SIST-TP CEN/TR 16988:2016
(Main)Estimation of uncertainty in the single burning item test
Estimation of uncertainty in the single burning item test
The measuring technique of the SBI (single burning item) test instrument is based on the observation
that, in general, the heats of combustion per unit mass of oxygen consumed are approximately the same
for most fuels commonly encountered in fires (Huggett [12]). The mass flow, together with the oxygen
concentration in the extraction system, suffices to continuously calculate the amount of heat released.
Some corrections can be introduced if CO2, CO and/or H2O are additionally measured.
Messunsicherheit - Thermische Beanspruchung durch einen einzelnen brennenden Gegenstand (SBI)
Ocena negotovosti s preskusom enega samega gorečega predmeta
Merilna tehnika instrumenta za preskušanje gorljivosti posameznega predmeta (SBI) temelji na ugotovitvi, da je toplota zgorevanja na enoto mase porabljenega kisika na splošno približno enaka za večino goriv, ki so običajna pri požarih (Huggett [12]). Masni pretok skupaj s koncentracijo kisika v sistemu za odvajanje zadostuje za neprekinjeno izračunavanje količine sproščene toplote. Nekateri popravki se lahko uporabijo, če se dodatno izmerijo vrednosti CO2, CO in/ali H2O.
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
SIST-TP CEN/TR 16988:2016
01-november-2016
2FHQDQHJRWRYRVWLVSUHVNXVRPHQHJDVDPHJDJRUHþHJDSUHGPHWD
Estimation of uncertainty in the single burning item test
Messunsicherheit - Thermische Beanspruchung durch einen einzelnen brennenden
Gegenstand (SBI)
Ta slovenski standard je istoveten z: CEN/TR 16988:2016
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
SIST-TP CEN/TR 16988:2016 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST-TP CEN/TR 16988:2016
---------------------- Page: 2 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988
TECHNICAL REPORT
RAPPORT TECHNIQUE
July 2016
TECHNISCHER BERICHT
ICS 17.200.01
English Version
Estimation of uncertainty in the single burning item test
Messunsicherheit - Thermische Beanspruchung durch
einen einzelnen brennenden Gegenstand (SBI)
This Technical Report was approved by CEN on 4 July 2016. It has been drawn up by the Technical Committee CEN/TC 127.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TR 16988:2016 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
Contents Page
European foreword . 4
1 Scope . 5
1.1 General . 5
1.2 Calculation procedure . 5
1.2.1 Introduction . 5
1.2.2 Synchronization of data . 5
1.2.3 Heat output . 5
2 Uncertainty . 9
2.1 Introduction . 9
2.2 Elaboration of terms and concepts . 11
2.2.1 Mean and variance . 11
2.2.2 Estimation of the confidence interval for the population mean . 12
2.2.3 Sources of uncertainty . 12
2.2.4 Standard uncertainties for different distributions . 12
2.2.5 Combined uncertainty . 15
2.2.6 Expanded uncertainty . 16
2.2.7 Uncorrected bias . 16
2.3 Combined standard uncertainties . 17
2.3.1 Combined standard uncertainty on sums . 17
2.3.2 Combined standard uncertainty on averages . 18
2.3.3 Combined standard uncertainty of a product and a division . 19
2.3.4 Combined standard uncertainty on the heat release rate (Q) . 20
2.3.5 Combined standard uncertainty on the depletion factor (ϕ) . 22
D°
2.3.6 Combined standard uncertainty on the initial O -concentration (X ) . 22
2 O2
2.3.7 Combined standard uncertainty on the volume flow rate (V ) . 23
D298
2.3.8 Combined standard uncertainty on the air density (ρ ) . 24
air
2.3.9 Combined standard uncertainty on specimen heat release rate (Qspecimen) . 24
2.3.10 Combined standard uncertainty on the average heat release rate (Q ) . 24
av
2.3.11 Combined standard uncertainty on FIGRA . 25
2.3.12 Combined standard uncertainty on THR600s . 25
2.3.13 Combined standard uncertainty on the volume flow (V(t)) . 25
2.3.14 Combined standard uncertainty on the smoke production rate (SPR) . 25
2.3.15 Combined standard uncertainty on specimen smoke production rate (SPR) . 26
2.3.16 Combined standard uncertainty on the average smoke production rate (SPR ) . 26
av
2.3.17 Combined standard uncertainty on SMOGRA . 26
2.3.18 Combined standard uncertainty on TSP600s . 27
2.4 Confidence interval classification parameters . 27
2.5 Standard uncertainty on the different components . 28
2.5.1 Uncertainty on the data acquisition (DAQ). 28
2.5.2 Transient error . 28
2.5.3 Aliasing error . 28
2.5.4 Uncertainty on data synchronicity . 29
2.5.5 Uncertainty on the component E and E’ . 30
2.5.6 Uncertainty on the component φ . 36
2.5.7 Uncertainty on the component p . 36
atm
2.5.8 Uncertainty on the component T . 36
room
2.5.9 Uncertainty on the component α . 38
2
---------------------- Page: 4 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
2.5.10 Uncertainty on the component c . 38
2.5.11 Uncertainty on the component A and L . 39
2.5.12 Uncertainty on the component q . 40
gas
2.5.13 Uncertainty on the component k . 40
t
2.5.14 Uncertainty on the component k . 43
p
2.5.15 Uncertainty on the component Δp . 44
2.5.16 Uncertainty on the component T . 44
ms
2.5.17 Uncertainty on the component I . 46
Annex A (informative) List of symbols and abbreviations . 48
3
---------------------- Page: 5 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
European foreword
This document (CEN/TR 16988:2016) has been prepared by Technical Committee CEN/TC 127 “Fire
Safety in Buildings”, the secretariat of which is held by BSI.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
4
---------------------- Page: 6 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
1 Scope
1.1 General
The measuring technique of the SBI (single burning item) test instrument is based on the observation
that, in general, the heats of combustion per unit mass of oxygen consumed are approximately the same
for most fuels commonly encountered in fires (Huggett [12]). The mass flow, together with the oxygen
concentration in the extraction system, suffices to continuously calculate the amount of heat released.
