Automatic electrical controls for household and similar use - Part 1: General requirements

In general, this part of IEC 60730 applies to automatic electrical controls for use in, on, or in
association with equipment for household and similar use. The equipment may use electricity,
gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof.
NOTE 1 Throughout this standard the word "equipment" means "appliance and equipment."
EXAMPLE 1 Controls for appliances within the scope of IEC 60335.
This International Standard is applicable to controls for building automation within the scope
of ISO 16484.
This standard also applies to automatic electrical controls for equipment that may be used
by the public, such as equipment intended to be used in shops, offices, hospitals, farms and
commercial and industrial applications.
EXAMPLE 2 Controls for commercial catering, heating and air-conditioning equipment.
This standard is also applicable to individual controls utilized as part of a control system or
controls which are mechanically integral with multifunctional controls having non-electrical
outputs.
EXAMPLE 3 Independently mounted water valves, controls in smart grid systems and controls for building
automation systems within the scope of ISO 16484-2.
This standard is also applicable to relays when used as controls for IEC 60335 appliances.
Additional requirements for the safety and operating values of relays when used as controls
for IEC 60335 appliances are contained in Annex U.
NOTE 2 These requirements are referred to in the scope of IEC 61810-1.
NOTE 3 This standard is intended to be used for the testing of any stand-alone relay which is intended to be used
as a control of an appliance according to IEC 60335-1. It is not intended to be used for any other stand-alone
relay, or to replace the IEC 61810 series of standards.
This standard does not apply to automatic electrical controls intended exclusively for
industrial process applications unless explicitly mentioned in the relevant part 2 or the
equipment standard.

Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche Anwendungen - Teil 1: Allgemeine Anforderungen

Dispositifs de commande électrique automatiques - Partie 1: Exigences générales

La IEC 60730-1:2013 s'applique aux dispositifs de commande électrique automatiques destinés à être utilisés dans, sur, ou avec des équipements à usage domestique et analogue. Les matériels peuvent utiliser l'électricité, le gaz, le pétrole, des combustibles solides, l'énergie thermique solaire, etc., ou une combinaison de ces sources d'énergie. La présente norme s'applique aux dispositifs de commande pour l'automatisation du bâtiment relevant du domaine d'application de l'ISO 16484. La présente norme s'applique également aux dispositifs de commande électriques automatiques des équipements qui peuvent être utilisés par le public (les équipements destinés à être utilisés dans des magasins, des bureaux, des hôpitaux, des fermes et des applications commerciales et industrielles, par exemple). La présente norme est également applicable aux dispositifs de commande individuels utilisés comme partie d'un système de commande ou de dispositifs de commande solidaires mécaniquement de dispositifs de commande multifonctions ayant des sorties non électriques. La présente norme s'applique également aux relais utilisés en tant que dispositifs de commande des appareils conformes à la CEI 60335. L'Annexe U contient des exigences supplémentaires relatives à la sécurité et aux valeurs de fonctionnement des relais utilisés en tant que dispositifs de commande des appareils conformes à la CEI 60335. La présente norme ne s'applique pas aux dispositifs de commande électrique automatiques prévus exclusivement pour des applications industrielles, sauf mention particulière dans la partie 2 ou la norme de l'équipement. Cette cinquième édition annule et remplace la quatrième édition parue en 2010. Elle constitue une révision technique. Les principales modifications apportées par rapport à l'édition précédente sont les suivantes:  - modification du titre et du domaine d'application;  - révisions de l'Article H.26 sur la base des évolutions en termes de technologie et d'applications, et afin d'améliorer la cohérence et la présentation;  - modification du Tableau H.12 pour alignement avec la CISPR 22;  - révisions de l'Annexe J pour corrélation avec les modes de panne des thermistances, et exemption des thermistances utilisées conjointement avec les dispositifs de commande de type 1 en circuits  TBTS de faible puissance à partir des essais spécifiés à l'Annexe J;  - nouvelles exigences concernant les dispositifs de commande alimentés par pile, et utilisation de piles dans les dispositifs de commande;  - révision concernant l'exclusion des pannes de relais;  - exigences nouvelles/mises à jour à l'Article 24, pour les alimentations en mode de commutation;  - révisions concernant les tolérances pour les organes de serrage sans vis conformes à la CEI 60999-1;  - nouvelles exigences concernant les fonctions de commande à distance;  - addition d'un diagramme de courant de fuite nouveau/mis à jour pour alignement du diagramme de l'Annexe E avec le diagramme de la CEI 60990 et exigences mises à jour pour les dispositifs de commande sensibles à la température. Mots-clés : commande, commande électrique, automatique

