Instrument transformers - Three-phase inductive voltage transformers having Um up to 52 kV

This European Standard specifies the requirements and tests for new three-phase voltage transformers with Um up to 52 kV and frequencies from 15 Hz to 100 Hz, for use with electrical instruments or electrical protective devices. NOTE Single-phase voltage transformers connected in a three-phase bank are not covered in this document.

Messwandler - Dreiphasige Spannungswandler mit Um bis 52 kV

Diese Europäische Norm legt die Anforderungen und Prüfungen für neue dreiphasige Spannungswandler mit Um bis 52 kV und Frequenzen von 15 Hz bis 100 Hz zur Anwendung mit elektrischen Messgeräten oder elektrischen Schutzeinrichtungen fest. ANMERKUNG Einphasige Spannungswandler, die zu einem dreiphasigen System zusammengeschaltet sind, werden in dieser Norm nicht behandelt.

Transformateurs de mesure - Transformateurs inductifs de tension triphasés avec Um jusqu'à 52 kV

La présente Norme Européenne spécifie les exigences et les essais pour les transformateurs de tension triphasés neufs avec Um jusqu’à 52 kV et des fréquences comprises entre 15 Hz à 100 Hz, utilisés avec des appareils de mesure électriques ou des dispositifs électriques de protection. NOTE Les transformateurs de tension monophasés raccordés en un banc triphasé ne sont pas couverts dans ce document.

Instrumentni transformatorji - Trifazni induktivni napetostni transformatorji z Um do 52 kV

General Information

Status
Withdrawn
Publication Date
23-Jan-2008
Drafting Committee
Parallel Committee
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
11-Mar-2014
Completion Date
11-Mar-2014

Relations

Buy Standard

Standard
EN 50482:2008
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-maj-2008
1DGRPHãþD
SIST HD 587 S1:2001
Instrumentni transformatorji - Trifazni induktivni napetostni transformatorji z Um
do 52 kV
Instrument transformers - Three-phase inductive voltage transformers having Um up to
52 kV
Messwandler - Dreiphasige Spannungswandler mit Um bis 52 kV
Transformateurs de mesure - Transformateurs inductifs de tension triphasés avec Um
jusqu'à 52 kV
Ta slovenski standard je istoveten z: EN 50482:2008
ICS:
17.220.20 0HUMHQMHHOHNWULþQLKLQ Measurement of electrical
PDJQHWQLKYHOLþLQ and magnetic quantities
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 50482
NORME EUROPÉENNE
January 2008
EUROPÄISCHE NORM
ICS 17.220.20 Supersedes HD 587 S1:1993

English version
Instrument transformers -
Three-phase inductive voltage transformers having U up to 52 kV
m
Transformateurs de mesure -  Messwandler -
Transformateurs inductifs de tension Dreiphasige Spannungswandler
triphasés avec U jusqu'à 52 kV mit U bis 52 kV
m m
This European Standard was approved by CENELEC on 2007-09-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50482:2008 E
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 38X, Instrument
transformers.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50482 on
2007-09-01.
This European Standard supersedes HD 587 S1:1993. It is to be used in conjunction with
EN 60044-2:1999.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2008-09-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2010-09-01
__________
– 3 – EN 50482:2008
Contents
1 General. 5
1.1 Scope. 5
1.2 Normative references . 5
2 Definitions . 5
3 General requirements. 5
4 Normal and special service conditions. 5
5 Ratings. 5
5.1 Standard values of rated voltages. 5
5.2 Standard values of rated output. 6
5.3 Standard values of rated voltage factor. 6
5.4 Limits of temperature rise . 6
6 Design requirements . 7
6.1 Insulation requirements . 7
6.2 Short-circuit withstand capability. 8
7 Classification of tests. 8
8 Type tests . 8
8.1 Temperature-rise tests. 8
8.2 Short-circuit withstand capability test . 8
8.3 Impulse test on primary winding. 8
8.4 Wet test for outdoor type transformers. 9
9 Routine tests. 9
9.1 Verification of terminal markings. 9
9.2 Power frequency tests on primary winding and partial discharge measurement. 9
9.3 Power-frequency tests between section and on secondary windings. 11
10 Special test . 11
11 Markings . 11
11.1 Rating plate and markings . 11
11.2 Terminal markings. 11
12 Accuracy requirements for three-phase inductive measuring voltage transformers. 12
12.1 Accuracy class designation for measuring voltage transformers. 12
12.2 Limits of voltage error and phase displacement for measuring voltage transformers. 12
12.3 Type test for accuracy of measuring voltage transformers. 12
12.4 Routine test for accuracy of measuring voltage transformers . 12
12.5 Markings of the rating plate of three-phase measuring voltage transformer . 12
13 Additional requirements for three-phase inductive protective voltage transformers . 12
13.1 Accuracy class designation for protective voltage transformers. 12
13.2 Limits of voltage error and phase displacement for protective voltage transformers. 12
13.3 Rated voltages for secondary windings intended to produce a residual voltage. 12
13.4 Output for secondary windings intended to produce a residual voltage. 12
13.5 Accuracy class for secondary windings intended to produce a residual voltage. 13
13.6 Type test for protective voltage transformers. 13
13.7 Routine test for protective transformers . 14
13.8 Markings of the rating plate of a three-phase protective voltage transformer . 14
Bibliography . 21