Some corrections can be introduced if CO , CO and/or H O are additionally measured.
2 2
1.2 Calculation procedure
1.2.1 Introduction
The main calculation procedures for obtaining the HRR and its derived parameters are summarized
here for convenience. The formulas will be used in the following clauses and especially in the clause on
uncertainty.
The calculations and procedures can be found in full detail in the SBI standard [1].
1.2.2 Synchronization of data
The measured data are synchronized making use of the dips and peaks that occur in the data due to the
switch from ‘primary’ to ‘main’ burner around t = 300 s, i.e. at the start of the thermal attack to the test
specimen. Synchronization is necessary due to the delayed response of the oxygen and carbon dioxide
analysers. The filters, long transport lines, the cooler, etc. in between the gas sample probe and the
analyser unit, cause this shift in time.
After synchronization, all data are shifted so that the ‘main’ burner ignites – by definition – at time
t = 300 s.
1.2.3 Heat output
1.2.3.1 Average heat release rate of the specimen (HRR )
30s
A first step in the calculation of the HRR contribution of the specimen is the calculation of the global
HRR. The global HRR is constituted of the HRR contribution of both the specimen and the burner and is
defined as
φ(t)
′
HRR (t)= EV (t)x (1)
total D298 a_O2
1+ 0,105φ(t)
where
is the total heat release rate of the specimen and burner (kW);
HRR (t)
total
′ is the heat release per unit volume of oxygen consumed at 298 K, = 17 200 (kJ/m3);
E
is the volume flow rate of the exhaust system, normalized at 298 K (m3/s);
Vt()
D298
is the mole fraction of oxygen in the ambient air including water vapour;
x
a_O2
is the oxygen depletion factor.
ϕ()t
φ(t)
The last two terms x and express the amount of moles of oxygen, per unit volume,
a_O2
1+ 0,105φ(t)
that have chemically reacted into some combustion gases. Multiplication with the volume flow gives the
5
---------------------- Page: 7 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
amount of moles of oxygen that have reacted away. Finally this value is multiplied with the ‘Huggett’
factor. Huggett stated that regardless of the fuel burnt roughly a same amount of heat is released.
The volume flow of the exhaust system, normalized at 298 K, V (t) is given by
D298
k Dp(t)
t
V (t)=cA (2)
D298
k T (t)
ρ ms
where
c
0,5 1,5 −0,5
(2T /ρ ) 22, 4 [K⋅ m ⋅ kg ]
00
A is the area of the exhaust duct at the general measurement section (m2);
is the flow profile correction factor; converts the velocity at the height of the bi-directional
k
t
probe in the axis of the duct to the mean velocity over the cross section of the duct;
is the Reynolds number correction for the bidirectional probe, taken as 1,08;
k
ρ
Dpt() is the pressure difference over the bi-directional probe (Pa);
is the temperature in the measurement section (K).
Tt()
ms
The oxygen depletion factor ϕ()t is defined as
xO (30s.90s){1−xCO (t)}−xO (t){1−xCO (30s.90s)}
2 2 2 2
φ(t)= (3)
xO (30s.90s){1−xCO (t)−xO (t)}
2 2 2
where
is the oxygen concentration in mole fraction;
xtO ()
2
is the carbon dioxide concentration in mole fraction;
xtCO ( )
2
Ys.Zs mean taken over interval Y s to Z s.
The mole fraction of oxygen in ambient air, taking into account the moisture content, is given by
H 3816
x = xO (30s.90s) 1− exp 23,2− (4)
a_O2 2
100p T (30s.90s)− 46
ms
where
is the oxygen concentration in mole fraction;
xtO ()
2
H is the relative humidity (%);
p is the ambient pressure (Pa);
Tms(t) is the temperature in the general measurement section (K).
Since we are interested in the HRR contribution of the specimen only, the HRR contribution of the
burner should be subtracted. An estimate of the burner contribution HRR (t) is taken as the
burner
HRR (t) during the base line period preceding the thermal attack to the specimen. A mass flow
total
controller ensures an identical HRR through the burners before and after switching from primary to the
main burner. The average HRR of the burner is calculated as the average HRR (t) during the base line
total
period with the primary burner on (210 s ≤ t ≤ 270 s):
6
=
---------------------- Page: 8 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
HRR = HRR total (210s.270s) (5)
av_burner
where
HRRav_burner is the average heat release rate of the burner (kW);
HRRtotal(t) is the total heat release rate of specimen and burner (kW).
HRR of the specimen
In general, the HRR of the specimen is taken as the global HRR, HRR (t), minus the average HRR of the
total
burner, HRR :
av_burner
For t > 312 s:
HRR(t)= HRR (t)− HRR (6)
total av_burner
where:
HRR(t) is the heat release rate of the specimen (kW);
HRRtotal(t) is the global heat release rate of specimen and burner (kW);
HRRav_burner is the average heat release rate of the burner (kW).
During the switch from the primary to the main burner at the start of the exposure period, the total heat
output of the two burners is less than HRR (it takes some time for the gas to be directed from one
av_burner
burner to the other). Formula (24) gives negative values for HRR(t) for at most 12 s (burner switch
response time). Such negative values and the value for t = 300 s are set to zero, as follows:
For t = 300 s:
HRR(300)= 0 kW (7)
For 300 s < t ≤ 312 s:
HRR(t)= max.{0 kW, HRR (t)− HRR } (8)
total av_burner
where
max.[a, b] is the maximum of two values a and b.
