Extended application of results from fire resistance tests for service installations - Part 2: Fire dampers

This document provides guidance and rules to notified bodies (for fire dampers) allowing them to produce/validate an extended field of application report for fire dampers. This document identifies the parameters that affect the fire resistance of dampers. It also identifies the factors that need to be considered when deciding whether, or by how much, the parameter can be extended when contemplating the fire resistance performance of an untested, or untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control.
It is the intention that the application of this document makes it possible to identify which specifications to test to maximize the field of application. Some information on test programmes is given for guidance purposes.

Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für Installationen - Teil 2: Brandschutzklappen

Dieses Dokument legt eine Anleitung und Regeln für notifizierte Stellen (für Brandschutzklappen) in Bezug auf die Erstellung/Überprüfung von Berichten zum erweiterten Anwendungsbereich für Brandschutzklappen fest. Dieses Dokument benennt die Parameter, die die Feuerwiderstandsfähigkeit von Brandschutzklappen beeinflussen. Sie benennt auch die Faktoren, die bei der Entscheidung zu berücksichtigen sind, ob oder bis zu welchem Ausmaß ein Parameter bei der Betrachtung der Feuerwiderstandsfähigkeit einer ungeprüften oder unprüfbaren Abweichung einer Konstruktion erweitert werden kann.
Dieses Dokument legt die Grundsätze dar, die eine Schlussfolgerung über den Einfluss von speziellen Parametern/Konstruktionsdetails, welche die entsprechenden Kriterien (E, I, S) betreffen, ermöglichen.
Dieses Dokument gilt nicht für Brandschutzklappen, die zur Entrauchung verwendet werden.
Das Ziel besteht darin, dass durch die Anwendung dieses Dokuments bestimmt werden kann, welche Spezifikationen zur Maximierung des Anwendungsbereiches geprüft werden müssen. Einige Informationen über Prüfprogramme sind zur Anleitung aufgeführt.

Application étendue des résultats des essais de résistance au feu des installations de service - Partie 2 : Clapets résistant au feu

Le présent document fournit des recommandations et des règles aux organismes notifiés (pour les clapets résistant au feu) leur permettant d'élaborer/de valider un rapport de domaine d'application étendue pour ces clapets. Le présent document identifie les paramètres qui ont une incidence sur la résistance au feu des clapets. Il identifie également les facteurs devant être pris en considération lorsqu'il s'agit de décider si, ou dans quelle mesure, un paramètre peut être étendu, en examinant la résistance au feu d'une variation non soumise à essai ou ne pouvant pas être soumise à essai dans la construction.
Le présent document explique les principes permettant d'arriver à une conclusion concernant l'influence de paramètres/détails de construction spécifiques pour les critères pertinents (E, I, S).
Le présent document ne couvre pas les volets de désenfumage.
Il est prévu que l'application du présent document permette d'identifier quelles spécifications contrôler pour optimiser le domaine d'application. Certaines informations relatives aux programmes d'essais sont fournies à titre de recommandations.

Razširjena uporaba rezultatov preskusov požarne odpornosti servisnih inštalacij - 2. del: Požarne lopute

Ta dokument podaja smernice in pravila (za požarne lopute), ki priglašenim organom omogočajo izdelavo/validacijo poročila o razširjenem področju uporabe za požarne lopute. Ta dokument določa parametre, ki vplivajo na požarno odpornost loput. Določa tudi dejavnike, ki jih je treba upoštevati pri odločanju, ali je pri obravnavi požarne odpornosti nepreskušene različice stavbe oziroma takšne, ki je ni mogoče preskusiti, mogoče razširiti ali zožiti parameter in za koliko.
Ta dokument pojasnjuje načela o tem, kako je mogoče doseči sklep o vplivu določenih parametrov/konstrukcijskih lastnosti v zvezi z zadevnimi merili (E, I, S).
Ta dokument ne zajema loput za nadzor dima.
Namen uporabe tega dokumenta je omogočiti identifikacijo specifikacij, ki jih je treba preskusiti za namene povečanja področja uporabe. Nekatere navedbe o preskusnih programih so podane kot smernice.

General Information

Status
Published
Public Enquiry End Date
19-May-2021
Publication Date
09-Oct-2022
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
04-Oct-2022
Due Date
09-Dec-2022
Completion Date
10-Oct-2022

Relations

Buy Standard

Standard
EN 15882-2:2022
English language
45 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 15882-2:2021
English language
41 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 15882-2:2022
01-november-2022
Nadomešča:
SIST EN 15882-2:2015
Razširjena uporaba rezultatov preskusov požarne odpornosti servisnih inštalacij -
2. del: Požarne lopute
Extended application of results from fire resistance tests for service installations - Part 2:
Fire dampers
Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für
Installationen - Teil 2: Brandschutzklappen
Application étendue des résultats des essais de résistance au feu des installations de
service - Partie 2 : Clapets résistant au feu
Ta slovenski standard je istoveten z: EN 15882-2:2022
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
SIST EN 15882-2:2022 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 15882-2:2022

