Abstract

IEC 62590-2-2:2026 describes functions and working principles, specifies requirements, interfaces, and test methods for controlled converters for DC electric traction power supply systems: – AC/DC converters: • rectifiers, • inverters, • combinations. – DC converters. The purpose of the converters can be a power connection to other power networks or energy storages. The common characteristic of this equipment is the possibility to influence the power flow in the DC electric traction power supply system. The converters can be: – line-commutated; – self-commutated. This document applies to fixed installations of the following electric traction systems: – railway networks, – metropolitan transport networks including metros, tramways, trolleybuses and fully automated transport systems, magnetic levitated transport systems, and electric road systems.

Status
Published
Publication Date
13-Aug-2026
Current Stage
6060 - Document made available - Publishing
Start Date
14-Aug-2026
Due Date
28-Mar-2024
Completion Date
28-Mar-2024

Buy Documents

Standard

EN IEC 62590-2-2:2026 - BARVE

English language (49 pages)
Preview
Preview
e-Library read for
×1 day

EN IEC 62590-2-2:2026 is a CENELEC European Standard published under IEC 62590-2-2 for railway fixed installations. It specifies functions, working principles, requirements, interfaces and test methods for controlled converters used in DC electric traction power supply systems, including AC/DC converters and DC converters. It is intended for designers, manufacturers, users and testers of railway, metro and other fixed traction systems.

What does EN IEC 62590-2-2:2026 specify?

EN IEC 62590-2-2:2026 covers controlled converters for DC electric traction power supply systems and the way they are described, integrated and tested. The document applies to fixed installations in railway networks and metropolitan transport networks, including metros, tramways, trolleybuses, fully automated transport systems, magnetic levitated transport systems and electric road systems.

The standard is organized into:

  • Scope and normative references
  • Terms, definitions, symbols and abbreviated terms
  • System configurations
  • Design and integration
  • Performance requirements
  • Tests
  • Informative annexes A to C
AnnexWhat it covers
Annex APower flow control strategies and DC-side coordination examples
Annex BCalculation factors for voltage relationships
Annex CTest circuits for load tests

What are the key requirements of EN IEC 62590-2-2:2026?

System configuration and working principle

EN IEC 62590-2-2:2026 defines controlled converters as equipment that can influence power flow in the DC traction supply system. It covers line-commutated and self-commutated converters, and both rectifier and inverter functions.

In practice, this matters because the user must choose the converter type according to the intended power direction - from a 3AC network to the DC traction system, from the DC system back to the 3AC network, or between DC systems and storage.

AC/DC converters, reversible converters and DC converters

EN IEC 62590-2-2:2026 distinguishes:

  • rectifiers for power flow from 3AC to DC
  • inverters for power flow from DC to 3AC
  • reversible converters for bidirectional exchange
  • DC converters for connection to another DC system or to storage

The document also describes combinations of rectifier and inverter functions, including arrangements with separate transformers, combined transformers, taps, or a reversible valve device assembly. For a project team, this section is the basis for selecting the topology and deciding which parts are shared and which are independent.

Design, integration and user-defined data

EN IEC 62590-2-2:2026 requires the user to define the operating conditions and installation data needed for design. Clause 5.3 and 5.4 list the key information to be specified, such as nominal DC voltage, network conditions, rated current, duty class or load cycle, insulation requirements, cooling method, efficiency, audible sound, IP code, dimensions, earthing and transport details.

This matters in procurement and engineering because the manufacturer uses these values to size the transformer, valve assembly, protection and enclosure, and to verify compatibility with the traction network and the site.

Protection and short-time withstand current

EN IEC 62590-2-2:2026 requires the converter to detect internal faults and react automatically. It also requires reaction to external faults, and the manufacturer has to state the external protection equipment and its characteristics.

For short-circuit behavior, the converter shall withstand a full DC short-circuit after continuous operation at rated current for 150 ms without loss of function, unless a faster protection device justifies a shorter time. For a thyristor inverter, commutation failure is a specific case and the equipment has to withstand the resulting current without damage.

