HD 632 S2:2008
(Main)Power cables with extruded insulation and their accessories for rated voltages above 36 kV (Um = 42 kV) up to 150 kV (Um = 170 kV)
Power cables with extruded insulation and their accessories for rated voltages above 36 kV (Um = 42 kV) up to 150 kV (Um = 170 kV)
This standard specifies test requirements for power cables with extruded insulation, of the types listed in Table 1, and their accessories, of rated voltage, U, above 36 kV (Um = 42 kV) up to and including 150 kV (Um = 170 kV), for fixed installations intended for transmission and distribution systems, and for use in power generating plants and sub-stations. Depending on the design and the system conditions, additional or even fewer tests or other requirements which are not described in the Part 1 can be specified in the particular sections of Parts 3 to 11. In these parts each section is either: 1) A full tabulation showing how the particular section either agrees, or deviates from, each clause of Part 1; or 2) A reduced tabulation showing only those places where the particular section deviates from Part 1. The requirements apply to single-core cables and three-core cables with separate cores and to their accessories for usual conditions of installation and operation, but not to special cables and their accessories, such as those designed for submarine cables, for which modification to the standard tests may be necessary or special test conditions may need to be devised. This standard does not cover transition joints between cables with extruded insulation and paper insulated cables.
Starkstromkabel mit extrudierter Isolierung und ihre Garnituren für Nennspannungen über 36 kV (Um = 42 kV) bis 150 kV (Um = 170 kV)
Câbles d'énergie à isolation extrudée et leurs accessoires pour des tensions assignées supérieures à 36 kV (Um = 42 kV) et jusqu'à 150 kV (Um = 170 kV)
Elektroenergetski kabli z ekstrudirano izolacijo in njihov pribor za nazivne napetosti nad 36 kV (Um = 42 kV) in do 150 kV (Um = 170 kV)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-marec-2009
1DGRPHãþD
SIST HD 632 S1:1999
SIST HD 632 S1:1999/A1:2002
Elektroenergetski kabli z ekstrudirano izolacijo in njihov pribor za nazivne
napetosti nad 36 kV (Um = 42 kV) in do 150 kV (Um = 170 kV)
Power cables with extruded insulation and their accessories for rated voltages above 36
kV (Um = 42 kV) up to 150 kV (Um = 170 kV)
Starkstromkabel mit extrudierter Isolierung und ihre Garnituren für Nennspannungen
über 36 kV (Um = 42 kV) bis 150 kV (Um = 170 kV)
Câbles d'énergie à isolation extrudée et leurs accessoires pour des tensions assignées
supérieures à 36 kV (Um = 42 kV) et jusqu'à 150 kV (Um = 170 kV)
Ta slovenski standard je istoveten z: HD 632 S2:2008
ICS:
29.060.20 Kabli Cables
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
HARMONIZATION DOCUMENT
HD 632 S2
DOCUMENT D'HARMONISATION
November 2008
HARMONISIERUNGSDOKUMENT
ICS 29.060.20 Supersedes HD 632 S1:1998 + A1:2002
English version
Power cables with extruded insulation and their accessories
for rated voltages above 36 kV (U = 42 kV) up to 150 kV (U = 170 kV)
m m
Câbles d'énergie à isolation extrudée Starkstromkabel
et leurs accessoires mit extrudierter Isolierung
pour des tensions assignées und ihre Garnituren für Nennspannungen
supérieures à 36 kV (U = 42 kV) über 36 kV (U = 42 kV)
m m
et jusqu'à 150 kV (U = 170 kV) bis 150 kV (U = 170 kV)
m m
This Harmonization Document was approved by CENELEC on 2008-10-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this
Harmonization Document at national level.
Up-to-date lists and bibliographical references concerning such national implementations may be obtained on
application to the Central Secretariat or to any CENELEC member.
This Harmonization Document exists in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 632 S2:2008 E
Page 0-2
FOREWORD
This Harmonization Document was prepared by WG 9 of the Technical Committee CENELEC TC 20,
Electric cables.
