Uninterruptible power systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements

Applies to single UPS units or UPS systems comprising a number of interconnected UPS and associated control/switchgear forming a single power system, intended to be installed in any operator accessible area or in separated electrical locations, connected to either industrial or public low voltage supply networks. Takes precedence over all aspects of the generic standards, and no additional testing is necessary. Takes into account differing test conditions necessary to encompass the range of physical sizes and power ratings of UPS. A UPS unit or system shall meet the relevant requirements of this standard as a stand-alone product. Special installation environments are not covered, nor are fault conditions of UPS taken into account. This standard does not cover d.c. supplied electronic ballast (IEC 60924 and IEC 60925) or UPS based on rotating machines. States EMC requirements, test methods, minimum performance levels.

Alimentations sans interruption (ASI) - Partie 2: Prescriptions pour la compatibilité électromagnétique (CEM)

S'applique aux ASI individuelles ou aux systèmes d'ASI comprenant un certain nmbre d'ASI interconnectées et de matériels de commande/commutation formant un système d'alimentation unique, les unes et les autres étant destingées à être installées dans n'impporte quel local accessible à l'opérateur ou dans des locaux séparés et reliés à des réseaux d'alimentation basse tension industriels ou publics. Prévaudra sur tous les aspects des normes génériques; aucun essai complémentaire n'est nécessaire. norme prend en compte les différentes conditions d'essai nécessaires pour couvrir le domaine des ASI en ce qui concerne leurs tailles et leurs puissances nominales. Une ASI unitaire ou un système d'ASI doit satisfaire aux prescriptions appropriées de la présente norme en tant que produit considéré individuellement. Les environnements spéciaux d'installation ne sont pas couverts et les conditions de défaut des ASI ne sont pas non plus pris en compte. La présente norme ne couvre pas les ballasts électroniques alimentés en courant continu (CEI 60924 et CEI 60925) ou les ASI mettant en jeu des machines tournantes. La présente norme fixe les prescriptions de CEM, des méthodes d'essai, des niveaux minimaux de performance.

General Information

Status
Published
Publication Date
25-Feb-1999
Current Stage
DELPUB - Deleted Publication
Start Date
19-Oct-2005
Completion Date
26-Oct-2025
Ref Project

Relations

Standard
IEC 62040-2:1999 - Uninterruptible power systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements Released:2/26/1999 Isbn:2831846978
English and French language
71 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NORME CEI
INTERNATIONALE IEC
62040-2
INTERNATIONAL
Première édition
STANDARD
First edition
1999-02
Alimentations sans interruption (ASI) –
Partie 2:
Prescriptions pour la compatibilité
électromagnétique (CEM)
Uninterruptible power systems (UPS) –
Part 2:
Electromagnetic compatibility
(EMC) requirements
Numéro de référence
Reference number
CEI/IEC 62040-2:1999
Numéros des publications Numbering

Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are

sont numérotées à partir de 60000. issued with a designation in the 60000 series.

Publications consolidées Consolidated publications

Les versions consolidées de certaines publications de Consolidated versions of some IEC publications
la CEI incorporant les amendements sont disponibles. including amendments are available. For example,

Par exemple, les numéros d’édition 1.0, 1.1 et 1.2 edition numbers 1.0, 1.1 and 1.2 refer, respectively, to

indiquent respectivement la publication de base, la the base publication, the base publication incor-
publication de base incorporant l’amendement 1, et la porating amendment 1 and the base publication
publication de base incorporant les amendements 1 incorporating amendments 1 and 2.

