SIST EN 15882-4:2012
(Main)Extended application of results from fire resistance tests for service installations - Part 4: Linear joint seals
Extended application of results from fire resistance tests for service installations - Part 4: Linear joint seals
This European standard prescribes the methodology and specifies rules for the preparation of extended application reports for linear joint sealing systems tested in accordance with EN 1366-4. The field of the extended application reports is additional to the direct field of application given within EN 1366-4 and may be applied to or based on a single test, or a number of tests, which provide the relevant information for the formulation of an extended application.
Mechanical metal seals are not part of the scope of this European standard.
Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für Installationen - Teil 4: Abdichtungssysteme für Bauteilfugen
Die Europäische Norm legt die Methodologie und Regeln für die Erarbeitung von Berichten zur erweiterten Anwendung von nach EN 1366 4 geprüften Abdichtungssystemen für Bauteilfugen fest. Der erweiterte Anwendungsbereich gilt zusätzlich zum direkten Anwendungsbereich nach EN 1366 4 und kann auf einer einzelnen Prüfung oder mehreren Prüfungen basieren, die die relevanten Informationen für eine erweiterte Anwendung liefern.
Mechanische Abdichtungen aus Metall sind nicht Gegenstand dieser Europäischen Norm.
Application étendue des résultats des essais de résistance au feu - Partie 4 : Calfeutrements de joints linéaires
La présente Norme européenne spécifie les règles et prescrit la méthodologie de préparation des rapports d'application étendue portant sur des systèmes de calfeutrements de joints linéaires soumis à l'essai conformément à l'EN 1366-4. Par rapport au domaine d’application directe décrit dans l’EN 1366-4, le domaine d’application étendue est complémentaire, et peut s’appliquer à un seul ou plusieurs essais ou être fondé sur ces derniers, lesquels fournissent les informations pertinentes permettant de formuler une application étendue.
Les calfeutrements métalliques mécaniques ne relèvent pas du domaine d'application de la présente Norme européenne.
Razširjena uporaba rezultatov preskusov požarne odpornosti - 4. del: Tesnilna sredstva za ravne stike
Ta evropski standard določa metodologijo in pravila za pripravo poročil o razširjeni uporabi za sisteme tesnilnih sredstev za ravne stike, preskušene v skladu s standardom EN 1366-4. Področje poročil o razširjeni uporabi je dodatek k neposrednemu področju uporabe iz standarda EN 1366-4 in se lahko uporablja ali temelji na posameznem preskusu ali več preskusih, ki zagotavljajo ustrezne informacije za oblikovanje razširjene uporabe.
General Information
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Razširjena uporaba rezultatov preskusov požarne odpornosti - 4. del: Tesnilna sredstva za ravne stikeErweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für Installationen - Teil 4: Abdichtungssysteme für BauteilfugenApplication étendue des résultats des essais de résistance au feu - Partie 4 : Calfeutrements de joints linéairesExtended application of results from fire resistance tests for service installations - Part 4: Linear joint seals91.100.50Veziva. Tesnilni materialiBinders. Sealing materials13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 15882-4:2012SIST EN 15882-4:2012en,fr,de01-julij-2012SIST EN 15882-4:2012SLOVENSKI
STANDARD
SIST EN 15882-4:2012
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15882-4
May 2012 ICS 13.220.99 English Version
Extended application of results from fire resistance tests for service installations - Part 4: Linear joint seals
Application étendue des résultats des essais de résistance au feu pour les installations de service - Partie 4 : Calfeutrements de joints linéaires
Erweiterter Anwendungsbereich der Ergebnisse aus Feuerwiderstandsprüfungen für Installationen - Teil 4: Abdichtungssysteme für Bauteilfugen This European Standard was approved by CEN on 30 March 2012.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15882-4:2012: ESIST EN 15882-4:2012
EN 15882-4:2012 (E) 2 Contents Page Foreword .31Scope .42Normative references .43Terms and definitions .44Extended application principles .74.1General .74.2Principles common to all generic seal types .74.2.1General .74.2.2Seal material (primary generic linear joint seal material as per Annex A).84.2.3Separating elements — Concrete or masonry .84.2.4Separating elements – Flexible constructions .84.2.5Seal depth .95Extended application report Contents of the extended application report .9Annex A (normative)
