Thermal insulation products for building equipment and industrial installations - Factory made mineral wool (MW) products - Specification

This European Standard specifies the requirements for factory made mineral wool products, which are used for the thermal insulation of building equipment and industrial installations with an operating temperature range of approximately 0 °C to + 800 °C. NOTE Below an operating temperature of ambient, special means against water vapour diffusion and water accumulation by air flow might be required. Below an operating temperature of - 50 °C, special tests regarding the suitability of the products in the intended application are advised (e.g. liquefaction of oxygen). Manufacturer's advice should be heeded in all cases. The products are manufactured with or without facings or coatings, in the form of rolls, boards, slabs, mats, felts, quilts, wired mats, lamella mats, bevelled lags and pipe sections. This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This European Standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,065 W/(m•K) at 10 °C are not covered by this standard. This Eurpean Standard does not cover products for in situ insulation (blowing or pouring) or products for the insulation of the building structure. This European Standard does not cover the following acoustical aspects: direct airborne sound insulation and
impact noise transmission index.

Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Mineralwolle (MW) - Spezifikation

Diese Europäische Norm legt die Anforderungen für werkmäßig hergestellte Produkte aus Mineralwolle fest, die als Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie im Temperaturbereich von etwa 0 °C bis 800 °C benutzt werden.
ANMERKUNG   Unterhalb einer Betriebstemperatur, die der Umgebungstemperatur entspricht, könnten besondere Maßnahmen gegen die Wasserdampfdiffusion und gegen Wasseransammlungen im Dämmstoff auf Grund von Luft¬bewegungen erforderlich sein. Unterhalb einer Betriebstemperatur von 50 °C sind besondere Prüfungen bezüglich der Eignung der Produkte für den beabsichtigten Anwendungsfall ratsam (z. B. Sauerstoffverflüssigung). In jedem Fall sollten die Empfehlungen des Herstellers beachtet werden.
Die Produkte werden mit oder ohne Kaschierung und Beschichtung in der Form von Rollen, Platten, Matten, Filzen, Matratzen, Drahtnetzmatten, Lamellen-Matten, abgeschrägten Segmenten und Rohrschalen her-gestellt.
Diese Europäische Norm beschreibt die Produkteigenschaften und enthält die Prüfverfahren und Fest-legungen für die Konformitätsbewertung, die Kennzeichnung und die Etikettierung.
Die in dieser Norm beschriebenen Produkte werden auch in vorgefertigten Wärmedämmsystemen und Mehr-schicht-Verbundplatten angewendet; die Eigenschaften von Systemen, in die diese Produkte integriert sind, werden nicht behandelt.
Diese Europäische Norm legt keine Leistungsstufen für eine vorgegebene Eigenschaft fest, die ein Produkt erreichen muss, um für einen bestimmten Anwendungsfall tauglich zu sein. Für bestimmte Anwendungen benötigte Stufen können Regelwerken oder Ausschreibungen entnommen werden.
Diese Europäische Norm gilt nicht für Produkte, deren Nennwert der Wärmeleitfähigkeit größer ist als 0,065 W/(mK) bei 10 °C.
Diese Europäische Norm gilt nicht für Produkte für an der Verwendungsstelle hergestellte Wärmedämmung (eingeblasen oder geschüttet) oder Produkte, die zur Dämmung des Bauwerks bestimmt sind.
Diese Europäische Norm gilt nicht für die folgenden akustischen Zwecke: Luftschalldämmung und Tritt-schall¬übertragung.

Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés à base de laines minérales (MW) - Spécification

La présente norme spécifie les exigences relatives aux produits manufacturés à base de laines minérales, utilisés pour l’isolation thermique de l’équipement du bâtiment et des installations industrielles, dont la température de service est approximativement comprise entre 0 °C et + 800 °C.
NOTE   En cas de température de service inférieure à la température ambiante, des moyens spéciaux contre la diffusion de la vapeur d’eau et l’accumulation d’eau par écoulement de l’air peuvent être requis. Pour une température de service inférieure à – 50 °C, des essais particuliers sont recommandés pour s'assurer de l'aptitude à l'emploi du produit dans l'application visée (p.ex. liquéfaction de l'oxygène). Il convient de se référer systématiquement aux conseils du fabricant.
Les produits sont manufacturés avec ou sans parements ou enduits de finition, sous la forme de rouleaux, de panneaux, de feutres, de «felts», de matelas capitonnés, de nappes grillagées, de feutres lamellaires, de segments à onglets et de coquilles.
La présente Norme européenne décrit les caractéristiques de ces produits et comporte des modes opératoires d’essai, d’évaluation de conformité, de marquage et d’étiquetage.
Les produits couverts par la présente norme sont également utilisés dans les systèmes d’isolation thermique préfabriqués et les panneaux composites ; les performances des systèmes incorporant ces produits ne sont pas traitées.
La présente Norme européenne ne spécifie pas le niveau requis pour une propriété donnée que doit posséder un produit pour démontrer son aptitude à une application particulière. Les niveaux requis pour une application donnée peuvent être trouvés dans les réglementations et les appels d’offre.
Les produits dont la conductivité thermique déclarée est supérieure à 0,065 W/(m•K) à 10 °C ne sont pas couverts par la présente norme.
La présente Norme européenne ne couvre ni les produits pour l’isolation in situ (soufflage ou déversement) ni les produits pour l’isolation des structures de bâtiments.
La présente Norme européenne ne couvre pas les critères acoustiques suivants : isolation contre le bruit aérien direct et indice de transmission du bruit d’impact.

Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz mineralne volne (MW) - Specifikacija

Ta evropski standard določa zahteve za proizvode iz mineralne volne, ki se uporabljajo za toplotno izolacijo opreme stavb in industrijskih inštalacij z razponom delovne temperature približno od 0 °C do 800 °C. OPOMBA Pod delovno temperaturo okolja se morda zahtevajo posebni ukrepi proti difuziji vodne pare in zbiranju vode s pretokom zraka. Pod delovno temperaturo –50 °C se priporočajo posebni preskusi glede primernosti proizvodov za nameravano vrsto uporabe (npr. utekočinjenje kisika). V vseh primerih je treba upoštevati napotke proizvajalca. Proizvodi so izdelani s površinsko prevleko ali lakom ali brez v obliki kolutov, desk, plošč, preprog, polstov, polnil, ožičenih preprog, lamelnih preprog, posnetih oblog in vodovodnih odsekov. Ta evropski standard opisuje lastnosti proizvodov ter zajema postopke za preskušanje, vrednotenje skladnosti, označevanje in etiketiranje. Proizvodi iz tega standarda se uporabljajo tudi v predizdelanih sistemih toplotne izolacije in vezanih ploščah; lastnosti sistemov iz teh proizvodov niso opisane. Ta evropski standard ne določa zahtevane ravni določene lastnosti, ki jo mora proizvod doseči, da se dokaže njegova primernost namenu za posamezno vrsto uporabe. Zahtevane ravni za posamezno uporabo so določene v uredbah in javnih razpisih. Proizvodi z deklarirano toplotno prevodnostjo, višjo od 0,065 W/mK pri 10 °C, v tem standardu niso zajeti. Ta evropski standard ne zajema proizvodov za izolacijo na kraju samem (pihanje ali vlivanje) ali proizvodov za izolacijo stavbne strukture. Ta evropski standard ne zajema naslednjih akustičnih vidikov: neposredne izolirnosti pred zvokom v zraku in indeksa prenosa udarnega zvoka.