Figures
Figure 1 – Three-phase transformer with a single secondary . 15
Figure 2 – Three-phase transformer with two secondaries . 15
Figure 3 – Three-phase transformer with one multi-tap secondary . 16
Figure 4 – Three-phase transformer with one residual voltage winding . 16
Figure 5 – Circuit for accuracy test on a voltage transformer having a rated voltage factor of 1,5 . 17
Figure 6 – Circuit for accuracy test on a voltage transformer having a rated voltage factor of 1,9 . 17
Figure 7 – Circuit for accuracy test on the residual voltage winding of a voltage transformer having
a rated voltage factor not exceeding 1,5 . 18
Figure 8 – Circuit for accuracy test on the residual voltage winding of a voltage transformer having
a rated voltage factor not exceeding 1,9 . 18
Figure 9 – Alternative circuit for accuracy test on the residual voltage winding of a voltage
transformer having a rated voltage factor of 1,9 . 19
Figure 10 – Test circuit for partial discharge measurement of a three-phase earthed voltage
transformer. 19
Figure 11 – Test circuit for partial discharge measurement of a three-phase unearthed voltage
transformer. 20
Figure 12 – Example of a calibration circuit used during the measurement of partial discharge
of a three-phase voltage transformer . 20
Table
Table 1 – Permissible partial discharge levels for various neutral earthing system and test voltages . 7

– 5 – EN 50482:2008
1 General
1.1 Scope
This European Standard specifies the requirements and tests for new three-phase voltage transformers with
U up to 52 kV and frequencies from 15 Hz to 100 Hz, for use with electrical instruments or electrical
m
protective devices.
NOTE Single-phase voltage transformers connected in a three-phase bank are not covered in this document.
1.2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 60044-2:1999, Instrument transformers – Part 2: Inductive voltage transformers
(IEC 60044-2:1997, mod.)
EN 60270:2001, High-voltage test techniques – Partial discharge measurements (IEC 60270:2000)
HD 588.1 S1:1991, High-voltage test techniques – Part 1: General definitions and test requirements
(IEC 60060-1:1989 + corr. March 1990)
2 Definitions
Clause 2 of EN 60044-2:1999 is applicable with the following additions:
2.3 Additional definitions for three-phase inductive voltage transformers
2.3.1
three-phase voltage transformer
a voltage transformer which has three line-to-neutral primary windings the neutral point of which can be
earthed or unearthed and in which one or more of the three line-to-neutral secondary windings can be
connected for three-phase operation or residual voltage operation
2.3.2
rated output of a three-phase voltage transformer
the per phase value of the apparent power (in volt-amperes at a specified power factor) that a
three-phase voltage transformer is intended to supply to the secondary circuit, at the rated secondary
voltage and with rated per-phase burden connected to it
3 General requirements
Clause 3 of EN 60044-2:1999 applies.
4 Normal and special service conditions
Clause 4 of EN 60044-2:1999 applies.
5 Ratings
5.1 Standard values of rated voltages
5.1.1 Rated primary voltages
The standard values of rated line-to-line primary voltage of three-phase voltage transformer shall be one
of the values of nominal system voltage designated by EN 60044-2:1999.
NOTE The performance of a voltage transformer as a measuring or protection transformer is based on the rated primary voltage,
whereas the rated insulation level is based on one value of the highest voltages for equipment of EN 60071.

5.1.2 Rated secondary voltages
The rated line-to-line secondary voltage shall be chosen according to practice at the location where the
transformer is to be used. The values given below are considered standard values for three-phase
voltage transformers:
– 100 V and 110 V;
– 200 V, for extended secondary circuits.
NOTE Whenever possible, the rated transformation ratio should be a simple value. If one of the following values: 10 – 12 – 15 – 20
– 25 – 30 – 40 – 50 – 60 – 80 and their decimal multiples is used for the rated transformation ra
...

Questions, Comments and Discussion