---------------------- Page: 2 ----------------------
SIST EN 15882-2:2022


EN 15882-2
EUROPEAN STANDARD

NORME EUROPÉENNE

September 2022
EUROPÄISCHE NORM
ICS 13.220.99 Supersedes EN 15882-2:2015
English Version

Extended application of results from fire resistance tests
for service installations - Part 2: Fire dampers
Application étendue des résultats des essais de Erweiterter Anwendungsbereich der Ergebnisse aus
résistance au feu des installations de service - Partie 2 : Feuerwiderstandsprüfungen für Installationen - Teil 2:
Clapets résistant au feu Brandschutzklappen
This European Standard was approved by CEN on 15 August 2022.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15882-2:2022 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
Contents Page
European foreword . 3
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 Test requirements for assessment of design changes and modification of the
manufacturing process . 7
4.1 General. 7
4.2 Design and manufacturing changes . 7
4.2.1 Pre-test . 7
4.2.2 Fire test . 8
4.2.3 Extended field of application . 8
4.3 Actuators, remote triggering devices, actuating mechanisms, fusible links and sensing
elements . 8
4.3.1 Actuators . 8
4.3.2 Actuators with an associated thermal element device that controls the action of the
actuator to close the fire damper in the event of fire . 9
4.3.3 Remote triggering device (e.g. magnet) . 10
4.3.4 Actuating mechanism . 10
4.3.5 Fusible links and elements (not associated with the actuator supplier) . 11
5 Determination of worst case . 12
6 Conditions and application rules . 13
6.1 Change of fixing damper to supporting construction . 13
6.2 Multiple damper assemblies . 13
6.2.1 E Classification only . 13
6.2.2 EI, E-S, EI-S classifications . 15
6.2.3 Field of application . 15

6.3 Alternative penetration seals . 16
7 Influence of parameters and factors on fire damper performance . 16
8 Critical parameters and factors . 16
8.1 General. 16
8.2 Common operational parameters and factors . 17
9 Constructional parameters . 17
9.1 General. 17
9.2 Parameters of components of damper . 18
9.3 Parameters for installation . 19
10 Methodology . 19
11 Extended field of application report . 42
Bibliography . 45

2

---------------------- Page: 4 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
European foreword
This document (EN 15882-2:2022) has been prepared by Technical Committee CEN/TC 127 “Fire safety
in buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by March 2023, and conflicting national standards shall be
withdrawn at the latest by March 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 15882-2:2015.
In comparison with the previous edition, the following technical modifications have been made:
— Clause 4 was expanded and re-titled “Test requirements for assessment of design changes and
modification of the manufacturing process”. This defines options for EXAP where changes are
proposed, what needs to be done pre-test, fire tests that need to be done etc. This is supported by the
new rule X.65 where such changes are proposed.
— Provisions on how to handle the replacement or new actuators, operating mechanisms and fusible
elements have become more detailed. Further support is also given in the rules.
— Clause 5 now details more comprehensively the selection of the worst case.
— Clause 6 now contains more details on hangers and fixing flanges and on the testing of multiple units.
It also covers the use of alternative penetration seals.
— The rules are similar (some are new, some changed); the numbering changed.
— Changes were made with respect to the use of different materials (particularly stainless steels) and
the positioning of flanges, brackets etc.
EN 15882, Extended application of results from fire resistance tests for service installations, consists of the
following parts:
— Part 1: Ducts
— Part 2: Fire dampers
— Part 3: Penetration seals
— Part 4: Linear joint seals
This document has been prepared under a Standardization Request given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of EU
Directive(s) / Regulation(s).
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
3

---------------------- Page: 5 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
4

---------------------- Page: 6 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
Introduction
It should be noted that fire resisting dampers are special products that are exposed to different conditions
than other elements of construction; in particular they are subjected to significantly different pressure
regimes. Integrity is also evaluated through leakage measurements. Consequently, this document may
adopt a different approach to other extended field of application standards, with more emphasis on
testing.
Some rule references and content have changed from the previous version of this document and some
conclusions to the previous version may not be acceptable in the light of this new information.

5

---------------------- Page: 7 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
1 Scope
This document provides guidance and rules to notified bodies (for fire dampers) allowing them to
produce/validate an extended field of application report for fire dampers based on testing undertaken in
accordance with EN 1366-2. This document identifies the parameters that affect the fire resistance of fire
dampers. It also identifies the factors that need to be considered when deciding whether, or by how much,
the parameter can be extended when contemplating the fire resistance performance of an untested, or
untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific
parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control or non-mechanical fire barriers.
It is the intention that the application of this document makes it possible to identify which specifications
to test to maximize the field of application. Some information on test programmes is given for guidance
purposes.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 1751, Ventilation for buildings - Air terminal devices - Aerodynamic testing of damper and valves
EN 1363-1, Fire resistance tests - Part 1: General requirements
EN 1366-1, Fire resistance tests for service installations — Part 1: Ventilation ducts
EN 1366-2, Fire resistance tests for service installations - Part 2: Fire dampers
EN 1366-3, Fire resistance tests for service installations - Part 3: Penetration seals
EN 13501-3, Fire classification of construction products and building elements — Part 3: Classification
using data from fire resistance tests on products and elements used in building service installations: fire
resisting ducts and fire dampers
EN 15882-1, Extended application of results from fire resistance tests for service installations — Part 1:
Ducts
EN 15650:2010, Ventilation for buildings - Fire dampers
ISO 21925-1, Fire resistance tests — Fire dampers for air distribution systems — Part 1: Mechanical
dampers
6

