EN ISO 10840:2026
(Main)Plastics - Specifications and guidance for the use of standard fire tests (ISO 10840:2026)
- Abstract
This document provides specifications and guidance for the use of standard fire testing for plastics and the products in the following aspects:
selection of appropriate tests that reflect realistic end-use conditions;
grouping of the reaction-to-fire characteristics that any given test or tests can measure;
assessment of tests as to their relevance in areas such as material characterisation, quality control, pre-selection, end-product testing, environmental profiling and design for the environment (DfE);
definition of potential problems that can arise when plastics are tested in standard fire tests.
This document does not include specification for development or design of new fire-tests for plastics.
- Status
- Published
- Publication Date
- 28-Sep-2027
- Technical Committee
- CEN/TC 249 - Plastics
- Drafting Committee
- CEN/TC 249 - Plastics
- Current Stage
- 6060 - Definitive text made available (DAV) - Publishing
- Start Date
- 14-Oct-2026
- Due Date
- 29-Sep-2027
- Completion Date
- 29-Sep-2027
EN ISO 10840:2026 is a CEN standard for plastics that gives guidance on using standard fire tests. It helps users choose tests that reflect end-use conditions, understand which reaction-to-fire characteristics a test can measure, and judge where a test is useful in practice. The standard is written for people who select, run, buy, or interpret fire tests on plastics materials and products.
What does EN ISO 10840:2026 specify?
EN ISO 10840:2026 specifies how to use standard fire tests for plastics and products incorporating plastics. Clause 1 sets out four main purposes: selecting appropriate tests for realistic end-use conditions, grouping the reaction-to-fire characteristics that a test can measure, judging the relevance of tests for material characterisation, quality control, pre-selection, end-product testing, environmental profiling and Design for the Environment (DfE), and identifying problems that can arise during testing.
The document also states that it is guidance for using existing fire tests, not for designing new fire tests for plastics. Its structure runs from general scope and references to fire scenarios, test categories, specimen and apparatus issues, scale effects, problematic behaviour, and two informative annexes.
| Annex | What it covers |
|---|---|
| Annex A | End-user relevant preparation of test specimens, including mounting, fixing, substrates, air gaps, joints, orientation and thermal attack |
| Annex B | Environmental-impact assessment, including combustion effluents, combustion conditions, and life-cycle considerations |
What are the key requirements of EN ISO 10840:2026?
EN ISO 10840:2026 is mainly a framework for choosing and interpreting tests, so the most important points are about matching the test to the real fire situation and recording the conditions that affect the result.
Clause 4 links test choice to fire development stages. The standard distinguishes pre-ignition, fire growth, flashover, fully developed fire and decay. In practice, this matters because reaction-to-fire behaviour is most relevant before flashover, while fire resistance becomes the issue after flashover.
Clause 5 separates the main test uses. The standard groups tests into material characterisation, quality-control, pre-selection, end-product, scenario-based fire testing, and fire safety engineering (FSE). This helps a reader decide whether the test is meant to screen materials, check production consistency, or support a real application assessment.
Quality-control tests need clear acceptance rules. Clause 5.2 says the characteristic to be checked, the test procedure, and pass/fail criteria must be defined, and the result has to correlate with the key performance parameter. In practice, this means a QC test is only useful if it can be applied consistently and compared with a real product requirement.
Pre-selection tests are for early comparison, not final use by themselves. Clause 5.3 warns that pre-selection data must be interpreted carefully because product geometry, fixing, ventilation, heat transfer and ignition source can change actual performance. The practical point is that a material that performs well in a standard specimen may still need end-product verification.
End-product tests should resemble the intended installation. Clause 5.4 says configuration, orientation, ventilation and the ignition source should reflect the end-use as far as possible. This matters because the same plastic can behave differently when it is flat, profiled, fixed to a substrate, or exposed at an edge.
Scenario-based testing and FSE need quantitative, model-friendly data. Clauses 5.5 and 5.6 say the test conditions and results should be quantitative and representative enough to support predictive methods. In practice, this is the bridge from a test result to a fire safety assessment of a real design.