Avtomatske električne krmilne naprave za uporabo v gospodinjstvu in za podobno uporabo - 1. del: Splošne zahteve

Ta del standarda IEC 60730 se na splošno uporablja za avtomatske električne krmilne naprave, ki se uporabljajo v opremi za gospodinjstvo in podobno uporabo, na njej ali v povezavi z njo. Za opremo se lahko samostojno ali v kombinaciji uporabljajo elektrika, plin, nafta, trdno gorivo, sončna toplotna energija itd.
OPOMBA 1: Beseda »oprema« v tem standardu vključuje »naprave in opremo«.
PRIMER 1: Krmiljenje naprav v okviru standarda IEC 60335.
Ta mednarodni standard se uporablja za krmiljenje sistemov za avtomatizacijo stavb v okviru standarda ISO 16484.
Ta standard se uporablja tudi za avtomatske električne krmilne naprave za opremo za javno uporabo, kot je oprema, namenjena za uporabo v trgovinah, pisarnah, bolnišnicah, na kmetijah ter za komercialno in industrijsko uporabo.
PRIMER 2: Krmiljenje komercialne opreme za pripravo in dostavo hrane, ogrevanje in klimatizacijo. Ta standard se uporablja tudi za posamezne naprave, ki se uporabljajo kot del krmilnega sistema, ali naprave, ki so mehansko integrirane v večfunkcijske krmilne naprave brez električnih izhodov.
PRIMER 3: Dodatno nameščeni ventili za vodo, krmilne naprave v sistemih pametnega omrežja in krmiljenje sistemov za avtomatizacijo stavb v okviru standarda ISO 16484-2.
Ta standard se uporablja tudi za releje, kadar se uporabljajo za krmiljenje naprav iz standarda IEC 60335. Dodatne zahteve za varnost in delovne vrednosti relejev, kadar se uporabljajo za krmiljenje naprav iz standarda IEC 60335, so podane v dodatku U.
OPOMBA 2: Te zahteve so navedene v standardu IEC 61810-1.
OPOMBA 3: Ta standard je namenjen za uporabo pri preizkušanju katerega koli samostojnega releja, ki se uporablja za krmiljenje naprave v skladu s standardom IEC 60335-1. Ni namenjen uporabi za kateri koli drug samostojni rele ali kot zamenjava skupine standardov IEC 61810.
Ta standard se ne uporablja za avtomatske električne krmilne naprave, namenjene izključno za industrijsko uporabo, razen če ni to izrecno navedeno v ustreznem 2. delu ali standardu za opremo.

General Information

Status
Published
Publication Date
17-Aug-2016
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
24-May-2016
Due Date
29-Jul-2016
Completion Date
18-Aug-2016

Relations

Buy Standard

Standard
EN 60730-1:2016 - BARVE
English language
311 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 60730-1:2016
01-september-2016
1DGRPHãþD
SIST EN 60730-1:2012
$YWRPDWVNHHOHNWULþQHNUPLOQHQDSUDYH]DXSRUDERYJRVSRGLQMVWYXLQ]DSRGREQR
XSRUDERGHO6SORãQH]DKWHYH
Automatic electrical controls for household and similar use - Part 1: General
requirements
Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche
Anwendungen - Teil 1: Allgemeine Anforderungen
Dispositifs de commande électrique automatiques - Partie 1: Exigences générales
Ta slovenski standard je istoveten z: EN 60730-1:2016
ICS:
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
SIST EN 60730-1:2016 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 60730-1:2016

---------------------- Page: 2 ----------------------

SIST EN 60730-1:2016


EUROPEAN STANDARD EN 60730-1

NORME EUROPÉENNE

EUROPÄISCHE NORM
July 2016
ICS 97.120 Supersedes EN 60730-1:2011
English Version
Automatic electrical controls -
Part 1: General requirements
(IEC 60730-1:2013 , modified + COR1:2014)
Dispositifs de commande électrique automatiques -  Automatische elektrische Regel- und Steuergeräte -
Partie 1: Exigences générales Teil 1: Allgemeine Anforderungen
(IEC 60730-1:2013 , modifiée + COR1:2014) (IEC 60730-1:2013 , modifiziert + COR1:2014)
This European Standard was approved by CENELEC on 2016-03-01. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN 60730-1:2016 E