---------------------- Page: 8 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1, EN 1366-2, EN 15650
and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at https://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
3.1
multiple damper assembly
assembly of several individual fire damper units arranged next to each other, or above each other, to form
a larger unit
3.2
horizontal
orientation/position of the damper mounted in a horizontal plane
EXAMPLE When installed in the plane of a floor or a ceiling.
3.3
vertical
orientation/position of the damper mounted in a vertical plane
EXAMPLE When installed in the plane of a wall.
3.4
supporting construction
construction used as part of the test assembly to support the test specimen and to fill in the furnace
aperture
3.5
standard supporting construction
supporting construction that has known fire behaviour (as described in EN 1363-1) and for which a direct
field of application has been established
4 Test requirements for assessment of design changes and modification of the
manufacturing process
4.1 General
Many manufacturers will want to introduce manufacturing changes to make use of differing production
techniques, whilst essentially keeping a product the same. In addition, they may wish, for example, to
change actuators and activating mechanisms, sometimes across a range of product models.
The test methods described in the following subclauses shall not be used to develop the application to
other supporting constructions and installation methods in those supporting constructions.
4.2 Design and manufacturing changes
4.2.1 Pre-test
Before any fire testing is undertaken the relevant cycle tests and leakage tests at ambient temperatures
shall be undertaken to prove the durability of the proposed change in accordance with EN 15650.
7

---------------------- Page: 9 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
4.2.2 Fire test
The effect of design and manufacturing changes on the declared performances of essential characteristics
of the fire damper shall be proven by fire testing the fire damper in a previously tested supporting
construction and using the same installation method.
The supporting construction shall be the lightest in terms of mechanical stability that the fire damper was
previously tested in (e.g. dry wall versus solid masonry etc.). The fire damper shall be presented to the
test from the direction of the worst result obtained in previous testing or, if this is not clear from previous
test evidence, then with the actuator inside the furnace.
4.2.3 Extended field of application
Having passed the fire test in 4.2.2, the fire damper shall have the ability to be used for all other existing
classifications with an equal or lower classification time for the same supporting construction using any
already tested installation methods.
This is also allowed for all its other existing models with classifications with equal or lower classification
times in heavier supporting constructions with their different installation methods in accordance with
the existing direct field of application.
4.3 Actuators, remote triggering devices, actuating mechanisms, fusible links and
sensing elements
4.3.1 Actuators
4.3.1.1 General
If the fire damper assembly is a new design, previously untested, this section does not apply, and the fire
damper shall be tested fitted with the actuator in accordance with EN 1366-2 from both sides.
If the fire damper assembly has not been previously tested from both sides using an actuator/mechanism
etc, then this section does not apply until the fire damper assembly has been tested with the actuator in
accordance with EN 1366-2 from both sides.
When either of the above have been successfully tested the following may be applied.
All the following shall be undertaken in the order shown.
Actuator models with different voltages (e.g. 24 V, 230 V or multi-voltage) are considered to have no
influence on fire safety. Just one voltage needs to be tested. In the case of multi-voltage any voltage may
be tested.
4.3.1.2 Fire damper ambient cycle test
At least one sample of the fire damper assembly with the proposed new actuator shall be subjected to an
ambient cycle test.
The minimum number of cycles performed shall correspond to the expected application as shown in
EN 15650.
If different motive powers are proposed, then an actuator with each motive power level shall be subjected
to the cycle tests.
4.3.1.3 Confirmatory acceptance fire test
At least one sample (different to those in 4.3.1.2) of the proposed new actuator shall be subjected to a fire
test in accordance with EN 1366-2 on a previously tested fire damper obtained from the fire damper
manufacturer, installed in the lightest wall construction (generally lightweight metal stud partition with
one board on each side as the worst case).
8