Ratings, marking and losses

EN IEC 62590-2-2:2026 requires rating plate marking for assembled units and separately delivered assemblies. The marking includes the manufacturer, equipment type, standard designation, serial number, nominal DC voltage, rated insulation voltage, input and output ratings, rated direct current, duty class or load cycle, short-time withstand current and cooling method.

The document also requires loss values to cover the valve device assemblies, smoothing equipment, filter equipment and auxiliary equipment. Losses have to be stated at 0 %, 50 % and 100 % of rated direct current, and at overload points defined by the user. That helps buyers compare designs and estimate operating efficiency and thermal loading.

Test methods and type/routine testing

EN IEC 62590-2-2:2026 sets out a test program in Clause 7, with mandatory and optional tests listed in Table 3. The tests cover visual inspection, accessory and auxiliary components, insulation, operational sequence, protective functions, control functions, light-load functional tests, load tests, temperature rise, short-time withstand current, power loss, EMC, harmonic measurements, power factor measurement and mechanical tests.

This is important because acceptance can be based on a mix of factory tests, site checks, and calculations or simulation where full-scale testing is impractical. Annex C gives example test circuits for load tests.

What terms does EN IEC 62590-2-2:2026 define?

  • rated current - The DC current a controlled converter is designed for on the traction supply side, and other rating values are derived from it.
  • rated DC power - The rated current multiplied by the nominal DC voltage.
  • reversible converter - A converter in which power flow can move in both directions.
  • trigger delay angle - The angular delay between the reference instant and the trigger pulse in phase control.
  • commutation failure - The failure to transfer current from one conducting arm to the next arm.
  • switched valve device - A controllable valve device that can be turned on and off by a control signal.
  • ESS - Energy storage system, used here for stationary storage connected to DC traction systems.
  • IGBT - Insulated gate bipolar transistor, one of the common switched valve devices mentioned for self-commutated converters.

Who uses EN IEC 62590-2-2:2026?

EN IEC 62590-2-2:2026 is used by railway power engineers, traction system designers, converter manufacturers, integrators, operators and test laboratories. It is relevant wherever fixed traction installations need controlled power conversion between 3AC networks, DC traction systems and energy storage.

It supports tasks such as:

  • selecting converter topology for rectification, inversion or bidirectional operation
  • defining project requirements for voltage, current, insulation, cooling and enclosure
  • coordinating converter behavior with transformers, protection and network conditions
  • planning type tests, routine tests and site acceptance checks
  • documenting ratings, losses, harmonics and protection data for procurement and operation

What changed in EN IEC 62590-2-2:2026 from the previous edition?

EN IEC 62590-2-2:2026 is the first edition of this part and the foreword states that it partially cancels and replaces IEC 62589 and IEC 62590. The foreword also identifies it as a technical revision.

Which standards are used with EN IEC 62590-2-2:2026?

EN IEC 62590-2-2:2026 cites these normative references:

  • IEC 60071-1 - used for insulation co-ordination principles and rules
  • IEC 60529 - used for the IP Code and degree of protection of enclosures
  • IEC 62590-1:2025 - provides the general requirements for electronic power converters for fixed installations
  • IEC 62695 - applies to traction transformers
  • IEC 62236-5 - applies to EMC emission and immunity for fixed power supply installations and apparatus

The document also uses companion parts in its technical content:

  • IEC 62590-2-1:2025 - used for uncontrolled rectifiers and for the uncontrolled part of reversible converters, if any
  • IEC 62924 - used for reversible converters for stationary energy storage systems in DC traction applications

What does the EN IEC 62590-2-2:2026 document contain?

EN IEC 62590-2-2:2026 contains configuration diagrams, symbol tables, coordinate examples and test arrangements that support design and verification. Figure 1 to Figure 7 show the main converter arrangements, including AC/DC converter topologies and DC converter configurations.

Annex A gives examples of power flow control strategies, including characteristic curves and circulating-current-related coordination cases. Annex B provides calculation factors for voltage relationships between transformer no-load voltage and DC voltage. Annex C shows test circuits that can be used for load tests, temperature-rise work and power-loss determination.