---------------------- Page: 3 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
European foreword
This document (EN 60730-1:2016) consists of the text of IEC 60730-1:2013 + corrigendum 1:2014
prepared by IEC/TC 72 "Automatic electrical controls", together with the common modifications prepared
by CLC/TC 72 "Automatic controls for household use".
The following dates are fixed:
• latest date by which the document has to be
(dop) 2017-01-29
implemented at national level
by publication of an identical
national standard or by endorsement
• latest date by which the national standards
(dow) - *
conflicting with the document have to be withdrawn

* Justification for no dow:
This European Standard supersedes EN 60730-1:2011. However, EN 60730-1:2011 remains valid until all the
Part 2’s which are used in conjunction with it have been withdrawn. No date of withdrawal (dow) has been given
pending the updating of all the Part 2's to align with this EN 60730-1:2016. The applicable date of withdrawal is given
in each Part 2. It is intended the dow for this Part 1 will be fixed once all the Part 2's have been updated.
This document supersedes EN 60730-1:2011.
EN 60730-1:2016 includes the following significant technical changes with respect to EN 60730-1:2011:
– changes of the title of the Standard into “Automatic electrical controls – Part 1: General
requirements”;
– revisions to Clause H.26 based on changes in technology, applications, and to improve consistency
and layout;
– modification to Table H.12 to align with CISPR 22;
– revisions to Annex J to correlate the fault modes of thermistors, and to exempt thermistors used in
conjunction with type 1 controls in SELV low power circuits from the tests specified in Annex J;
– new requirements covering battery-powered controls, and the use of batteries in controls;
– revision addressing the relay faults in Table H.24;
– new/updated requirements in Clause 24, for switch mode power supplies;
– revisions covering the allowance of screwless-type clamping units complying with IEC 60999-1;
– new requirements addressing remotely actuated control functions;
– addition of a new/updated leakage current diagram to align the Annex E diagram with the diagram in
IEC 60990;
– updated requirements for temperature sensing controls.
This Part 1 is to be used in conjunction with the appropriate Part 2 for a particular type of control, or for
controls for particular applications. This Part 1 may also be applied, so far as reasonable, to controls not
mentioned in a Part 2, and to controls designed on new principles, in which case additional requirements
may be considered to be necessary.
Where, for a particular clause or subclause, the text of Part 2 indicates:
Addition: the Part 1 text applies with the additional requirement indicated in a Part 2;
Modification: the Part 1 text applies with a minor change as indicated in a Part 2;
Replacement: the Part 2 text contains a change which replaces the Part 1 text in its entirety.
Where no change is necessary, the Part 2 indicates that the relevant clause or subclause applies.
2

---------------------- Page: 4 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
NOTE In this standard the following print types are used:
– Requirements proper: in roman type.
– Test specifications: in italic type.
– Explanatory matter: in smaller roman type.
- Defined terms: bold type.
Some table titles contain reference in brackets to table numbers in IEC 60730-1:1999 (edition 3) for ease
of correlation between Parts 2 and the Part 1.
Clauses, subclauses, notes, tables, figures and annexes which are additional to those in
IEC 60730-1:2013 are prefixed “Z”.
Special national conditions are listed in Annex ZB (normative) which forms part of this standard.
National deviations are listed in Annex ZC (informative).

Endorsement notice
The text of the International Standard IEC 60730-1:2013 was approved by CENELEC as a European
Standard with agreed common modifications.
COMMON MODIFICATIONS
Contents
Annexes After Annex V, add the following:
Annex ZA (normative) Normative references to international publications with their
corresponding European publications
Annex ZB (normative) Special national conditions
Annex ZC (informative) A-deviations
Annex ZD (normative) EMC immunity for controls
Figures Delete Figures 25 to 30 and Figures H.3 and H.4.
After Figure S.1, add the following:
Figure ZD.1 – EMC test framework for controls
Tables Delete Table 2.
After Table 13, add "Table Z1".
In the title of Table 14, delete “(this table applies in all countries except Canada, and the USA).”
Delete Tables 15 to 18, Table 25 and Table H.18.
After Table H.23, add the following:
Table H.Z1 (21.4 of edition 3) – Mercury switch short-circuit conditions
After Table S.2, add the following:
Table ZD.1 – Classification and test overview
3