---------------------- Page: 10 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
In cases of insulated fire dampers (with an EI classification), the actuator shall be positioned inside the
furnace. With only E classification dampers, two units shall be tested; one mounted on an E classification
fire damper inside the furnace and one mounted on an E classification fire damper outside the furnace.
Successful completion of a fire test on E classification fire dampers will allow use on EI classification fire
dampers.
To avoid confusion, even if the fire damper has the actuator mounted on the centre line, the product shall
be tested from both sides in the case of E or EI classification dampers.
In each case the fire damper shall perform at least as well, with regard to its classification times, as it did
in the same test previously. Tests performed on a vertically mounted fire damper will be applicable to
horizontally mounted fire dampers and vice versa.
4.3.1.4 Field of application
Provided all the above are fulfilled in order, the actuator may be fitted by the fire damper manufacturer
on tested families and series of fire damper. This shall apply to all tested installations and applications.
4.3.2 Actuators with an associated thermal element device that controls the action of the
actuator to close the fire damper in the event of fire
4.3.2.1 General
If the fire damper assembly is a new design, not previously tested, this section does not apply, and the
fire damper shall be tested fitted with the associated actuator in accordance with EN 1366-2 from both
sides.
If the fire damper assembly has not been previously tested from both sides using an actuator with
associated thermal element device then this section does not apply until the fire damper assembly has
been tested with the associated actuator in accordance with EN 1366-2 from both sides.
When either of the above have been successfully tested, the following may be applied.
All the following shall be undertaken in the order shown.
Actuator models with different voltages (e.g. 24 V, 230 V or multi-voltage) are considered to have no
influence on fire safety. Just one voltage needs to be tested. In the case of multi-voltage any voltage may
be tested.
4.3.2.2 Fire damper ambient cycle test
As in 4.3.1.2.
4.3.2.3 Confirmation of the thermal element device
The thermal element device shall pass the requirements of ISO 21925-1 (previously in ISO 10294-4 as
originally referenced in EN 15650).
4.3.2.4 Confirmatory acceptance fire test
As in 4.3.1.3.
If only the design of a thermal element device has been changed, conformity with 4.3.1.2 shall be fulfilled
without additional fire testing.
4.3.2.5 Field of application
Provided all the above are fulfilled in order, the actuator with the thermal element device may be fitted
by the fire damper manufacturer on tested families and series of fire damper. This shall apply to all tested
installations and applications.
9

---------------------- Page: 11 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
4.3.3 Remote triggering device (e.g. magnet)
4.3.3.1 General
In all cases fire dampers must have a thermal element device. This section covers any additional remote
mechanical triggering device.
If the fire damper is a new product, not previously tested, this section does not apply, and the fire damper
shall be tested fitted with an associated remote triggering device in accordance with EN 1366-2, from
both sides.
If the fire damper has not been previously tested from both sides using an associated remote triggering
device, then this section does not apply until the fire damper has been tested in accordance with
EN 1366-2 from both sides.
When either of the above have been successfully tested the following may be applied.
All the following shall be undertaken in the order shown.
4.3.3.2 Fire damper ambient cycle test
At least one sample of the fire damper assembly with the proposed new remote triggering device shall be
subjected to an ambient cycle test.
The minimum number of cycles performed shall correspond to the expected application as shown in
EN 15650.
4.3.3.3 Confirmatory acceptance fire test
At least two samples (different from 4.3.3.2) of the fire damper with the proposed new remote triggering
device shall be subjected to a fire test in accordance with EN 1366-2 on a previously tested fire damper
obtained from the fire damper manufacturer in the lightest wall construction (generally lightweight metal
stud partition with one board on each side as the worst case).
Two units shall be tested; one with new remote triggering device mounted inside the furnace and one
with the new remote triggering device mounted outside the furnace.
To avoid confusion, even if the fire damper has the new remote triggering device mounted on the centre
line, the product shall still be tested from both sides.
In each case the fire damper shall perform at least as well as it did in the same test previously. Tests
performed on a vertically mounted fire damper will be applicable to horizontally mounted fire dampers
and vice versa.
4.3.3.4 Field of application
Provided all the above are fulfilled in order, the new remote triggering device may be fitted by the fire
damper manufacturer on tested families and series of fire damper. This shall apply to all tested
installations and applications.
4.3.4 Actuating mechanism
4.3.4.1 General
The actuating mechanism is the connection mechanism between the actuator and/or remote release
mechanism and the damper blade. Modification may be made for different reasons (e.g. to simplify the
construction or change mechanical advantage).
If the fire damper assembly is a new product, previously untested, this section does not apply, and the
fire damper assembly shall be tested in accordance with EN 1366-2 from both sides.
10

