Testing and rating of direct exchange ground coupled heat pumps with electrically driven compressors for space heating and/or cooling - Part 1: Direct exchange-to-water heat pumps

This European Standard specifies the terms and definitions, test conditions, test procedures and requirements for the rating and performance of direct exchange-to-water ground coupled heat pumps with electrically driven compressors, used for space heating and/or cooling. Brine can be used instead of water.
This European Standard applies to factory-made units with horizontal in-ground collectors. In the case of units consisting of several parts, this standard applies only to those designed and supplied as a complete package.
Water-to-direct exchange and direct-exchange-to-direct exchange ground coupled heat pumps are covered by EN 15879-2.
Direct exchange-to-air ground coupled heat pumps and air-to-direct exchange heat pumps are covered by EN 15879-3.
This European Standard does not apply to units using transcritical cycles, e.g. with CO2 as refrigerant.

Prüfung und Leistungsbemessung von erdreichgekoppelten Direktübertragung - Wärmepumpen mit elektrisch angetriebenen Verdichtern zur Raumbeheizung und/oder -kühlung - Teil 1: Direktübertragung/Wasser-Wärmepumpe

Diese Europäische Norm legt die Begriffe, Prüfbedingungen, Prüfverfahren für und Anforderungen an die Bemessung und Leistung von erdreichgekoppelten Direktübertragung/Wasser Wärmepumpen mit elektrisch angetriebenen Verdichtern fest, die zur Raumbeheizung und/oder Kühlung verwendet werden. Anstelle von Wasser kann auch Sole verwendet werden.
Die vorliegende Europäische Norm gilt für werkseitig zusammengebaute Geräte mit horizontal verlegten Erdwärmekollektoren. Bei Geräten, die aus mehreren Teilen bestehen, gilt diese Norm nur für die als vollständige Baueinheit konstruierten und gelieferten Teile.
Erdeichgekoppelte Wasser/Direktübertragung- und erdreichgekoppelte Direktübertragung/Direktübertragung  - Wärmepumpen sind in EN 15879 2 behandelt.
Erdreichgekoppelte Direktübertragung/Luft Wärmepumpen und Luft/Direktübertragung Wärmepumpen sind in EN 15879 3, behandelt.
Diese Europäische Norm gilt nicht für Geräte, bei denen der transkritische Kreislauf, z. B. mit CO2 als Kältemittel, betrieben wird.

Essais et détermination des caractéristiques des pompes à chaleur à échange direct avec le sol avec compresseur entraîné par moteur électrique pour le chauffage et/ou la réfrigération des locaux - Partie 1: Pompes à chaleur à échange direct avec l'eau

La présente Norme européenne spécifie les termes et définitions, les conditions et modes opératoires d'essai,
ainsi que les exigences relatifs à la détermination des caractéristiques et des performances des pompes à
chaleur à échange direct de type sol/eau, avec compresseur entraîné par moteur électrique, utilisées pour le
chauffage et/ou la réfrigération des locaux. L'eau glycolée peut être utilisée à la place de l'eau.
La présente Norme européenne s'applique aux appareils à capteurs horizontaux enterrés fabriqués en usine.
Dans le cas d'appareils comportant plusieurs éléments, la présente norme ne s'applique qu'aux appareils
conçus et fournis comme un ensemble complet.
Les pompes à chaleur eau-sol et les pompes à chaleur à échange direct dans le sol, de type sol-sol, sont
couvertes par l’EN 15879-2.
Les pompes à chaleur à échange direct dans le sol, de type sol-air, et les pompes à chaleur air-sol sont
couvertes par l'EN 15879-3.
La présente Norme européenne ne s'applique pas aux appareils utilisant des cycles transcritiques, par
exemple avec le CO2 comme fluide frigorigène.

Preskušanje in ocenitev toplotnih črpalk zemlja/voda (neposredna izmenjava) z električnimi kompresorji za segrevanje in/ali hlajenje prostora - 1. del: Toplotne črpalke z neposredno izmenjavo z vodo

Ta evropski standard določa izraze in definicije, preskusne pogoje, preskusne postopke in zahteve za ocenitev in učinkovitost toplotnih črpalk zemlja/voda z neposredno izmenjavo z vodo z električnimi kompresorji, ki se uporabljajo za segrevanje in/ali hlajenje prostora. Namesto vode se lahko uporablja slanica. Ta evropski standard velja za tovarniško izdelane enote z vodoravnimi zbiralniki v zemlji. Pri enotah, sestavljenih iz več kosov, ta standard velja samo za tiste, ki so načrtovane in dostavljene kot celoten paket. Toplotne črpalke zemlja/voda na vodo-neposredno izmenjavo ter neposredno izmenjavo-neposredno izmenjavo zajema EN 15879-2. Toplotne črpalke zemlja/voda na neposredno izmenjavo-zrak in toplotne črpalke na zrak-neposredno izmenjavo zajema EN 15879-3.