Specimen preparation and mounting can change the result. Clause 6 and Annex A give guidance on sampling, conditioning, thickness, density, surface coating, joints, air gaps, edges, orientation and exposure to thermal attack. This matters because mounting a specimen in a way that does not match end use can overstate or understate the fire performance.
The standard expects difficult specimen behaviour to be reported. Clauses 6.8 and 6.9 cover shrinking, curling, slumping, dripping, debris, collapse and deformation. In practice, the test report should explain these behaviours because they can affect ignition, flame spread, and whether the chosen method was suitable.
Scale and measurement quality must be considered. Clause 7 explains the trade-off between small-, intermediate- and large-scale tests, and requires calibration of key measurements plus attention to measurement uncertainty. This is important when comparing test data or using it in certification and engineering decisions.
What terms does EN ISO 10840:2026 define?
EN ISO 10840:2026 defines a small set of terms in Clause 3 and uses several key abbreviations in the guidance.
- End-product test - a fire hazard assessment test on a complete product, part, component or sub-assembly.
- Pre-selection test - a combustion characteristic test on a standardized shape used to compare candidate materials, components or subassemblies before choosing an end product.
- Spalling - the breaking off of fragments or solid pieces from a heated surface.
- Flashover - the stage in a compartment fire where a localised fire can rapidly become a fully developed fire as the hot gas layer ignites.
- Fire safety engineering (FSE) - the use of quantitative fire data and predictive methods to support defined fire safety objectives.
- Design for the Environment (DfE) - a design approach that uses fire performance and environmental considerations when selecting plastics materials and products.
Who uses EN ISO 10840:2026?
EN ISO 10840:2026 is used by plastics material suppliers, product manufacturers, test laboratories, certification bodies, fire safety engineers, quality managers and product designers. These users apply it when they need to choose a suitable fire test, prepare specimens, interpret unusual behaviour, or decide whether a result is relevant to an end use.
It is especially relevant for plastics used in building products, transport products, cables, furniture, textiles and other applications named in the references and examples. The standard is also useful where a buyer or specifier needs to compare a material screening test with a product-level fire assessment.
What changed in EN ISO 10840:2026 from the previous edition?
EN ISO 10840:2026 replaces ISO 10840:2008. The foreword states three main changes: the reference documents were reviewed and collected, the terms and definitions were reviewed and collected, and a new clause on fire safety engineering was added.
Which standards are used with EN ISO 10840:2026?
EN ISO 10840:2026 relies on several referenced standards that supply vocabulary, fire-scenario concepts, uncertainty methods and engineering guidance.
- ISO/TS 3814 - provides the fire-stage framework used in Clause 4.
- ISO 10093 - defines standard ignition sources used when selecting test exposure.
- ISO 13943 - supplies the fire-safety vocabulary, including key terms used in reporting specimen behaviour.
- ISO 23932-1 - gives the general principles of fire safety engineering used in Clause 5.6.
- ISO 23948 - gives the cone calorimeter method for measuring intumescence properties of PVC materials and products.
- ISO 29473 - gives the approach for uncertainty of measurement in fire tests.
- IEC 60695-1-11 - gives guidance for assessing fire hazard in scenario-based evaluations.
- IEC 60695-1-12 - gives guidance on fire safety engineering for electrotechnical products and is cited alongside scenario-based assessment.
What does the EN ISO 10840:2026 document contain?
EN ISO 10840:2026 contains a fire-safety framework, not a single test method. It includes a compartment-fire description with a figure showing fire development in terms of time, temperature and heat release rate, plus a table that separates pre-flashover reaction-to-fire parameters from post-flashover resistance-to-fire parameters.
It also contains guidance on specimen effects such as melting, bubbling, intumescence, shrinkage, flaming drips, edge effects and profiled products. The text refers to many standard fire tests - including cone calorimeter, room corner, ignitability and spread-of-flame methods - to show where each kind of test is useful.