---------------------- Page: 5 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
Table ZD.2 – Compliance criteria
Table ZD.3 – Test levels for voltage surges
Table ZD.4 – Test levels for burst
Table ZD.5 – Test application for electrical fast transient burst test
Table ZD.6 – Test levels for conducted disturbances on mains, I/O lines and DC power lines
Table ZD.7 – Test levels for electrostatic discharge
Table ZD.8 – Test levels for radiated electromagnetic field on enclosure
Table ZD.9 – Test levels for power-frequency magnetic field on enclosure
Table ZD.10 – Voltage dips (50 Hz / 60 Hz)
Table ZD.11 – Voltage interruption (50 Hz / 60 Hz)
1 Scope and normative references
1.1.3 Add the following note:
NOTE Starting relays are tested as voltage sensing or current sensing controls.
1.2 Add the following normative references:
EN 50525-2-11, Electric cables – Low voltage energy cables of rated voltages up to and
including 450/750 V (U /U) – Part 2-11: Cables for general applications – Flexible cables
o
with thermoplastic PVC insulation
EN 50525-2-21, Electric cables – Low voltage energy cables of rated voltages up to and
including 450/750 V (U /U) – Part 2-21: Cables for general applications – Flexible cables
o
with crosslinked elastomeric insulation
EN 55016-1-1, Specification for radio disturbance and immunity measuring apparatus and
methods – Part 1-1: Radio disturbance and immunity measuring apparatus – Measuring
apparatus (CISPR 16-1-1)
EN 60669-1:1999 + A1:2002 + A2:2008, Switches for household and similar fixed-electrical
installations – Part 1: General requirements (IEC 60669-1:1998, mod. + A1:1999, mod.
+ A2:2006, mod.)
EN 60730 Series, Automatic electrical controls for household and similar use
(IEC 60730 series)
2 Terms and definitions
2.1.5 Replace the text of Note 3 to entry by “Void”.
2.1.15 Delete “(conductive) shield (US)”.
2.1.16 Delete “(electrically) protective shield (US)”.
2.1.17 Delete “(electrically) protective shielding (US)”.
4

---------------------- Page: 6 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
2.7.2 Replace Note 2 to entry by:
Note 2 to entry: See Annex ZB.
2.7.3 Replace Note 1 to entry by:
Note 1 to entry: See Annex ZB.
2.7.5.3 Add the following Note 2 to entry:
Note 2 to entry: See Annex ZB.
2.14.2 Delete Note 1 to entry.
4 General notes on tests
Delete the NOTE.
4.3.3.1 Add “See Annex ZB.” at the end of the paragraph.
4.3.3.3 Add “See Annex ZB.” at the end of the paragraph.
5 Rating
st
5.1 Add a new requirement paragraph after the 1 paragraph:
The rated voltage of controls, having terminals intended to be directly connected to the
supply mains single phase, shall cover usage at 230 V and to the supply mains multi-
phase, 400 V.
6 Classification
6.6.1 Delete the NOTE.
6.8.2.1 Add “(see Annex ZB)” before the semicolon.
6.8.2.2 Add “(see Annex ZB)” before the semicolon.
6.8.3.1 Add “(see Annex ZB)” before the semicolon.
6.8.3.2 Add “(see Annex ZB)” before the semicolon.
7 Information
b
Table 1 In Requirement 7, replace the wording by "The type of load and rated current ".
d
In Requirement 19, delete “ ”.
In Requirement 23, add to the wording "if more than 20 K above T ”.
max
5