General Information

Status
Published
Publication Date
22-Feb-2011
Withdrawal Date
30-Aug-2011
Current Stage
9060 - Closure of 2 Year Review Enquiry - Review Enquiry
Start Date
04-Mar-2019
Completion Date
04-Mar-2019
Standard
EN 15879-1:2011
English language
24 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Prüfung und Leistungsbemessung von Direktaustausch- Erdreichwärmepumpen mit elektrisch angetriebenen Verdichtern zur Raumbeheizung und/oder -kühlung - Teil 1: Direktaustausch/Wasser-WärmepumpeEssais et détermination des caractéristiques des pompes à chaleur à détente directe avec le sol avec compresseur entraîné par moteur électrique pour le chauffage et/ou la réfrigération des locaux - Partie 1: Pompes à chaleur à échange direct avec l'eauTesting and rating of direct exchange ground coupled heat pumps with electrically driven compressors for space heating and/or cooling - Part 1: Direct exchange-to-water heat pumps27.080Heat pumpsICS:Ta slovenski standard je istoveten z:EN 15879-1:2011SIST EN 15879-1:2011en,fr,de01-oktober-2011SIST EN 15879-1:2011SLOVENSKI
STANDARD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15879-1
February 2011 ICS 27.080 English Version
Testing and rating of direct exchange ground coupled heat pumps with electrically driven compressors for space heating and/or cooling - Part 1: Direct exchange-to-water heat pumps
Essais et détermination des caractéristiques des pompes à chaleur à détente directe avec le sol avec compresseur entraîné par moteur électrique pour le chauffage et/ou la réfrigération des locaux - Partie 1: Pompes à chaleur à échange direct avec l'eau
Prüfung und Leistungsbemessung von erdreichgekoppelten Direktübertragung - Wärmepumpen mit elektrisch angetriebenen Verdichtern zur Raumbeheizung und/oder -kühlung - Teil 1: Direktübertragung/Wasser-WärmepumpeThis European Standard was approved by CEN on 8 January 2011.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2011 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15879-1:2011: ESIST EN 15879-1:2011

Example for the calculation of the Coefficient of Performance (COP) and the Energy Efficiency Ratio (EER) . 21B.1 Calculation of the COP for heating applications . 21B.1.1 Input Data . 21B.1.2 Calculation of the heating power PH . 22B.1.3 Calculation of the volume flow rate q . 23B.1.4 Calculation of the COP if a liquid pump is integrated into the heat pump unit . 23B.1.5 Calculation of the COP if a liquid pump is not integrated into the heat pump unit . 23B.2 Calculation of the EER for cooling applications . 23B.2.1 General . 23B.2.2 Calculation of the EER if a liquid pump is integrated into the heat pump unit . 23B.2.3 Calculation of the EER if a liquid pump is not integrated into the heat pump unit . 24 SIST EN 15879-1:2011

Measurement of airborne noise
Determination of the sound power level EN 14511-1:2007, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling
Part 1: Terms and definitions EN 14511-3, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling
Part 3: Test Methods EN 60204-1, Safety of machinery
Electrical equipment of machines
Part 1: General requirements (IEC 60204-1:2005, modified) EN 60335-2-40, Household and similar electrical appliances
Safety
Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers (IEC 60335-2-40:2002, modified) EN 61000-3-11, Electromagnetic compatibility (EMC)
Part 3-11: Limits; Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems; Equipment with rated current ≤ 75 A and subject to conditional connection (IEC 61000-3-11:2000) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2007 and the following apply. 3.1 direct exchange ground coupled heat pump heat pump which consists of an in-ground heat exchanger and a heat pump module 3.2 in-ground heat exchanger heat exchanger buried in the ground that consists of a series of parallel loops, each consisting of a single tube, in which the refrigerant is circulating for a direct heat exchange with the ground SIST EN 15879-1:2011