et 2.
Validité de la présente publication Validity of this publication
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. the content reflects current technology.
Des renseignements relatifs à la date de reconfir- Information relating to the date of the reconfirmation
mation de la publication sont disponibles dans le of the publication is available in the IEC catalogue.
Catalogue de la CEI.
Les renseignements relatifs à des questions à l’étude et Information on the subjects under consideration and
des travaux en cours entrepris par le comité technique work in progress undertaken by the technical
qui a établi cette publication, ainsi que la liste des committee which has prepared this publication, as well
publications établies, se trouvent dans les documents ci- as the list of publications issued, is to be found at the
dessous: following IEC sources:
• «Site web» de la CEI* • IEC web site*
• Catalogue des publications de la CEI • Catalogue of IEC publications
Publié annuellement et mis à jour Published yearly with regular updates
régulièrement (On-line catalogue)*
(Catalogue en ligne)*
• IEC Bulletin
• Bulletin de la CEI Available both at the IEC web site* and
Disponible à la fois au «site web» de la CEI* as a printed periodical
et comme périodique imprimé
Terminology, graphical and letter
Terminologie, symboles graphiques
symbols
et littéraux
For general terminology, readers are referred to
En ce qui concerne la terminologie générale, le lecteur IEC 60050: International Electrotechnical Vocabulary
se reportera à la CEI 60050: Vocabulaire Electro- (IEV).
technique International (VEI).
For graphical symbols, and letter symbols and signs
Pour les symboles graphiques, les symboles littéraux approved by the IEC for general use, readers are
et les signes d'usage général approuvés par la CEI, le referred to publications IEC 60027: Letter symbols to
lecteur consultera la CEI 60027: Symboles littéraux à be used in electrical technology, IEC 60417: Graphical
utiliser en électrotechnique, la CEI 60417: Symboles symbols for use on equipment. Index, survey and
graphiques utilisables sur le matériel. Index, relevé et compilation of the single sheets and IEC 60617:
compilation des feuilles individuelles, et la CEI 60617: Graphical symbols for diagrams.
Symboles graphiques pour schémas.
* See web site address on title page.
* Voir adresse «site web» sur la page de titre.

NORME CEI
INTERNATIONALE IEC
62040-2
INTERNATIONAL
Première édition
STANDARD
First edition
1999-02
Alimentations sans interruption (ASI) –
Partie 2:
Prescriptions pour la compatibilité
électromagnétique (CEM)
Uninterruptible power systems (UPS) –
Part 2:
Electromagnetic compatibility
(EMC) requirements
 IEC 1999 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in
utilisée sous quelque forme que ce soit et par aucun procédé, any form or by any means, electronic or mechanical,
électronique ou mécanique, y compris la photo-copie et les including photocopying and microfilm, without permission in
microfilms, sans l'accord écrit de l'éditeur. writing from the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
W
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 62040-2  CEI:1999
SOMMAIRE
Pages
AVANT-PROPOS . 4

Articles
1 Généralités . 6

1.1 Domaine d'application . 6

1.2 Références normatives . 6

1.3 Définitions. 10
2 Perturbations émises. 10
2.1 Prescriptions générales. 12
2.2 Classification des ASI . 12
2.3 Conditions générales de mesure . 14
2.3.1 Documentation pour l'acheteur/utilisateur . 16
2.3.2 Applicabilité. 16
2.4 Perturbations émises . 16
2.4.1 Limites de la tension de perturbation sur les bornes d'alimentation
à partir du réseau. 16
2.4.2 Limites de la tension de perturbation sur la sortie c.a. 18
2.4.3 Limites des accès de signalisation. 18
2.4.4 Limites des accès en c.c. . 18
2.4.5 Perturbations émises en basse fréquence – Harmoniques
de courant d'entrée . 20
2.5 Limites de valeur de champ de perturbations rayonnées . 20
2.5.1 Composante électrique du champ électromagnétique . 20
2.5.2 Composante magnétique du champ électromagnétique (facultatif) . 20
2.5.3 Limites de la puissance rayonnée (à l'étude). 20
3 Immunité. 22
3.1 Prescriptions générales et critères de fonctionnement . 22
3.2 Immunité aux décharges électrostatiques . 22
3.3 Immunité aux champs électromagnétiques rayonnés . 24
3.4 Immunité aux transitoires rapides. 24
3.5 Immunité aux surtensions. 24
3.6 Immunité aux signaux basses fréquences . 24