Relations

Effective Date
28-Jul-2026
Effective Date
28-Jul-2026

Buy Documents

Standard

EN IEC 62590-2-2:2026 - BARVE

English language (49 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

EN IEC 62590-2-2:2026 is a standard published by CLC. Its full title is "Railway applications - Electronic power converters for fixed installations - Part 2-2: DC Traction applications - Controlled converters". This standard covers: IEC 62590-2-2:2026 describes functions and working principles, specifies requirements, interfaces, and test methods for controlled converters for DC electric traction power supply systems: – AC/DC converters: • rectifiers, • inverters, • combinations. – DC converters. The purpose of the converters can be a power connection to other power networks or energy storages. The common characteristic of this equipment is the possibility to influence the power flow in the DC electric traction power supply system. The converters can be: – line-commutated; – self-commutated. This document applies to fixed installations of the following electric traction systems: – railway networks, – metropolitan transport networks including metros, tramways, trolleybuses and fully automated transport systems, magnetic levitated transport systems, and electric road systems.

IEC 62590-2-2:2026 describes functions and working principles, specifies requirements, interfaces, and test methods for controlled converters for DC electric traction power supply systems: – AC/DC converters: • rectifiers, • inverters, • combinations. – DC converters. The purpose of the converters can be a power connection to other power networks or energy storages. The common characteristic of this equipment is the possibility to influence the power flow in the DC electric traction power supply system. The converters can be: – line-commutated; – self-commutated. This document applies to fixed installations of the following electric traction systems: – railway networks, – metropolitan transport networks including metros, tramways, trolleybuses and fully automated transport systems, magnetic levitated transport systems, and electric road systems.

EN IEC 62590-2-2:2026 is classified under the following ICS (International Classification for Standards) categories: 29.280 - Electric traction equipment. The ICS classification helps identify the subject area and facilitates finding related standards.

EN IEC 62590-2-2:2026 has the following relationships with other standards: It is inter standard links to EN IEC 62590-1:2025, EN IEC 60071-1:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN IEC 62590-2-2:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions, symbols, and abbreviated terms
  • 3.1 Terms and definitions
  • 3.1.1.1 rated current
  • 3.1.1.2 rated DC power
  • 3.1.1.3 reversible converter
  • 3.1.2.1 trigger delay angle
  • 3.1.2.2 commutation failure
  • 3.1.3.1 switched valve device
  • 3.1.3.2 free-wheeling diode
  • 3.1.3.3 buck converter
  • 3.2 Graphical symbols
  • 3.3 Abbreviated terms
  • 4 System configurations
  • 4.1 General
  • 4.2 Purpose of converters
  • 4.3 Basic characteristic of converters
  • 4.4 Interface to 3AC power network
  • 4.5 Interface to DC electric traction power supply system
  • 5 Design and integration
  • 5.1 System integration and coordination requirements
  • 5.2 Load requirements
  • 5.3 Data to be defined by the user's specification
  • 5.4 Mechanical requirements defined by the user's specification
  • 6 Performance requirements
  • 6.1 General
  • 6.2 Protection
  • 6.3 Short-time withstand current
  • 6.4 Rating plate
  • 6.5 Main circuit terminals marking
  • 6.6 Losses
  • 7 Tests
  • 7.1 General
  • 7.2 Test specifications
  • Annex A
  • Annex B
  • Annex C
  • Bibliography

INTRODUCTION Semiconductor converters for traction power supply differ from other electronic power converters for industrial use due to special electrical service conditions and due to the large range of load variation and the particular characteristics of the load. Controlled rectifiers supply a DC traction network from a three-phase power network using controllable semiconductor valves. Inverters allow the recuperation of power from a DC traction network into a three-phase power network. Reversible converters combine the functions of a rectifier and an inverter.

DC converters are self-commutated converters for connecting the DC traction network to other DC networks or storage devices.