Calculation of HRR
30s
In view of the calculation of the FIGRA index, the HRR data are smoothened with a ‘flat’ 30 s running
average filter using 11 consecutive measurements:
0,5HRR(t−15)+ HRR(t−12 )+ .+ HRR(t+12)+ 0,5HRR(t+15)
(9)
HRR (t)=
30s
10
where
HRR (t) is the average of HRR(t) over 30 s (kW);
30s
HRR(t) is the heat release rate at time t (kW).
1.2.3.2 Calculation of THR(t) and THR
600s
The total heat release of the specimen THR(t) and the total heat release of the specimen in the first
600 s of the exposure period (300 s ≤ t ≤ 900 s), THR , are calculated as follows:
600s
7
---------------------- Page: 9 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
t
a
1
THR(t )= HRR(t)×3 (10)
a ∑
1000
300s
900s
1
THR = HRR(t)×3 (11)
600s ∑
1000
300s
whereby the factor 1 000 is introduced to convert the result from kJ into MJ and the factor 3 stands for
the time interval in-between 2 consecutive measurements,
and where
THR(t ) is the total heat release of the specimen during the period 300 s ≤ t ≤ t (MJ);
a a
HRR(t) is the heat release rate of the specimen (kW);
THR is the total heat release of the specimen during the period 300 s ≤ t ≤ 900 s (MJ);
600s
(equal to THR(900)).
1.2.3.3 Calculation of FIGRA and FIGRA (Fire growth rate indices)
0.2MJ 0.4MJ
The FIGRA is defined as the maximum of the ratio HRR (t)/(t − 300), multiplied by 1 000. The ratio is
av
calculated only for that part of the exposure period in which the threshold levels for HRR and THR
av
have been exceeded. If one or both threshold values are not exceeded during the exposure period,
FIGRA is equal to zero. Two combinations of threshold values are used, resulting in FIGRA and
0,2MJ
FIGRA .
0,4MJ
a) The average of HRR, HRR , used to calculate the FIGRA is equal to HRR , with the exception of the
av 30s
first 12 s of the exposure period. For data points in the first 12 s, the average is taken only over the
widest possible symmetrical range of data points within the exposure period:
For t 300 s: HRR (300 s) 0 (12)
av
For t 303 s: HRR (303 s) HRR(300 s306 s) (13)
av
For t 306 s: HRR (306 s) HRR(300 s312 s) (14)
av
For t 309 s: HRR (309 s) HRR(300 s318 s) (15)
av
For t 312 s: HRR (312 s) HRR(300 s324 s) (16)
av
For t≥=315 s: HRR (tt) HRR ( ) (17)
av 30s
b) Calculate FIGRA for all t where:
0,2MJ
(HRR (t) > 3 kW) and (THR(t) > 0,2 MJ) and (300 s < t ≤ 1 500 s);
av
and calculate FIGRA for all t where:
0,4MJ
(HRRav(t) > 3 kW) and (THR(t) > 0,4 MJ) and (300 s < t ≤ 1 500 s);
both using:
8
==
==
==
==
==
---------------------- Page: 10 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
HRR (t)
av
FIGRA=1000× max. (18)
t− 300
where:
FIGRA is the fire growth rate index
HRR (t) is the average of HRR(t) as specified in a) (kW);
av
As a consequence, specimens with a HRR not exceeding 3 kW during the total test have FIGRA values
av
FIGRA and FIGRA equal to zero. Specimens with a THR not exceeding 0,2 MJ over the total test
0,2MJ 0,4MJ
period have a FIGRA equal to zero and specimen with a THR not exceeding 0,4 MJ over the total test
0,2MJ
period have a FIGRA equal to zero.
0,4MJ
2 Uncertainty
2.1 Introduction
According to EN ISO/IEC 17025 [3], which sets out the general requirements for the competence of
testing and calibration laboratories, and EN ISO 10012 [7], which sets out the requirements for assuring
the quality of measuring equipment, uncertainties shall be reported in both testing and calibration
reports.
The general principles for evaluating and reporting uncertainties are given in the ISO Guide to the
Expression of Uncertainty in Measurement (GUM) [6], but need to be applied to the specific case of fire
testing. Due to the harmonization of fire testing in the European Community (EUROCLASSES;
EN 13501-1 [21]) and the pressure on testing laboratories to operate under accreditation, this is
becoming even more important.
It is of common knowledge that measurement results are never perfectly accurate. In practice the
sources of systematic and random errors which can affect the results of measurement are numerous,
even for the most careful operators. To describe this lack of perfection, the term 'uncertainty' is used.
Although the concept of uncertainty may be related to a 'doubt', in the real sense the knowledge of
uncertainty implies increased confidence in the validity of results.
The qualitative concept of accuracy is quantified by the uncertainty which varies inversely
‘proportioned’ to it. Accuracy consists of both trueness and precision as shown in Figure 1. A numerical
measure for precision is the standard deviation, while trueness is expressed numerically by the
systematic error or the bias.
It is considered good practice to eliminate any systematic errors. However, if the value of a systematic
error is unknown it may be regarded as a random error. Random errors result in a spread of the values
and can usually be reduced by increasing the number of observations. Its expectation or expected value
is zero.
9
---------------------- Page: 11 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
high precision low precision
high
trueness
(high accuracy)
low
trueness
Figure 1 — Concepts of accuracy (uncertainty), precision (standard deviation) and trueness
(bias)
In general, the result of a measurement is only an approximation or estimate of the value of the specific
quantity subject to measurement, that is, the measurand, and so the result is complete only when
accompanied by a quantitative statement of its uncertainty.