Extended application principles for generic joint seal types . 11A.1General rules . 11A.2Specific rules . 12 SIST EN 15882-4:2012
EN 15882-4:2012 (E) 3 Foreword This document (EN 15882-4:2012) has been prepared by Technical Committee CEN/TC 127 “Fie safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by November 2012, and conflicting national standards shall be withdrawn at the latest by November 2012. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. EN 15882 consists of the following parts: EN 15882-1, Extended application of results from fire resistance tests for service installations Part 1: Ducts; prEN 15882-2, Extended application of results from fire resistance tests for service installations Part 2: Dampers; EN 15882-3, Extended applications of results from fire resistance tests for service installations Part 3: Penetration seals; EN 15882-4, Extended application of results from fire resistance tests for service installations — Part 4: Linear joint seals. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
SIST EN 15882-4:2012
EN 15882-4:2012 (E) 4 1 Scope This European standard specifies rules and prescribes the methodology for the preparation of extended application reports for linear joint sealing systems tested in accordance with EN 1366-4. The field of the extended application reports is additional to the direct field of application given in EN 1366-4. It may be applied to or based on a single test, or a number of tests, which provide the relevant information for the formulation of an extended application.
Mechanical metal seals are not part of the scope of this European Standard.
2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:1999, Fire resistance tests — Part 1: General requirements EN 1363-2:1999, Fire resistance tests — Part 2: Alternative and additional procedures EN 1366-4:2006+A1:2010, Fire resistance tests for service installations — Part 4: Linear joint seals EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements — Part 1: Classification using data from reaction to fire tests EN 13501-2:2007+A1:2009, Fire classification of construction products and building elements — Part 2: Classification using data from fire resistance tests, excluding ventilation services EN ISO 13943:2010, Fire safety — Vocabulary (ISO 13943:2008) 3 Terms and definitions For the purposes of this document the terms and definitions given in EN 1363-1:1999, EN 1363-2:1999,
EN 1366-4:2006+A1:2010, EN 13501-1:2007+A1:2009, EN 13501-2:2007+A1:2009 and EN ISO 13943:2010, and the following apply: 3.1 fabric seal seal comprised of a woven fabric, usually glass cloth or similar, which may be used in a combination with other material, such as metal facings, etc. to provide a composite seal 3.2
foam seal seal made from a one, two or three component expanding foam (expands during application), applied in-situ 3.3
joint depth overall distance between the exposed and unexposed faces across the thickness of the separating element Note 1 to entry: See Figure 1. 3.4
joint face framing additional substrate incorporated between the supporting construction and the joint seal SIST EN 15882-4:2012
EN 15882-4:2012 (E) 5 3.5
joint width distance between the two adjacent faces of the building element(s) Note 1 to entry: See Figure 1. 3.6
mineral wool seal seal comprised mostly or entirely of glass, stone, slag or ceramic wool, which is either faced/coated or non-faced/coated
3.7
mortar seal seal comprising a cementitious or gypsum based compound together with other filler materials, usually mixed on site with water to achieve the required workability 3.8
movement joint joint between adjacent building elements or within a building element designed to accommodate a degree of movement greater than ± 7,5% (such as deflection, thermal movement or seismic) 3.9
non-movement joint joint between adjacent building elements or within a building element not designed to accommodate movement greater than ± 7,5% (such as those designed to accommodate construction tolerances or irregularities of fit) 3.10
seal depth shortest distance between the exposed and unexposed surfaces of the seal
Note 1 to entry: See Figure 1. 3.11 seal width width of the seal in the non-installed condition (for uncompressed solid
...
Questions, Comments and Discussion