---------------------- Page: 7 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
After requirements 95, add the following new requirements:
Z1 EMC standard/test method 23.1 X
Z2 Declared voltage and declared current for the purposes of EMC 23.1.1 D
Za
emission tests

b
Replace footnote by:
b
For each circuit of the control, the type of load and rated current. For controls with more than one circuit, it
shall be made clear to which circuit or terminal the information applies. For circuits for resistive and inductive
rd
loads, the rated current, or the rated load in VA, at power factors as indicated in Table 14 (17.2.1 of the 3
edition).
d
Replace the text of footnote by 'Void'.
m to t
After footnote , add the following new note:
Za
These declarations are intended to cover normal use.
7.4.3 Replace the NOTE by
NOTE See Annex ZB.
7.4.3.2 Replace NOTE 1 to NOTE 4 by.
NOTE See Annex ZB.
8 Protection against electric shock
8.1.1.1 Delete the NOTE.
8.4 Delete NOTE 1 and NOTE 2.
9 Provision for protective earthing
st
9.1.1 Add “See Annex ZB.” after the 1 paragraph.
st
9.1.2 Add “See Annex ZB.” after the 1 paragraph.
9.3.2 Delete NOTE 1, NOTE 2 and Table 2 (9.3.2 of edition 3).
9.3.4 Delete the NOTE.
9.5.2 Delete the entire subclause.
10 Terminals and terminations
b b
Table 3 Delete " " in the heading row and replace the text of footnote by 'Void'.
10.1.4.1 Delete NOTE 1 and NOTE 2.
10.1.14 Delete the NOTE.
6

---------------------- Page: 8 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
10.1.16 Delete the entire subclause including 10.1.16.1.
st
10.2.1 Add a new requirement paragraph after the 1 paragraph:
A terminal or termination is not required if a conductor is permanently connected to the
control by the control manufacturer.
b b
Table 6 Delete " " in the heading row and replace the text of footnote by 'Void'.
11 Constructional requirements
11.2.1.1 Delete the NOTE.
11.3.2 Delete in the sixth line the word “or”.
11.5 Delete NOTE 3.
11.8.1 Replace “60245 IEC 53” by “EN 50525-2-21”.
Replace “60227 IEC 53” by “EN 50525-2-11”.
b b
Table 10 Delete " " in the heading row and replace the text of footnote by 'Void'.
11.9.4 Add “see Annex ZB” at the end of the first sentence.
11.10.3 Delete the NOTE.
11.11.1.2 Delete NOTE 1 and NOTE 2.
11.11.1.3 Replace the text of the NOTE by "Void".
11.11.1.4 Replace the text of the NOTE by "Void".
12 Moisture and dust resistance
12.1.6 Delete the NOTE.
12.3 Delete the entire subclause, including 12.3.1 to 12.3.7.
7

---------------------- Page: 9 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
13 Electric strength and insulation resistance
a
Table 12 Replace the text of footnote by 'Void'.
d
Add “See Annex ZB.” to footnote .
i
Replace the text of footnote by 'Void'.
13.3 Delete the entire subclause, including 13.3.1 to 13.3.4.
14 Heating
14.4 Replace the text including the NOTE by:
All circuits and terminals intended to control external loads shall be loaded as declared in
Table 1, requirement 3, such that each circuit or terminal carries that current between 0,9
and 1,1 of its declared rating that will prove most arduous. All controls shall be tested at a
voltage between 0,9 and 1,1 times rated voltage but controls that are not sensitive to
voltage may be tested at a lower voltage provided that 1,1 times rated current is passed.
Internal circuits shall be connected as specified by the manufacturer.
f
Table 13 Delete the last two sentences of footnote .
After Table 13, add the following:
14.Z1 If the maximum permitted temperature of a winding or core lamination exceeds the
value specified for the text described in 14.1, six additional samples shall be subjected to
the following tests:
Moving parts, if any, are locked and a current is passed individually through each winding,
this current being such that the temperature of the relevant winding is equal to the
maximum temperature measured under the conditions specified in 14.1. This temperature
is increased by whichever value is chosen from Table Z1. The total time during which the
current is passed is as indicated in Table Z1 for the temperature increase chosen.
Table Z1
Temperature increase Total time
ºC (K) h
a
0 ± 3
p
10 ± 3
0,5 p
20 ± 3 0,25 p
0,125 p
30 ± 3
a
In general, p equals 8 000 for controls for EN 60335-1 applications.

