Chimneys - Clay/ceramic flue liners - Requirements and test methods

Amendment instead of revision (UAP of 4 months) (CC/010705)
Aug 2001: Ashok: DOW = DAV + 21 months (please contact Ashok before DAV)

Abgasanlagen - Keramik-Innenrohre - Anforderungen und Prüfungen

ergänze im ersten Satz, vor dem Wort "Abgasanlagen" das Wort "mehrschaligen".

Conduits de fumée - Conduits intérieurs en terre cuite/céramique - Exigences et méthodes d'essai

Dans la premiere phrase, apres " des conduits de raccordement " ajouter " multiparois ".

Dimniki - Keramične tuljave - Zahteve in preskusne metode

General Information

Status
Withdrawn
Publication Date
31-Dec-2002
Withdrawal Date
11-Apr-2012
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
16-Feb-2012
Due Date
10-Mar-2012
Completion Date
12-Apr-2012

Relations

Buy Standard

Amendment
EN 1457:1999/A1:2003
English language
14 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 1457:1999/A1:2003
01-januar-2003
'LPQLNL.HUDPLþQHWXOMDYH=DKWHYHLQSUHVNXVQHPHWRGH
Chimneys - Clay/ceramic flue liners - Requirements and test methods
Abgasanlagen - Keramik-Innenrohre - Anforderungen und Prüfungen
Conduits de fumée - Conduits intérieurs en terre cuite/céramique - Exigences et
méthodes d'essai
Ta slovenski standard je istoveten z: EN 1457:1999/A1:2002
ICS:
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
SIST EN 1457:1999/A1:2003 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD
EN 1457:1999/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2002
ICS 91.060.40
English version
Chimneys - Clay/ceramic flue liners - Requirements and test
methods
Conduits de fumée - Conduits intérieurs en terre Abgasanlagen - Keramik-Innenrohre - Anforderungen und
cuite/ceramique - Exigences et méthodes d'essai Prüfungen
This amendment A1 modifies the European Standard EN 1457:1999; it was approved by CEN on 26 August 2002.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the Management Centre or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2002 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1457:1999/A1:2002 E
worldwide for CEN national Members.

---------------------- Page: 2 ----------------------

EN 1457:1999/A1:2002 (E)
Foreword
This document EN 1457:1999/A1:2002 has been prepared by Technical Committee CEN/TC 166
"Chimneys", the secretariat of which is held by UNI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by April 2003, and conflicting national standards shall be
withdrawn at the latest by April 2003.
This document has been prepared under a mandate given to CEN by the European Commission and
the European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative annex ZA, which is an integral part of this
document.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Czech
Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Malta,
Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.
2

---------------------- Page: 3 ----------------------

EN 1457:1999/A1:2002 (E)
Foreword Delete the third paragraph and insert the following paragraphs:
“This document has been prepared under a mandate given to CEN by the European
Commission and the European Free Trade Association and supports essential
requirements of EU Directives.
For the relationship with the EU Directives, see informative annex ZA, which is an integral
part of this document.”
Contents 5 delete "Classes" insert "Types".
7 delete “Dimensions” insert “Tolerances on dimensions’’.
9 delete “Gastightness (leakage test) after thermal testing for straight flue liners”, insert
“Gastightness and thermal shock resistance for straight flue liners”.
12 delete ”Sweeping resistance” insert “abrasion resistance”.
13 delete “Water and vapour flow resistance” insert “Water vapour permeability and flow
resistance”.
Change status of annex B from "informative" to "normative".
Insert annex C (normative) Flow resistance test.
Insert annex ZA (informative) Clauses of this European Standard addressing the
provisions of the EU Construction Products Directive.
1 In the first sentence, after “in the construction of” insert “multiwall”.
2 Replace prEN 1443 with EN 1443.
Delete reference to EN ISO 9002.
Delete reference to EN 45012.
3.1 a) Add "or square" after "circular".
4 Add the following definition ‘ Ability of the flue liners
4.4 Resistance to fire of flue liners
and fittings to be resistant to soot fire’.
5 Change the title to ‘Types of flue liners’. Delete the first paragraph and notes 1, 2 and 3,
and insert the following text and note: ‘There are four main types of clay/ceramic flue liner
dependent on working temperature, with sub-types dependent on whether the flue liners
are to be used in chimneys designed to work under negative or positive pressure, or are
to have soot fire resistance. The types, working temperatures, test pressures and
maximum air permeability rates are given in Table 1. The suitability of each type of flue
liner to be used in chimneys designed to operate under negative or positive pressure and
wet or dry conditions is also given.
NOTE  A flue liner can be designated in one or more types provided that it complies with the appropriate
requirements for each type.”
Table 1 In heading delete ‘classes’ insert ‘types’ and in column 1 delete ‘class’ insert 'type’. In the
column for sootfire resistance, insert “(G)” after every “Yes”, and “(O)” after every “No”.
3