Annex A gives detailed preparation guidance for mounting and fixing plastics products so the test matches end use as closely as possible. Annex B explains how combustion tests can support assessment of environmental impact by considering combustion conditions, effluents, heat release and life-cycle context.
Relations
- Consolidated By
ISO 10840:2026 - Plastics — Specifications and guidance for the use of standard fire tests - Effective Date
- 12-Feb-2026
Get Certified
Connect with accredited certification bodies for this standard
DIN CERTCO
DIN Group product certification.
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Sponsored listings
Frequently Asked Questions
EN ISO 10840:2026 is a standard published by the European Committee for Standardization (CEN). Its full title is "Plastics - Specifications and guidance for the use of standard fire tests (ISO 10840:2026)". This standard covers: This document provides specifications and guidance for the use of standard fire testing for plastics and the products in the following aspects: selection of appropriate tests that reflect realistic end-use conditions; grouping of the reaction-to-fire characteristics that any given test or tests can measure; assessment of tests as to their relevance in areas such as material characterisation, quality control, pre-selection, end-product testing, environmental profiling and design for the environment (DfE); definition of potential problems that can arise when plastics are tested in standard fire tests. This document does not include specification for development or design of new fire-tests for plastics.
This document provides specifications and guidance for the use of standard fire testing for plastics and the products in the following aspects: selection of appropriate tests that reflect realistic end-use conditions; grouping of the reaction-to-fire characteristics that any given test or tests can measure; assessment of tests as to their relevance in areas such as material characterisation, quality control, pre-selection, end-product testing, environmental profiling and design for the environment (DfE); definition of potential problems that can arise when plastics are tested in standard fire tests. This document does not include specification for development or design of new fire-tests for plastics.
EN ISO 10840:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.40 - Ignitability and burning behaviour of materials and products; 83.080.01 - Plastics in general. The ICS classification helps identify the subject area and facilitates finding related standards.
EN ISO 10840:2026 has the following relationships with other standards: It is inter standard links to ISO 10840:2026. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN ISO 10840:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 end-product test
- 3.2 pre-selection test
- 3.3 spalling
- 4 Enclosure fire scenarios
- 4.1 General
- 4.2 Initiation and early growth of fire
- 4.3 Development of fire
- 4.4 Fully developed fire
- 4.5 Decay
- 4.6 Important parameters for the fire stages
- 5 Categories of fire tests
- 5.1 Material characterisation tests
- 5.2 Quality-control tests
- 5.3 Pre-selection tests
- 5.4 End-product tests
- 5.5 Fire test based on the fire scenario
- 5.6 Use of fire safety engineering (FSE)
- 6 Important considerations in the fire testing of plastics materials and products
- 6.1 Influence of the chemical or physical nature of the test specimen
- 6.2 Sample and test specimen preparation and conditioning
- 6.3 Influence of test procedures
- 6.4 Burning behaviours of specimens
- 6.5 Operation of tests
- 6.6 Other critical factors
- 6.7 Characteristics of ignition sources
- 6.8 Operating procedures in the event of specimen collapse or deformation
- 6.9 Debris of specimen
- 7 Advantages and disadvantages of scale in fire tests
- 7.1 General
- 7.2 Large-scale tests
- 7.3 Intermediate-scale tests
- 7.4 Small-scale tests
- 7.5 Influence of test apparatus design on the applicability of test data
- 7.6 Calibration of the test apparatus and attainable precision
- 7.7 Uncertainty associated with fire test measurements
- 8 Potentially problematical specimen behaviour
- 8.1 Test developed for materials other than plastics
- 8.2 Shrinking
- 8.3 Bubbling
- 8.4 Intumescence
- 8.5 Extinguishing of pilot flames by highly flame retarded plastics
- 8.6 Slumping of thermoplastic sheets
- 8.7 Detection of flaming drips
- 8.8 Edge effects
- 8.9 Profiles products
- Annex A
- Annex B
- Bibliography
Introduction