General Information

Status
Withdrawn
Publication Date
04-Apr-2013
Withdrawal Date
06-Jan-2016
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
07-Jan-2016
Due Date
30-Jan-2016
Completion Date
07-Jan-2016

Relations

Buy Standard

Standard
EN 14303:2010+A1:2013
English language
35 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz mineralne volne (MW) - SpecifikacijaWärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Mineralwolle (MW) - SpezifikationProduits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés à base de laines minérales (MW) - SpécificationThermal insulation products for building equipment and industrial installations - Factory made mineral wool (MW) products - Specification91.100.60Thermal and sound insulating materialsICS:Ta slovenski standard je istoveten z:EN 14303:2009+A1:2013SIST EN 14303:2010+A1:2013en,fr,de01-maj-2013SIST EN 14303:2010+A1:2013SLOVENSKI
STANDARD



SIST EN 14303:2010+A1:2013



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14303:2009+A1
January 2013 ICS 91.100.60 Supersedes EN 14303:2009English Version
Thermal insulation products for building equipment and industrial installations - Factory made mineral wool (MW) products - Specification
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés à base de laines minérales (MW) - Spécification
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Mineralwolle (MW) -Spezifikation This European Standard was approved by CEN on 29 September 2009 and includes Amendment 1 approved by CEN on 11 November 2012.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2013 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14303:2009+A1:2013: ESIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 2
Contents Page Foreword .3 1 Scope .5 2 Normative references .5 3 Terms, definitions, symbols, units and abbreviated terms .6 4 Requirements .9 5 Test methods . 15 6 Designation code . 18 7 Evaluation of conformity . 19 8 Marking and labelling . 19 Annex A (normative)
Factory production control . 21 Annex B (informative)
Additional Properties . 25 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive . 27 Bibliography . 35 Figures Figure ZA.1 — Example of CE marking information . 34 Tables Table 1 — Levels and classes for thickness tolerances. 11 Table 2 — Levels and classes for dimensional tolerances . 11 Table 3 — Load for thickness measurements . 12 Table
4 — Water vapour diffusion equivalent air layer thickness . 14 Table 5 — Test methods, specimens and conditions . 17 Table A.1 — Minimum product testing frequencies . 21 Table A.2 — Minimum product testing frequencies for the reaction to fire characteristics . 23 Table B.1 — Test methods, specimens and conditions . 26 Table ZA.1 — Relevant clauses . 28 Table ZA.2 — System(s) of attestation of conformity . 29 Table ZA.3 — Assignment of evaluation of conformity tasks for products under system 1 . 30 Table ZA.4 — Assignment of evaluation of conformity tasks for products under system 3 or system 3 combined with system 4 for reaction to fire . 31
SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 3 Foreword This European Standard (EN 14303:2009+A1:2013) has been prepared by Technical Committee CEN/TC 88 “Thermal insulating materials and products”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by July 2013, and conflicting national standards shall be withdrawn at the latest by July 2013. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 14303:2009. This document includes Amendment 1 approved by CEN on 2012-11-11. The start and finish of text introduced or altered by amendment is indicated in the text by tags !". This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive 89/106/EEC. For relationship with EU Directive 89/106/EEC, see informative Annex ZA, which is an integral part of this document. Locally responsible authorities and contracting entities, who are bound by EU Directives to specify their requirements using European harmonized product standards, are allowed to demand additional properties outside the provisions of this standard if this is technically necessary because of prevailing operational conditions of the building equipment or the industrial installation projected or because of safety regulations. This European Standard contains three annexes:  Annex A (normative), Factory production control;  Annex B (informative), Additional properties;  Annex ZA (informative), Clauses of this European Standard addressing the provisions of the EU Construction Products Directive. This document includes a bibliography. This European Standard is one of a series of standards for insulation products used in building equipment and industrial installations, but this standard can be used in other areas, where appropriate. In pursuance of Resolution BT 20/1993 revised, CEN/TC 88 have proposed