Plastics piping systems for water supply and for buried and above ground drainage, sewerage and irrigation under pressure - Oriented unplasticized poly(vinyl chloride) (PVC-O) - Part 5: Fitness for purpose of the system

This part of prEN 17176 specifies the characteristics for the fitness for purpose of oriented unplasticized poly(vinyl chloride) (PVC-O) piping systems intended for water supply, pressurized sewer systems and irrigation systems to be used underground or above-ground where protected to direct sunlight.
In conjunction with prEN 17176-2, prEN 17176-3, EN ISO 1452 3, EN ISO 1452 4 and EN 12842 this part is applicable to PVC-O pipes, PVC-O and PVC-U fittings, cast iron fittings and valves, their joints and to joints with components of other plastics and non-plastics materials intended to be used for the following:
a)   water mains and services lines;
b)   conveyance of water for both outside and inside buildings;
c)   drainage and sewerage under pressure;
d)   irrigation under pressure.
It is applicable to piping systems intended for the supply of water under pressure up to and including 25 °C (cold water) intended for human consumption and for general purposes as well as for waste water and water for irrigation under pressure.
This part of prEN 17176 is also applicable for the conveyance of water, waste water and water for irrigation up to and including 45 °C. For temperatures between 25 °C and 45 °C, prEN 17176-2:2017, Figure C.1 applies.
NOTE    It is the responsibility of the purchaser or specifier to make the appropriate selections from these aspects, taking into account their particular requirements and any relevant national regulations and installation practices or codes.

Kunststoff-Rohrleitungssysteme für die Wasserversorgung und für erdverlegte und nicht erdverlegte Entwässerungs-, Abwasser- und Bewässerungsdruckleitungen - Orientiertes weichmacherfreies Polyvinylchlorid (PVC-O) - Teil 5: Gebrauchstauglichkeit des Systems

Dieser Teil von prEN 17176 legt die Eigenschaften für die Gebrauchstauglichkeit von Rohrleitungssystemen aus orientiertem weichmacherfreiem Polyvinylchlorid (PVC O) fest, die für die Wasserversorgung und für erdverlegte und nicht erdverlegte Abwasser  und Bewässerungsdruckleitungen vorgesehen sind.
Zusammen mit prEN 17176-2, prEN 17176-3, EN ISO 1452-3, EN ISO 1452-4 und EN 12842 gilt dieser Teil für PVC O Rohre, PVC O Formstücke und PVC U Formstücke, Formstücke und Armaturen aus Gusseisen, deren Verbindungen untereinander sowie Verbindungen mit Bauteilen aus anderen Kunststoffen und aus anderen, nicht aus Kunststoff bestehenden Werkstoffen, die für folgende Anwendungsgebiete vorgesehen sind:
a)   Versorgungs  und Hausanschlussleitungen;
b)   Transport von Wasser sowohl außerhalb als auch innerhalb von Gebäuden;
c)   Entwässerung und Abwasser unter Druck;
d)   Bewässerung unter Druck.
Er ist anwendbar auf Rohrleitungssysteme, die für die Versorgung mit Wasser unter Druck bis einschließlich 25 °C (Kaltwasser) für den menschlichen Gebrauch und für allgemeine Zwecke sowie für Abwasser und Wasser zur Bewässerung unter Druck vorgesehen sind.
Dieser Teil von prEN 17176 gilt auch für den Transport von Wasser, Abwasser und Wasser zur Bewässerung bis einschließlich 45 °C. Für Temperaturen zwischen 25 °C und 45 °C gilt prEN 17176-2:2017, Bild C.1.
ANMERKUNG   Der Käufer oder Auftraggeber ist unter Berücksichtigung der eigenen Anforderungen sowie der geltenden nationalen Verordnungen und Verlegeverfahren oder  vorschriften für die entsprechende Auswahl dieser Eigenschaften verantwortlich.