Without knowledge of the accuracy (trueness and precision) of measurement methods and/or the
uncertainty of measurement results, it can appear very easy to make decisions. But, in practice, these
decisions might be incorrect and sometimes lead to serious consequences, if the measurement
uncertainty is not taken into account.
For example, in fire testing, when rejecting instead of accepting a good product during a certification
process or, conversely, when accepting a bad product by error. So, it is vital to quantify the reliability of
the measurement results to greatly reduce any disputes and adverse consequences of legal proceedings.
This is of particular importance if the growing number of cases of litigation in Europe and the liability
problems of manufacturers in case of accidents are considered.
The difference between error and uncertainty should always be borne in mind. For example, the result
of a measurement after correction can unknowably be very close to the unknown value of the
measurand, and thus have negligible error, even though it might have a large uncertainty.
10
---------------------- Page: 12 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
Key
X value
Y frequency
1 bias
2 repeated measurements would give values with this frequency curve
3 standard deviation (σ)
4 true value
5 expected value
Figure 2 — Concepts of accuracy (uncertainty), precision (standard deviation) and trueness
(bias)
2.2 Elaboration of terms and concepts
2.2.1 Mean and variance
A population with a ‘normal’ probability density function is characterized by its mean value μ and its
2 2 2
variance σ : N(μ,σ ). When both μ and σ are unknown, they can be estimated by taking a number n of
2
samples and by calculating the estimated mean x , the estimated variance s and the estimated
standard deviation s.
n
1
(19)
x= x
∑
i
n
i=1
n
1
2
2
( ) (20)
s = x−x
∑
i
n−1
i=1
If a covariance exists between two variables x and y, it is given by
n
1
2
s = (x−x)(y− y) (21)
ij ∑ i i
n−1
i=1
11
---------------------- Page: 13 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
2.2.2 Estimation of the confidence interval for the population mean
Often the standard deviation σ is unknown. To evaluate the confidence interval, some estimate of σ shall
be made. The most obvious candidate is the sample standard deviation s. But the use of s introduces an
additional source of unreliability, especially if the sample is small. To retain the confidence interval, the
interval shall therefore be widened. This is done by using the t distribution instead of the standard
normal distribution. For a sample size larger than 100, the t-distribution approaches the normal
distribution. For a 95 % (two tails of 2,5 %) confidence interval – which we strive for – the uncertainty
is estimated by
s
t (22)
0.025
n
2
The value t depends on the amount of information used in calculating s , i.e. on the degrees of
0.025
freedom. For large sample sizes, t approaches 1,96 which is the value for a normal distribution. For a
0.025
normal distribution, a coverage factor 2 (1,96) corresponds to a 95 % confidence interval (see 2.2.6).
2.2.3 Sources of uncertainty
According to GUM [6] any detailed report of the uncertainty should consist of a complete list of the
components, specifying for each the method used to obtain its numerical value. The components may be
grouped into two categories based on their method of evaluation:
2
Type A The components in category A are characterized by the estimated variances s
i
or by the estimated standard deviation s derived from data by statistical
i
2
methods. Where appropriate the covariance s should be given.
ij
For such a component, the standard uncertainty is ui = si.
Type B The standard uncertainty of a Type B evaluation is approximated based on
specifications, calibrations, handbooks, experience, judgements etc. and is
represented by a quantity uj. It is obtained from an assumed probability
distribution based on all the available information.
Where appropriate the covariance should be given and should be treated in a
similar way.
The ‘type’ classification does not indicate any difference in the nature of the components resulting from
the two types of evaluation. Both are based on probability distributions, and the uncertainty
components resulting from either type are quantified by standard deviations. It should be recognized
that a Type B evaluation of standard uncertainty can be as reliable as a Type A evaluation.
The standard deviation of a Type B evaluation is based on the shape of the distribution. Distributions
used in this dcoument are the rectangular, the triangular, the trapezoidal and the normal distribution.
For the rectangular and triangular also asymmetric distributions are discussed.
2.2.4 Standard uncertainties for different distributions
Normal distribution
Often calibration certificates, handbooks, manufacturer’s specifications, etc. state a particular multiple
of a standard deviation. In this case, a normal distribution is assumed to obtain the standard
uncertainty.
Rectangular distribution
In other cases the probability that the value of X lies within the interval a- to a+ for all practical
i
purposes is equal to one and the probability that X lies outside this interval is essentially zero. If there
i
is no specific knowledge about the possible values of X within the interval, a uniform or rectangular
i
12
---------------------- Page: 14 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
distribution of values is assumed. The associated standard deviation is function of the width of the
distribution as:
a
(23)
u =
rect
3
Indeed, for a rectangular distribution, the variance is obtained as in 24. Given the probability function of
the rectangular distribution
0 x
1
Vitryalice1P(x)= a< x
b−a
0 x>b
This can be written in terms of the Heaviside step function H(x) as
H (x−a)−H (x−b)
P(x)= (25)
b−a
2
This makes that the variance σ with population mean μ for an asymmetric distribution becomes
∞ b
x b+a
µ= P(x)xdx= dx= (26)
∫ ∫
(b−a) 2
−∞ a
∞
2 2
σ = P(x)(x−µ) dx (27)
∫
−∞
∞
H (x−a)−H (x−b) a+b
2 2
(28)
σ = (x− ) dx
∫
b−a 2
−∞
a+b
2
b (x− ) 2
(a+b)
2
2
σ = dx= (29)
∫
b−a 12
a
So for a symmetric rectangular interval a- to a+, the variance reduces to
2
a
2
σ = . (30)
3
The sample estimate of the standard deviation thus is:
a
u = . (31)
rect
3
13
---------------------- Page: 15 ----------------------
SIST-TP CEN/TR 16988:2016
CEN/TR 16988:2016 (E)
The rectangular distribution is a reasonable default model in the absence of any other information. But
if it is known that values of the quantity in question near the centre of the limits are more likely than
values close to the limits, a triangular or a normal distribution migth be a better model.