Annexe A (normative) Perturbations électromagnétiques – Méthodes d'essai . 26
Annexe B (informative) Perturbations électromagnétiques émises. Les limites
du champ magnétique – Champ H (sur demande facultative de l'acheteur). 58
Annexe C (informative) Perturbations électromagnétiques émises –
Limites pour les connexions de signaux de communication . 60
Annexe D (normative) Immunité électromagnétique – Méthodes d'essai . 62
Annexe E (informative) Méthode d'essai d'atténuation en ASI (à l'étude) . 70

62040-2 © IEC:1999 – 3 –
CONTENTS
Page
FOREWORD . 5

Clause
1 General. 7

1.1 Scope . 7

1.2 Normative references. 7

1.3 Definitions. 11
2 Emission . 11
2.1 General requirements. 13
2.2 Classification of UPS. 13
2.3 General measurement conditions . 15
2.3.1 Documentation for the purchaser/user . 17
2.3.2 Applicability. 17
2.4 Conducted emissions . 17
2.4.1 Limits of mains terminal interference voltage . 17
2.4.2 Limits of a.c. output interference voltage. 19
2.4.3 Limits of signal ports . 19
2.4.4 Limits of d.c. ports. 19
2.4.5 Low frequency emissions – Input current harmonics . 21
2.5 Radiated emissions. 21
2.5.1 Electric field . 21
2.5.2 Magnetic field (optional) . 21
2.5.3 Limits of power (under consideration) . 21
3 Immunity . 23
3.1 General requirements and performance criteria . 23
3.2 Immunity to electrostatic discharges. 23
3.3 Immunity to radiated electromagnetic fields . 25
3.4 Immunity to fast transients . 25
3.5 Immunity to surges. 25
3.6 Immunity to low-frequency signals . 25

Annex A (normative) Electromagnetic emission – Test methods . 27
Annex B (informative) Electromagnetic emission limits of magnetic field – H field (optional
where requested by purchaser). 59
Annex C (informative) Electromagnetic emission – Limits of signal ports . 61
Annex D (normative) Electromagnetic immunity – Test methods. 63
Annex E (informative) UPS attenuation test method (under consideration). 71

– 4 – 62040-2  CEI:1999
COMMISSION ELECTROTECHNIQUE INTERNATIONALE

––––––––––
ALIMENTATIONS SANS INTERRUPTION (ASI) –

Partie 2: Prescriptions pour la compatibilité électromagnétique (CEM)

AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes Internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques, représentent, dans la mesure
du possible un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, rapports techniques ou guides et agréés comme tels par les Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme de la CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 62040-2 a été établie par le sous-comité 22B: Convertisseurs à
semiconducteurs, du comité d’études 22 de la CEI: Electronique de puissance.
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
22B/118 et 118A/FDIS 22B/121RVD

Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Les annexes A et D font partie intégrante de cette norme.
Les annexes B, C et E sont données uniquement à titre d'information.

62040-2 © IEC:1999 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION

–––––––––––
UNINTERRUPTIBLE POWER SYSTEMS (UPS) –

Part 2: Electromagnetic compatibility (EMC) requirements

FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62040-2 has been prepared by subcommittee 22B: Semiconductor
converters, of IEC technical committee 22: Power electronics.
The text of this standard is based on the following documents:
FDIS Report on voting
22B/118 and 118A/FDIS 22B/121/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
Annexes A and D are an integral part of this standard.
Annexes B, C and E are for information only.