SIST EN IEC 62590-2-2:2026

1 Scope

This part of IEC 62590 describes functions and working principles, specifies requirements, interfaces, and test methods for controlled converters for DC electric traction power supply systems:

  • AC/DC converters:
  • rectifiers,
  • inverters,
  • combinations.
  • DC converters.

The purpose of the converters can be a power connection to other power networks or energy storages.

The common characteristic of this equipment is the possibility to influence the power flow in the DC electric traction power supply system. The converters can be:

  • line-commutated;
  • self-commutated.

This document applies to fixed installations of the following electric traction systems:

  • railway networks,
  • metropolitan transport networks including metros, tramways, trolleybuses and fully automated transport systems, magnetic levitated transport systems, and electric road systems.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60071-1, Insulation co-ordination - Part 1: Definitions, principles and rules IEC 60529, Degrees of protection provided by enclosures (IP code) IEC 62590-1:2025, Railway applications - Electronic power converters for fixed installations - Part 1: General requirements IEC 62695, Railway applications - Fixed installations - Traction transformers IEC 62236-5, Railway applications - Electromagnetic compatibility - Part 5: Emission and immunity of fixed power supply installations and apparatus

SIST EN IEC 62590-2-2:2026

3 Terms, definitions, symbols, and abbreviated terms

For the purposes of this document, the terms and definitions given in IEC 62590-1 and the following apply.

ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

3.1 Terms and definitions

3.1.1 Semiconductor devices and combinations

3.1.1.1 rated current

I Nd <of a controlled converter> value of a DC current a controlled converter is designed for, referring to the DC electric traction power supply system Note 1 to entry: All rated values of the components are derived from this value. Note 2 to entry: A converter can have a rated continuous current and rated currents in conjunction with a duty class.

3.1.1.2 rated DC power

<of a controlled converter> rated current multiplied with nominal DC voltage Note 1 to entry: This value refers to DC electric traction power supply system side.

3.1.1.3 reversible converter

converter in which the direction of the power flow is reversible [SOURCE IEC 60050-551:1998, 551-12-37, modified – Figure 1 has been omitted.]

3.1.2 Line-commutated converters

3.1.2.1 trigger delay angle

time expressed in angular measure by which the trigger pulse is delayed with respect to the reference instant in the case of phase control Note 1 to entry: With line, machine or load commutated converters the reference instant is the zero crossing instant of the commutating voltage. With AC controllers it is the zero crossing instant of the supply voltage. For AC controllers with inductive loads the trigger delay angle is the sum of the phase shift and the current delay angle. [SOURCE: IEC 60050-551:1998, 551-16-33, modified – In the definition, “the” has been deleted.]

3.1.2.2 commutation failure

failure to commutate the current from a conducting arm to the succeeding arm [SOURCE: IEC 60050-551:1998, 551-16-59, modified – In the definition, “a” has been deleted]

SIST EN IEC 62590-2-2:2026

3.1.3 Self-commutated converters

3.1.3.1 switched valve device

controllable valve device which can be turned on and off by a control signal [SOURCE: IEC 60050-551:1998, 551-14-08, modified – In the definition, “a” has been deleted, "may" has been replaced with "can".]

3.1.3.2 free-wheeling diode

diode parallel to a switched valve device in reverse direction fulfilling the purpose of a freewheeling arm

3.1.3.3 buck converter

direct DC converter providing an output voltage which is lower than the input voltage [SOURCE: IEC 60050-551:1998, 551-12-33]

3.2 Graphical symbols

Table 1 lists all symbols used in this document. These symbols are based on symbols registered in IEC 60617.

Table 1 – Graphical symbols Symbol Explanation AC/DC converter with optional indication of power flow direction SOURCE: IEC 60617-S00213:2001-07; 3~ 3~ 3~ IEC 60617-S01402:2001-09; IEC 60617-S01403:2001-09 DC DC DC

IEC 60617-S00099:2001-07; IEC 60617-S00100:2001-07; IEC 60617-S01407:2001-10.

DC converter DC SOURCE: IEC 60617-S00213:2001-07; DC IEC 60617-S01402:2001-09.

