Safety rules for the construction and installation of lifts - Existing lifts - Part 83: Rules for the improvement of the resistance against vandalism

This Technical Specification provides ways on how to apply EN 81-71 referred to in EN 81-80:2003 (2), 5.3 to existing lifts in order to improve their vandal resistance. This document applies to permanently installed lifts serving defined landing levels, having a car designed for the transportation of persons or persons and goods and moving between guide rails inclined not more than 15° to the vertical.

Sicherheitsregeln für die Konstruktion und den Einbau von Aufzügen - Bestehende Aufzüge - Teil 83: Regeln für die Verbesserung der Schutzmaßnahmen gegen mutwillige Zerstörung

1.1 Die vorliegende Technische Spezifikation zeigt Wege auf, wie die EN 81-71, auf die in EN 81-80:2003,
5.2.1, verwiesen wird, auf bestehende Aufzüge anzuwenden ist, um deren Schutzmaßnahmen gegen
mutwillige Zerstörung zu verbessern.
1.2 Das vorliegende Dokument gilt für dauerhaft eingebaute Aufzüge, die definierte Haltestellen bedienen,
über einen für die Beförderung von Personen oder Personen und Lasten ausgelegten Fahrkorb verfügen und
sich zwischen Führungsschienen bewegen, die zur Senkrechten um nicht mehr als 15° geneigt sind.

Règles de sécurité pour la construction et l'installation des élévateurs - Ascenseurs existants - Partie 83: Règles pour l'amélioriation de la resistance aux actes de vandalisme

1.1 La présente Spécification Technique précise comment appliquer l'EN 81-71, mentionnée dans l'EN 81—
80:2003 [2], 5.3, aux ascenseurs existants afin d'améliorer leur résistance aux actes de vandalisme.
1.2 Le présent document s'applique aux ascenseurs installés à demeure desservant des paliers définis,
comportant une cabine conçue pour le transport de personnes ou de personnes et de marchandises et se
déplaçant entre des guides inclinés de 15° maximum par rapport à la verticale.

Varnostna pravila za konstruiranje in vgradnjo dvigal (liftov) - Obstoječa dvigala - 83. del: Pravila za izboljšanje odpornosti proti vandalizmu

Ta tehnična specifikacija zagotavlja načine uporabe EN 81-71, na katerega se sklicuje EN 81-80:2003 (2), 5.3, pri obstoječih dvigalih, da se izboljša odpornost proti vandalizmu. Ta standard velja za stalno nameščena dvigala s pripustom določene ravni za iztovarjanje in s kabino, zasnovano za prenos oseb ali oseb in blaga, ki se premikajo med vodilnimi tračnicami pod naklonom, manjšim od 15° glede na navpičnico.

General Information

Status
Published
Publication Date
14-Sep-2010
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
20-Aug-2010
Due Date
25-Oct-2010
Completion Date
15-Sep-2010

Relations

Buy Standard

Technical specification
TS CEN/TS 81-83:2010
English language
23 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST-TS CEN/TS 81-83:2010
01-oktober-2010
9DUQRVWQDSUDYLOD]DNRQVWUXLUDQMHLQYJUDGQMRGYLJDO OLIWRY 2EVWRMHþDGYLJDOD
GHO3UDYLOD]DL]EROMãDQMHRGSRUQRVWLSURWLYDQGDOL]PX
Safety rules for the construction and installation of lifts - Existing lifts - Part 83: Rules for
the improvement of the resistance against vandalism
Sicherheitsregeln für die Konstruktion und den Einbau von Aufzügen - Bestehende
Aufzüge - Teil 83: Regeln für die Verbesserung der Schutzmaßnahmen gegen mutwillige
Zerstörung
Règles de sécurité pour la construction et l'installation des élévateurs - Ascenseurs
existants - Partie 83: Règles pour l'amélioriation de la resistance aux actes de
vandalisme
Ta slovenski standard je istoveten z: CEN/TS 81-83:2009
ICS:
91.140.90 'YLJDOD7HNRþHVWRSQLFH Lifts. Escalators
SIST-TS CEN/TS 81-83:2010 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST-TS CEN/TS 81-83:2010