---------------------- Page: 12 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
If the fire damper assembly has not been previously tested from both sides, then this section does not
apply until the fire damper assembly has been tested in accordance with EN 1366-2 from both sides.
When either of the above have been successfully tested the following may be applied.
All the following shall be undertaken in the order shown.
4.3.4.2 Fire damper ambient cycle test
At least one sample of the fire damper assembly with the proposed new actuating mechanism shall be
subjected to an ambient cycle test in each orientation proposed (e.g. horizontal and/or vertical).
The minimum number of cycles performed shall correspond to the expected application as shown in
EN 15650.
The mechanical advantage shall not be reduced.
If the previous actuating mechanism to be replaced does not have this data available for comparison then
the previous actuating mechanism shall be tested in this way at the same time as the proposed new
actuating mechanism to maintain consistency of testing.
4.3.4.3 Confirmatory acceptance fire test
At least two samples (different to those used 4.3.4.2 above) of the fire damper with the proposed new
actuating mechanism shall be subjected to a fire test in accordance with EN 1366-2, on a previously tested
fire damper in the lightest wall construction (generally lightweight metal stud partition with one board
on each side).
The actuator shall be mounted such that if the fastenings or pins preventing rotation fail, the weight of
the damper shall act to try and open the blades by putting an opening moment on the drive spindle to the
actuating mechanism.
Two units shall be tested, one with the actuating mechanism mounted inside the furnace and one with
the actuating mechanism mounted outside the furnace.
To avoid confusion, if the fire damper has the actuating mechanism mounted on the centre line, the
product shall still be tested from both sides.
In each case the fire damper shall perform at least as well as it did in the same test previously. Tests
performed on a vertically mounted fire damper will be applicable to horizontally mounted fire dampers
and vice versa.
4.3.4.4 Field of application
Provided all the above are fulfilled in order, the actuating mechanism may be fitted to any smaller fire
damper of the same type/family with the same or lower nominal declared torque on all the
manufacturers tested families and series of fire damper. This shall apply to all tested installations and
applications.
4.3.5 Fusible links and elements (not associated with the actuator supplier)
4.3.5.1 General
If the fire damper assembly is a new product, previously untested, this section does not apply, and the
fire damper assembly shall be tested in accordance with EN 1366-2 from both sides.
If the fire damper assembly has not been previously tested from both sides, then this section does not
apply until the fire damper assembly has been tested with the associated fusible link and element in
accordance with EN 1366-2 from both sides.
When either of the above have been successfully tested, the following may be applied.
11

---------------------- Page: 13 ----------------------
SIST EN 15882-2:2022
EN 15882-2:2022 (E)
All the following shall be undertaken in the order shown.
4.3.5.2 Fire damper ambient cycle test
At least one sample of the fire damper assembly with the proposed new fusible link or sensing element
shall be subject to an ambient cycle test. The cycles performed shall correspond to the expected
application at a minimum.
The test method shall follow the cycling tests for the expected application, as shown in EN 15650.
4.3.5.3 Confirmation of the fusib
...

SLOVENSKI STANDARD
oSIST prEN 15882-2:2021
01-maj-2021
Razširjena uporaba rezultatov preskusov požarne odpornosti servisnih inštalacij -
2. del: Požarne lopute
Extended application of results from fire resistance tests for service installations - Part 2:
Fire dampers
Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für
Installationen - Teil 2: Brandschutzklappen
Application étendue des résultats des essais de résistance au feu des installations de
service - Partie 2: Clapets résistant au feu
Ta slovenski standard je istoveten z: prEN 15882-2
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
oSIST prEN 15882-2:2021 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 15882-2:2021

---------------------- Page: 2 ----------------------
oSIST prEN 15882-2:2021


DRAFT
EUROPEAN STANDARD
prEN 15882-2
NORME EUROPÉENNE

EUROPÄISCHE NORM

March 2021
ICS 13.220.99 Will supersede EN 15882-2:2015
English Version

Extended application of results from fire resistance tests
for service installations - Part 2: Fire dampers
Application étendue des résultats des essais de Erweiterter Anwendungsbereich der Ergebnisse aus
résistance au feu des installations de service - Partie 2: Feuerwiderstandsprüfungen für Installationen - Teil 2:
Clapets résistant au feu Brandschutzklappen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 127.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15882-2:2021 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021 (E)
Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 Test requirements for assessment of design changes . 6
4.1 General. 6
4.2 Manufacturing changes . 6
4.2.1 Pre-test . 6
4.2.2 Fire test . 6
4.2.3 Extended field of application . 6
4.3 Actuators, remote triggering devices, actuating mechanisms, fusible links and sensing
elements . 7
4.3.1 Actuators . 7
4.3.2 Actuators with an associated thermal element device that controls the action of the
actuator to close the fire damper in the event of fire . 8
4.3.3 Remote triggering device (e.g. magnet) . 9
4.3.4 Actuating mechanism . 10
5 Determination of worst case . 12
6 Conditions and application rules . 12
6.1 Change of fixing damper to supporting construction . 12
6.2 Multiple damper assemblies . 12
6.2.1 E Classification only . 12
6.2.2 EI, E-S, EI-S Classifications . 14
6.2.3 Field of application . 15
6.3 Alternative penetration seals . 15
7 Influence of parameters and factors on fire damper performance . 15
8 Critical parameters and factors . 16
8.1 General. 16
8.2 Common operational parameters and factors . 16
8.3 Constructional parameters . 16
8.4 Parameters of components of damper . 17
8.5 Installing parameters . 18
9 Methodology . 19
10 Extended field of application report . 38
Bibliography . 41
2

---------------------- Page: 4 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021(E)
European foreword
This document (prEN 15882-2:2021) has been prepared by Technical Committee CEN/TC 127 “Fire
safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
EN 15882, Extended application of results from fire resistance tests for service installations, consists of the
following parts:
— Part 1: Ducts
— Part 2: Fire dampers
— Part 3: Penetration seals
— Part 4: Linear joint seals
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
3

---------------------- Page: 5 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021 (E)
Introduction
It should be noted that fire resisting dampers are special products that are exposed to different conditions
than other elements of construction; in particular they are subjected to significantly different pressure
regimes. Integrity is also evaluated through leakage measurements. Consequently, this document may
adopt a different approach to other extended field of application standards, with more emphasis on
testing.
4

