Fire resistance tests for door and shutter assemblies - Part 3: Smoke control doors and shutters

This Part of EN 1634 specifies a method for determining the leakage of cold and warm smoke from one side of a door assembly to the other under the specified test conditions. The test can be applied to door and shutter assemblies of different types intended for purposes of controlling the passage of smoke in case of fire. This test can also be applied to lift landing doors and conveyor system doors and shutters. The principle of the test is explained briefly in annex A.

Feuerwiderstandsprüfungen für Tür- und Abschlusseinrichtungen - Teil 3: Rauchschutzabschlüsse

Dieser Teil von EN 1634 beschreibt ein Prüfverfahren zur Ermittlung der Leckage von kaltem und warmem
Rauch von einer Seite eines Abschlusses zur anderen unter festgelegten Prüfbedingungen. Die Prüfung kann auf
Abschlüsse unterschiedlicher Bauart angewendet werden, die zur Behinderung der Rauchbewegung im Brandfall
vorgesehen sind. Dieses Prüfverfahren kann auch auf Fahrschachttüren und Abschlüsse bahngebundener
Förderanlagen angewendet werden. Das Prüfprinzip wird im Anhang A kurz erläutert.

Essais de résistance au feu des portes et fermetures - Partie 3: Portes et volets pare-fumées

La présente partie de l'EN 1634 spécifie une méthode permettant d'établir l'étanchéité d'un côté d'un bloc-porte à la fumée froide et chaude, dans les conditions d'essai spécifiées. L'essai peut être appliqué à différents types de blocs-portes et de blocs-fermetures destinés à contrôler le passage de la fumée en cas d'incendie. Cet essai peut également être appliqué aux portes palières des ascenseurs et aux portes des systèmes de bandes transporteuses. Le principe de l'essai est expliqué brièvement dans l'annexe A.

Preskusi požarne odpornosti vrat in drugih zapornih sestavov - 3. del: Dimna vrata in zapore

General Information

Status
Withdrawn
Publication Date
24-Apr-2001
Withdrawal Date
19-Oct-2004
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
20-Oct-2004
Completion Date
20-Oct-2004

Relations

Buy Standard

Standard
EN 1634-3:2002
English language
17 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Preskusi požarne odpornosti vrat in drugih zapornih sestavov - 3. del: Dimna vrata in zaporeFeuerwiderstandsprüfungen für Tür- und Abschlusseinrichtungen - Teil 3: RauchschutzabschlüsseEssais de résistance au feu des portes et fermetures - Partie 3: Portes et volets pare-fuméesFire resistance tests for door and shutter assemblies - Part 3: Smoke control doors and shutters91.060.50Vrata in oknaDoors and windows13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 1634-3:2001SIST EN 1634-3:2002en01-februar-2002SIST EN 1634-3:2002SLOVENSKI
STANDARD



SIST EN 1634-3:2002



EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 1634-3April 2001ICS 13.220.50; 91.060.50English versionFire resistance tests for door and shutter assemblies - Part 3:Smoke control doors and shuttersEssais de résistance au feu des portes et fermetures -Partie 3: Portes et volets pare-fuméesFeuerwiderstandsprüfungen für Tür- undAbschlusseinrichtungen - Teil 3: RauchschutzabschlüsseThis European Standard was approved by CEN on 7 March 2001.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2001 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 1634-3:2001 ESIST EN 1634-3:2002



Page 2EN 1634-3:2001CONTENTSPageForeword31Scope42Normative references43Definitions, symbols and designations44Test equipment55Test conditions66Test specimen67Installation of test specimen78Conditioning79Application of instrumentation810Test procedure811Performance criteria1012Test report1113Field of direct application of test results11Annex A (informative) - Test principle15Annex B (informative) - Test apparatus16SIST EN 1634-3:2002



Page 3EN 1634-3:2001ForewordThis European Standard has been prepared by Technical Committee CEN/TC 127 "Fire safety inbuildings", the secretariat of which is held by BSI.This European Standard shall be given the status of a national standard, either by publication of anidentical text or by endorsement, at the latest by October 2001, and conflicting national standardsshall be withdrawn at the latest by October 2001.EN 1634 ‘Fire resistance tests for door and shutter assemblies’ consists of the followingPart 1:Fire doors and shuttersPart 2:Fire door hardware (in course of preparation)Part 3:Smoke control doors.According to the CEN/CENELEC Internal Regulations, the national standards organizations of thefollowing countries are bound to implement this European Standard: Austria, Belgium, CzechRepublic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg,Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.CautionThe attention of all persons concerned with managing and carrying out this test is drawn to thefollowing. Mechanical and operation hazards may arise during the construction of the test elements orstructures, their testing and disposal of test residues. An assessment of all potential hazards and risksto health should be made and safety precautions should be identified and provided.
Written safetyinstructions should be issued.
Appropriate training should be given to relevant personnel.Laboratory personnel should ensure that they follow written safety instructions at all times.The annexes A and B are informative.SIST EN 1634-3:2002