---------------------- Page: 2 ----------------------

SIST-TS CEN/TS 81-83:2010


TECHNICAL SPECIFICATION
CEN/TS 81-83

SPÉCIFICATION TECHNIQUE

TECHNISCHE SPEZIFIKATION
October 2009
ICS 91.140.90
English Version
Safety rules for the construction and installation of lifts - Existing
lifts - Part 83: Rules for the improvement of the resistance
against vandalism
Règles de sécurité pour la construction et l'installation des Sicherheitsregeln für die Konstruktion und den Einbau von
élévateurs - Ascenseurs existants - Partie 83: Règles pour Aufzügen - Bestehende Aufzüge - Teil 83: Regeln für die
l'amélioriation de la resistance aux actes de vandalisme Verbesserung der Schutzmaßnahmen gegen mutwillige
Zerstörung
This Technical Specification (CEN/TS) was approved by CEN on 10 August 2009 for provisional application.

The period of validity of this CEN/TS is limited initially to three years. After two years the members of CEN will be requested to submit their
comments, particularly on the question whether the CEN/TS can be converted into a European Standard.

CEN members are required to announce the existence of this CEN/TS in the same way as for an EN and to make the CEN/TS available
promptly at national level in an appropriate form. It is permissible to keep conflicting national standards in force (in parallel to the CEN/TS)
until the final decision about the possible conversion of the CEN/TS into an EN is reached.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.






EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TS 81-83:2009: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
Contents page
Foreword . 3
Introduction . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 List of significant hazards . 6
5 Safety requirements and/or measures . 6
5.1 Lift well . 6
5.1.1 Well enclosure . 6
5.1.2 Inspection and emergency doors and inspection traps . 7
5.1.3 Ventilation . 7
5.2 Machinery spaces, pulley space(s) and machinery cabinets . 7
5.3 Landing and car doors . 7
5.3.1 Landing and car door construction . 7
5.3.2 Landing door security system – Category 2 lifts . 8
5.3.3 Door coupling mechanism for automatically operating sliding doors . 9
5.3.4 Door reversal mechanism . 10
5.3.5 Locking of car doors . 10
5.3.6 Manipulation of door operator and locks . 10
5.4 Car . 10
5.4.1 Car bodywork, Interior and fixings . 10
5.4.2 Car emergency doors and trap doors. 10
5.4.3 Car ventilation . 11
5.4.4 Car lighting . 11
5.5 Car and landing fixtures . 11
5.5.1 Car and landing controls . 11
5.5.2 Car and Landing Control Stations . 11
5.5.3 Position indicators. 11
5.6 Alarm sounder . 11
5.7 Steel work . 12
5.8 Signs and markings . 12
6 Verification of improvement measures . 12
7 Information for use . 12
Annex A (informative) Method for implementation of TS 81-83 . 13
A.1 Categorisation of the lift . 13
A.2 Identification of deficiencies . 13
A.3 Selection of risk reduction measures by priority levels . 13
Annex B (informative) Check list for improving the vandal resistance of lifts . 15
Bibliography . 23

2

---------------------- Page: 4 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
Foreword
This document (CEN/TS 81-83:2009) has been prepared by Technical Committee CEN/TC 10 “Lifts, escalators
and moving walks”, the secretariat of which is held by AFNOR.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights.
CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This standard is part of the EN 81 series of standards: “Safety rules for the construction and installation of lifts”.
CEN/CENELEC have embarked on a programme of work to produce a series of related machinery and lift safety
standards as part of the process of European harmonisation. This document makes use of and refers to EN 81-
71:2005.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to announce this Technical Specification: Austria, Belgium, Bulgaria, Cyprus, Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden,
Switzerland and the United Kingdom.