---------------------- Page: 6 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021(E)
1 Scope
This document provides guidance and rules to notified bodies (for fire dampers) allowing them to
produce/validate an extended field of application report for fire dampers. This document identifies the
parameters that affect the fire resistance of dampers. It also identifies the factors that need to be
considered when deciding whether, or by how much, the parameter can be extended when contemplating
the fire resistance performance of an untested, or untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific
parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control.
It is the intention that the application of this document makes it possible to identify which specifications
to test to maximize the field of application. Some information on test programmes is given for guidance
purposes.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 1363-1, Fire resistance tests — Part 1: General requirements
EN 1366-1:2014+A1:2020, Fire resistance tests for service installations — Part 1: Ventilation ducts
EN 1366-2, Fire resistance tests for service installations — Part 2: Fire dampers
EN 13501-3, Fire classification of construction products and building elements — Part 3: Classification
using data from fire resistance tests on products and elements used in building service installations: fire
resisting ducts and fire dampers
EN 15882-1, Extended application of results from fire resistance tests for service installations — Part 1:
Ducts
EN 15650, Ventilation for buildings — Fire dampers
ISO 21925-1, Fire resistance tests — Fire dampers for air distribution systems — Part 1: Mechanical
dampers
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1, EN 1366-2, EN 15650
and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
3.1
multiple assembly
multiple damper assembly
assembly of individual damper units to form larger units
5

---------------------- Page: 7 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021 (E)
3.2
horizontal
orientation/position of the damper mounted horizontally
EXAMPLE When installed in the plane of a floor or a ceiling.
3.3
vertical
orientation/position of the damper mounted vertically
EXAMPLE When installed in the plane of a wall.
3.4
supporting construction
construction used as part of the test assembly to support the test specimen and to fill in the furnace
aperture
3.5
standard supporting construction
supporting construction that has known fire behaviour and for which a direct field of application has been
established
4 Test requirements for assessment of design changes
4.1 General
Many manufacturers will want to introduce manufacturing changes to make use of differing production
techniques, whilst essentially keeping a product the same. In addition, they may wish to change actuators
and activating mechanisms, sometimes across a range of products.
Such a test shall not be used to develop the application to other supporting constructions and installation
methods in those supporting constructions.
4.2 Manufacturing changes
4.2.1 Pre-test
Before any fire testing is undertaken the relevant cycle tests and leakage tests at ambient temperatures
shall be undertaken to prove the durability of the proposed change.
4.2.2 Fire test
Manufacturing changes shall be proven by fire testing the fire damper in previously tested supporting
construction and using the same installation method. The supporting construction shall be the lightest
that the fire damper was previously tested in (e.g. dry wall versus solid masonry etc.). The fire damper
shall be presented to the test from the direction of the worst result obtained in previous testing or, if this
is not clear from previous test evidence, then with the actuator inside the furnace.
4.2.3 Extended field of application
The fire damper shall have the ability to be used for all other existing classifications for the same
supporting construction using different installation methods and also all for all its existing classifications
in heavier supporting constructions with their different installation methods.
6

---------------------- Page: 8 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021(E)
4.3 Actuators, remote triggering devices, actuating mechanisms, fusible links and
sensing elements
4.3.1 Actuators
4.3.1.1 General
This only applies to new ranges of actuator provided by the same actuator manufacturer.
If the fire damper is a new product, previously untested, this section does not apply, and the fire damper
shall be tested fitted with the actuator associated with EN 1366-2 from both sides.
If the fire damper has not been previously tested from both sides using an actuator, then this section does
not apply until the fire damper has been tested with the actuator associated with EN 1366-2 from both
sides.
When either of the above have been successfully tested the following may be applied.
All the following shall be undertaken in the order shown.
4.3.1.2 Actuator ambient cycle test under load
At least one sample of the proposed new actuator shall be subjected to an ambient cycle test under load
in both directions of rotation by the actuator manufacturer. The actuator will not be connected to a fire
damper for this test. The load applied shall be at least the nominal declared load in accordance with the
actuator specification and shall be set by the actuator manufacturer. The minimum number of cycles
performed shall correspond to the expected application. This shall be 10 200 for general purpose fire
damper actuators and 20 000 for modulating fire dampers. If different motive powers are proposed, then
an actuator with each motive power level shall be subjected to the cycle tests.
The ambient spring return running time shall be the same or shorter than the actuator being replaced.
The ambient spring return torque shall be the same or greater than the actuator being replaced.
The ambient angle of rotation shall be the same as the actuator being replaced.
The calorific value of any combustible material in the actuator construction shall be the same or less than
the actuator being replaced.
If the actuator range (from the same manufacturer) of the actuator being replaced does not have this data
available for comparison it shall be tested in this way at the same time as the proposed new actuator.
4.3.1.3 Actuator fire test
At least one sample (different from that in 4.3.1.2) of the proposed new actuator shall be subjected to a
fire test under load by the actuator manufacturer. The load to be used shall be set by the actuator
manufacturer and shall be at least the nominal declared load corresponding to 4.3.1.2.
The actuator shall perform 50 cycles at ambient prior to the fire test under nominal declared load
specified by actuators manufacturer.
The actuator shall be mounted on the inside of the furnace with the loading arranged on the outside of
the furnace.
The actuator shall be subjected to a fire test following the general fire test parameters of EN 1366-2.
The actuator shall be powered to the ON (open) position before the test is started and released to the OFF
(closed) position by removing the supply power when furnace reaches 50°C. The actuator shall reach the
OFF (closed) position in less than two minutes.
The actuator shall maintain its position for the same time or longer than the actuator being replaced.
7