---------------------- Page: 4 ----------------------

EN 1457:1999/A1:2002 (E)
7 Delete heading, insert “Tolerances on dimensions".
7.1 Delete heading, insert “Transverse dimension”.
9 Delete heading, insert “Gastightness, thermal shock resistance and resistance to fire
for straight flue liners”.
9.2 Delete 9.2 and insert a new sub-clause 9.2
"9.2 Final gas tightness after thermal shock testing
When tested in accordance with 16.8 flue liners A1, B1 and D1 shall have a leakage rate
after thermal shock testing not greater than the values given in Table 3 for the
appropriate type of flue liner, test temperature and differential pressure.”.
9.3 Insert the following sub-clause
"9.3 Final gas tightness after thermal shock testing
When tested in accordance with 16.8 flue liners not included in 9.2 shall have a leakage
rate after thermal testing not greater than the values given in Table 3 for the appropriate
type of flue liner, test temperature and differential pressure.”.
Table 3 In column 1 delete ‘class’ insert ‘type’.
Table 4 In column 1 delete ‘class’ insert type’.
11.1.1 In line 4 delete ‘for five samples taken…….type test.’, insert ‘from the last type test.’
11.1.2 In line 3 delete ‘for five samples taken…….type test.’, insert ‘from the last type test.’
12 Delete heading, insert “Abrasion resistance”.
13 Delete heading and text, and insert the following:
13. Water vapour permeability and flow resistance
13.1 Water vapour permeability
When tested in accordance with 16.13, Type A2 P1, Type B2, Type C2, Type D2 and Type D3 straight
-1 -2
flue liners for wet conditions shall not allow more than 2,0 g of water h m of flue liner internal
surface to pass through the wall of the flue liners.
13.2 Flow resistance
Where required, determine the mean roughness of flue liners according to annex C.
14. After “a flue temperature of 200°C” delete “or” and replace with “and”.
4

---------------------- Page: 5 ----------------------

EN 1457:1999/A1:2002 (E)
Delete clause 15 and insert the following.
15
15.Evaluation of conformity
15.1 Initial type testing
Type tests relating to material composition shall be performed initially together with factory production
control tests as given in Table 5. One test shall be carried for each requirement.
The thermal testing shall be carried out on one size of flue liner for each geometrical configuration e.g.
circular, square, rectangular. For circular flue liners the size to be tested shall be 200 mm ± 50 mm
internal diameter. For other geometrical configurations the flue liner shall have an equivalent cross-
sectional area range.
15.2 Further type tests
Type tests shall be performed when a change is made either in material composition, processing
technique or to the design or method of manufacture of the flue liner, but they may be performed more
frequently by incorporation into a plan for monitoring the consistency of manufacture (see Table 5).
Table 5 - Factory production control and type tests
Relevant requirement clauses
Item Factory production control Type tests
15.3 (1)
15.1 and 15.2
Straight flue liners 7.1, 7.2, 7.4, 7.5, 7.6, 11 8.1, 9.1, 9.2, 10, 12, and 13
Flue liner bends 7.1, 7.3, 11 8.2, 10
(1) The tests carried out during FPC are intended to verify that the performance
requirements assessed through the initial type testing are maintained.
15.3 Factory production control
To achieve compliance with this standard the manufacturer shall establish and maintain an effective
documented quality system.
Factory production control tests are carried out following manufacture to monitor the quality of product
(see Table 5).
Sampling and testing of any batch shall be completed prior to removal from the works and shall be in
accordance with ISO 2859-1 at an AQL of 10 % and inspection level S2. Isolated batches of units shall
be assessed in accordance with tightened inspection procedures, with a maximum batch size of 1 200
(see annex A).
Batches rejected under the factory production control procedure may be resubmitted once, after
removal of units with previously undetected visible defects, under the tightened inspection procedures,
in respect only of the defect that caused initial rejection.
NOTE  A quality system assessed by a certification body which complies with the requirements of EN 45012 can
be applied to ensure that the requirements of ISO EN 9002 and clause 15 are complied with.”
5

---------------------- Page: 6 ----------------------

EN 1457:1999/A1:2002 (E)
Table 6 In column 1 delete ‘class’ and insert ‘ type’.
16.8 Under the heading insert the following:
“NOTE  The thermal testing to 1000 ºC is a method to assess the flue liner for its ability to resist sootfire.”
16.8.2 In last paragraph last line delete ‘class’ insert ‘type’.
16.8.3 In paragraph 2 line 5 delete ‘class’ insert ‘type’.
16.8.4 In paragraph 1 line 4 delete ‘class’ insert ‘type’.
16.8.5 In paragraph 1 line 4 delete ‘class’ insert ‘type’.
16.9.3 In paragraph 1 line 5 add at end of first sentence “at 24 h intervals”.
17 In line 6 delete ‘class or classes insert ‘type or types’.
In example delete ‘class’ insert ‘type’.
Table 7 Delete Table 7.
18 In line 5 delete ‘class number or classes numbers’ insert ‘type number or type
numbers’.
Add a note ‘for CE marking and labelling, clause ZA.3 in annex ZA applies’.
Annex B Change status from “informative” to “normative”.
Method I” insert “Thermal resistance for solid wall flue liners”.
After “
After “Method II” delete sub-title and insert “Thermal resistance for multiwall flue
liners”.
Annex C Insert the following annex:
Annex C
(normative)
Measurement of the coefficient of friction of chimneys
Measurement of the coefficient of jointed flue liners shall be done using the measuring set up shown in
Figure C.1.
6

---------------------- Page: 7 ----------------------

EN 1457:1999/A1:2002 (E)
Key
1 Fan
2 Measuring devi
...

Questions, Comments and Discussion