IEC 61009-1:2010/AMD2:2013
(Amendment)Amendment 2 - Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) - Part 1: General rules
Amendment 2 - Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) - Part 1: General rules
The contents of the corrigendum of January 2014 have been included in this copy.
Amendement 2 - Interrupteurs automatiques à courant différentiel résiduel avec dispositif de protection contre les surintensités incorporé pour usages domestiques et analogues (DD) - Partie 1: Règles générales
Le contenu du corrigendum de janvier 2014 a été pris en considération dans cet exemplaire.
General Information
Relations
Standards Content (Sample)
IEC 61009-1 ®
Edition 3.0 2013-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Residual current operated circuit-breakers with integral overcurrent protection
for household and similar uses (RCBOs) –
Part 1: General rules
Interrupteurs automatiques à courant différentiel résiduel avec dispositif de
protection contre les surintensités incorporé pour usages domestiques et
analogues (DD) –
Partie 1: Règles générales
IEC 61009-1:2010/A2:2013
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les
microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.
IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
Useful links:
IEC publications search - www.iec.ch/searchpub Electropedia - www.electropedia.org
The advanced search enables you to find IEC publications The world's leading online dictionary of electronic and
by a variety of criteria (reference number, text, technical electrical terms containing more than 30 000 terms and
committee,…). definitions in English and French, with equivalent terms in
It also gives information on projects, replaced and additional languages. Also known as the International
withdrawn publications. Electrotechnical Vocabulary (IEV) on-line.
IEC Just Published - webstore.iec.ch/justpublished Customer Service Centre - webstore.iec.ch/csc
Stay up to date on all new IEC publications. Just Published If you wish to give us your feedback on this publication
details all new publications released. Available on-line and or need further assistance, please contact the
also once a month by email. Customer Service Centre: csc@iec.ch.
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
Liens utiles:
Recherche de publications CEI - www.iec.ch/searchpub Electropedia - www.electropedia.org
La recherche avancée vous permet de trouver des Le premier dictionnaire en ligne au monde de termes
publications CEI en utilisant différents critères (numéro de électroniques et électriques. Il contient plus de 30 000
référence, texte, comité d’études,…). termes et définitions en anglais et en français, ainsi que
Elle donne aussi des informations sur les projets et les les termes équivalents dans les langues additionnelles.
publications remplacées ou retirées. Egalement appelé Vocabulaire Electrotechnique
International (VEI) en ligne.
Just Published CEI - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications de la CEI.
Just Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur
Disponible en ligne et aussi une fois par mois par email. cette publication ou si vous avez des questions
contactez-nous: csc@iec.ch.
IEC 61009-1 ®
Edition 3.0 2013-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Residual current operated circuit-breakers with integral overcurrent protection
for household and similar uses (RCBOs) –
Part 1: General rules
Interrupteurs automatiques à courant différentiel résiduel avec dispositif de
protection contre les surintensités incorporé pour usages domestiques et
analogues (DD) –
Partie 1: Règles générales
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX G
ICS 29.120.50 ISBN 978-2-8322-1065-9
– 2 – 61009-1 Amend. 2 © IEC:2013
FOREWORD
This amendment has been prepared by subcommittee 23E: Circuit-breakers and similar
equipment for household use, of IEC technical committee 23: Electrical accessories.
The text of this amendment is based on the following documents:
FDIS Report on voting
23E/796/FDIS 23E/820/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of January 2014 have been included in this copy.
_____________
8.1.3 Clearances and creepage distances (see also Annex B)
Replace the third paragraph of this subclause, and the modifications brought to it by
Amendment 1, as follows:
The clearances of items 2 and 4 (except accessible surface after installation, see Note 1) may
be reduced provided that the measured clearances are not shorter than the minimum allowed
in IEC 60664-1 for homogenous field conditions.
Add the following new note after the third paragraph and renumber the existing notes of this
subclause, introduced by Amendment 1, accordingly:
NOTE 1 Accessible surface after installation means any surface accessible by the user when the RCD is installed
according to the manufacturer's instructions. The test finger can be applied to determine whether a surface is
accessible or not.
8.5 Operating characteristics
Delete "and 9.21" from the existing text
8.15 Behaviour of RCBOs in case of earth fault currents comprising a d.c. component
Replace the second paragraph as follows:
Compliance is checked by the tests of 9.9.3.
Table 12 – List of type tests
Delete the following item:
61009-1 Amend. 2 © IEC:2013 – 3 –
– Behaviour of RCBOs in case of an earth fault current comprising a d.c. component
9.21
9.7.2 Insulation resistance of the main circuit
Replace the existing text in item c) with the following text:
c) with the RCBO in the closed position, between all poles connected together and the frame
including a metal foil or part in contact with the outer surface of the housing of insulating
material but with the terminal areas kept completely free to avoid flashover between
terminals and the metal foil;
Replace 9.9.1 and the modifications brought to it by Amendment 1 by the following:
9.9.1 Verification of the operating characteristics under residual current conditions
9.9.1.1 Test circuit and test procedure
The RCBO is installed as for normal use.