3

---------------------- Page: 5 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
Introduction
Background
More than 4 million lifts are in use today in EU and EFTA and almost 50 % were installed more than 25 years ago.
Existing lifts were installed to the safety level appropriate at that time. This level is less than today’s state of the art
lifts built to EN 81-1 or EN 81-2, offering already a reasonable degree of protection against vandalism.
Furthermore the life cycle of a lift is longer than most other transportation systems and building equipment, which
therefore means that lift design, performance, safety and resistance against vandalism can fall behind modern
technologies. If existing lifts are not upgraded to today's state of the art of safety and/or protection against
vandalism the number of incidents will increase.
This document provides guidance to building owners addressing in particular existing lifts installed in buildings
where it is considered additional security or other measures may be required to protect against the risk of
vandalism. The building owner will need to consider the extent of additional protection required, as covered by the
enclosed proposals, which may be adopted according to the environment in which the lift installation is situated and
the type of vandalism that is likely to be experienced.
This document is based upon and referring to EN 81-71:2005 and addresses additional protective measures
against deliberate acts that may result in equipment damage or injury to persons.
Approach
This Technical Specification
 defines the categories of vandalism according to EN 81-71:2005, Annex A, taking into account the existing
environment and the likelihood of persons acting as a vandal;
 categorises various hazards and hazardous situations, each of which has been analysed by a risk
assessment;
 is intended to provide corrective actions to progressively and selectively improve, step by step, the level of
vandal resistance of existing passenger and goods passenger lifts towards today’s state of the art;
 enables each lift to be audited and measures against vandalism to be identified and implemented in a step by
step and selective fashion;
 lists the high, medium and low priorities and corrective actions which can be applied in separate steps in order
to eliminate the risks.
Other designs to previous national regulations or standards, providing they have an equivalent safety level, may be
acceptable.
Use
This Technical Specification can be used as a guideline for:
a) national authorities to determine its own programme of implementation in a step by step process via a filtering
1)
process (see Annex A) in a reasonable and practicable way based on the priorities level (high, medium, low)
and social and economic considerations;

1)
"Reasonable and practicable” is defined as follows: “In deciding what is reasonably practicable the seriousness of a risk to
injury should be weighted against the difficulty and cost of removing or reducing that risk. Where the difficulty and costs are
high, and a careful assessment of the risk shows it to be comparatively unimportant, action may not need to be taken. On the

other hand where the risk is high, action should be taken at whatever cost.”
4

---------------------- Page: 6 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
b) owners to follow their responsibilities according to existing regulations;
c) maintenance companies and/or inspection bodies to inform the owners on the vandal resistance level of their
installations;
d) owners to upgrade the existing lifts on a voluntary basis in accordance with c) if no regulations exist.
In making an audit of an existing lift installation Annex B can be used to identify the deviations to the state of the art
and corrective actions in this Technical Specification.
However, where a situation is identified not covered in this Technical Specification a separate risk assessment
should be made. This risk assessment should be based on ISO 14798 [1].
5

---------------------- Page: 7 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
1 Scope
1.1 This Technical Specification provides ways on how to apply EN 81-71 referred to in EN 81-80:2003 [2], 5.3
to existing lifts in order to improve their vandal resistance.
1.2 This document applies to permanently installed lifts serving defined landing levels, having a car designed for
the transportation of persons or persons and goods and moving between guide rails inclined not more than 15° to
the vertical.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references,
only the edition cited applies. For undated references, the latest edition of the referenced document (including any
amendments) applies.
EN 81-1:1998, Safety rules for the construction and installation of lifts – Part 1: Electric lifts
EN 81-2:1998, Safety rules for the construction and installation of lifts – Part 2: Hydraulic lifts
EN 81-71:2005, Safety rules for the construction and installation of lifts – Particular applications for passenger lifts
and goods passenger lifts – Part 71: Vandal resistant lifts
EN 60529, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989)
EN ISO 13857:2008, Safety of machinery – Safety distances to prevent hazard zones being reached by the upper
and lower limbs (ISO 13857:2008)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in the EN 81 series of standards apply.
4 List of significant hazards
EN 81-71:2005, Clause 4 applies.
5 Safety requirements and/or measures
5.1 Lift well
5.1.1 Well enclosure
5.1.1.1 Well enclosures shall be imperforate. For Category 1 lifts where it is difficult to replace perforate
enclosures, existing enclosures may remain if they comply with EN ISO 13857:2008, 4.2.4.2.
The strength and the fire resistance of materials used for the well shall comply with the requirements of
EN 81-71:2005, 5.1.1.1.
5.1.1.2 For Category 1 lifts with a partially enclosed well the height of the enclosure according to 5.2.1.2 a) of
EN 81-1:1998 or EN 81-2:1998 shall be a minimum of 5,0 m.
5.1.1.3 Category 2 lifts shall be provided with a totally enclosed well.
6