DC converter with isolation between 2 electrical circuits DC SOURCE: IEC 60617-S00213:2001-07; DC IEC 60617-S01402:2001-09;

IEC 60617-S01407:2001-10 diode rectifier (valve device) assembly SOURCE: IEC 60617-S00641:2001-07; Rec

SIST EN IEC 62590-2-2:2026

Symbol Explanation IGBT converter (valve device) assembly SOURCE: IEC 60617-S00616:2001-07; IEC 60617 S00621:2001-07; IEC 60617-S00624:2001-07;

IEC 60617-S00641:2001-07.

thyristor converter (valve device) assembly SOURCE: IEC 60617-S00654:2001-07.

Rec

Transformer with two windings SOURCE: IEC 60617-S00841:2001-07.

Transformer with three windings SOURCE: IEC 60617-S00844:2001-07.

Group of connections

SOURCE: IEC 60617-S00002:2001-07.

3.3 Abbreviated terms

3AC three phase alternating current AC alternating current ACTB apparatus for connecting the ESU to the DC bus DC direct current ESS energy storage system ESU energy storage unit IGBT insulated gate bipolar transistor U power frequency test voltage for power frequency withstand voltage test a U nominal DC voltage dN U no load transformer voltage, valve side v0

4 System configurations

4.1 General

The main purpose of controlled electronic power converters for DC electric traction power supply systems is to establish an intended power flow. The power can flow from a 3AC power network to the DC electric traction system or vice versa. This can also be a bidirectional power flow to energy storages or other equipment using regenerated power.

SIST EN IEC 62590-2-2:2026

4.2 Purpose of converters

4.2.1 AC/DC converters
4.2.1.1 General

The AC/DC converters connect a 3AC power network with a DC electric traction power supply system as shown in Figure 1. Requirements from both networks shall be applied, see 5.3.

Figure 1 – General arrangement of AC/DC converters

4.2.1.2 Rectifiers

The purpose of rectifiers is to have a power flow from the 3AC power network to the DC electric traction power supply system.

Controlled rectifiers operate on an adjustable characteristic curve in the current versus voltage plane. This characteristic can be adjustable. Examples are given in Annex A. Limits can be included.

Controlled rectifiers can be line-commutated or self-commutated. A suitable duty class should be chosen from IEC 62590-1:2025, 5.7.2.

4.2.1.3 Inverters

The purpose of inverters is to enable a power flow from the DC electric traction power supply system to the 3AC power network to improve the energy efficiency of the railway system. Inverters operate on an adjustable characteristic curve in the current versus voltage plane. This characteristic can be adjustable. Examples are given in Annex A. Limits can be included. Inverters can be line-commutated or self-commutated.

The definition of a load cycle is appropriate in most cases, see IEC 62590-1:2025, 5.7.3.

4.2.1.4 Reversible converters

The purpose of the combination of a rectifier and an inverter is to enable a bidirectional power exchange between a 3AC power network and the DC electric traction power supply system. Reversible converters operate on an adjustable characteristic curve in the current versus voltage plane. This characteristic can be adjustable. Examples are given in Annex A. Limits can be included.

SIST EN IEC 62590-2-2:2026

There is a broad variety of combinations using line-commutated and self-commutated converters, see Table 2.

Figure 2 to Figure 5 show various possible combinations of rectifiers and inverters that can be installed in a reversible substation. They can share the same transformer, the same control, or the same filter.

Commonly used parts of the reversible converter are subject to a combined load requirement. For the rectifier part a suitable duty class should be chosen. For the inverter part a suitable load cycle or a suitable duty class should be chosen according to the application, see Figure 2 to Figure 5. This can result in an asymmetric load for 3 winding transformers in special cases shown in Figure 3 and Figure 4.

IEC 62590-2-1 applies to the uncontrolled part of the reversible converter, if any, and this document applies to the inverter part.

Table 2 – Rectifiers, inverters and combinations Rectifier Inverter Reversible converter 3~ 3~ 3~ General symbol DC DC DC

Inv Rec Rec Inv Examples of associated Rec Inv transformer and valve device assembly Rec Inv

Rec Inv Rec Inv Rec/Inv

NOTE 1 The symbols represent typical valve devices used in the respective application. NOTE 2 "Rec" indicates the use of a rectifier and "Inv" the use of an inverter.