The text of the draft was submitted to the Unique Acceptance Procedure and was approved by CENELEC
as HD 632 S2 on 2008-10-01.
This Harmonization Document supersedes HD 632 S1:1998 + corrigendum November 1998 and its
amendment A1:2002.
By comparison with the S1 version, this full revision of HD 632:
- uses IEC 60840, Ed 3, 2004, as its Part 1;
- amends Part 2 “Additional test methods” accordingly;
- revises the particular sections in Parts 3-11 inclusive in one of three ways, namely:
a) by presenting a fully updated section;
b) by indicating only those requirements that differ from, or add to, those of Part 1;
c) by withdrawing the section.
The consequential parts and particular sections are listed hereafter. In respect of the particular sections in
Parts 3 to 11, and by decision of the Technical Board (D68/047), National Committees need only
implement those sections having national applicability. The obligation remains however to announce the
full HD in public by titles and numbers, and also to withdraw any conflicting national standards.
Page numbering reflects the arrangements into Parts and Particular sections, e.g. Page 4-C-3 is page 3
of particular Section C of Part 4.
References to other HDs, ENs and international standards are given in the particular parts or sections.
By decision of the Technical Board (D81/139 extended by D104/118 & D114/076) this HD exists only in
English.
The following dates were fixed:
– latest date by which the existence of the HD
(doa) 2009-04-01
has to be announced at national level
– latest date by which the HD has to be implemented
at national level by publication of a harmonized
(dop) 2009-10-01
national standard or by endorsement
– latest date by which the national standards conflicting
(dow) 2011-10-01
with the HD have to be withdrawn
__________
Page 0-3
CONTENTS
PART 1 Test methods and requirements
PART 2 Additional test methods
PART 3 Test requirements for cables with XLPE
insulation and metallic screen and
their accessories
3-D Cables with XLPE insulation and copper
screen and their accessories (Test list 3D)
3-K Cables with XLPE insulation and copper
screen and their accessories (Test list 3K)
3-L Cables with XLPE insulation and metallic
screen and their accessories (Test list 3L)
3-M Cables with XLPE insulation, copper
screen and their accessories (Test list 3M)
3-N Cables with XLPE insulation and copper
screen and their accessories (Test list 3N)
PART 4 Test requirements for cables with XLPE
insulation, metallic screen and
metal-laminated sheath and their accessories
4-A Cables with XLPE insulation and polyolefine
compound sheath (Types 1, 2 and 3)(Test list 4A)
4-C Cables with XLPE insulation, copper or aluminium wires
screen and aluminium or copper-laminated sheath
and their accessories (Test list 4C)
4-D Cables with XLPE insulation, copper
screen and aluminium-laminated sheath
and their accessories (Test list 4D)
4-F Cables with XLPE insulation, copper
screen and aluminium-laminated sheath
and their accessories (Test list 4F)
4-G Cables with XLPE insulation and metal-
laminated screen and their accessories
(Test list 4G)
4-K Cables with XLPE insulation, copper
screen and aluminium-laminated sheath
and their accessories (Test list 4K)
4-L Cables with XLPE insulation, copper
screen and aluminium-laminated sheath
and their accessories (Test list 4L)
4-M Cables with XLPE insulation, copper
screen and aluminium-laminated sheath
and their accessories (Test list 4M)
4-O Cables with XLPE insulation, copper or
aluminium screen and copper or
aluminium laminated sheath and their
accessories (Test list 4O)
4-P Cables with XLPE insulation, copper
screen and metal-laminated sheath
and their accessories (Test list 4P)
PART 5 Test requirements for cables with XLPE
insulation and metallic sheath and
their accessories
Page 0-4
5-C Cables with XLPE insulation and lead or