– 6 – 62040-2  CEI:1999
ALIMENTATIONS SANS INTERRUPTION (ASI) –

Partie 2: Prescriptions pour la compatibilité électromagnétique (CEM)

1 Généralités
1.1 Domaine d'application
La présente Norme internationale s'applique aux ASI individuelles ou aux systèmes d'ASI
comprenant un certain nombre d'ASI interconnectées et de matériels de commande/commutation
formant un système d'alimentation unique, les unes et les autres étant destinées à être
installées dans n'importe quel local accessible à l'opérateur ou dans des locaux séparés et
reliés à des réseaux d'alimentation basse tension industriels ou publics.
La présente norme de produit sur la CEM prévaudra sur tous les aspects des normes
génériques; aucun essai complémentaire n'est nécessaire.
Les prescriptions ont été choisies de manière à assurer un niveau adéquat de compatibilité
électromagnétique (CEM) pour les ASI dans les emplacements publics et industriels. Ces
niveaux ne peuvent toutefois pas couvrir des cas extrêmes que l'on peut rencontrer dans
n'importe quel emplacement, mais avec une probabilité d'apparition extrêmement faible.
Cette norme prend en compte les différentes conditions d'essai nécessaires pour couvrir le
domaine des ASI en ce qui concerne leurs tailles et leurs puissances nominales.
Une ASI unitaire ou un système d'ASI doit satisfaire aux prescriptions appropriées de la
présente norme en tant que produit considéré individuellement. Les phénomènes de CEM
produits par une quelconque charge connectée par un client à la sortie de l'ASI ne doivent pas
être pris en compte.
Les environnements spéciaux d'installation ne sont pas couverts et les conditions de défaut
des ASI ne sont pas non plus pris en compte.
La présente norme ne couvre pas les ballasts électroniques alimentés en courant continu
(CEI 60924 et CEI 60925) ou les ASI mettant en jeu des machines tournantes.
La présente norme fixe:
– les prescriptions de CEM;
– des méthodes d'essai;
– des niveaux minimaux de performance.
1.2 Références normatives
Les documents normatifs suivants contiennent des dispositions qui, par suite de la référence
qui y est faite, constituent des dispositions valables pour la présente Norme internationale.
Pour les références datées, les amendements ultérieurs ou les révisions de ces publications ne
s’appliquent pas. Toutefois, les parties prenantes aux accords fondés sur la présente Norme
internationale sont invitées à rechercher la possibilité d'appliquer les éditions les plus récentes
des documents normatifs indiqués ci-après. Pour les références non datées, la dernière édition
du document normatif en référence s’applique. Les membres de la CEI et de l'ISO possèdent
le registre des Normes internationales en vigueur.

62040-2 © IEC:1999 – 7 –
UNINTERRUPTIBLE POWER SYSTEMS (UPS) –

Part 2: Electromagnetic compatibility (EMC) requirements

1 General
1.1 Scope
This International Standard applies to single UPS units or UPS systems comprising a number
of interconnected UPS and associated control/switchgear forming a single power system,
intended to be installed in any operator accessible area or in separated electrical locations,
connected to either industrial or public low voltage supply networks.
This product EMC standard takes precedence over all aspects of the generic standards, and no
additional testing is necessary.
The requirements have been selected so as to ensure an adequate level of electromagnetic
compatibility (EMC) for UPS at public and industrial locations. These levels cannot, however,
cover extreme cases which may occur in any location, but with extremely low probability of
occurrence.
It takes into account differing test conditions necessary to encompass the range of physical
sizes and power ratings of UPS.
A UPS unit or system shall meet the relevant requirements of this standard as a stand-alone
product. EMC phenomena produced by any customers' load connected to the output of the
UPS equipment shall not be taken into account.
Special installation environments are not covered, nor are fault conditions of UPS taken into
account.
This standard does not cover d.c. supplied electronic ballast (IEC 60924 and IEC 60925) or
UPS based on rotating machines.
This standard states:
– EMC requirements;
– test methods;
– minimum performance levels.
1.2 Normative references
The following normative documents contain provisions which, through reference in this text,
constitute provisions of this International Standard. For dated references, subsequent
amendments to, or revisions of, any of these publications do not apply. However, parties to
agreements based on this International Standard are encouraged to investigate the possibility
of applying the most recent editions of the normative documents indicated below. For undated
references, the latest edition of the normative document referred to applies. Members of IEC
and ISO maintain registers of currently valid International Standards.