---------------------- Page: 8 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
5.1.2 Inspection and emergency doors and inspection traps
5.1.2.1 Inspection and emergency doors and inspection traps shall be of such a construction that it is not
possible to open them with any of the items as listed in EN 81-71:2005, Table E.1.
5.1.2.2 The strength of doors and trap doors shall be according to EN 81-71:2005, 5.1.2.2.
5.1.3 Ventilation
Ventilation openings shall be in accordance with EN 81-71:2005, 5.2.3 and 5.2.4.
5.2 Machinery spaces, pulley space(s) and machinery cabinets
5.2.1 The strength and the fire resistance of the materials used in the construction of any machinery space,
pulley spaces or cabinet outside of the well shall comply with EN 81-71:2005, 5.1.1.1.
5.2.2 Windows, if provided and accessible to persons, shall be in accordance with EN 81-71:2005, 5.2.2.
5.2.3 If ventilation openings are accessible to persons from the outside, dimensions and protections of the
openings shall be according to EN 81-71:2005, 5.2.3.
5.2.4 The means of protection in 5.2.3 shall be of a strength as specified in EN 81-71:2005, 5.1.1.1.
5.2.5 Doors and trap doors with their locks shall meet the requirements of EN 81-71:2005, 5.1.2.2.
5.2.6 For Category 2 lifts, an intruder alarm system shall be provided in compliance with EN 81-71:2005, 5.2.6.
5.2.7 In the case of a Category 2 machine-room-less lift, equipment located in a machinery space in the pit, e.g.
machine, tank, controller, shall be covered according to EN 81-71:2005, 5.2.7.
5.3 Landing and car doors
5.3.1 Landing and car door construction
5.3.1.1 Landing and car doors shall be of the automatically horizontally sliding power operated type. Hinged
doors may remain respecting the specifications mentioned in 5.3.2.2.
A car door shall always be installed (see EN 81-80:2003, 5.8.3) and respect the specifications mentioned below.
5.3.1.2 Materials used for door panels and frames/architraves and decorative finishes for car and landing
doors shall comply with EN 81-71:2005, 5.3.1.1.
5.3.1.3 The strength of car and landing door assemblies, together with their frames and fixings shall comply
with the requirements of EN 81-71:2005, 5.3.1.2.
5.3.1.4 Doors shall be provided with a means for retaining the door panels in position should the roller or guide
shoe assemblies fail. The strength of these devices shall comply with EN 81-71:2005, 5.3.1.3.
5.3.1.5 For Category 2 lifts vision panels shall not be used according to EN 81-71:2005, 5.3.1.4.
5.3.1.6 For Category 2 lifts, the design of the door panels and the distance between each landing door, or its
attachments at the leading edge, and the car door(s), or its attachments at the leading edge, shall comply with
EN 81-71:2005, 5.3.1.5.
5.3.1.7 For Category 2 lifts, in addition to the requirements of 7.2.3.2 of EN 81-1:1998 and EN 81-2:1998, it
shall not be possible to pass a rod of 10 mm diameter from the landing side of the entrance into the well according
to EN 81-71:2005, 5.3.1.6.
7