lead alloy sheath, or aluminium or copper
sheath and their accessories
(Test list 5C)
5-D Cables with XLPE insulation and metallic
sheath and their accessories
(Test list 5D)
5-F Cables with XLPE insulation and lead or
lead alloy sheath and their accessories
(Test list 5F)
5-G Cables with XLPE insulation and lead
sheath and their accessories (Test list 5G)
5-H Cables with XLPE insulation and metallic
sheath and their accessories (Test list 5H)
5-K Cables with XLPE insulation and lead
sheath and their accessories (Test list 5K)
5-L Cables with XLPE insulation and metallic
sheath and their accessories (Test list 5L)
5-M Cables with XLPE insulation and metallic
sheath and their accessories (Test list 5M)
5-O Cables with XLPE insulation and metallic
sheath and their accessories (Test list 5O)
5-P Cables with XLPE insulation and lead alloy
sheath and their accessories (Test list 5P)
PART 6 Test requirements for cables with EPR
insulation and metallic screen and
their accessories
6-A Cables with HEPR insulation and polyolefine
compound sheath (Types 1, 2 and 3) (Test list 6A)
6-J Cables with HEPR insulation and copper
screen and their accessories (Test list 6J)
6-O Cables with EPR insulation and copper or
aluminium screen and their accessories
(Test list 6O)
PART 7 Test requirements for cables with EPR
insulation, metallic screen and
metal-laminated sheath and their accessories
7-O Cables with EPR insulation, copper or
aluminium screen and copper or aluminium-
laminated sheath and their accessories
(Test list 7O)
Page 0-5
PART 8 Test requirements for cables with EPR
insulation and metallic sheath and
their accessories
8-J Cables with HEPR insulation and metallic
sheath and their accessories (Test list 8J)
8-O Cables with EPR insulation and metallic
sheath and their accessories (Test list 8O)
PART 9 (Spare)
PART 10 Test requirements for cables with PE or
HDPE insulation, metallic screen and
metal-laminated sheath and their accessories
10-G Cables with PE or HDPE insulation and metal-
laminated screen and their accessories
(Test list 10G)
PART 11 Test requirements for cables with PE or
HDPE insulation and metallic sheath and
their accessories
11-G Cables with PE or HDPE insulation and lead
sheath and their accessories (Test list 11G)
__________
Page 0-6
– Blank Page –
Page 1-1
PART 1
CONTENTS
1 Scope . 4
2 Normative re f e r enc es . 4
3 Definitions . 5
3.1 Definitions of dimensional values (thicknesses, cross-sections, etc.) . 5
3.2 Definitions concerning the tests . 5
4 Voltage designations and materials . 6
4.1 Rated voltages . 6
4.2 Cable insulating m aterials . 6
4.3 Cable oversheathing materials . 6
5 Precautions against water penetration in cables . 6
6 Cable characteristics . 7
7 Accessory characteristics. 7
8 Test conditions . 8
8.1 Ambient temperature . 8
8.2 Frequency and waveform of power frequency test voltages . 8
8.3 Waveform of lightning impulse test voltages . 8
8.4 Relationship of test voltages to rated voltages . 8
8.5 Determination of the cable conductor temperature . 8
9 Routine tests on cables and on the main insulation of prefabricated accessories . 8
9.1 General . 8
9.2 Partial discharge test . 9
9.3 Voltage test . 9
9.4 Electrical test on oversheath of the cable . 9
10 Sample tests on cables . 9
10.1 General . 9
10.2 Frequency of tests . 10
10.3 Repetition of tests . 10
10.4 Conductor examination . 10
10.5 Measurement of electrical resistance of conductor and metallic screen . 10
10.6 Measurement of thickness of cable insulation and oversheath . 10
10.7 Measurement of thickness of metallic sheath . 11
10.8 Measurement of diameter . 12
10.9 Hot set test for XLPE, EPR and HEPR insulations . 12
10.10 Measurement of capacitance . 13
10.11 Measurement of density of HDPE insulation . 13
11 Sample tests on accessories . 13
11.1 Tests on components . 13
11.2 Tests on complete accessory .
...
Questions, Comments and Discussion