SIST EN IEC 62590-2-2:2026

Figure 2 – Connection with separate transformers A reversible converter configuration can consist of a separated rectifier and inverter. Figure 2 shows such a configuration. Both can be connected to the same 3AC power network or to different 3AC power networks. The function and design are as independent as possible.

NOTE Dashed symbols represent optional components to achieve symmetry. Figure 3 – Connection with combined transformer A reversible converter configuration can share the same main transformer. Such a configuration is shown in Figure 3. In this case an additional transformer is used to adapt the inverter 3AC voltage to the rectifier 3AC voltage. If a three-winding transformer with two traction side windings is used, a single inverter or multiple inverters can be connected to one or both windings equally. The main transformer shall be designed for both power flow directions.

SIST EN IEC 62590-2-2:2026

NOTE Dashed symbols represent optional components to achieve symmetry. Figure 4 – Connection with combined transformer with taps Figure 4 shows a configuration with a combined transformer with taps. No additional transformer is used for the adaptation of the inverter and rectifier voltage.

Figure 5 – Converter with reversible valve device assembly Figure 5 shows the configuration of a reversible converter using a unique all-in-one reversible valve device assembly associated with a unique transformer. In this case, the control for both flow directions is integrated.

More than one traction side transformer winding can be used.

4.2.1.5 Reversible AC/DC converters for energy storages

The purpose of a reversible converter for an energy storage is to connect the DC electric traction power supply system to an energy storage unit. In this case the ESU is a rotating machine. IEC 62924 covers reversible converters for energy storage. The converter fulfils the function of the ACTB.

The configuration is shown in Figure 6.

SIST EN IEC 62590-2-2:2026

Load requirements are defined in IEC 62924.

NOTE DC bus means the DC traction power supply system in the addressed use case. Figure 6 – Common system configuration of stationary ESS

4.2.2 DC converters

A DC converter connects the DC electric traction power supply system to another DC system. This can be for example a capacitor or battery for energy storage purposes or a DC distribution system. DC converters can also be used for controlling a wayside braking resistor for consuming power of braking rolling stock.

NOTE A controlled wayside braking resistor is often called an automatic assured receptivity unit, or a braking resistor unit.

Figure 7 shows the basic configuration of DC converters.

Figure 7 – Configurations of DC converters Both sides of a non-isolating DC converter are part of the DC electric traction power supply system.

An isolating DC converter separates the DC electric traction power supply system from another system with different insulation coordination.

IEC 62924 covers energy storage. The converter is fulfilling the function of an ACTB. See Figure 6.

For energy storage purpose load requirements are defined in IEC 62924. For any other purpose a load class should be selected.

SIST EN IEC 62590-2-2:2026

4.3 Basic characteristic of converters

4.3.1 General

Controlled converters have different basic working principles. A coordination between the transformer and the valve device assembly is required. In most cases the transformer is part of a filter circuit. The choice of the transformer main values has a major influence on the power quality of the connected networks.

All controlled converters use voltage and current sensors. Their signals are processed and used to create firing signals for the semiconductors. For all converters connected to a 3AC power network, a synchronization with this network is necessary.

The user shall specify the complete operating range, together with the tolerance of the 3AC network voltage. This information shall be used by the manufacturer to design the transformer and the valve device assembly.

4.3.2 Line-commutated converters
4.3.2.1 General

The basic behaviour of line-commutated converters is broadly described in IEC 60146-1-1. An application guide is IEC/TR 60146-1-2.

For basic connections, 6-pulse bridges or combinations thereof are used. The most common types of line-commutated converters are those with 12-pulse connections. The basic connections and calculation factors for uncontrolled operation can be taken from IEC 62590-2-1:2025, Table 1.

NOTE The ratio between the direct voltage drop and the impedance voltage specified in IEC 60146-1-1:2024, Table 10 have a slightly different meaning.