The total time is divided into four equal periods, each of them being followed by a period of
48 h during which the control is subjected to a humidity treatment as specified in 12.2. After
the final humidity treatment, the insulation shall withstand an electric strength test as
specified in Clause 13, the test voltage for the electric strength being, however, reduced to
50 % of the values specified in the table of that clause.
8

---------------------- Page: 10 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
Failure of only one of the six samples during the first of the four periods of the test is
ignored.
If one of the six samples fails during the second, third or fourth period of the test, the
remaining five samples are subjected to an additional fifth period of passing current and
humidity treatment, followed by an electric strength and insulation resistance test as
specified before.
Failure of any of the remaining five controls will entail a rejection.
The controls are then subjected to the test of 17.8, but only for half the number of cycles
specified in that subclause. All controls shall then withstand an electric strength test as
specified before.
EXAMPLES Examples of cases where there may be doubt with regard to the classification of the insulating
system of a winding are those cases where well-known insulating materials are used in an unconventional way,
where combinations of materials of different temperature classes are used at a temperature higher than that
allowed for the lowest class used or where materials are used for which no sufficient experience is available, as
may be the case for integral core insulation.
If it is desired to establish that the insulation system falls within the temperature class
claimed by the manufacturer, the winding temperature shall be equal to the temperature
limit for the class of insulation claimed, increased by the temperature increase chosen from
Table Z1.
The temperature increase chosen from Table Z1 should be agreed with the manufacturer.
15 Manufacturing deviation and drift
15.1 Delete the NOTE.
16 Environmental stress
16.2.1 Add “See Annex ZB." at the end of the first dashed paragraph.
Delete the NOTE.
17 Endurance
17.1.3 Add the following NOTE:
NOTE For the test sequence and conditions of non-resettable thermal cut-outs, see 17.16.
17.1.3.1 Delete in the second and fifth dashed paragraphs the text in brackets.
17.2.2 Replace the text by:
The electrical loads to be used are those specified in Table 14 at rated voltage V , with this
R
voltage then being increased to 1,15 V for the overvoltage test of 17.7 and 17.10.
R
17.2.3 Replace up to 17.2.3.2 inclusive by “Void”.
Table 14 Delete the words in brackets at the end of the title.
c c
Delete " " in the last cell of the last row and replace the text of footnote by 'Void'.
9

---------------------- Page: 11 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
Za
Add ' ' in the column ‘Type of circuit’ to the cell for ‘Declared specific load’ and add the
following footnote to the table:
Za
For the tests of tungsten filament lamp load, the load and test of EN 60669-1:1999, 18.2 and for fluorescent
lamp load the load of EN 60669-1:1999, 19.2 shall be used, under the conditions as specified in 17.16 in the
relevant Part 2.
Table 15 Delete.
Table 16 Delete.
17.3.1 Replace the last sentence of the third dashed paragraph by:
If T is less than 0 °C, the following additional tests shall be carried out with the switch
min
head maintained between T and (T – 5) ° C:
min min
− Controls with Type 1 action – Clauses 16 and 17;
− Controls with Type 2 action – Clauses 15, 16 and 17.
Three additional samples required.
17.5.1 Delete the NOTE.
17.7 Delete the words in brackets.
17.7.1 Delete the words in brackets.
17.7.7 Delete the NOTE.
17.8.4.1 Delete the NOTE.
17.10 Delete the words in brackets.
17.10.1 Delete the words in brackets.
17.10.4 Delete.
17.12.5 Delete.
18 Mechanical strength
18.1.6 Delete 18.1.6 to 18.1.6.3 inclusive.
18.2.1 Delete “, except as provided in 18.4,”.
18.4 Replace by “Void”.
Table 17 Delete.
Table 18 Delete.
18.4.1 Delete.
10

---------------------- Page: 12 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
19 Threaded parts and connections
19.1.7 Replace “screws” by "threaded parts”.
19.2.4.1 Delete the NOTE.
19.2.5.1 Delete the NOTE.
20 Creepage distances, clearances and distances through solid insulation
20.1 Replace in the fourth line “impulse withstand test” by “impulse voltage test”.
Replace in NOTE 2 “impulse test” by “impulse voltage test”.
20.1.7 Replace in the second line “impulse withstand test” by “impulse voltage test”.
Replace in the NOTE “impulse test” by “impulse voltage test”.
21 Resistance to heat, fire and tracking
21.1 Delete the NOTE.
21.2.7 Replace the test specification by:
Compliance is checked by the tests of Clause G.4, carried out at a voltage corresponding
to the PTI value declared for Table 1, requirement 30.
21.3 Replace the existing text by:
The test sequence of 21.2.1 through 21.2.7 applies, preceded by the preconditioning of
21.3.1.
For parts that maintain or retain in position electrical connections, the glow-wire test shall
be carried-out at a temperature of 850 °C.
21.4 Delete the entire subclause, including Table 25.
23 Electromagnetic compatibility (EMC) requirements - Emission
23.1 Replace the first line of the third paragraph by:
Compliance is checked by one of the following methods as declared by the manufacturer
(Table 1, requirement Z1) (see also Table H.10).
23.1.1 Add the following before the first dashed paragraph:
- the test is conducted at the lowest declared voltage and lowest declared current
(Table 1, requirement Z2);
23.1.2 Replace the second paragraph by:
The duration of radio interference is measured by an oscilloscope, or the measuring
equipment specified in EN 55016-1-1 but with the capability to measure 20 ms, connected
to the control so as to measure the voltage drop across the contacts.
11

