EN 15218:2006
(Main)Air conditioners and liquid chilling packages with evaporatively cooled condenser and with electrically driven compressors for space cooling - Terms, definitions, test conditions, test methods and requirements
Air conditioners and liquid chilling packages with evaporatively cooled condenser and with electrically driven compressors for space cooling - Terms, definitions, test conditions, test methods and requirements
This standard specifies the terms, definitions, test conditions, test methods and requirements for rating the performance of air conditioners and liquid chilling packages, with electrically driven compressors and with evaporatively cooled condenser when used for space cooling. The evaporatively cooled condenser is cooled by air and by the evaporation of external additional water. This additional external water is fed by a specific water supply circuit or by a water tank.
This standard does not apply to air-to-air and air-to-water air conditioners with a condenser cooled by air and by the evaporation of water condensed on their evaporator.
This standard does not apply to units equipped with a water tank or with a continuous water circuit supply that cannot operate without water feeding.
This standard applies to factory-made units which can be ducted.
This standard applies to factory-made units of either fixed capacity or variable capacity by any means.
Packaged units, single split and multisplit systems are covered by this standard.
With regard to units consisting of several parts, this standard applies only to those designed and supplied as a complete package.
Installations used for industrial processes cooling are not within the scope of this standard.
NOTE All the symbols given in this text should be used regardless of language.
Luftkonditionierer und Flüssigkeitskühlsätze mit verdunstungsgekühltem Verflüssiger und elektrisch angetriebenen Verdichtern für die Raumkühlung - Begriffe, Prüfbedingungen, Prüfverfahren und Anforderungen
Diese Norm legt die Begriffe, Prüfbedingungen, Prüfverfahren und Anforderungen für die Einstufung und Leis-tung
von Luftkonditionierern und Flüssigkeitskühlsätzen mit elektrisch angetriebenen Verdichtern und dampf-gekühlten
Verflüssigern für die Raumkühlung fest. Der dampfgekühlte Verflüssiger wird durch Belüftung und
durch Verdampfung von zusätzlichem, von außen zugeführtem Wasser abgekühlt. Dieses zusätzliche Wasser
wird über einen speziellen Wasserversorgungskreislauf oder einen Wasserbehälter von außen zugeführt.
Diese Norm gilt nicht für Luft/Luft- und Luft/Wasser-Luftkonditionierer, deren Verflüssiger durch Belüftung und
durch Verdampfung des an ihrem Verdampfer kondensierten Wassers abgekühlt wird.
Diese Norm gilt nicht für Geräte, die mit einem Wasserbehälter oder einem Wasserkreislauf mit konstanter
Versorgung versehen sind, die ohne diese Wasserzuleitung nicht betrieben werden können.
Diese Norm gilt für fabrikmäßig zusammengebaute Geräte, die mit Luftkanalanschlüssen versehen sein
können.
Diese Norm gilt für fabrikmäßig zusammengebaute Geräte mit fest eingestellter oder durch beliebige Vorrich-tungen
zu verändernder Leistung (variable Leistung).
Kompaktgeräte, Einzelgeräte in Split-Bauweise und Multi-Split-Systeme fallen in den Anwendungsbereich
dieser Norm.
Wenn die Geräte aus mehreren Teilen bestehen, gilt diese Norm nur für die Teile, die als vollständige Bau-einheit
konstruiert und geliefert werden.
Anlagen für die Kühlung industrieller Prozesse fallen nicht in den Anwendungsbereich dieser Norm.
ANMERKUNG Alle in dieser Norm enthaltenen Symbole sollten sprachunabhängig verwendet werden.
Climatiseurs et groupes refroidisseurs de liquide à condenseur refroidi par évaporation et compresseur entraîné par moteur électrique pour la réfrigération des locaux - Termes, définitions, conditions d'essai, méthodes d'essai et exigences
La présente norme spécifie les termes, définitions, conditions d'essai, méthodes d'essai et exigences relatives
à la détermination des caractéristiques nominales et aux performances des climatiseurs et groupes
refroidisseurs de liquide à compresseur entraîné par moteur électrique et condenseur refroidi par évaporation
utilisés pour la réfrigération des locaux. Le condenseur est refroidi par air et par évaporation d'eau extérieure
supplémentaire. Cette source extérieure d'eau supplémentaire provient d'un circuit d'alimentation en eau
spécifique ou d'un réservoir d'eau.
La présente norme ne s'applique pas aux climatiseurs air/air et air/eau avec un condenseur refroidi par air et
par évaporation des condensats de l'évaporateur.
La présente norme ne s'applique pas aux appareils avec un réservoir d'eau ou avec un circuit d'eau en
alimentation continue qui ne peuvent pas fonctionner sans apport d'eau.
La présente norme s'applique aux appareils fabriqués en usine qui peuvent être raccordés.
La présente norme s'applique aux appareils fabriqués en usine de capacité fixe ou variable par tous les
moyens.
La présente norme couvre les systèmes monoblocs, à deux éléments séparés et multi-split.