defining the standards listed below as a European package of standards, setting 21 months after availability as the date of withdrawal (dow) of national standards which conflict with the European Standards of this package. The package of standards comprises the following group of interrelated standards for the specifications of factory made thermal insulation products, all of which come within the scope of CEN/TC 88: EN 14303, Thermal insulation products for building equipment and industrial installations — Factory made mineral wool (MW) products — Specification EN 14304, Thermal insulation products for building equipment and industrial installations — Factory made flexible elastomeric foam (FEF) products — Specification SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 4
EN 14305, Thermal insulation products for building equipment and industrial installations — Factory made cellular glass (CG) products — Specification EN 14306, Thermal insulation products for building equipment and industrial installations — Factory made calcium silicate (CS) products — Specification EN 14307,Thermal insulation products for building equipment and industrial installations — Factory made extruded polystyrene foam (XPS) products — Specification EN 14308, Thermal insulation products for building equipment and industrial installations — Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products — Specification EN 14309, Thermal insulation products for building equipment and industrial installations — Factory made products of expanded polystyrene (EPS) — Specification EN 14313, Thermal insulation products for building equipment and industrial installations — Factory made polyethylene foam (PEF) products — Specification EN 14314, Thermal insulation products for building equipment and industrial installations — Factory made phenolic foam (PF) products — Specification According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 5 1 Scope This European Standard specifies the requirements for factory made mineral wool products, which are used for the thermal insulation of building equipment and industrial installations with an operating temperature range of approximately 0 °C to + 800 °C. NOTE Below an operating temperature of ambient, special means against water vapour diffusion and water accumulation by air flow might be required. Below an operating temperature of - 50 °C, special tests regarding the suitability of the products in the intended application are advised (e.g. liquefaction of oxygen). Manufacturer's advice should be heeded in all cases. The products are manufactured with or without facings or coatings, in the form of rolls, boards, slabs, mats, felts, quilts, wired mats, lamella mats, bevelled lags and pipe sections.
This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This European Standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,065 W/(m·K) at 10 °C are not covered by this standard. This Eurpean Standard does not cover products for in situ insulation (blowing or pouring) or products for the insulation of the building structure. This European Standard does not cover the following acoustical aspects: direct airborne sound insulation and impact noise transmission index.
2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 822, Thermal insulating products for building applications — Determination of length and width EN 823, Thermal insulating products for building applications — Determination of thickness EN 824, Thermal insulating products for building applications — Determination of squareness EN 826, Thermal insulating products for building applications — Determination of compression behaviour EN 1604, Thermal insulating products for building applications — Determination of dimensional stability under specified temperature and humidity conditions EN 1609, Thermal insulating products for building applications — Determination of short term water absorption by partial immersion EN 12086, Thermal insulating products for building applications — Determination of water vapour transmission properties EN 12667, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Products of high and medium thermal resistance SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 6