---------------------- Page: 13 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
24 Components
st
24.1.1 In the 1 paragraph, delete ", 17.2.3.1 and 17.2.3.2".
27 Abnormal operation
27.2 Replace the title “Burnout test” by “Locked mechanism test”.
st
27.2.1 In the 1 paragraph, delete ", 17.2.3.1 and 17.2.3.2".
27.2.3.1 Delete the NOTE.
Figures
a
Figure 14 Replace footnote by:
a
Tabs may have an optional detent for latching. Round dimple detents, rectangular dimple detents and hole
detents shall be located in the area bounded by dimensions b , l and l along the centre line of the tab.
1 3 4
Figure 15 Delete the reference ‘t’, and the words “Flatness tolerance” (in two places).
Figure 25 Delete.
Figure 26 Delete.
Figure 27 Delete.
Figure 28 Delete.
Figure 29 Delete.
Figure 30 Delete.
Annexes
Annex C Replace the text by 'Void'.
Annex D Replace the text by 'Void'.
Annex H
H.7 In requirement 36, add H.2.4.6,’ after "11.3.2,"in the second column
H.7 In requirement 60, delete in the second column “Annex R”.
H.26.1 After the last paragraph, add the following:
For EMC immunity of operating controls of Type 1 action intended to be used as “free
standing controls, independently mounted and/or in-line cord controls”, the tests of
Annex ZD apply instead of those of Clause H.26.
H.26.7 Replace by “Void”.
12

---------------------- Page: 14 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
H.26.10 Replace the entire subclause including Figure H.3, Figure H.4, Table H.18 and the NOTE
by “Void”.

H.27.1.1.3 Delete NOTE 1.
H.27.1.1.3a) Replace the text of the NOTE 2 by the following:
The wrapping tissue paper is specified in ISO 4046:1978 as thin, soft, relatively tough paper, generally intended
2 2
for packing delicate articles, its substance being between 12 g/m and 25 g/m .
Annex J
th
J.17.17 a) Replace in the 7 dashed line “Thermal runaway” by “Thermal runaway by increased
voltage”.
J.17.18.5 Replace the title of this subclause by “Thermal runaway by increased voltage”.
Annex K
b
c
Table K.1 In row for 150 V, delete “120/208 in the second column and " " in the fifth column.
b c
Delete footnote and footnote .
b
Table K.2 In row for 150 V, delete “120/208 ” in the second column.
b
Delete footnote .
Annex T
T.3.2 Delete NOTE 2.
13

---------------------- Page: 15 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
Add Annexes ZA, ZB, ZC, ZD as follows.
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.

Publication Year Title EN/HD Year
- - Electric cables - Low voltage energy EN 50525-2-11 -
cables of rated voltages up to and
including 450/750 V (U /U)
o
Part 2-11: Cables for general applications -
Flexible cables with thermoplastic PVC
insulation
- - Electric cables - Low voltage energy EN 50525-2-21 -
cables of rated voltages up to and
/U)
including 450/750 V (U
o
Part 2-21: Cables for general applications -
Flexible cables with crosslinked
elastomeric insulation
IEC 60038 -  IEC standard voltages EN 60038 -
1)
IEC 60065 (mod) 2001 Audio, video and similar electronic EN 60065 2002
1)
+ A1 (mod) 2005 apparatus - Safety requirements + A1 2006
1)
- - + corrig. August 2007
1)
- - + A11 2008
1)
+ A2 (mod) 2010 + A2 2010
1)
- - + A12 2011
IEC 60068-2-75 -  Environmental testing EN 60068-2-75 -
Part 2-75: Tests - Test Eh: Hammer tests
IEC 60085 -  Electrical insulation - Thermal evaluation EN 60085 -
and designation
IEC 60099-1 -  Surge arresters EN 60099-1 -
Part 1: Non-linear resistor type gapped
surge arresters for a.c. systems
IEC 60112 2003 Method for the determination of the proof EN 60112 2003
+ A1 2009 and the comparative tracking indices of + A1 2009
solid insulating materials