Many of the current reaction-to-fire tests were developed, prior to the widespread use of synthetic polymers, to assess products incorporating materials such as wood (in the building industry), paper (in electrical wires and cables), and naturally occurring fibres such as cotton, wool and horsehair (in many textile, furniture and electrical applications). The reaction-to-fire characteristics of these so-cold traditional materials are often very different from those of synthetic materials, especially thermoplastics. ISO/TC 61/SC 4 recognises the need for guidance for users of fire-test standards commonly applied to materials and products made of, or incorporating, plastics. In 2003, the first edition of ISO 10840 was published, based on the now withdrawn ISO TR 10840:1993 (Plastics – Burning behaviour – Guidance for development and use of fire test), which listed a series of potential problems associated with the reaction-tofire testing of plastics materials and products. ISO TR 10840, however, provided users of the test methods with no practical assistance on how to cope with the listed difficulties. This document provides detailed information about how to conduct standard fire tests which are more relatable to the real conditions of plastics products in a variety of applications. With more concerns expressed about the environmental impact of fires involving plastics, additional guidance has been included in the second edition, and extended in this third edition. Particular attention is given to the provision of guidance for inexperienced users who need to assess the fire performance of materials or products made of, or incorporating, plastics. This document also provides answers to frequently asked questions concerning fire tests; these cover factors such as cost, duration, complexity, required operator skills, quality of the data produced, relevance to fire hazard assessment as well as test repeatability and reproducibility. This document contains a bibliography of the most frequently used fire tests applied to the materials and products within the scope of ISO/TC 61/SC 4. The main focus of this document is on reaction-to-fire testing. Fire resistance testing has also been considered, in particular for the use of plastic construction of small ships, to take account of the widespread use of advanced polymer composites and related materials with superior thermo-mechanical stability which can be used in applications where there is a demand for some degree of fire resistance. This document provides specifications and guidance for use of fire test of plastics based on the fire [45] [46] safety engineering (FSE) using methodologies prescribed in ISO 23932-1 , IEC 60695-1-11 and [47] IEC 60695-1-12 .
This document also provides guidance on some standard fire tests which give data that is applicable for assessment of the potentially adverse environmental impact of combustion products that can be generated in large-scale fires involving plastics materials and products (see Annex B). NOTE The term, ‘adverse environmental impact’, covers undesirable direct effects on the environment as well as indirect effects on people of ISO 10840 through environmental exposure.
SIST EN ISO 10840:2026 International Standard ISO 10840:2026(en) Plastics — Specifications and guidance for the use of standard fire tests
1 Scope
This document provides specifications and guidance for the use of standard fire testing for plastics and the products in the following aspects:
- selection of appropriate tests that reflect realistic end-use conditions;
- grouping of the reaction-to-fire characteristics that any given test or tests can measure;
- assessment of tests as to their relevance in areas such as material characterisation, quality control, preselection, end-product testing, environmental profiling and design for the environment (DfE);
- definition of potential problems that can arise when plastics are tested in standard fire tests. This document does not include specification for development or design of new fire-tests for plastics.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 10093, Plastics — Fire tests — Standard ignition sources ISO 13943, Fire safety — Vocabulary
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 13943 and the following apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https:// www .iso .org/ obp
- IEC Electropedia: available at https:// www .electropedia .org/
3.1 end-product test
fire hazard assessment test on a complete product, piece, part component or sub-assembly
3.2 pre-selection test
combustion characteristic test made on a standardized shape, for the process of assessing and choosing candidate materials, components or subassemblies for making an end product
3.3 spalling
breaking off of fragments or solid articles from a heated surface
SIST EN ISO 10840:2026 ISO 10840:2026(en)
4 Enclosure fire scenarios
4.1 General
A number of fire parameters influence the development of a fire. The fire parameters measured during the pre-flash-over and the post-flash-over conditions differ greatly. There are four main stages of fire development within an enclosure (i.e. pre-ignition, fire growth, flashover and fully developed fire), which are assessed using measurements of temperature and heat release rate in terms of time. Figure 1 shows the different phases in the development of fires, (see Table 1), within an [3] enclosure space (see ISO/TS 3814 ).