---------------------- Page: 9 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
5.3.1.8 For Category 2 lifts, where panels are mechanically linked, the linkage shall be so designed or located
that it cannot be disengaged by a user, with an item as described in EN 81-71:2005, Annex E within a period of
60 s.
5.3.1.9 For Category 2 lifts, the leading edge profile of car and landing doors shall be formed as an integral
part of the door according to EN 81-71:2005, 5.3.1.8.
5.3.2 Landing door security system – Category 2 lifts
5.3.2.1 Automatic sliding doors
For Category 2 lifts with automatic sliding doors, a landing door security system according to EN 81-71:2005, 5.3.2
shall be provided.
5.3.2.2 Hinged doors
5.3.2.2.1 General
If hinged doors remain, an alarm system (see 5.3.2.2.2) and or blocking system (see 5.3.2.2.3) shall be installed for
Category 2 lifts.
5.3.2.2.2 Alarm system
The warning flashing light installed on the landing door side and the acoustic signal shall remain active as long as
the landing door is unlocked and/or opened outside the unlocking zone. Once the system is activated, the electric
displacement of the car shall be impossible, even during maintenance actions.
This device installed on each served landing, shall be composed by a warning flashing light, including a sign
“access prohibited” installed on the landing door frame. In addition to this warning signal, an acoustic signal shall
also exist, providing a minimum noise level of 65 dB (A) measured in a distance of 1 m in front of the closed landing
door concerned.
The setting and re-setting of this device shall only be possible by an authorised person from:
a) a landing, or
b) the machine room, or
c) the lift control panel, or
d) the control panel located at the landing (MRL), or
e) the control room of the building, if there exists in the vicinity (in the same building).
The warning flashing light installed on the landing door side remains active as long as the landing door is unlocked
and/or opened outside the unlocking zone.
The identification of the device (as specified in EN 81-71:2005, Annex C) to set and reset the alarm device shall be
clearly and permanently located on or adjacent to the lift entrance at the main entry/exit floor of the building.
To avoid the alarm device to be left inoperative, a timer shall automatically reactivate it after a maximum period of
30 min. However, when the lift is in inspection mode or a stopping device (on the roof of the car, or in the pit, or in
the machine room or in the pulley room) is actuated, the timer shall be interrupted. Once the lift turned into normal
service, the timer shall be automatically re-activated.
In the event of loss of electrical supply the alarm device shall remain operative for at least 2 h.
In the event of a damaged alarm device at the landing, a complementary warning flashing light, located in the well
and being visible from the landing door side, shall be active. In addition, an acoustic signal shall also exist in the
8

---------------------- Page: 10 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
well providing a minimum noise level of 65 dB (A) measured in a distance of 1 m in front of the closed landing door
concerned.
The manual displacement of the car with open landing door from the machine room shall activate the flashing lights
and the acoustic signal in the well.
It shall be impossible to dismount the locking mechanism of the landing doors and the elements of the alarm device
from inside of the well.
5.3.2.2.3 Blocking device
The blocking device shall prevent the manual opening of the landing door in the absence of the car at the landing
from the landing and from the car itself with a special item as mentioned in EN 81-71:2005, Annex E.
If the blocking device, once activated, is not in the position to prevent the manual opening of the landing doors, in
the absence of the car at the landing level, all new departure of the lift shall be prevented.
The setting and re-setting of this device shall only be possible by an authorised person from:
a) a landing, or
b) the machine room, or
c) the lift control panel, or
d) the control panel located at the landing (MRL), or
e) the control room of the building, if there exists in the vicinity (in the same building).
The warning flashing light installed on the landing door side remains active as long as the landing door is unlocked
and/or opened outside the unlocking zone.
The identification of the device (as specified in EN 81-71:2005, Annex C) to set and reset the blocking device shall
be clearly and permanently located on or adjacent to the lift entrance at the main entry/exit floor of the building.
To avoid the blocking device to be left inoperative, a timer shall automatically reactivate it after a maximum period
of 30 min. However, when the lift is in inspection mode or a stopping device (on the roof of the car, or in the pit, or
in the machine room or in the pulley room) is actuated, the timer shall be interrupted. Once the lift turned into
normal service, the timer shall be automatically re-activated.
In the event of loss of electrical supply the blocking device shall remain operative for at least 2 h.
In the event of a damaged blocking device at the landing, a complementary warning flashing light, located in the
well and being visible from the landing door side, shall be active. In addition, an acoustic signal shall also exist in
the well providing a minimum noise level of 65 dB (A) measured in a distance of 1 m in front of the closed landing
door concerned.
The manual displacement of the car with open landing door from the machine room shall activate the flashing lights
and the acoustic signal in the well.
It shall be impossible to dismount the locking mechanism of the landing doors and the elements of the blocking
device from inside of the well.
5.3.3 Door coupling mechanism for automatically operating sliding doors
For Category 2 lifts, whilst the car is stationary in the unlocking zone it shall not be possible to de-couple the car
and landing doors by hand or the use of a item as described in EN 81-71:2005, Annex E within a period of 60 s.
9