– 8 – 62040-2  CEI:1999
CEI 60050(161):1990, Vocabulaire Electrotechnique International (VEI) – Chapitre 161:
Compatibilité électromagnétique

CEI 60083:1997, Prises de courant pour usages domestiques et analogues normalisées par les
pays membres de la CEI
CEI 61000-2-2:1990, Compatibilité électromagnétique (CEM) – Partie 2: Environnement –
Section 2: Niveaux de compatibilité pour les perturbations conduites basse fréquence et la
transmission de signaux sur les réseaux publics d'alimentation à basse tension

CEI 61000-3-2:1998, Compatibilité électromagnétique (CEM) – Partie 3-2: Limites – Limites
pour les émissions de courant harmonique (courant appelé par les appareils ≤ 16 A par phase)
CEI 61000-3-3:1994, Compatibilité électromagnétique (CEM) – Partie 3: Limites – Section 3:
Limitation des fluctuations de tension et du flicker dans les réseaux basse tension pour les
équipements ayant un courant appelé ≤ 16 A
CEI 61000-4-1:1992, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d'essai et
de mesure – Section 1: Vue d'ensemble sur les essais d'immunité. Publication fondamentale en
CEM
CEI 61000-4-2:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 2: Essais d’immunité aux décharges électrostatiques. Publication
fondamentale en CEM
CEI 61000-4-3:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 3: Essai d’immunité aux champs électromagnétiques rayonnés aux
fréquences radioélectriques
CEI 61000-4-4:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 4: Essais d’immunité aux transitoires électriques rapides en salves.
Publication fondamentale en CEM
CEI 61000-4-5:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
mesure – Section 5: Essai d’immunité aux ondes de choc
CEI 61000-4-11:1994, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d'essai et
de mesure – Section 11: Essais d'immunité aux creux de tension, coupures brèves et
variations de tension
CEI 62040-3, —, Alimentations sans interruption (ASI) – Partie 3: Méthode de spécification des
1)
performances et procédures d'essai
CISPR 16-1:1993, Spécification des méthodes et des appareils de mesure des perturbations
radioélectriques et de l'immunité aux perturbations radioélectriques – Partie 1: Appareils de
mesure des perturbations radioélectriques et de l'immunité aux perturbations radioélectriques
CISPR 22:1997, Appareils de traitement de l'information – Caractéristiques des perturbations
radioélectriques – Limites et méthodes de mesure
———————
1)
A publier.
62040-2 © IEC:1999 – 9 –
IEC 60050(161):1990, International Electrotechnical Vocabulary (IEV) – Chapter 161:
Electromagnetic compatibility
IEC 60083:1997, Plugs and socket-outlets for domestic and similar general use, standardized
in member countries of IEC
IEC 61000-2-2:1990, Electromagnetic compatibility (EMC) – Part 2: Environment – Section 2:
Compatibility levels for low frequency conducted disturbances and signalling in public low-
voltage supply systems
IEC 61000-3-2:1998, Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for
harmonic current emissions (equipment input current ≤ 16 A per phase)
IEC 61000-3-3:1994, Electromagnetic compatibility (EMC) – Part 3: Limits – Section 3:
Limitation of voltage fluctuations and flicker in low-voltage supply systems for equipment with
rated current ≤ 16 A
IEC 61000-4-1:1992, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 1: Overview of immunity test. Basic EMC publication
IEC 61000-4-2:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 2: Electrostatic discharge immunity test. Basic EMC publication
IEC 61000-4-3:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 3: Radiated, radio-frequency, electromagnetic filed immunity test
IEC 61000-4-4:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 4: Electrical fast transient/burst immunity test. Basic EMC publication
IEC 61000-4-5:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 5: Surge immunity test
IEC 61000-4-11:1994, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 11: Voltage dips, short interruptions and voltage variations immunity test
IEC 62040-3, —, Uninterruptible power systems (UPS) – Part 3: Method of specifying the
1)
performance and test requirements
CISPR 16-1:1993, Specification for radio disturbance and immunity measuring apparatus and
methods – Part 1: Radio disturbance and immunity measuring apparatus