EN 12939, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Thick products of high and medium thermal resistance EN 13172, Thermal insulating products — Evaluation of conformity EN 13467, Thermal insulating products for building equipment and industrial installations — Determination of dimensions, squareness and linearity of preformed pipe insulation EN 13468, Thermal insulating products for building equipment and industrial installations — Determination of trace quantities of water soluble chloride, fluoride, silicate, sodium ions and pH EN 13469, Thermal insulating products for building equipment and industrial installations — Determination of water vapour transmission properties of preformed pipe insulation EN 13472, Thermal insulating products for building equipment and industrial installations — Determination of short term water absorption by partial immersion of preformed pipe insulation EN 13501-1:2007, Fire classification of construction products and building elements — Part 1: Classification using test data from reaction to fire tests EN 13820, Thermal insulating materials for building applications — Determination of organic content EN 13823, Reaction to fire tests for building products — Building products excluding floorings exposed to the thermal attack by a single burning item EN 14706, Thermal insulating products for building equipment and industrial installations — Determination of maximum service temperature EN 14707, Thermal insulating products for building equipment and industrial installations — Determination of maximum service temperature for preformed pipe insulation EN 15715:2009, Thermal insulation products — Instructions for mounting and fixing for reaction to fire testing — Factory made products EN ISO 354, Acoustics — Measurement of sound absorption in a reverberation room (ISO 354:2003) EN ISO 1182, Reaction to fire tests for building products — Non-combustibility test (ISO 1182:2002) EN ISO 1716, Reaction to fire tests for building products — Determination of the heat of combustion (ISO 1716:2002) EN ISO 8497, Thermal insulation — Determination of steady-state thermal transmission properties of thermal insulation for circular pipes (ISO 8497:1994) EN ISO 11654, Acoustics — Sound absorbers for use in buildings — Rating of sound absorption (ISO 11654:1997) EN ISO 11925-2, Reaction to fire tests — Ignitability of building products subjected to direct impingement of flame — Part 2: Single-flame source test (ISO 11925-2:2002) EN ISO 13787, Thermal insulation products for building equipment and industrial installations — Determination of declared thermal conductivity (ISO 13787:2003) 3 Terms, definitions, symbols, units and abbreviated terms 3.1 Terms and definitions For the purposes of this document, the following terms and definitions apply. SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 7 3.1.1 Terms and definitions as given in EN ISO 9229:2007 3.1.1.1 batt portion of a mat in the form of a rectangular piece generally between 1 m and 3 m in length and usually supplied flat or folded 3.1.1.2 bevelled lag rigid or semi-rigid insulation product with one or more edges bevelled for application to large diameter cylindrical or spherical equipment 3.1.1.3 felt thin, loosely bonded mat 3.1.1.4 lamella mat mat made from fibrous materials in which the general orientation of the fibres is perpendicular to the major surfaces 3.1.1.5 mineral wool generic term for insulation wool manufactured from molten rock, slag or glass 3.1.1.6 pipe section (insulation) product in the shape of a cylindrical annulus that may be split to facilitate application 3.1.1.7 mattress quilt flexible insulation product, normally faced on one or both sides, or totally enclosed with fabric, wire netting, expanded metal or a similar covering attached mechanically to the insulation material 3.1.1.8 roll (insulation) product supplied in the form of a wound cylinder 3.1.1.9 board
slab (insulation) rigid or semi-rigid product of rectangular shape and cross-section in which the thickness is uniform and substantially smaller than the other dimensions NOTE Boards are usually thinner than slabs. They can also be supplied in tapered form. 3.1.2 Additional terms and definitions 3.1.2.1 mat flexible fibrous insulation product supplied rolled or flat, which may be faced or enclosed 3.1.2.2 wired mat insulation mat covered by flexible metal mesh facing or other types of high temperature resistant threads or wires, suitable for mounting the mats, attached on one or both sides
NOTE Metallic foils (reinforced aluminium foil, etc.) may be sewn on the mats as facings on one or more sides of the mat. SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 8
3.1.2.3 level given value, which is the upper or lower limit of a requirement
NOTE The level is given by the declared value of the characteristic concerned. 3.1.2.4 class combination of two levels of the same property between which the performance shall fall 3.1.2.5 production line assemblage of equipment that produces products using a continuous process 3.1.2.6 production unit assemblage of equipment that produces products using a discontinuous process 3.2 Symbols, units and abbreviated terms 3.2.1 Symbols and units used in this standard αp is the practical sound absorption coefficient – αw is the weighted sound absorption coefficient – B is the width mm Di is the inside diameter