Systèmes de canalisations en plastique pour l’alimentation en eau, les branchements et collecteurs d’assainissement et les systèmes d’irrigation sous pression, enterrés ou aériens - Poly(chlorure de vinyle) non plastifié orienté (PVC-O) - Partie 5 : Aptitude à l’emploi du système

La présente partie de la prEN 17176 spécifie les caractéristiques d’aptitude à l’emploi des systèmes de canalisations en poly(chlorure de vinyle) non plastifié orienté (PVC O) destinés à l’alimentation en eau, aux branchements et collecteurs d’assainissement et aux systèmes d’irrigation sous pression, enterrés ou aériens, lorsqu’ils sont protégés des rayons directs du soleil.
Conjointement avec la prEN 17176 -2 la prEN 17176 -3, l’EN ISO 1452-3, l’EN ISO 1452-4 et l’EN 12842, cette partie s’applique aux tubes en PVC O, aux raccords en PVC-O et en PVC-U, aux raccords et robinets en fonte ainsi qu’à leurs assemblages, et aux assemblages avec des composants à base d’autres matériaux, plastiques ou non plastiques, pouvant être utilisés pour les usages suivants :
a)   les conduites principales et les conduites de branchement ;
b)   le transport de l’eau à l’extérieur et à l’intérieur des bâtiments ;
c)   les branchements et collecteurs d’assainissement sous pression ;
d)   l’irrigation sous pression.
Elle s’applique aux systèmes de canalisations destinés à être utilisés pour l’alimentation en eau sous pression jusqu’à 25 °C (eau froide) inclus, destinée à la consommation humaine et à des usages généraux, mais aussi aux eaux usées et à l’eau pour l’irrigation sous pression.
La présente partie de la prEN 17176 s’applique également au transport de l’eau, des eaux usées et de l’eau pour l’irrigation jusqu’à 45 °C inclus. Pour des températures comprises entre 25 °C et 45 °C, la prEN 17176:2017, Figure C.1 s’applique.
NOTE   Il est de la responsabilité de l’acheteur ou du prescripteur d’effectuer les choix appropriés à partir de ces données, en tenant compte des exigences particulières et de toute réglementation nationale applicable ainsi que des pratiques ou codes de pose.

Cevni sistemi iz polimernih materialov za oskrbo z vodo in za podzemne in nadzemne sisteme odvodnjavanja, kanalizacije ter namakanja pod tlakom - Orientiran nemehčan polivinilklorid (PVC-O) - 5. del: Ustreznost sistema namenu

Ta del standarda prEN 17176 določa lastnosti ustreznosti sistema namenu za orientiran nemehčan polivinilklorid (PVC-O) za podzemne in nadzemne cevne sisteme za oskrbo z vodo, kanalizacijo in namakanje pod tlakom, kjer so ti sistemi zaščiteni pred neposredno sončno svetlobo.
V povezavi s standardi prEN 17176-2, prEN 17176-3, EN ISO 1452 3, EN ISO 1452 4 in EN 12842 se ta del uporablja za cevi iz orientiranega nemehčanega polivinilklorida, fitinge iz orientiranega nemehčanega polivinilklorida in iz PVC-U, ter fitinge in ventile iz litega železa, njihove spoje ter spoje s komponentami iz drugih polimernih in nepolimernih materialov, ki se uporabljajo za:
a) vodovod in priključke na vodovod;
b) prenos vode zunaj in znotraj stavb;
c) odvodnjavanje in kanalizacijo pod tlakom;
d) namakanje pod tlakom.
Uporablja se za cevni sistem, namenjen dovajanju vode pod tlakom do vključno 25 °C (hladna voda), ki je namenjena za pitje in za splošne namene ter tudi za odpadne vode in vode za namakanje pod tlakom.
Ta del standarda prEN 17176 se uporablja tudi za prenos vode, odpadne vode in vode za namakanje s temperaturo do vključno 45 °C. Za temperature med 25 °C in 45 °C se uporablja slika C.1 iz standarda prEN 17176-2:2017.
OPOMBA:    Za ustrezno izbiro teh vidikov je odgovoren kupec ali projektant, pri čemer mora upoštevati posebne zahteve ter vse pomembne nacionalne predpise in prakse ali kodekse vgradnje.