Page 4EN 1634-3:20011ScopeThis Part of EN 1634 specifies a method for determining the leakage of cold and warm smoke fromone side of a door assembly to the other under the specified test conditions.
The test can be appliedto door and shutter assemblies of different types intended for purposes of controlling the passage ofsmoke in case of fire.
This test can also be applied to lift landing doors and conveyor system doorsand shutters. The principle of the test is explained briefly in annex A.2Normative referencesThis European Standard incorporates by dated or undated references, provisions from otherpublications. These normative references are cited at the appropriate places in the text and thepublications are listed hereinafter.
For dated references, subsequent amendments to or revisions ofany of these publications apply to the European standard only when incorporated in it by amendmentor revision.
For undated references the latest edition of the publication referred to applies (includingamendments).EN 1363-1
Fire resistance tests - Part 1 General requirementsEN 1634-1
Fire resistance tests for door and shutter assemblies - Part 1 Fire doors and shuttersEN ISO 13943
Fire safety - Vocabulary (ISO 13943:1999)3Definitions, symbols and designations3.1
Terms and definitionsFor the purposes of this Part of EN 1634, the terms and definitions given in EN 1363-1, EN 1634-1and EN ISO 13943, together with the following, apply:3.1.1smoke control doorA door assembly which has the function of restricting the passage of smoke, when in a closedposition, to prescribed limits.3.1.2ambient temperatureFor the purpose of this standard ambient temperature is an air temperature of (20 ± 10) 0C.3.1.3medium temperatureFor the purpose of this standard medium temperature is an air temperature of (200 ± 20) 0C.3.1.4test specimenA door or shutter assembly on which leakage measurements are to be made.
It includes all thecomponents necessary for the use of the door when installed in a building e.g. side panels and overpanels.3.1.5associated constructionA specific form of construction in which the test specimen is mounted which is identical to that intowhich the door
or shutter assembly is designed to be installed in practice.
The method of sealing thejoint between the test specimen and the associated construction is specific to that construction andforms part of the construction being evaluated by the test.SIST EN 1634-3:2002



Page 5EN 1634-3:20013.1.6supporting constructionA form of construction with adequate strength and stiffness which is used to support the testspecimen and to fill up the difference between the size of the test specimen and the opening in thetest frame in an impermeable manner.
The seal between the test specimen and the supportingconstruction should be impermeable and withstand the test temperature and is part of the test. Thetest frame can be considered to be part of the supporting construction.3.1.7test specimen leakage rate QspecThe leakage through the test specimen (3.1.4) and seal between that and the test frame or anysupporting/associated construction used.3.1.8aspect ratioThe fixed relationship of width divided by height of a four sided constructional component.3.2
Symbols and designationThe symbols and designation listed below define those used in this Standard.SymbolUnitDesignationQm3/hleakage rateQappm3/happaratus leakage rateQsup/assocm3/hsupporting/associated construction leakage rateQspecm3/htest specimen leakage rateQtm3/htotal leakage rate4Test equipment4.1
Test apparatusThe test apparatus consists of a test chamber with an open front where the test construction ismounted to provide a sealed enclosure.
The opening of the test frame shall be sufficient toaccommodate the test specimen with its associated or supporting construction, in general an openingof 3 m x 3 m would be sufficient for most door types.A fan and heating system is used to create the pressure differential and temperatures specified inclause 5. The fan and the heating system shall be able to replace air at ambient and mediumtemperature to compensate for leakage rates through the test assembly.Annex B provides an outline specification for a suitable apparatus but other designs are possible toachieve the same objectives.SIST EN 1634-3:2002