CISPR 22:1997, Information technology equipment – Radio disturbance characteristics – Limits
and methods of measurement
———————
1)
To be published.
– 10 – 62040-2  CEI:1999
1.3 Définitions
Pour les besoins de la présente norme internationale, les définitions concernant la CEM et les

phénomènes correspondants qui se trouvent dans la CEI 60050(161), sont applicables ainsi

que les définitions particulières suivantes:

1.3.1
accès
interface particulière de l'ASI spécifiée avec l'environnement électromagnétique extérieur (voir

figure 1)
1.3.2
accès par l'enveloppe
frontière physique de l'ASI à travers laquelle des champs électromagnétiques peuvent rayonner
ou affecter l'ASI
Accès par l'enveloppe
Accès par l'alimentation c.a. Accès par la sortie c.a.
ASI
Accès par les bornes
de signalisation/ commande
Accès par la borne de terre
Accès par l'alimentation c.c.
(batterie)
IEC  309/99
Figure 1 – Exemples d'accès
2 Perturbations émises
La présente norme couvre les perturbations dans le domaine des fréquences comprises entre
0 Hz et 1,0 GHz.
Les prescriptions quant aux perturbations émises ont été choisies de manière à assurer que
les perturbations engendrées par l'ASI en fonctionnement normal n'atteignent pas un niveau
qui pourrait empêcher d'autres appareils de fonctionner comme normalement prévu.

NOTE 1 – Les limites données dans la présente norme peuvent toutefois ne pas fournir une protection totale contre
la perturbation de la réception des émissions de radio ou de télévision lorsque l'ASI est utilisée à moins de 10 m
des antennes réceptrices, pour les ASI de classe B et de 30 m pour les ASI de classe A.
NOTE 2 – Dans les cas particuliers, par exemple lorsqu'un appareil très susceptible est utilisé à proximité, des
mesures supplémentaires peuvent devoir être prises pour réduire les perturbations électromagnétiques en deçà des
niveaux spécifiés.
62040-2 © IEC:1999 – 11 –
1.3 Definitions
For the purpose of this International Standard, the definitions in IEC 60050(161) related to

EMC and to relevant phenomena apply, together with the following particular definitions.

1.3.1
port
particular interface of the specified UPS with the external electromagnetic environment
(see figure 1)
1.3.2
enclosure port
the physical boundary of the UPS through which electromagnetic fields may radiate or impinge
Enclosure port
AC output power port
AC input power port
UPS
Signal/control port
Earth port
DC power port (battery)
IEC  309/99
Figure 1 – Examples of ports
2 Emission
Disturbances in the frequency range from 0 Hz to 1,0 GHz are covered.
The emission requirements have been selected so as to ensure that disturbances generated by
UPS operating normally do not reach a level which could prevent other apparatus from
operating as intended.
NOTE 1 – The limits in this standard may not, however, fully provide protection against interference to radio and
television reception when the UPS is used closer than 10 m to the receiving antenna for Class B-UPS and 30 m for
Class A-UPS.
NOTE 2 – In special cases, for instance when highly susceptible apparatus is being used in proximity, additional
mitigation measures may have to be employed to reduce the electromagnetic emission further below the specified
levels.
– 12 – 62040-2  CEI:1999
2.1 Prescriptions générales
Le matériel doit satisfaire aux limites définies en 2.3 à 2.5 en ce qui concerne les perturbations

émises.
Les essais doivent être effectués avec l'ASI dans les conditions suivantes:

– tension d'alimentation nominale;

– fonctionnement à partir de l'alimentation normale et à partir de la réserve d'énergie;

– charge linéaire qui se traduit par le niveau le plus élevé de perturbations.

