105 – Diagram of test to verify resistance to torsional stress .24
Figure 106 – Diagram of test to verify impact force withstand.24
Figure 107 – Diagram of test to verify mechanical strength of door .25
Figure 108 – Striker element for test of resistance to impact by sharp edged objects .25

Tables
Table 101 – List of additional verifications and tests .12
Table 102 – Axial load to be applied to the inserts .16
Table A.1 – Minimum and maximum cross-sections of copper and aluminium
conductors suitable for connection (see 7.1.3.2).21

Introduction
The clauses of this standard supplement, modify or replace clauses in EN 60439-1:1999, Low-voltage
switchgear and controlgear assemblies - Part 1: Type-tested and partially type-tested assemblies.
Where there is no corresponding clause or subclause in this standard, the clause or subclause of the
main document applies without modification.
In view of the fact that this publication is to be read in conjunction with EN 60439-1, the numbering of
its clauses and subclauses correspond with the latter.
Subclauses, figures and tables which are additional to those in EN 60439-1 are numbered starting
from 101.
1 General
1.1 Scope and object
This standard gives supplementary requirements for low voltage switchgear and controlgear
assemblies for public distribution transforming sub-stations. They are stationary, type tested
assemblies (TTA) for installation in places where only authorised persons have access for their use,
however, outdoor types may be installed in situations which may be accessible to the public.
They are connected to the low voltage terminals of distribution transformers by means of connecting
bars, rods or cables and are for use in low voltage public three phase systems.
Individual components such as fuses and switching devices complying with other standards, shall also
comply with the supplementary requirements of this standard.
The object of this standard is to state the definitions and to specify the service conditions, construction
requirements, technical characteristics and tests for Substation Cable Distribution Boards. Network
parameters may require type tests at higher performance levels.
NOTE Where local regulations and practices permit, a Substation Cable Distribution Board to this standard may be used in
other than public networks as agreed between the manufacturer and the user.
1.2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 60068-2-11:1999 Environmental testing -- Part 2: Tests - Test Ka: Salt mist
(IEC 60068-2-11:1981)
EN 60068-2-30:1999 Environmental testing -- Part 2: Tests - Test Db and guidance: Damp heat,
cyclic (12 + 12 hour cycle) (IEC 60068-2-30:1980 + A1:1985)
EN 60238:1998 Edison screw lampholders (IEC 60238:1998)
EN 60269-1:1989 Low-voltage fuses -- Part 1: General requirements (IEC 60269-1:1986)
EN 60439-1:1999 Low-voltage switchgear and controlgear assemblies -- Part 1: Type-tested
and partially type-tested assemblies (IEC 60439-1:1999)

– 5 – EN 50300:2004
and partially type-tested assemblies (IEC 60439-1:1999)
EN 60445:2000 Basic and safety principles for man-machine interface, marking and
identification - Identification of equipment terminals and of terminations of
certain designated conductors, including general rules for an alphanumeric
system (IEC 60445:1999)
EN 60446:1999 Basic and safety principles for man-machine interface, marking and
identification - Identification of conductors by colours or numerals
(IEC 60446:1999)
EN 60529:1991 Degrees of protection provided by enclosures (IP Code) (IEC 60529:1989)
EN 60695-11-10:1999 Fire hazard testing -- Part 11-10: Test flames - 50 W horizontal and vertical
flame test methods (IEC 60695-11-10:1999)
EN ISO 3231:1997 Paints and varnishes - Determination of resistance to humid atmospheres
containing sulfur dioxide (ISO 3231:1993)
EN ISO 4892-2:1999 Plastics - Methods of exposure to laboratory light sources - Part 2: Xenon-arc
sources (ISO 4892-2:1994)
EN ISO 6506 (series) Metallic materials - Brinell hardness test (ISO 6506 series)
ISO 4628-3:1982 Paints and varnishes - Evaluation of degradation of paint coatings -
Designation of intensity, quantity and size of common types of defect –
Part 3: Designation of degree of rusting
ISO 9223:1992 Corrosion of metals and alloys - Corrosivity of atmospheres - Classification
2 Definitions
For the majority of the definitions required in connection with this standard see Clause 2 of EN 60439-1.
For the purpose of this standard the following additional definitions shall apply.
2.1.100 Additional general definitions
2.1.101
substation cable distribution board (SCDB)
ASSEMBLY for stationary installation connected directly or through an incoming circuit to a distribution
transformer. The ASSEMBLY contains busbars connected to the incoming circuit to enable electrical
energy to be distributed to one or more outgoing circuits which may have current breaking and/or
switching devices for the protection and isolation of the outgoing cable or overhead line. It is installed,
operated and maintained solely by skilled persons
2.1.102
SCDB - indoor (SCDB-I)
substation cable distribution board (SCDB) for installation indoors, generally without an enclosure, or
outdoors, in a weather protected enclosure. It comprises structural parts which are suitable for
supporting busbars, a group of functional units, with fuses or switching devices and other ancillary
devices, for the purposes of protecting, controlling and/or connecting one or more outgoing circuits fed
from one or more incoming circuits

2.1.103
substation cable distribution board - outdoor cable connected (SCDB-CCO)
cubicle type substation cable distribution board (SCDB) for outdoor installation which is independently
mounted and connected to the distribution transformer by means of cables
2.1.103.1
SCDB-CCO - ground mounted
SCDB-CCO suitable for outdoor installation at or slightly above ground level in a situation which may
be accessible to the public
2.1.103.2
SCDB-CCO - pole mounted
SCDB-CCO suitable for outdoor installation above ground level on a pole
2.1.104
substation cable distribution board - outdoor transformer mounted (SCDB-TMO)
cubicle type substation cable distribution board (SCDB) for outdoor installation, which is suitable for
fixing to the low voltage flange of a distribution transformer
2.1.104.1
SCDB-TMO - ground mounted
SCDB-TMO which is suitable for fixing to the low voltage flange of a ground mounted distribution
transformer
2.1.104.2
SCDB-TMO - pole mounted
SCDB-TMO which is suitable for fixing to the low voltage flange of a pole mounted distribution
transformer
2.2 Constructional units of ASSEMBLIES
2.2.1
section (see Figure C.4)
Not applicable.
2.2.2
sub-section
Not applicable.
2.2.3
compartment
Not applicable.
3 Classification of ASSEMBLIES
Delete:
- the conditions of installation with respect to mobility (see 2.5.3 and 2.5.4);

– 7 – EN 50300:2004
4 Electrical characteristics of ASSEMBLIES
4.101 Rated current (of a SCDB)
The rated current of a SCDB is that stated by the manufacturer as the rated current of the incoming
circuit. If there is more than one incoming circuit, the rated current of that SCDB is either, the arithmetic
sum of the rated currents of all incoming circuits that are intended to be used simultaneously, or the
rated current of the main phase busbars, whichever is the lower value. This current shall be carried
without the temperature rise of the individual parts exceeding the limits specified in 7.3 when tested
according to 8.2.1.
5 Information to be given regarding the ASSEMBLY
5.1 Nameplates
Replace t) by u) in the third paragraph.
Add to the list at end of the subclause:
u) rated current of the SCDB as defined in 4.101 of this standard.
Nameplates may be placed inside enclosures of SCDB provided their intended place provides good
legibility and visibility when the door is open or the cover is removed.
NOTE Further information may be included by agreement between the user and the manufacturer.
5.2 Markings
Add at the end of the subclause:
It shall be possible to identify the circuit designation of each functional unit in a position clearly visible
from the front of the ASSEMBLY when the door(s), if any, giving access to the operating face, are
open.
In the case of removable fuse-carriers which
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.