Page 6EN 1634-3:20014.2
Instrumentation4.2.1
Air temperatureAll thermocouples for the measurement of air temperature shall be of bare metal type with a wirediameter of 0,5 mm or steel sheathed type with the overall diameter not exceeding 1,0 mm. Alltemperature measuring equipment shall be capable of measuring temperatures up to 250 0C with anaccuracy of
5°C.4.2.2
PressureA suitable instrument shall be provided to measure the static pressure difference between the insideand outside of the test chamber. The pressure measuring equipment shall be capable of measuringpressures with an accuracy of 10% of the measured value.4.2.3
Air flowInstrumentation shall be provided to measure the volume, Qt, and the temperature of air supplied to orextracted from the apparatus to compensate for the total leakage.
The apparatus shall be able tomeasure leakage up to at least 55 m3/h to an accuracy of 1 m3/h.5Test conditionsA fan system is provided to create a pressure differential across the test specimen of at least 55 Pa.Provision shall be made to heat the circulating air to test temperature of (200 ± 20) 0C within the testduration and to control the temperature within the prescribed limits. The test chamber shall be well sealed and the apparatus leakage rate together with the leakage ratethrough an associated/supporting construction (Qapp + Qsup/assoc) shall not exceed 10 m3/h at 50 Pa andambient temperature.6Test specimen6.1
SizeThe test specimen and all its components shall be full size unless limited by the size of the frontopening of the test apparatus, which will normally be 3 m x 3 m. Door assemblies which cannot betested at full size shall normally be tested to the maximum size possible consistent with the use ofsupporting or associated constructions. If an associated construction is used, a minimum zone shall beexposed within the chamber, 200 mm wide each side and over the top of the aperture, into which thedoor assembly is to be fixed.6.2
NumberAs doors are usually of asymmetrical construction leakage tests shall be carried out from both sidesfor full evaluation. The number of tests shall be as given in table 1SIST EN 1634-3:2002



Page 7EN 1634-3:2001Table 1
Number of testsApplicationTemperatureNumber of testsGeneralGeneralSpecialAmbientMediumAmbient/mediumone test for each side: the same door may
be used byeither reversing the sample or by creatingunderpressure in the test chamberone test for each side: a separate specimen is requiredin each caseone test from the specified side6.3
Design and constructionTest specimen construction and finish shall be fully representative of that intended to be used inpractice.
Any seal used in the door or between the door assembly and the associated constructionshall be identical to that intended for application in practice.6.4
VerificationWhere practicable, the size, thickness and
material specification of the door assembly, shall bedetermined before the test to check the construction of the door against the manufacturersspecification and to allow adequate description of the tested assembly.All gaps through which smoke can leak shall be measured and recorded. Generally these are gapsbetween the edge of the door leaf/leaves and the door frame, between door leaves and at the sill level.A full description shall be given of the conditions prevailing at each edge and the presence and thenature of any seals.7Installation of test specimenThe test specimen shall be mounted as in practice, in an associated or supporting construction, inaccordance with the manufacturer's instructions, with appropriate gaps and clearances between thefixed and moveable parts.All gaps between the supporting or associated construction and test frame shall be tightly sealed withan impermeable material.8Conditioning8.1 Moisture contentThe test construction shall be conditioned in accordance with EN 1363-1. Door assemblies madeentirely of non-hygroscopic materials, e.g. metal, glass etc., shall be left in the laboratory for at leastthree days before testing. Any additional conditioning requirements in the relevant product standardshall also be observed.8.2MechanicalReference shall be made to the product standard for details of requirements for mechanicalconditioning of the test specimen before smoke leakage testing e.g. operational test or specimen selfclosing test.Durability requirements are given in the relevant product standard.SIST EN 1634-3:2002



Page 8EN 1634-3:20019Application of instrumentation9.1
ThermocouplesFor the medium temperature test nine thermocouples shall be used to monitor and control thetemperature inside the test chamber. The thermocouples shall be arranged in three horizontal rows.These thermocouples shall be spread equally across the chamber with three 150 mm from the bottomedge of the opening in the test frame, three in the centre and three at ¾ height position. The hotjunctions shall be positioned (100
50) mm from the exposed face of the test construction.9.2
PressureThe pressure measuring device head (see 4.2.2) shall be mounted in the test chamber at the centre ofthe test specimen (100
50) mm from the inside face of the test specimen.9.3
Air flowThe equipment described in 4.2.3 shall be installed.10Test procedure10.1
Pre-test procedures10.1.1
GeneralAfter installation of the assembly in the associated or the supporting construction, but before it ismounted in front of the test chamber, each door leaf, or moving element of a hinged door assembly,shall be opened to an angle of 30° and closed 10 times, using the automatic closing devices, ifprovided, to ensure the assembly operates normally.
With other types of doors, such as folding,sliding or rolling shutters, the opening and closing operation shall be carried out as far as practicableto check the operation of the assembly.
This procedure is not a durability test, for which specialprocedures are available.10.1.2
Retention force measurementsThe retention forces for all door assemblies which incorporate closing devices and which are meantto be opened unaided by mechanical power shall be measured. These measurements are needed toestablish the magnitude of the forces used to retain the door leaves closed to ensure that they arerepresentative of those used in normal practice.For each door leaf, the retention force shall be determined as given below. For double action doorsthe retention force shall be determined for each direction of opening, and for folding doors theretention force shall be determined in the direction of opening.The retention forces for all door assemblies which incorporate closing devices operated by egressingpersonnel without mechanical assistance shall be measured as follows:Open the test door slowly, using a force gauge attached to the handle and operatin
...