General Information

Status
Published
Public Enquiry End Date
14-Jan-2018
Publication Date
26-May-2019
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
25-Apr-2019
Due Date
30-Jun-2019
Completion Date
27-May-2019

Buy Standard

Standard
EN 17176-5:2019
English language
12 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 17176-5:2019
01-julij-2019
Cevni sistemi iz polimernih materialov za oskrbo z vodo in za podzemne in
nadzemne sisteme odvodnjavanja, kanalizacije ter namakanja pod tlakom -
Orientiran nemehčan polivinilklorid (PVC-O) - 5. del: Ustreznost sistema namenu
Plastics piping systems for water supply and for buried and above ground drainage,
sewerage and irrigation under pressure - Oriented unplasticized poly(vinyl chloride)
(PVC-O) - Part 5: Fitness for purpose of the system
Kunststoff-Rohrleitungssysteme für die Wasserversorgung und für erdverlegte und nicht
erdverlegte Entwässerungs-, Abwasser- und Bewässerungsdruckleitungen - Orientiertes
weichmacherfreies Polyvinylchlorid (PVC-O) - Teil 5: Gebrauchstauglichkeit des Systems
Systèmes de canalisations en plastique pour l’alimentation en eau, les branchements et
collecteurs d’assainissement et les systèmes d’irrigation sous pression, enterrés ou
aériens - Poly(chlorure de vinyle) non plastifié orienté (PVC-O) - Partie 5 : Aptitude à
l’emploi du système
Ta slovenski standard je istoveten z: EN 17176-5:2019
ICS:
23.040.01 Deli cevovodov in cevovodi Pipeline components and
na splošno pipelines in general
91.140.80 Drenažni sistemi Drainage systems
93.030 Zunanji sistemi za odpadno External sewage systems
vodo
SIST EN 17176-5:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 17176-5:2019

---------------------- Page: 2 ----------------------

SIST EN 17176-5:2019


EN 17176-5
EUROPEAN STANDARD

NORME EUROPÉENNE

April 2019
EUROPÄISCHE NORM
ICS 23.040.20; 23.040.45
English Version

Plastics piping systems for water supply and for buried
and above ground drainage, sewerage and irrigation under
pressure - Oriented unplasticized poly(vinyl chloride)
(PVC-O) - Part 5: Fitness for purpose of the system
Systèmes de canalisations en plastique pour Kunststoff-Rohrleitungssysteme für die
l'alimentation en eau, les branchements et collecteurs Wasserversorgung und für erdverlegte und nicht
d'assainissement et les systèmes d'irrigation sous erdverlegte Entwässerungs-, Abwasser- und
pression, enterrés ou aériens - Poly(chlorure de vinyle) Bewässerungsdruckleitungen - Orientiertes
non plastifié orienté (PVC-O) - Partie 5 : Aptitude à weichmacherfreies Polyvinylchlorid (PVC-O) - Teil 5:
l'emploi du système Gebrauchstauglichkeit des Systems
This European Standard was approved by CEN on 14 January 2019.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 17176-5:2019 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 17176-5:2019
EN 17176-5:2019 (E)
Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 6
4 Fitness for purpose of joints and the system . 6
4.1 Assemblies with non-end-load-bearing joints . 6
4.2 Assemblies with end-load-bearing joints . 7
5 Test methods . 8
5.1 Short-term test for leaktightness under internal pressure with angular deflection . 8
5.1.1 Test procedure . 8
5.1.2 Test pressure . 9
5.2 Leaktightness under negative pressure, angular deflection and deformation . 9
5.3 Long-term leaktightness under internal water pressure . 10
5.4 Short-term positive pressure test for leak tightness of assemblies . 11
5.5 Short term negative pressure test for leak tightness of assemblies . 11
5.6 Cycling pressure test for leak tightness of assemblies with cast iron fittings . 11
Bibliography . 12