In Figure 1, the pre-ignition stage is in the duration from the start until ignition time. The fire growth stage starts at the ignition and continue until flash-over (see 4.2). The fully developed fire stage starts at the flashover (see 4.4) followed by fire decade stage (see 4.5). Sometimes, fire does not reach flash-over due to limited combustibles present or due to the intervention of active firefighting measures (e.g. sprinklers, fire brigades). Key X time Y1 heat release rate (kW) o Y2 temperature ( C) 1 ignition 2 flash-over 3 heat release rate curve 4 temperature curve Figure 1 — Development of fire in terms of temperature and heat release rate
4.2 Initiation and early growth of fire
This stage of fire includes the exposure of a product to a heat source, ignition and early development of a fire. [6] [7] ISO 871 gives a test method to determine the ignition temperature of plastic materials. ISO 3582 , ISO 4589 [8][9][10][11] [31] [12] [13] [33][34][35] [14] series , ISO 9239-1 , ISO 9772 , ISO 9773 , ISO 11925 series and ISO 12992
SIST EN ISO 10840:2026 ISO 10840:2026(en) specify fire test method for determination of ignitability of plastics and building materials which contain [28] plastics by small heat sources. ISO 10093 specifies ignition sources for use in fire tests. ISO 1182 [23] [24] specifies the test methods for non-combustibility (no-ignition). IEC 60695-11-2 , IEC 60695-11-5 , [25] [27] IEC 60695-11-10 and IEC 60695-11-20 specify various test methods for determination of ignitability and flame spread of materials used in electrotechnical products (in many cases, plastics). Two types of combustion can exist at this stage, smouldering and flaming. Smouldering is a slow, flameless combustion producing very little heat, but having the potential to fill an enclosure with smoke and toxic [60] gases. A test method for measuring toxic gases in fire efluents is given in ISO/TS 19700 . After ignition, the development of a flaming fire will depend on the following effects:
- fire growth on first ignited item;
- fire spread to other items;
- the effect of intervention (portable extinguishers, sprinklers, fire brigades);
- the ventilation conditions.
4.3 Development of fire
As a fire develops, a hot smoke and gas layer usually builds up below the ceiling. The radiant heat transfer to combustible items accelerates the thermal decomposition of material below the smoke layer, and the [30] [19] [21] rate of fire spread increases. ISO 5658-2 , ISO 21367 and ISO 23949 specify test methods for the [48] determination of flame spread capability. ISO 5659 provides test method for smoke generation. [29] Heat release from burning materials and products governs the fire growth. ISO 1716 , ISO 5660 [49][50][51][52] [36] [15] [37] [53] series , ISO 12136 , ISO 13927 , ISO 14696 and ISO 24473 give fire test methods for measurement of heat release from burning materials and products. Flash-over, which usually occurs at temperatures around 600 °C, corresponds to an abrupt sudden transition from a localised fire to the ignition of the gas layer and to the sudden subsequent ignition of all exposed flammable surfaces, leading to a fully developed fire. The rate of heat release increases rapidly, and this leads to a rapid temperature rise within the enclosure. However, temperature at flash-over is not always the maximum temperature in the compartment of the fire. Flash-over is uncommon in large enclosures, as the required temperature conditions are not often reached.
4.4 Fully developed fire
A fire is regarded as fully developed when all fuel within an enclosure is burning. This stage usually follows flash-over, but some fires can become fully developed without passing through the flash-over phase.
4.5 Decay
The decay stage of a fire is reached when the fire load or available air has been consumed, or when the fire is suppressed. In the pre-flash-over phase reaction to fire characteristics of products are important, while in the post-flash-over phase resistance to fire parameters of complete assemblies apply.