mm Do is the outside diameter
mm d is the thickness mm dN is the nominal thickness of the product mm ∆εb is the relative change in width % ∆εd is the relative change in thickness % ∆εl is the relative change in length % l is the length m or mm λ is the thermal conductivity W/(m.K) λD is the declared thermal conductivity W/(m.K) µ is the water vapour diffusion resistance factor – Sb is the deviation from squareness on length and width mm/m sd is the water vapour diffusion equivalent air layer thickness m σ10 is the compressive stress at 10 % deformation kPa SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 9 σm is the compressive strength kPa v is the deviation from squareness for pipe sections mm Wp is the short term water absorption kg/m2 AP is the symbol of the declared level of practical sound absorption coefficient
AW is the symbol of the declared level of weighted sound absorption coefficient
CL is the symbol of the declared level of soluble chloride ions
CS(10\Y) is the symbol of the declared level for compressive stress or strength
DS(TH) is the symbol of the declared value for dimensional stability under specified temperature and relative humidity conditions
F is the symbol of the declared level of soluble fluoride ions
MV is the symbol of the declared level for water vapour diffusion equivalent air-layer thickness
NA is the symbol of the declared level of soluble sodium ions
pH is the symbol of the declared level of the pH-value
SI is the symbol of the declared level of soluble silicate ions
!ST(+) is the symbol of the declared level for maximum service temperature with a test load of 500 Pa
ST(+/250) is the symbol of the declared level for maximum service temperature with a test load of 250 Pa
ST(+/100) is the symbol of the declared level for maximum service temperature with a test load of 100 Pa"
T is the symbol of the declared class for thickness tolerances
WS is the symbol of the declared level for short term water absorption
3.2.2 Abbreviations used in this standard MW is Mineral Wool ITT is Initial Type Test ML is Manufacturer's Literature FPC is Factory Production Control 4 Requirements 4.1 General Product properties shall be assessed in accordance with Clause 5. To comply with this standard, products shall meet the requirements of 4.2, and the requirements of 4.3 as appropriate. SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 10
NOTE Information on additional properties is given in Annex B. One test result for a product property is the average of the measured values on the numbers of test specimens given in Table 5. 4.2 For all applications 4.2.1 Thermal conductivity For flat specimens thermal conductivity shall be based upon measurements carried out in accordance with EN 12667 or EN 12939 for thick products. For cylindrical specimens EN ISO 8497 shall be used as specified in 5.3.2.
In both cases the thermal conductivity values shall be determined by the manufacturer and verified in accordance with EN ISO 13787. They shall be declared by the manufacturer according to the measuring standards mentioned above covering the product service temperature range. The following conditions apply:  the measured value shall be expressed with three significant figures;  the declared thermal conductivity curve shall be given as a limit curve, defined in EN ISO 13787;  the value of the declared thermal conductivity, λD, shall be rounded upwards to the nearest 0,001 W/(m⋅K). The declared equation/limit curve is the "declared reference" with three significant figures, that is to 0,000 1 W/(m·K) for λ values below 0,1 W/(m·K) and in 0,001 W/(m·K) for λ values above 0,1 W/(m·K). This shall be used as a reference for the verification of the declaration. When thermal conductivity is declared as a table derived from the equation, rounding upwards to the next 0,001 W/(m·K) has to be done for the full range of the thermal conductivity.
NOTE Determinations of the declared thermal conductivity of pipe sections, following EN ISO 8497, having joints in the metering area, include the effects of these joints as defined in EN ISO 23993. 4.2.2 Dimensions and tolerances 4.2.2.1 Linear dimensions The length, l, width, b, and thickness, d, for flat products shall be determined in accordance with EN 822 and
EN 823. Length, thickness and inside diameter, Di for pipe sections shall be determined in accordance with
EN 13467. Thickness, d, of slabs/boards, lamella products, mats, mattresses, quilts, rolls, and wired mats shall be determined in accordance with EN 823. The load shall be as shown in Table 3. !The measurements shall be done excluding the preparation of test specimens of compressed products expressed in 5.4 and EN 823:2013, Annex A. This preparation may be used upon request by the manufacturer." For wired mats the manufacturer may declare the thickness under loads of 50 Pa or 1 000 Pa. The thickness declaration shall be accompanied by the relevant thickness measurement load.