---------------------- Page: 9 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021 (E)
If the actuator range (from the same manufacturer) of the actuator being replaced does not have this data
available for comparison it shall be tested in this way at the same time as the proposed new actuator.
4.3.1.4 Confirmatory acceptance fire test
At least one sample (different to those in 4.3.1.2 and 4.3.1.3) of the proposed new actuator shall be
subjected to a fire test in accordance with EN 1366-2 on a previously tested fire damper obtained from
any fire damper manufacturer, installed in the lightest wall construction (generally lightweight metal
stud partition with one board on each side as the worst case).
In cases of insulated fire dampers (with an EI classification), the actuator shall be positioned inside the
furnace. With only E classification dampers, two units shall be tested; one mounted on an E classification
fire damper inside the furnace and one mounted on an E classification fire damper outside the furnace.
Successful completion of a fire test on E classification fire dampers will allow use on EI classification fire
dampers.
To avoid confusion, even if the fire damper has the actuator mounted on the centre line, the product shall
be tested from both sides in the case of E or EI classification dampers.
In each case the fire damper shall perform at least as well, with regard to its classification times, as it did
in the same test previously. Tests performed on a vertically mounted fire damper will be applicable to
horizontally mounted fire dampers and vice versa.
4.3.1.5 Field of application
Provided all the above are satisfactorily fulfilled in order, the actuator may be supplied to and fitted by
any fire damper manufacturer who has previously fitted a similar actuator from the same actuator
manufacturer on tested families and series of fire damper. This shall apply to all tested installations and
applications.
4.3.2 Actuators with an associated thermal element device that controls the action of the
actuator to close the fire damper in the event of fire
4.3.2.1 General
This only applies to new ranges of actuator provided by the same actuator manufacturer
If the fire damper is a new product, not previously tested, this section does not apply, and the fire damper
shall be tested fitted with the associated actuator in accordance with EN 1366-2 from both sides.
If the fire damper has not been previously tested from both sides using an actuator with associated
thermal element device then this section does not apply until the fire damper has been tested with the
associated actuator in accordance with EN 1366-2 from both sides.
When either of the above have been successfully tested, the following may be applied.
All the following shall be undertaken in the order shown.
4.3.2.2 Actuator ambient cycle test under load
As in 4.3.1.2.
4.3.2.3 Actuator fire test
As in 4.3.1.2.
4.3.2.4 Confirmation of the thermal element device
The thermal element device shall satisfactorily pass the requirements of ISO 21925-1 (previously in
ISO 10294-4).
8

---------------------- Page: 10 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021(E)
4.3.2.5 Confirmatory acceptance fire test
As in 4.3.1.3.
If only the design or type of a thermal element device has been changed, conformity with 4.3.1.2 shall be
fulfilled without additional fire testing.
4.3.2.6 Field of application
Provided all the above are satisfactorily fulfilled in order, the actuator with the thermal element device
may be supplied to and fitted by any fire damper manufacturer who has previously fitted a similar
actuator with a thermal element device from the same actuator manufacturer on tested families and
series of fire damper. This shall apply to all tested installations and applications.
4.3.3 Remote triggering device (e.g. magnet)
4.3.3.1 General
If the fire damper is a new product, not previously tested, this section does not apply, and the fire damper
shall be tested fitted with an associated remote triggering device in accordance with EN 1366-2, from
both sides.
If the fire damper has not been previously tested from both sides using an associated remote triggering
device, then this section does not apply until the fire damper has been tested in accordance with EN 1366-
2 from both sides.
When either of the above have been successfully tested the following may be applied.
All the following shall be undertaken in the order shown.
4.3.3.2 Damper ambient cycle test
At least one sample of the fire damper with the proposed new remote triggering device shall be subjected
to an ambient cycle test under load. The cycles performed shall be at minimum corresponding to the
expected application. The minimum number of cycles performed shall correspond to the expected
application: This shall be at least 300 cycles (10 200 or 20 000 may be selected). If different motive
powers are proposed, then a remote triggering mechanism with each motive power level shall be
subjected to the cycle tests.
4.3.3.3 Confirmatory acceptance fire test
At least two samples (different from 4.3.1.2) of the proposed new remote triggering device shall be
subjected to a fire test in accordance with EN 1366-2 on a previously tested fire damper obtained from
any fire damper manufacturer in the lightest wall construction (generally lightweight metal stud partition
with one board on each side / worst case).
Two units shall be tested; one with new remote triggering device mounted inside the furnace and one
with the new remote triggering device mounted outside the furnace.
To avoid confusion, even if the fire damper has the new remote triggering device mounted on the centre
line, the product shall still be tested from both sides.
In each case the fire damper shall perform at least as well as it did in the same test previously. Tests
performed on a vertically mounted fire damper will be applicable to horizontally mounted fire dampers
and vice versa.
4.3.3.4 Field of application
Provided all the above are satisfactorily fulfilled in order, the new remote triggering device may be
supplied to and fitted by any fire damper manufacturer who has previously fitted a similar remote
9