Designation of direct exchange-to-water (brine) heat pumps Outdoor heat exchanger Indoor heat exchanger Designation Classification In-ground heat exchanger Water Direct exchange-to-water units DX / water Brine Direct exchange-to-brine units DX / brine
5 Test conditions 5.1 Environmental conditions and electrical power supply requirements The test shall be carried out under the environmental conditions around the heat pump module specified in Table 2. For all units, electrical power, voltage and frequency shall be given by the manufacturer. Table 2
Environmental conditions Type Measured quantity Environmental conditions DX / water or DX / brine to be installed outdoors – heating operation Air dry bulb temperature 0 °C to 7 °C DX / water or DX / brine to be installed outdoors – cooling operation Air dry bulb temperature 25 °C to 35 °C DX / water or DX / brine to be installed
indoors – heating or cooling operation Air dry bulb temperature 15 °C to 30 °C SIST EN 15879-1:2011

Rating conditions for the heating mode
In-ground heat exchanger Indoor heat exchanger
Bath temperature (°C) Inlet temperature (°C) Outlet temperature (°C)
Standard rating conditions DX / water or DX / brine for low heating temperature applications 4 30 35 DX / water or DX / brine for medium heating temperature applications 4 40 45 DX / water or DX / brine for high heating temperature applications 4 47 55 DX / water or DX / brine for very high heating temperature applications 4 55 65 Application rating conditions DX / water or DX / brine for low heating temperature applications 4 25 30 DX / water and DX / brine for low heating temperature applications 1,5 30 35 DX / water and DX / brine for medium heating temperature applications 1,5 40 45 SIST EN 15879-1:2011

Rating conditions for the cooling mode
In-ground heat exchanger Indoor heat exchanger
Bath temperature (°C) Inlet temperature (°C) Outlet temperature (°C) Standard rating conditions DX / water or DX / brine for high cooling temperature applications 30 23-a 18 DX / water or DX / brine for low cooling temperature applications 30 12-a 7 Application rating conditions DX / water or DX / brine for high cooling temperature applications 10 b 18 DX / water or DX / brine for low cooling temperature applications 10 b 7 (a) For reversed cycle units, the test is performed at the flow rate obtained during the test for the corresponding standard rating conditions in the heating mode in Table 3. (b) With the water flow rate as determined for the standard rating condition. 6 Rating capacity tests 6.1 Basic principles 6.1.1 Heating capacity The heating capacity of direct exchange heat pumps shall be determined in accordance with the direct method at the water or brine heat exchanger. This shall be done by determination of the volume flow of the heat transfer medium and the inlet and outlet temperatures, taking into consideration the specific heat capacity and density of the heat transfer medium. The heating capacity shall be determined using the following formula: PH = q × ρ × cp × ∆T (1) where PH
is the heating capacity, in watts; q
is the volume flow rate, in cubic meters per second; ρ
is the density, in kilograms per cubic meter; cp
is the specific heat at constant pressure, in joules per kilogram per kelvin; ∆T
is the difference between inlet and outlet temperatures, in kelvin. The heating capacity shall be corrected for the heat from the circulating pump:  if the pump at the indoor heat exchanger is an integral part of the unit, the same power (calculated in 6.1.3.1) which is excluded from the total power input shall also be subtracted from the heating capacity; SIST EN 15879-1:2011

is the cooling capacity, in watts; q
is the volume flow rate, in cubic meters per second; ρ
is the density, in kilograms per cubic meter; cp
is the specific heat at constant pressure, in joules per kilogram per kelvin; ∆T
is the difference between inlet and outlet temperatures, in kelvin. The cooling capacity shall be corrected for the heat from the circulating pump:  if the pump at the indoor heat exchanger is an integral part of the unit, the same power (calculated in 6.1.3.1) which is excluded from the total power input shall also be added to the cooling capacity;  if the pump at the indoor heat exchanger is not an integral part of the unit, the same power (calculated in 6.1.3.2) which is included in the effective total power input shall also be subtracted from the cooling capacity. 6.1.3 Power input of liquid pumps If the liquid pump is integrated in the unit, it shall be connected for operation. When the liquid pump is delivered by the manufacturer apart from the unit, it shall be connected for operation according to the manufacturer’s instructions and be considered as an integral part of the unit. 6.1.3.1 If a liquid pump is an integral part of the unit, only a fraction of the input to the pump motor shall be included in the effective power absorbed by the unit. The fraction which is to be excluded from the total power absorbed by the unit shall be calculated from the following formula: ûη×=[]eLPqpPW (3) where η is the efficiency of the liquid pump according to EN 14511-3; ∆pe is the measured external static pressure difference as defined in EN 14511-1, in pascal; q is the nominal heat transfer medium flow rate, in cubic meters per second. 6.1.3.2 If no liquid pump is provided with the unit, the proportional
...