2

---------------------- Page: 4 ----------------------

SIST EN 17176-5:2019
EN 17176-5:2019 (E)
European foreword
This document (EN 17176-5:2019) has been prepared by Technical Committee CEN/TC 155 “Plastics
piping systems and ducting systems”, the secretariat of which is held by NEN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by September 2019 and conflicting national standards shall
be withdrawn at the latest by September 2019.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent
rights.
EN 17176 consists of the following parts, under the general title Plastics piping systems for water supply
and for buried and above ground drainage, sewerage and irrigation under pressure — Oriented
unplasticized poly(vinyl chloride) (PVC-O):
— Part 1: General;
— Part 2: Pipes;
— Part 3: Fittings (Technical Specification);
— Part 5: Fitness for purpose of the system (this document);
— Part 7: Guidance for assessment of conformity (in preparation).
For valves, see EN ISO 1452-4.
Guidance for installation is given in ISO/TR 4191 [3].
According to the CEN-CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands,
Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
the United Kingdom.
3

---------------------- Page: 5 ----------------------

SIST EN 17176-5:2019
EN 17176-5:2019 (E)
Introduction
The System Standard, of which this is Part 5, specifies the characteristics of the fitness for purpose for a
piping system made from oriented unplasticized poly(vinyl chloride) (PVC-O) and its components. The
piping system is intended to be used for water supply, pressurized drainage, sewerage, treated waste
water and irrigation systems to be used underground or above ground where protected from direct
sunlight.
In respect of potential adverse effects on the quality of water intended for human consumption, caused
by the products covered by this part of EN 17176, the following is relevant:
a) This part of EN 17176 provides no information as to whether or not the products can be used without
restriction.
b) Existing national regulations concerning the use and/or the characteristics of these products remain
in force.
Requirements and test methods for PVC-O components are specified in EN 17176-2 and
CEN/TS 17176-3. For other components (not manufactured from PVC-O) reference is made to the
following standards: EN ISO 1452-3 (PVC-U) and EN 12842 (cast Iron).
This part of EN 17176 specifies the characteristics of fitness for purpose of the plastics piping system
composed of pipes, fittings, ancillaries and their joints.
4

---------------------- Page: 6 ----------------------

SIST EN 17176-5:2019
EN 17176-5:2019 (E)
1 Scope
This part of EN 17176 specifies the characteristics of the fitness for purpose of oriented unplasticized
poly(vinyl chloride) (PVC-O) solid wall piping systems intended for water supply and for buried drainage,
sewerage, treated waste water and irrigation under pressure or above-ground where protected from
direct sunlight. It also specifies the test parameters for the test methods referred to in this document.
NOTE 1 This document is not intended for on-site testing of pipe systems.
In conjunction with EN 17176-1, EN 17176-2, CEN/TS 17176-3 and EN ISO 1452-3, it is applicable to
PVC-O pipes, PVC-O fittings, their joints and to joints with components of other plastics and non-plastics
materials intended to be used for the following:
a) water mains and services lines;
b) conveyance of water for both outside and inside buildings;
c) drainage and sewerage under pressure;
d) irrigation under pressure.
Joints constructed of other materials shall meet their own standards in addition to the fitness of purpose
requirements specified in this document.
It is applicable to piping systems intended for the supply of water with a maximum allowable operating
1)
pressure (PFA) up to and including 25 bar . The piping system according to this document is intended
for the conveyance of cold water up to and including 45 °C and especially in those applications where
special performance requirements are needed, such as impact loads and pressure fluctuations.
For temperatures between 25 °C and 45 °C, EN 17176-2:2019, Figure C.1 applies.
NOTE 2 It is the responsibility of the purchaser or specifier to make the appropriate selections from these
aspects, taking into account their particular requirements and any relevant national regulations and installation
practices or codes.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12842:2012, Ductile iron fittings for PVC-U or PE piping systems — Requirements and test methods
EN 17176-1:2019, Plastics piping systems for water supply and for buried and above ground drainage,
sewerage and irrigation under pressure — Oriented unplasticized poly(vinyl chloride) (PVC-O) — Part 1:
General
EN 17176-2:2019, Plastics piping systems for water supply and for buried and above ground drainage,
sewerage and irrigation under pressure — Oriented unplasticized poly(vinyl chloride) (PVC-O) — Part 2:
Pipes
CEN/TS 17176-3, Plastic piping systems for water supply and for buried and above ground drainage,
sewerage and irrigation under pressure — Oriented unplasticized poly(
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.