---------------------- Page: 11 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
5.3.4 Door reversal mechanism
For Category 2 lifts, any protective devices for reversing the car and landing doors when closing shall be positioned
such as to be inaccessible to unauthorised persons.
5.3.5 Locking of car doors
The car door(s) shall always be provided with a mechanical locking device in compliance with EN 81-1:1998 or
EN 81-2:1998, 8.9.3.
NOTE The reference to 11.2.1c) in 8.9.3 of EN 81-1:1998 and EN 81-2:1998 should be disregarded.
5.3.6 Manipulation of door operator and locks
For Category 2 lifts it shall not be possible to manipulate the door operator and locks, to render them ineffective by
use of any of the item described in EN 81-71:2005, Annex E within 60 s.
5.4 Car
5.4.1 Car bodywork, Interior and fixings
5.4.1.1 The walls of the car shall have a mechanical strength at least equal to the landing doors as specified in
EN 81-71:2005, 5.3.1.2 a) or b) as applicable.
5.4.1.2 For Category 1 lifts, the strength and design of the car ceilings shall be according to EN 81-71:2005,
5.4.1.2.
5.4.1.3 For Category 2 lifts the ceiling shall be so designed that there are no points from which persons can
suspend themselves.
5.4.1.4 The fire resistance of materials used for the car bodywork, the ceiling, wall finishes and car flooring
shall comply with EN 81-71:2005, 5.4.1.4.
5.4.1.5 The car bodywork shall resist cutting through with items as identified in EN 81-71:2005, Annex E.
5.4.1.6 Any car flooring material shall be so fixed as to prevent the creation of a tripping hazard when cut.
5.4.1.7 For Category 2 lifts, any handrail shall be capable of supporting at its most unfavourable point a force
of 2 500 N applied in any direction.
5.4.1.8 For Category 2 lifts, where a mirror is installed it shall:
a) be flush fitted;
b) be laminated if made of glass.
5.4.1.9 Elements e.g. fixtures and fittings, that are accessible to users shall:
a) for Category 1 lifts, be removable only with special tools;
b) for Category 2 lifts, be fitted in a way that they are not visible to users.
5.4.2 Car emergency doors and trap doors
For Category 2 lifts any emergency trap doors or emergency doors shall meet the requirements of 8.12.4 of
EN 81-1:1998 and EN 81-2:1998 and be provided with a security system in accordance with EN 81-71:2005, 5.3.2.
10

---------------------- Page: 12 ----------------------

SIST-TS CEN/TS 81-83:2010
CEN/TS 81-83:2009 (E)
5.4.3 Car ventilation
Any normally accessible car ventilation openings shall be provided with a means of protection so that a straight rod
of any cross section shall not pass through.
5.4.4 Car lighting
5.4.4.1 For Category 1 and 2 lifts the car shall be provided with permanently installed electric lighting, which
ensures a light intensity of at least 100 lx at floor level and at the control devices.
5.4.4.2 All light fixtures within the lift car shall:
a) be flush fitted without visible fixings and in a manner such as to prevent unauthorised access;
b) when tested as described in Annexes B and F of EN 81-71:2005 remain functional and unbroken.
5.5 Car and landing fixtures
5.5.1 Car and landing controls
5.5.1.1 When mounted in their assemblies cont
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.