Triangular and trapezoidal distribution
In many cases it is more realistic to expect that values near the bounds are less likely than those near
the midpoint. It is then reasonable to replace the symmetric rectangular distribution by a symmetric
trapezoidal distribution having
...
SLOVENSKI STANDARD
kSIST-TP FprCEN/TR 16988:2016
01-maj-2016
2FHQDQHJRWRYRVWLVSUHVNXVRPHQHJDVDPHJDJRUHþHJDSUHGPHWD
Estimation of uncertainty in the single burning item test
Messunsicherheit - Thermische Beanspruchung durch einen einzelnen brennenden
Gegenstand (SBI)
Ta slovenski standard je istoveten z: FprCEN/TR 16988
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
kSIST-TP FprCEN/TR 16988:2016 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
kSIST-TP FprCEN/TR 16988:2016
---------------------- Page: 2 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FINAL DRAFT
TECHNICAL REPORT
FprCEN/TR 16988
RAPPORT TECHNIQUE
TECHNISCHER BERICHT
March 2016
ICS 17.200.01
English Version
Estimation of uncertainty in the single burning item test
Messunsicherheit - Thermische Beanspruchung durch
einen einzelnen brennenden Gegenstand (SBI)
This draft Technical Report is submitted to CEN members for Vote. It has been drawn up by the Technical Committee CEN/TC
127.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a Technical Report. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a Technical Report.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CEN All rights of exploitation in any form and by any means reserved Ref. No. FprCEN/TR 16988:2016 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
Contents Page
European foreword . 4
1 Scope . 5
1.1 General . 5
1.2 Calculation procedure . 5
1.2.1 Introduction . 5
1.2.2 Synchronization of data . 5
1.2.3 Heat output . 5
2 Uncertainty . 9
2.1 Introduction . 9
2.2 Elaboration of terms and concepts . 11
2.2.1 Mean and variance . 11
2.2.2 Estimation of the confidence interval for the population mean . 12
2.2.3 Sources of uncertainty . 12
2.2.4 Standard uncertainties for different distributions . 12
2.2.5 Combined uncertainty . 15
2.2.6 Expanded uncertainty . 16
2.2.7 Uncorrected bias . 16
2.3 Combined standard uncertainties . 18
2.3.1 Combined standard uncertainty on sums . 18
2.3.2 Combined standard uncertainty on averages . 18
2.3.3 Combined standard uncertainty of a product and a division . 19
2.3.4 Combined standard uncertainty on the heat release rate (Q) . 20
2.3.5 Combined standard uncertainty on the depletion factor (ϕ) . 22
D°
2.3.6 Combined standard uncertainty on the initial O -concentration (X ) . 22
2 O2
2.3.7 Combined standard uncertainty on the volume flow rate (V ) . 23
D298
2.3.8 Combined standard uncertainty on the air density (ρ ) . 24
air
2.3.9 Combined standard uncertainty on specimen heat release rate (Qspecimen) . 24
2.3.10 Combined standard uncertainty on the average heat release rate (Q ) . 25
av
2.3.11 Combined standard uncertainty on FIGRA . 25
2.3.12 Combined standard uncertainty on THR600s . 25
2.3.13 Combined standard uncertainty on the volume flow (V(t)) . 25
2.3.14 Combined standard uncertainty on the smoke production rate (SPR) . 25
2.3.15 Combined standard uncertainty on specimen smoke production rate (SPR) . 26
2.3.16 Combined standard uncertainty on the average smoke production rate (SPR ) . 26
av
2.3.17 Combined standard uncertainty on SMOGRA . 26
2.3.18 Combined standard uncertainty on TSP600s . 27
2.4 Confidence interval classification parameters . 27
2.5 Standard uncertainty on the different components . 28
2.5.1 Uncertainty on the data acquisition (DAQ). 28
2.5.2 Transient error . 28
2.5.3 Aliasing error . 28
2.5.4 Uncertainty on data synchronicity . 29
2.5.5 Uncertainty on the component E and E’ . 30
2.5.6 Uncertainty on the component φ . 36
2.5.7 Uncertainty on the component p . 36
atm
2.5.8 Uncertainty on the component T . 36
room
2.5.9 Uncertainty on the component α . 38
2
---------------------- Page: 4 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
2.5.10 Uncertainty on the component c . 38
2.5.11 Uncertainty on the component A and L . 39
2.5.12 Uncertainty on the component q . 40
gas
2.5.13 Uncertainty on the component k . 40
t
2.5.14 Uncertainty on the component k . 43
p
2.5.15 Uncertainty on the component Δp . 44
2.5.16 Uncertainty on the component T . 44
ms
2.5.17 Uncertainty on the component I . 46
Annex A (informative) List of symbols and abbreviations . 48
Bibliography . 52
3
---------------------- Page: 5 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
European foreword
This document (FprCEN/TR 16988:2016) has been prepared by Technical Committee CEN/TC 127
“Fire Safety in Buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the vote.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
4
---------------------- Page: 6 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
1 Scope
1.1 General
The measuring technique of the SBI (single burning item) test instrument is based on the observation
that, in general, the heats of combustion per unit mass of oxygen consumed are approximately the same
for most fuels commonly encountered in fires (Huggett [12]). The mass flow, together with the oxygen
concentration in the extraction system, suffices to continuously calculate the amount of heat released.