Dans le cas d'appareils à éléments séparés, la présente norme ne s'applique qu'aux appareils conçus et
fournis comme un ensemble complet.
Les installations utilisées pour le refroidissement des procédés industriels ne sont pas incluses dans le
domaine d'application de la présente norme.
NOTE Il convient d'utiliser tous les symboles donnés dans le présent document, quelle que soit la langue.
Klimatske naprave in enote za tekočinsko hlajenje s kondenzatorjem, ohlajenim z izhlapevanjem, in električnimi kompresorji za hlajenje prostora - Izrazi, definicije, preskusni pogoji, preskusne metode in zahteve
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Air conditioners and liquid chilling packages with evaporatively cooled condenser and with electrically driven compressors for space cooling - Terms, definitions, test conditions, test methods and requirementsClimatiseurs et groupes refroidisseurs de liquide a condenseur refroidi par évaporation et compresseur entraîné par moteur électrique pour la réfrigération des locaux - Termes, définitions, conditions d'essai, méthodes d'essai et exigencesLuftkonditionierer und Flüssigkeitskühlsätze mit verdunstungsgekühltem Verflüssiger und elektrisch angetriebenen Verdichtern für die Raumkühlung - Begriffe, Prüfbedingungen, Prüfverfahren und AnforderungenTa slovenski standard je istoveten z:EN 15218:2006SIST EN 15218:2007en,fr,de91.140.30VLVWHPLVentilation and air-conditioning27.200Hladilna tehnologijaRefrigerating technology23.120QDSUDYHVentilators. Fans. Air-conditionersICS:SLOVENSKI
STANDARDSIST EN 15218:200701-januar-2007
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 15218October 2006ICS 23.120; 27.200; 91.140.30 English VersionAir conditioners and liquid chilling packages with evaporativelycooled condenser and with electrically driven compressors forspace cooling - Terms, definitions, test conditions, test methodsand requirementsClimatiseurs et groupes refroidisseurs de liquide àcondenseur refroidi par évaporation et compresseurentraîné par moteur électrique pour la réfrigération deslocaux - Termes, définitions, conditions d'essai, méthodesd'essai et exigencesLuftkonditionierer und Flüssigkeitskühlsätze mitverdunstungsgekühltem Verflüssiger und elektrischangetriebenen Verdichtern für die Raumkühlung - Begriffe,Prüfbedingungen, Prüfverfahren und AnforderungenThis European Standard was approved by CEN on 11 September 2006.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2006 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15218:2006: E
NOTE Desuperheating and sub-cooling of the refrigerant may occur as well 3.2 water tank tank designed as an integral part of the unit to contain external additional water which is fed to the evaporatively cooled condenser 3.3 continuous supply water circuit circuit designed as an integral part of the unit to feed continuously the evaporatively cooled condenser with water from an external water source 3.4 effective power input PE average electrical power input of the unit within a defined interval of time obtained from: power input for operating the compressor; power input for all control and safety devices of the unit; power input of the circulating pump which provides water to the evaporatively cooled condenser, if any; proportional power input of the conveying devices (e.g. fans, pumps) for ensuring the transport of the heat transfer media inside the unit. Expressed in Watt. For the purpose of this standard the present definition replaces the one in EN 14511-1:2004 and it shall be used to calculate the EER 3.5 cleaning cycle interval of time during which water is sprayed on the evaporatively cooled condenser in order to remove fouling and scale buildup 3.6 functioning cycle interval of time elapsed between the start of two successive cleaning cycles for evaporatively cooled condenser units with a continuous water supply 4 Classification If the heat transfer medium for the indoor heat exchanger is water, the unit shall be denominated as evaporatively cooled condenser liquid chilling package.
Table 1 — Environmental conditions for units designed for indoor installation
Type Measured quantities Rating test Evaporatively cooled condenser liquid chilling packages with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Evaporatively cooled condenser liquid chilling packages without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature As air inlet temperatures, see Table 5 or Table 6 Evaporatively cooled condenser air conditioners with duct connection on the indoor air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Evaporatively cooled condenser air conditioners without duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature As air inlet temperatures, see Table 3 or Table 4
Table 2 — Environmental conditions for units designed for outdoor installation
Type Measured quantities Rating test Evaporatively cooled condenser liquid chilling packages Dry bulb temperature Wet bulb temperature As air inlet temperatures, see Table 5 and Table 6 Evaporatively cooled condenser air conditioners with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature As inlet temperatures, see Table 3 and Table 4
Table 3 –Evaporatively cooled condenser air conditioner with continuous water supply circuit
Evaporatively cooled condenser
Air Water Indoor heat exchanger
Inlet dry bulb temperature
ºC Inlet wet bulb temperature ºC Inlet temperature
ºC Inlet dry bulb temperature
ºC Inlet wet bulb temperature
ºC Comfort (outdoor air / recycled air) 35 24 15 27 19 Comfort (exhaust air / recycled air) 27 19 15 27 19 Comfo
...
Questions, Comments and Discussion