4.6 Important parameters for the fire stages
Fire building regulations make a distinction between these two conditions. Table 1 summarises the important [48] fire parameters associated with reaction to fire and resistance to fire. ISO 5659 gives specification of test [55][56] method for measuring generation of smoke. ISO 11907 series give specifications for corrosivity tests. [57][58][59] Some literatures also give guidance for consideration on corrosivity.
SIST EN ISO 10840:2026 ISO 10840:2026(en) Table 1 — Phases of fire Phase Stage Parameters Pre-flashover Fire initiation Ignitability Developing fire Fire growth (ignitability, flame spread, heat-, smoke- and toxic effluent release) Post-flash-over Developed fire Resistance to fire (load-bearing, integrity, insulation)
5 Categories of fire tests
5.1 Material characterisation tests
5.1.1 Tests done on behalf of customers undertaking no further reaction-to-fire testing
This type of testing imposes an obligation on the material supplier to assess reaction-to-fire characteristics of the material likely to be of relevance to the application of the customer’s product, or foreseeable misuse of the product as imposed by product stewardship aspects of Responsible Care programmes, or product liability litigation, or both. The objective should be to provide answers to questions such as:
a) Do the properties of the thermal decomposition products (heat release, smoke density, toxicity or corrosivity) pose a foreseeable problem?
b) Is the thermomechanical response of the material (e.g. melting or retreating from the heat source) likely to constitute a hazard or an advantage in the customer’s product application, or in foreseeable misuse scenarios?
5.1.2 Tests done on behalf of customers seeking compliance with reaction-to-fire tests on a finished product In this case, the test method(s) used by the material manufacturer should provide an indication of the likely influence on the product test result of material characteristics such as melting, dripping, or retreat from heat source.
5.2 Quality-control tests
Quality control fire tests can be conducted at manufacturers of materials and products for the purpose of examining that the quality of the products is maintained.
In order to select a quality control test, it is important to:
- decide which characteristics should be checked by the test;
- select or develop the appropriate test methodology;
- specify the required performance criteria;
- compare test result to ensure that the parameter measured by the quality-control test correlates with the key performance parameter being investigated.
It is necessary to specify:
- the characteristics which have to be checked by test;
- the appropriate test procedure;
- the required pass (acceptance) and fail (rejection) criteria of the test;
SIST EN ISO 10840:2026 ISO 10840:2026(en) and then to compare test result with the specified criterion/criteria (acceptance level). Repeatability is of crucial importance in tests selected for the purpose of quality control; in this context the relevance of the test to any given application of the material is of secondary importance.
5.3 Pre-selection tests
Data developed using pre-selection tests requires careful consideration to ensure their relevance in relation to the intended application and to avoid misuse and erroneous interpretation. The actual fire performance of a product is affected by its surroundings, design variables such as shape and size, fabrication techniques, heat -transfer effects, the type of potential ignition source and the length of exposure to it.
The advantages of pre-selection testing are as follows.
a) To a first approximation a material which reacts more favourably than another when tested as a standard test specimen will usually also react more favourably when used as a finished part in the product. This will be valid provided that no overriding, interactive, product-specific effects are present. b) Data concerning relevant combustion characteristics can aid the selection of materials, components and sub-assemblies during the design stage.
c) The precision of pre-selection tests is usually higher, and their sensitivity can be superior when compared with end-product tests.
d) Pre-selection tests can be used in a decision-making process directed to minimize the fire hazard. Where applicable for the purpose of fire hazard assessment, they can lead to a reduction in the number of end-product tests with a consequent reduction in the total testing effort. e) When fire hazard requirements need to be upgraded quickly, it can be possible to do this by upgrading the requirements of a pre-selection test before modifying the end-product test. f) The grading and classification obtained from the pre-selection test results can be used to specify a basic minimum performance of materials used in product specifications. It should be noted that when pre-selection testing is used to replace some of the end-product testing, it is necessary to fix an increased margin of safety in an attempt to ensure satisfactory performance of the end product. Following a pre-selection procedure, it is necessary to implement a value analysis on the end product, in order not to over-specify materials where a more economical material can be used. In this case, [5] an end-product test is necessary. IEC 60695-1-30 gives guidance for preselection process.