NOTE The choice of load for thickness measurement for wired mats is not related to the compression behaviour. No test result shall deviate from the declared values by more than the tolerances given in Table 1 or Table 2 for the labelled level or class.
SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 11 Table 1 — Levels and classes for thickness tolerances Level or class Tolerances T1 – 5 % or – 5 mm a Excess permitted T2 – 5 % or – 5 mm a + 15 % or + 15 mm b T3 – 3 % or – 3 mm a + 10 % or + 10 mm b T4 – 3 % or – 3 mm a + 5 % or + 5 mm b T5 – 1 % or – 1 mm a + 3 mm T8 – 5 % or – 3 mm a + 5 % or + 3 mm a T9 – 6 % or – 5 mm a + 6 % or + 5 mm a a
Whichever gives the greatest numerical tolerance. b
Whichever gives the smallest numerical tolerance.
Table 2 — Levels and classes for dimensional tolerances Form of delivery Width Length Thickness class Inside
diameter Thickness uniformity Square-ness Slabs/boards ± 1,5 % ± 2 % T3 to T5
± 5 mm/m Lamella mats ± 5 mm + excess – 0 mm T4 and T5
Wired mats ± 10 mm + excess – 0 mm T2 and T3
Batts, mats, rolls, quilts, mattress, feltsb ± 10 mm + excess – 0 mm T1 to T5
Pipe sections Do < 150 mm
± 5 mm T8 + 4 mm
– 0 mm Difference less than 6 mm or 10 % a ± 4 mm or ± 2 % of the external nominal diameter a Pipe sections Do ≥ 150 mm
± 5 mm T9 + 5 mm or
+ 2 % a – 0 mm Difference less than 10 mm or 12 % a ± 4 mm or ± 2 % of the external nominal diameter a a
Whichever gives the greatest numerical tolerance. b
T2 only.
SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 12
Table 3 — Load for thickness measurements Product form Load
Pa Boards Mats, Mattresses, Rolls, Slabs, Quilts - with compressive stress or strength less than 10 kPa 50 Lamella Mats 250 Boards Mats, Mattresses, Rolls, Slabs, Quilts - with compressive stress or strength equal to or greater than 10 kPa 250 Wired mats50
50 Wired mats1 000 1 000
4.2.2.2 Squareness Deviation from squareness, Sb, of boards and slabs shall be determined in accordance with EN 824. Deviation from squareness, v, of pipe sections shall be determined in accordance with EN 13467. No test result shall exceed the corresponding tolerance given in Table 2. 4.2.3 Dimensional stability
Dimensional stability under specified temperature and humidity conditions shall be determined in accordance with EN 1604. The test shall be carried out after storage for 48 h exposure at (23 ± 2) °C and (90 ± 5) % relative humidity. The relative change in thickness ∆εd shall not result in a relative thickness reduction exceeding 1,0 %. The relative changes in length, ∆εl and width ∆εb shall not exceed 1,0 %. The relative change in flatness, ∆εs
shall not exceed 1 mm/m. This test shall not be performed when the more severe test, described in 4.3.2 is used. 4.2.4 Reaction to fire of the product as placed on the market Reaction to fire classification of the product, as placed on the market, shall be determined in accordance with EN 13501-1 and the basic Mounting and Fixing rules given in EN 15715:2009.
NOTE 1 This classification is compulsory and always included in the CE Marking label.
EN 13501-1:2007, Table 1, is applicable to products applied to flat surfaces or to curved surfaces with a diameter greater than 300 mm. If a flat product which has a classification according to EN 13501-1:2007, Table 1, is used in a linear application it does not require further classification. EN 13501-1:2007, Table 3, is applicable for products applied on linear objects or with a diameter below or equal 300 mm. Detailed information about the test conditions and the field of application of the classification as stated in the reaction to fire classification report shall be given in the manufacturer's literature.
Manufacturers declaring Euroclass A1 without further test shall demonstrate by testing in accordance with EN 13820 that the products do not contain more than 1,0 % by weight of organic matter.
NOTE 2 The commission decision 96/603/EC of 4 October 1996 amended by the commission Decision 00/605/EC of 26 September 2000 gives the list of products to be considered as reaction to fire class Euroclass A1 without the need for testing. SIST EN 14303:2010+A1:2013



EN 14303:2009+A1:2013 (E) 13 4.2.5 Durability characteristics 4.2.5.1 General The appropriate durability characteristics have been considered and are covered in 4.2.5.2, 4.2.5.3 and 4.2.5.4. 4.2.5.2 Durability of reaction to fire against ageing/degradation and high temperature The reaction to fire performance of MW products does not change with time or when subjected to the declared maximum service temperature. 4.2.5.3 Durability of thermal resistance agai
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.