The DC voltage can be controlled by varying the trigger delay angle. A voltage versus current characteristic can be established.

4.3.2.2 Line-commutated rectifiers

The transformer’s no-load voltage shall be chosen according to the required range of operation. The transformer’s no-load voltage for a controlled rectifier is higher than for an uncontrolled diode rectifier. The trigger delay angle reduces the DC voltage as described in IEC TR 60146-1-2.

NOTE For the purposes of the rectifier, the trigger delay angle is in the range clearly below 90°. The trigger delay angle depends on the point of operation and is usually between 60° and 5°. For practical reasons, a trigger delay angle of 0° is not achievable as thyristors can only be switched on with a forward voltage. The no-load transformer voltage is higher than the one for a comparable diode rectifier. With a higher no-load voltage:

  • the control range increases;
  • the reactive power at the 3AC side increases;
  • the DC harmonic content increases;
  • the transformer power for the same traction load is higher;
  • the 3AC harmonic content is higher at low current.

SIST EN IEC 62590-2-2:2026

4.3.2.3 Line-commutated inverters

The transformer’s no-load voltage shall be chosen according to the required range of operation. NOTE For inverters the trigger delay angle is higher than 90° and the cathodes are connected to the negative polarity of the supply voltage. A practical range is between 130° and 165° including some reserve. The expected worst-case operational situation should not lead to a commutation failure. This worst case consists of the maximum operational DC voltage at the maximum DC current in combination with the minimum expected operational 3AC power network voltage. A commutation failure is a short-circuit and leads to an interruption of the inverter operation. Only intended protection devices shall operate.

A commutation failure shall not lead to any damage of the inverter by design. Only the foreseen protection devices should be reset. Neighbouring rectifiers should not be affected to guarantee the availability of the power supply function.

The maximum allowable trigger delay angle depends on:

  • the recovery time of the thyristor;
  • the overlap angle as a function of the current;
  • the commutation inductance provided by the transformer and the short-circuit impedance;
  • the 3AC power network voltage;
  • the transformer's rated no-load voltage;
  • the DC operating voltage.

The choice of a proper traction side no-load voltage for the transformer is important for the overall behaviour of the inverter. With a higher no-load voltage:

  • the probability of a commutation failure decreases;
  • the DC harmonic content is higher;
  • the reactive power increases;
  • the transformer power for the same current is higher.

In most cases a DC side inductor should be used to improve the operational behaviour in case of a commutation failure and to reduce the DC harmonic current.

4.3.3 Self-commutated converters
4.3.3.1 General

Self-commutated converters are described in IEC 60146-2.

Self-commutated converters are characterized using switched valve devices that can be switched on and off. The most commonly used valves are transistors and turn-off thyristors, both with an antiparallel free-wheeling diode.

Self-commutated converters contain a major capacitor smoothing the DC side voltage. Together with other components, they form a filter. Converters can be pre-charged in order to avoid current surges.

SIST EN IEC 62590-2-2:2026

4.3.3.2 AC/DC converters

A broad variety of connections are used in AC/DC converters.

The common main characteristics of self-commutated AC/DC converters are as follows. - Use of free-wheeling diodes. The free-wheeling diodes are forming an uncontrolled rectifier. The DC voltage is higher than the amplitude of the 3AC transformer traction side voltage. - There is no fixed ratio between the 3AC transformer traction side voltage and the DC voltage. The ratio is determined by pulse patterns and modulation methods. Safety margins are used for the adaption to all points of operation.

  • The converters can be operated in both directions even if not intended in some applications.
  • The transformer is used for voltage adaption and electric isolation of the two networks
  • The impedance of the transformer is used for power flow control and is part of a filter.
  • Harmonic orders are specific for every converter type, on the DC side as well as on the AC side.
  • A major capacitance on the DC side is required for operation. Pulse frequency, modulation method and number of parallel units define the harmonic orders on the 3AC power network side as well as on the DC side. Coordination is recommended to avoid frequencies used by the signalling system as well as resonance frequencies as far as they are identified.

...