1)
Superseded by EN 60065:2014 (IEC 60065:2014): DOW = 2017-11-17.
14

---------------------- Page: 16 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
Publication Year Title EN/HD Year
IEC 60127-1 -  Miniature fuses EN 60127-1 -
Part 1: Definitions for miniature fuses and
general requirements for miniature fuse-
links
IEC 60227-1 -  Polyvinyl chloride insulated cables of rated - -
voltages up to and including 450/750 V
Part 1: General requirements
IEC 60245-1 -  Rubber insulated cables - Rated voltages - -
up to and including 450/750 V
Part 1: General requirements
IEC 60269-1 -  Low-voltage fuses EN 60269-1 -
Part 1: General requirements
IEC 60335-1 (mod) 2010 Household and similar electrical EN 60335-1 2012
- - appliances - Safety + AC 2014
Part 1: General requirements
IEC 60364 Series Low-voltage electrical installations HD 384 / Series
HD 60364
IEC 60384-14 -  Fixed capacitors for use in electronic EN 60384-14 -
equipment
Part 14: Sectional specification - Fixed
capacitors for electromagnetic interference
suppression and connection to the supply
mains
IEC 60384-16 -  Fixed capacitors for use in electronic EN 60384-16 -
equipment
Part 16: Sectional specification: Fixed
metallized polypropylene film dielectric d.c.
capacitors
IEC 60384-17 -  Fixed capacitors for use in electronic EN 60384-17 -
equipment
Part 17: Sectional specification: Fixed
metallized polypropylene film dielectric a.c.
and pulse capacitors
IEC 60417 series Graphical symbols for use on equipment - -
IEC 60423 -  Conduit systems for cable management - EN 60423 -
Outside diameters of conduits for electrical
installations and threads for conduits and
fittings
IEC 60529 1989 Degrees of protection provided by EN 60529 1991
- - enclosures (IP Code) + corrig. May 1993
+ A1 1999 + A1 2000
IEC 60539 series Directly heated negative temperature EN 60539 series
coefficient thermistors
IEC 60664-1 2007 Insulation coordination for equipment EN 60664-1 2007
within low-voltage systems
Part 1: Principles, requirements and tests
IEC 60664-3 2003 Insulation coordination for equipment EN 60664-3 2003
+ A1 2010 within low-voltage systems + A1 2010
Part 3: Use of coating, potting or moulding
for protection against pollution
15

---------------------- Page: 17 ----------------------

SIST EN 60730-1:2016
EN 60730-1:2016
Publication Year Title EN/HD Year
IEC 60664-4 -  Insulation coordination for equipment EN 60664-4 -
within low-voltage systems
Part 4: Consideration of high-frequency
voltage stress
IEC 60669-1 (mod) 1998 Switches for household and similar fixed- EN 60669-1 1999
+ A1 (mod) 1999 electrical installations + A1 2002
+ A2 (mod) 2006 Part 1: General requirements + A2 2008
IEC 60695-2-10 -  Fire hazard testing EN 60695-2-10 -
Part 2-10: Glowing/hot-wire based test
methods - Glow-wire apparatus and
common test procedure
2)
IEC 60695-2-11 2000 Fire hazard testing EN 60695-2-11 2001
Part 2-11: Glowing/hot-wire based test
methods - Glow-wire flammability test
method for end-products
IEC 60695-10-2 -  Fire hazard testing EN 60695-10-2 -
Part 10-2: Abnormal heat - Ball pressure
test
IEC 60730 series Automatic electrical controls for household EN 60730 series
and similar use
IEC 60738-1 -  Thermistors - Directly heated positive EN 60738-1 -
temperature coefficient
Part 1: Generic specification
IEC 60738-1-1 -  Thermistors - Directly heated positive step- EN 60738-1-1 -
function temperature coefficient
Part 1-1: Blank detail specification -
Current limiting application - Assessment
level EZ
IEC 60947-1 2007 Low-voltage switchgear and control
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.