The test circuit shall be of negligible inductance. For tests according to 9.9.1.2, the test circuit
shall correspond to Figure 4. For tests according to 9.9.1.3, the test circuit shall correspond to
Figure 5 or Figure 6, as applicable.
The instruments for the measurement of the residual current shall display (or allow to
determine) the true r.m.s. value.
NOTE The information for instrument measurement is available at the following CTL webserver:
Unless otherwise specified, the tests are performed with no load at the reference temperature
of 20 °C ± 5 °C.
The RCBO shall perform the tests of 9.9.1.2, 9.9.1.3 and 9.9.1.4, as applicable. Each test is
made on one pole only, taken at random, with five measurements, unless otherwise specified.
For RCBOs having more than one rated frequency, the tests shall be carried out at the lowest
and highest frequency, except for test in 9.9.1.2 e), where verification is performed at only
one frequency.
For RCBOs having multiple settings of residual operating current, the tests shall be made for
each setting.
9.9.1.2 Tests for all RCBOs
The test conditions according to 9.9.1.1 apply to all RCBOs.
a) Verification of correct operation in case of a steady increase of the residual current.
and S and the RCBO being in the closed position, the residual
The test switches S
1 2
current is steadily increased, starting from a value not higher than 0,2 I , trying to attain
∆n
the value of I within 30 s, the tripping current being measured each time.
∆n
All five measured values shall be situated between I and I .
∆no ∆n
b) Verification of correct operation on closing on a residual current
The test circuit being calibrated at the value of the rated residual operating current I and
∆n
the test switches S and S being closed, the RCBO is closed so as to simulate service
1 2
conditions as closely as possible. The break time is measured five times. No measurement
shall exceed the limiting value specified for I in Table 2, according to the type of RCBO.
∆n
c) Verification of correct operation in case of sudden appearance of residual current
– 4 – 61009-1 Amend. 2 © IEC:2013
1) All types
The test circuit being successively calibrated at each of the values of residual current
specified in Table 2, the test switch S and the RCBO being in the closed position, the
test voltage is suddenly established by closing the test switch S .
The RCBO shall trip during each test.
Five measurements of the break time are made at each value of residual current.
No value shall exceed the relevant specified limiting value given in Table 2.
2) Additional test for type S
The test circuit being successively calibrated at each of the values of residual current
specified in Table 2, the test switch S and the RCBO being in the closed position, the
residual current is suddenly established by closing the test switch S for periods
corresponding to the relevant minimum non-actuating times, with a tolerance of %.
− 5
Each application of residual current shall be separated from the previous one by an
interval of at least 1 min.
The RCBO shall not trip during any of the tests.
d) Verification of correct operation in case of sudden appearance of residual currents
between 5 I and 500 A
∆n
The test circuit is calibrated at any two values of the residual current chosen at random
within the range 5 A to 200 A, among the following list 5 A, 10 A, 20 A, 50 A, 100 A,
200 A.
NOTE In Australia the measurement of the break time is made at 5 A, 10 A, 20 A, 50 A, 100 A, 200 A.
The test switch S and the RCBO being in the closed position, the residual current is
suddenly established by closing the test switch S .
The RCBO shall trip during each test. The break time shall not exceed the times given in
Table 2.
The test is made once for each value of residual current on one pole only, taken at
random.
e) Verification of correct operation with load
The tests of 9.9.1.2 b) and 9.9.1.2 c) are repeated, the pole under test and one other pole
of the RCCB being loaded with rated current, this current being established shortly before
the test.
For the test of 9.9.1.2 c), the switch S and the RCBO are in closed position. The residual
current is established by closing S .
f) Tests at the temperature limits
The RCBO shall perform the tests specified in 9.9.1.2 c) under the following conditions,
successively:
1) ambient temperature: –5 °C, off-load;
2) ambient temperature: +40 °C, the RCBO having been previously loaded with the rated
current, at any convenient voltage, until it attains thermal steady-state conditions.
In practice these conditions are reached when the variation of temperature-rise does
not exceed 1 K per hour.
For the tripping tests in 2), the flow of rated current may be interrupted, provided that
the total interruption period does not exceed 30 s. As soon as the sum of interruption
periods exceed 30 s, the RCBO shall be loaded again with rated current for 5 min
before next tripping time measurement.
NOTE Preheating may be carried out at any convenient voltage at either 50 Hz or 60 Hz but auxiliary circuits shall
be connected to their normal operating voltage (particularly for components depending on line voltage).
61009-1 Amend. 2 © IEC:2013 – 5 –
9.9.1.3 Verification of correct operation at residual currents with d.c. components
This subclause applies to type A RCBOs, under test conditions of 9.9.1.1.
a) Verification of correct operation in case of a continuous rise of residual pulsating direct
current
The test shall be performed according to Figure 5.
The auxiliary switches S and S and the RCBO shall be closed. The relevant thyristor
1 2
shall be controlled in such a manner that current delay angles α of 0°, 90° and 135° are
obtained. Each pole of the RCBO shall be tested twice at
...