Some corrections can be introduced if CO , CO and/or H O are additionally measured.
2 2
1.2 Calculation procedure
1.2.1 Introduction
The main calculation procedures for obtaining the HRR and its derived parameters are summarized
here for convenience. The formulas will be used in the following clauses and especially in the clause on
uncertainty.
The calculations and procedures can be found in full detail in the SBI standard [1].
1.2.2 Synchronization of data
The measured data are synchronized making use of the dips and peaks that occur in the data due to the
switch from ‘primary’ to ‘main’ burner around t = 300 s, i.e. at the start of the thermal attack to the test
specimen. Synchronization is necessary due to the delayed response of the oxygen and carbon dioxide
analysers. The filters, long transport lines, the cooler, etc. in between the gas sample probe and the
analyser unit, cause this shift in time.
After synchronization, all data are shifted so that the ‘main’ burner ignites – by definition – at time
t = 300 s.
1.2.3 Heat output
1.2.3.1 Average heat release rate of the specimen (HRR )
30s
A first step in the calculation of the HRR contribution of the specimen is the calculation of the global
HRR. The global HRR is constituted of the HRR contribution of both the specimen and the burner and is
defined as
φ(t)
′
HRR (t)= EV (t)x (1)
total D298 a_O2
1+ 0,105φ(t)
where
is the total heat release rate of the specimen and burner (kW);
HRR (t)
total
3
′ is the heat release per unit volume of oxygen consumed at 298 K, = 17 200 (kJ/m );
E
3
is the volume flow rate of the exhaust system, normalized at 298 K (m /s);
Vt()
D298
is the mole fraction of oxygen in the ambient air including water vapour;
x
a_O2
is the oxygen depletion factor.
ϕ()t
φ(t)
The last two terms x and express the amount of moles of oxygen, per unit volume,
a_O2
1+ 0,105φ(t)
that have chemically reacted into some combustion gases. Multiplication with the volume flow gives the
5
---------------------- Page: 7 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
amount of moles of oxygen that have reacted away. Finally this value is multiplied with the ‘Huggett’
factor. Huggett stated that regardless of the fuel burnt roughly a same amount of heat is released.
The volume flow of the exhaust system, normalized at 298 K, V (t) is given by
D298
k Dp(t)
t
V (t)=cA (2)
D298
k T (t)
ρ ms
where
c 0,5 1,5 −0,5
(2T /ρ ) 22, 4 [K⋅ m ⋅ kg ]
00
2
A is the area of the exhaust duct at the general measurement section (m );
is the flow profile correction factor; converts the velocity at the height of the bi-directional
k
t
probe in the axis of the duct to the mean velocity over the cross section of the duct;
is the Reynolds number correction for the bidirectional probe, taken as 1,08;
k
ρ
Dpt() is the pressure difference over the bi-directional probe (Pa);
is the temperature in the measurement section (K).
Tt()
ms
The oxygen depletion factor ϕ()t is defined as
xO (30s.90s){1−xCO (t)}−xO (t){1−xCO (30s.90s)}
2 2 2 2
φ(t)= (3)
xO (30s.90s){1−xCO (t)−xO (t)}
2 2 2
where
is the oxygen concentration in mole fraction;
xtO ()
2
is the carbon dioxide concentration in mole fraction;
xtCO ( )
2
Ys.Zs mean taken over interval Y s to Z s.
The mole fraction of oxygen in ambient air, taking into account the moisture content, is given by
H 3816
x = xO (30s.90s) 1− exp 23,2−
a_O2 2
100p T (30s.90s)− 46
ms
(4)
where
is the oxygen concentration in mole fraction;
xtO ()
2
H is the relative humidity (%);
p is the ambient pressure (Pa);
T (t) is the temperature in the general measurement section (K).
ms
Since we are interested in the HRR contribution of the specimen only, the HRR contribution of the
burner should be subtracted. An estimate of the burner contribution HRR (t) is taken as the
burner
HRR (t) during the base line period preceding the thermal attack to the specimen. A mass flow
total
controller ensures an identical HRR through the burners before and after switching from primary to the
main burner. The average HRR of the burner is calculated as the average HRR (t) during the base line
total
period with the primary burner on (210 s ≤ t ≤ 270 s):
6
=
---------------------- Page: 8 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
HRR = HRR total (210s.270s) (5)
av_burner
where
HRR is the average heat release rate of the burner (kW);
av_burner
HRR (t) is the total heat release rate of specimen and burner (kW).
total
HRR of the specimen
In general, the HRR of the specimen is taken as the global HRR, HRR (t), minus the average HRR of the
total
burner, HRR :
av_burner
For t > 312 s:
HRR(t)= HRR (t)− HRR (6)
total av_burner
where:
HRR(t) is the heat release rate of the specimen (kW);
HRR (t) is the global heat release rate of specimen and burner (kW);
total
HRR is the average heat release rate of the burner (kW).
av_burner
During the switch from the primary to the main burner at the start of the exposure period, the total heat
output of the two burners is less than HRR (it takes some time for the gas to be directed from one
av_burner
burner to the other). Formula (24) gives negative values for HRR(t) for at most 12 s (burner switch
response time). Such negative values and the value for t = 300 s are set to zero, as follows:
For t = 300 s:
HRR(300)= 0 kW (7)
For 300 s < t ≤ 312 s:
HRR(t)= max.{0 kW, HRR (t)− HRR }
total av_burner
(8)
where
max.[a, b] is the maximum of two values a and b.