5.4 End-product tests
These tests should reflect the end-use application scenario as far as is possible. Important factors to consider include relevance of configuration, orientation, ventilation and the nature of the ignition source. Reaction-to-fire testing for fire safety and for fire hazard assessment of products should be programmed as follows:
a) specify the fire hazard to be assessed (e.g. vision impairment by smoke); b) define the relevant product-application (or misuse) scenario and specify the required safety criterion; c) select the appropriate test method and specify the pass/fail criterion; d) conduct the tests and analyse the data; e) select acceptable or reject unacceptable candidate materials or products.
SIST EN ISO 10840:2026 ISO 10840:2026(en) In case fire safety of a large constructions made of plastics must be considered within a scope of overall fire safety of the constructions, fire resistance of such product might need to be evaluated. [38] NOTE 1 ISO 30021 gives fire resistance test method on plastics including fibre reinforced plastics (FRP) for evaluation of fire safety of such product in small ships (crafts). It is also possible to develop an intermediate scale reaction-to-fire test that has close relationship to large scale reaction-to-fire test used for regulatory purposes.
[16] [17] NOTE 2 ISO 15791-1 and ISO/TS 15791-2 have been developed for application of intermediate-scale reactionto-fire tests.
5.5 Fire test based on the fire scenario
In case it becomes necessary to evaluate fire performance of plastics and/or product made of plastics in anticipated condition of use, fire scenario-based approach can be utilized. The fire scenario-based fire hazard assessment can be conducted in the process as described below:
a) define the target of the evaluation, i.e. plastic materials, product made of plastics; b) identify conditions where the target is used; c) establish fire scenario that realize the identifies conditions and existence of the target; d) identify fire performance parameters to evaluate fire performance of the target; e) establish criteria to decide acceptability of the target in the fire conditions; f) develop or choose fire test method(s) that realize the identified fire conditions and provide the results in terms of identified fire performance parameters g) evaluate the test results in light of established criteria. [46] Detailed process of scenario based fire hazard assessment is given in IEC 60695-1-11 . NOTE A fire test method of plastic materials in a condition of micro gravity is given in ISO 4589-4. Basic and overall approach fire safety evaluation based on the fire scenario and fire safety engineering is [45] [47] given in ISO 23932-1 and IEC 60695-1-12 .
5.6 Use of fire safety engineering (FSE)
5.6.1 Basics of fire safety engineering
[45] [42] [43] Basic approach on fire safety engineering is given in ISO 23932-1 , ISO 16732-1 , ISO 16733-1 and [44] ISO/TR 16738 give various specifications and information for the use of FSE. Additional fire safety engineering approach for electrotechnical products, which in most cases contain [46] [47] [26] plastics, is given in IEC 60695-1-11 , IEC 60695-1-12 and IEC 60695-11-11 . Fire safety engineering was developed and is continuing to develop to enable the design, implementation and maintenance of objects and structures in the built environment, using scientific principles, so that defined fire safety engineering objectives can be met. In order to do this, quantitative fire tests are used to provide input data for the necessary calculations.
When applied to a major project in the built environment, the fire engineering process is both complex and comprehensive. A flow chart illustrating such a fire safety engineering process is shown in Figure 2. Fire safety engineering should be used when safety objectives cannot adequately be met by prescriptive requirements and can also be used in parallel with prescriptive requirements, e.g. to support, from a scientific point of view, that such requirements are valid, or to further improve the fire safety of the product.
SIST EN ISO 10840:2026 ISO 10840:2026(en)
5.6.2 Fire tests for fire safety engineering on plastic products
Any physical or chemical tests on plastics products, to be used in fire safety engineering, should provide data appropriate to enable ‘in-use’ plastics product performance to be assessed through utilization of predictive methods.
It follows that:
...