---------------------- Page: 11 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021 (E)
triggering device from the same manufacturer on tested families and series of fire damper. This shall
apply to all tested installations and applications.
4.3.4 Actuating mechanism
4.3.4.1 General
The actuating mechanism is the connection mechanism between any actuator or remote release
mechanism and the damper blade. Modification may be made for different reasons (e.g. to simplify the
construction or change mechanical advantage).
If the fire damper is a new product, previously untested, this section does not apply, and the fire damper
shall be tested in accordance with EN 1366-2 from both sides.
If the fire damper has not been previously tested from both sides, then this section does not apply until
the fire damper has been tested in accordance with EN 1366-2 from both sides.
When either of the above have been successfully tested the following may be applied.
All the following shall be undertaken in the order shown.
4.3.4.2 Damper ambient cycle test
At least one sample of the fire damper with the proposed new actuating mechanism shall be subjected to
an ambient cycle test.
The minimum number of cycles performed shall correspond to the expected application. This shall be
300 for remote release only, 10 200 for general purpose fire damper actuators and 20 000 for modulating
fire dampers.
The mechanical advantage shall not be reduced.
If the previous actuating mechanism to be replaced does not have this data available for comparison it
shall be tested in this way at the same time as the proposed new actuator.
4.3.4.3 Confirmatory acceptance fire test
At least two samples (different to those used above) of the fire damper with the proposed new actuating
mechanism shall be subjected to a fire test in accordance with EN 1366-2, on a previously tested fire
damper in the lightest wall construction (generally lightweight metal stud partition with one board on
each side).
The actuator shall be mounted such that if the fastenings or pins preventing rotation fail, the weight of
the damper shall act to try and open the blades by putting an opening moment on the drive spindle to the
actuating mechanism.
Two units shall be tested, one with the actuating mechanism mounted inside the furnace and one with
the actuating mechanism mounted outside the furnace.
To avoid confusion, if the fire damper has the actuating mechanism mounted on the centre line, the
product shall still be tested from both sides.
In each case the fire damper shall perform at least as well as it did in the same test previously. Tests
performed on a vertically mounted fire damper will be applicable to horizontally mounted fire dampers
and vice versa.
4.3.4.4 Field of application
Provided all the above are satisfactorily fulfilled in order, the actuating mechanism may be fitted to any
smaller fire damper with the same or lower nominal declared torque on all the manufacturers tested
families and series of fire damper. This shall apply to all tested installations and applications.
10

---------------------- Page: 12 ----------------------
oSIST prEN 15882-2:2021
prEN 15882-2:2021(E)
4.3.4.5 Fusible links and elements (not associated with the actuator supplier)
If the fire damper is a new product, previously untested, this section does not apply, and the fire damper
shall be tested in accordance with EN 1366-2 from both sides.
If the fire damper has not been previously tested from both sides, then this section does not apply until
the fire damper has been tested with the associated fusible link and element in accordance with
EN 1366-2 from both sides.
When either of the above have been successfully tested, the following may be applied.
All the following shall be undertaken in the order shown.
4.3.4.6 Damper ambient cycle test
At least one sample of the fire damper with the proposed new fusible link or sensing element shall be
subject to an ambient cycle test. The cycles performed shall correspond to the expected application at a
minimum.
The test method shall follow the cycling tests for the expected application, as shown in EN 15650.
4.3.4.7 Confirmation of the thermal element device
The thermal element device shall satisfactorily pass the requirements of ISO 21925-1 (previously in
ISO 10294-4).
4.3.4.8 Confirmatory acceptance fire test
At least two samples (different from those in 4.3.1.2 and 4.3.1.3) of the fire damper with the proposed
new fusible link or sensing element shall be subjected to a fire test, in accordance with EN 1366-2, on a
previously tested fire damper in the lightest wall construction (generally lightweight metal stud partition
with one board on each side as the worst case).
Two units shall be tested, one with the fusible link or sensing element mounted inside the furnace and
one with the fusible link or sensing element mounted outside the furnace.
To avoid confusion, even if the fire damper has the fusible link or sensing element mounted on the centre
line, the product shall still be tested from both sides.
In each case the fire damper shall perform at least as well as it did in the same test previously. Tests
performed on a vertically mounted fire damper will be applicable to horizontally mounted fire dampers
and vice versa.
4.3.4.9 Field of application
Provided all the above are satisfactorily fulfilled in order, the fusible link or sensing element may be
supplied to and fitt
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.