Calculation of HRR
30s
In view of the calculation of the FIGRA index, the HRR data are smoothened with a ‘flat’ 30 s running
average filter using 11 consecutive measurements:
0,5HRR(t−15)+ HRR(t−12 )+ .+ HRR(t+12)+ 0,5HRR(t+15)
HRR (t)= (9)
30s
10
where
HRR (t) is the average of HRR(t) over 30 s (kW);
30s
HRR(t) is the heat release rate at time t (kW).
7
---------------------- Page: 9 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
1.2.3.2 Calculation of THR(t) and THR
600s
The total heat release of the specimen THR(t) and the total heat release of the specimen in the first
600 s of the exposure period (300 s ≤ t ≤ 900 s), THR , are calculated as follows:
600s
t
a
1
THR(t )= HRR(t)×3 (10)
a ∑
1000
300s
900s
1
THR = HRR(t)×3 (11)
600s ∑
1000
300s
whereby the factor 1 000 is introduced to convert the result from kJ into MJ and the factor 3 stands for
the time interval in-between 2 consecutive measurements,
and where
THR(t ) is the total heat release of the specimen during the period 300 s ≤ t ≤ t (MJ);
a a
HRR(t) is the heat release rate of the specimen (kW);
THR is the total heat release of the specimen during the period 300 s ≤ t ≤ 900 s (MJ); (equal to
600s
THR(900)).
1.2.3.3 Calculation of FIGRA and FIGRA (Fire growth rate indices)
0.2MJ 0.4MJ
The FIGRA is defined as the maximum of the ratio HRR (t)/(t − 300), multiplied by 1 000. The ratio is
av
calculated only for that part of the exposure period in which the threshold levels for HRR and THR
av
have been exceeded. If one or both threshold values are not exceeded during the exposure period,
FIGRA is equal to zero. Two combinations of threshold values are used, resulting in FIGRA and
0,2MJ
FIGRA .
0,4MJ
a) The average of HRR, HRR , used to calculate the FIGRA is equal to HRR , with the exception of the
av 30s
first 12 s of the exposure period. For data points in the first 12 s, the average is taken only over the
widest possible symmetrical range of data points within the exposure period:
For t 300 s: HRR (300 s) 0 (12)
av
For t 303 s: HRR (303 s) HRR(300 s306 s) (13)
av
For t 306 s: HRR (306 s) HRR(300 s312 s) (14)
av
For t 309 s: HRR (309 s) HRR(300 s318 s) (15)
av
For t 312 s: HRR (312 s) HRR(300 s324 s) (16)
av
For t≥=315 s: HRR (tt) HRR ( ) (17)
av 30s
b) Calculate FIGRA for all t where:
0,2MJ
(HRR (t) > 3 kW) and (THR(t) > 0,2 MJ) and (300 s < t ≤ 1 500 s);
av
and calculate FIGRA for all t where:
0,4MJ
8
==
==
==
==
==
---------------------- Page: 10 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
(HRR (t) > 3 kW) and (THR(t) > 0,4 MJ) and (300 s < t ≤ 1 500 s);
av
both using:
HRR (t)
av
(18)
FIGRA=1000× max.
t− 300
where:
FIGRA is the fire growth rate index
HRR (t) is the average of HRR(t) as specified in a) (kW);
av
As a consequence, specimens with a HRR not exceeding 3 kW during the total test have FIGRA values
av
FIGRA and FIGRA equal to zero. Specimens with a THR not exceeding 0,2 MJ over the total test
0,2MJ 0,4MJ
period have a FIGRA equal to zero and specimen with a THR not exceeding 0,4 MJ over the total test
0,2MJ
period have a FIGRA equal to zero.
0,4MJ
2 Uncertainty
2.1 Introduction
According to EN ISO/IEC 17025 [3], which sets out the general requirements for the competence of
testing and calibration laboratories, and EN ISO 10012 [7], which sets out the requirements for assuring
the quality of measuring equipment, uncertainties shall be reported in both testing and calibration
reports.
The general principles for evaluating and reporting uncertainties are given in the ISO Guide to the
Expression of Uncertainty in Measurement (GUM) [6], but need to be applied to the specific case of fire
testing. Due to the harmonization of fire testing in the European Community (EUROCLASSES;
EN 13501-1 [21]) and the pressure on testing laboratories to operate under accreditation, this is
becoming even more important.
It is of common knowledge that measurement results are never perfectly accurate. In practice the
sources of systematic and random errors which can affect the results of measurement are numerous,
even for the most careful operators. To describe this lack of perfection, the term 'uncertainty' is used.
Although the concept of uncertainty may be related to a 'doubt', in the real sense the knowledge of
uncertainty implies increased confidence in the validity of results.
The qualitative concept of accuracy is quantified by the uncertainty which varies inversely
‘proportioned’ to it. Accuracy consists of both trueness and precision as shown in Figure 1. A numerical
measure for precision is the standard deviation, while trueness is expressed numerically by the
systematic error or the bias.
It is considered good practice to eliminate any systematic errors. However, if the value of a systematic
error is unknown it may be regarded as a random error. Random errors result in a spread of the values
and can usually be reduced by increasing the number of observations. Its expectation or expected value
is zero.
9
---------------------- Page: 11 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
high precision low precision
high
trueness
(high accuracy)
low
trueness
Figure 1 — Concepts of accuracy (uncertainty), precision (standard deviation) and trueness
(bias)
In general, the result of a measurement is only an approximation or estimate of the value of the specific
quantity subject to measurement, that is, the measurand, and so the result is complete only when
accompanied by a quantitative statement of its uncertainty.
Without knowledge of the accuracy (trueness and precision) of measurement methods and/or the
uncertainty of measurement results, it can appear very easy to make decisions. But, in practice, these
decisions might be incorrect and sometimes lead to serious consequences, if the measurement
uncertainty is not taken into account.
For example, in fire testing, when rejecting instead of accepting a good product during a certification
process or, conversely, when accepting a bad product by error. So, it is vital to quantify the reliability of
the measurement results to greatly reduce any disputes and adverse consequences of legal proceedings.
This is of particular importance if the growing number of cases of litigation in Europe and the liability
problems of manufacturers in case of accidents are considered.
The difference between error and uncertainty should always be borne in mind. For example, the result
of a measurement after correction can unknowably be very close to the unknown value of the
measurand, and thus have negligible error, even though it might have a large uncertainty.
10
---------------------- Page: 12 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
Key
X value
Y frequency
1 bias
2 repeated measurements would give values with this frequency curve
3 standard deviation (σ)
4 true value
5 expected value
Figure 2 — Concepts of accuracy (uncertainty), precision (standard deviation) and trueness
(bias)
2.2 Elaboration of terms and concepts
2.2.1 Mean and variance
A population with a ‘normal’ probability density function is characterized by its mean value μ and its
2 2 2
variance σ : N(μ,σ ). When both μ and σ are unknown, they can be estimated by taking a number n of
2
samples and by calculating the estimated mean x , the estimated variance s and the estimated
standard deviation s.
n
1
(19)
x= x
∑
i
n
i=1
n
1
2
2
( ) (20)
s = x−x
∑
i
n−1
i=1
If a covariance exists between two variables x and y, it is given by
11
---------------------- Page: 13 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
n
1
2
s = (x−x)(y− y) (21)
ij ∑ i i
n−1
i=1
2.2.2 Estimation of the confidence interval for the population mean
Often the standard deviation σ is unknown. To evaluate the confidence interval, some estimate of σ shall
be made. The most obvious candidate is the sample standard deviation s. But the use of s introduces an
additional source of unreliability, especially if the sample is small. To retain the confidence interval, the
interval shall therefore be widened. This is done by using the t distribution instead of the standard
normal distribution. For a sample size larger than 100, the t-distribution approaches the normal
distribution. For a 95 % (two tails of 2,5 %) confidence interval – which we strive for – the uncertainty
is estimated by
s
t (22)
0.025
n
2
The value t depends on the amount of information used in calculating s , i.e. on the degrees of
0.025
freedom. For large sample sizes, t approaches 1,96 which is the value for a normal distribution. For a
0.025
normal distribution, a coverage factor 2 (1,96) corresponds to a 95 % confidence interval (see 2.2.6).
2.2.3 Sources of uncertainty
According to GUM [6] any detailed report of the uncertainty should consist of a complete list of the
components, specifying for each the method used to obtain its numerical value. The components may be
grouped into two categories based on their method of evaluation:
2
Type A The components in category A are characterized by the estimated variances s or by
i
the estimated standard deviation s derived from data by statistical methods. Where
i
2
appropriate the covariance s should be given.
ij
For such a component, the standard uncertainty is u = s .
i i
Type B The standard uncertainty of a Type B evaluation is approximated based on
specifications, calibrations, handbooks, experience, judgements etc. and is
represented by a quantity u . It is obtained from an assumed probability distribution
j
based on all the available information.
Where appropriate the covariance should be given and should be treated in a similar
way.
The ‘type’ classification does not indicate any difference in the nature of the components resulting from
the two types of evaluation. Both are based on probability distributions, and the uncertainty
components resulting from either type are quantified by standard deviations. It should be recognized
that a Type B evaluation of standard uncertainty can be as reliable as a Type A evaluation.
The standard deviation of a Type B evaluation is based on the shape of the distribution. Distributions
used in this dcoument are the rectangular, the triangular, the trapezoidal and the normal distribution.
For the rectangular and triangular also asymmetric distributions are discussed.
2.2.4 Standard uncertainties for different distributions
Normal distribution
Often calibration certificates, handbooks, manufacturer’s specifications, etc. state a particular multiple
of a standard deviation. In this case, a normal distribution is assumed to obtain the standard
uncertainty.
Rectangular distribution
12
---------------------- Page: 14 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
In other cases the probability that the value of X lies within the interval a- to a+ for all practical
i
purposes is equal to one and the probability that X lies outside this interval is essentially zero. If there
i
is no specific knowledge about the possible values of X within the interval, a uniform or rectangular
i
distribution of values is assumed. The associated standard deviation is function of the width of the
distribution as:
a
u = (23)
rect
3
Indeed, for a rectangular distribution, the variance is obtained as in 24. Given the probability function of
the rectangular distribution
0 x
1
Vitryalice1P(x)= a< x
b−a
0 x>b
This can be written in terms of the Heaviside step function H(x) as
H (x−a)−H (x−b)
P(x)= (25)
b−a
2
This makes that the variance σ with population mean μ for an asymmetric distribution becomes
∞ b
x b+a
µ= P(x)xdx= dx= (26)
∫ ∫
(b−a) 2
−∞ a
∞
2 2
σ = P(x)(x−µ) dx (27)
∫
−∞
∞
H (x−a)−H (x−b) a+b
2 2
(28)
σ = (x− ) dx
∫
b−a 2
−∞
a+b
2
b (x− ) 2
(a+b)
2
2
σ = dx= (29)
∫
b−a 12
a
So for a symmetric rectangular interval a- to a+, the variance reduces to
2
a
2
σ = . (30)
3
The sample estimate of the standard deviation thus is:
13
---------------------- Page: 15 ----------------------
kSIST-TP FprCEN/TR 16988:2016
FprCEN/TR 16988:2016 (E)
a
u = . (31)
rect
3
The rectangular distribution is a reasonable default model in the absence o
...