L'objet de 2.4 et de 2.5 est de définir des limites et des méthodes d'essai pour les ASI
correspondant au domaine d'application de la norme, et cela en ce qui concerne les
perturbations électromagnétiques émises susceptibles de perturber d'autres appareils, par
exemple des récepteurs radio.
Ces limites de perturbations émises représentent les prescriptions essentielles quant à la
compatibilité électromagnétique.
Les prescriptions pour les essais sont spécifiées pour chaque connexion considérée. Se
référer à l'annexe A pour la méthodologie des essais.
2.2 Classification des ASI
Les ASI doivent être classées de deux manières en ce qui concerne les perturbations
électromagnétiques émises.
a) Equipements distribués d'une façon incontrôlée
Lorsque la vente des ASI se fait par le canal d'une distribution non contrôlée et qui ne
dépend pas de la compétence technique du client ou de l'utilisateur quant à l'usage
ultérieur de l'ASI, l'ASI est caractérisée par le terme «équipement distribué d'une façon
incontrôlée» et des limites de perturbations émises plus sévères lui sont imposées en
accord avec les prescriptions essentielles de protection quant à la CEM. Les produits
entrant dans cette catégorie sont classés en ASI de classe A ou ASI de classe B.
– ASI de classe A
ASI convenant à une utilisation dans tous les locaux autres que ceux à usage
d'habitation, et ASI convenant à une utilisation dans les locaux autres que ceux
directement connectés à un réseau public d'alimentation basse tension (un tel réseau
public étant par ailleurs susceptible de fournir des bâtiments à usage d'habitation).
(Toutes les ASI connectées par des prises de courant industrielles ou connectées à
demeure et les ASI connectées par des prises de courant nationales vendues

exclusivement pour un usage industriel, sont des ASI de classe A.)
Le texte suivant doit être inclus dans le manuel d'utilisation:
AVERTISSEMENT Il s'agit d'un produit de classe A. Dans un environnement
correspondant à un usage d'habitation, ce produit peut être la source de
perturbations radioélectriques, auquel cas il peut être demandé à l'utilisateur de
prendre des mesures supplémentaires.
Les ASI de classe A doivent satisfaire aux limites de la classe A de la présente norme.
NOTE – Bien que les limites de la classe A aient été établies pour les établissements industriels et commerciaux,
les administrations peuvent autoriser, avec les mesures complémentaires nécessaires, l'installation et l'emploi
d'ASI de classe A dans un local domestique ou dans un établissement connecté directement aux réseaux de
distribution d'électricité à usage domestique.

62040-2 © IEC:1999 – 13 –
2.1 General requirements
UPS shall comply with the emission limits of 2.3 to 2.5.

The tests shall be made with the UPS in the following conditions:

– rated input voltage;
– normal and stored energy mode of operation;

– linear load that results in the highest interference level.

The objective of 2.4 and 2.5 is to define limits and test methods for UPS defined in the scope in

this standard in relation to electromagnetic emissions which may cause interference in other
apparatus, for example radio receivers.
These emission limits represent essential electromagnetic compatibility requirements.
Test requirements are specified for each port considered. Refer to annex A for test methodology.
2.2 Classification of UPS
UPS products shall be classified in two ways for electromagnetic emissions.
a) UPS for unrestricted sales distribution
Where the sales distribution of the UPS is unrestricted and not dependent on the technical
competence of the customer or user for the further employment of the UPS, it is described
by the term: "unrestricted sales distribution", and implements lower emission limits in
accordance with the essential EMC protecting requirements. Products in this category are
classified as class A-UPS or class B-UPS.
– Class A-UPS
UPS suitable for use in all establishments other than domestic, and those directly
connected to a low voltage public supply network which supplies buildings used for
domestic purposes.
(All UPS connected by industrial plugs and sockets or permanently connected and UPS
fitted with national plugs and sockets marketed solely for industrial use, are class A-UPS.)
The following wording shall be included in the instructions for use:
WARNING This is a class A-UPS product. In a domestic environment, this product
may cause radio interference, in which case, the user may be required to take
additional measures.
Class A-UPS shall meet class A-UPS limits of this standard.

NOTE – Although class A-UPS limits have been derived for industrial and commercial establishments,
administrations may allow, with whatever additional measures are necessary, the installation and use of class
A-UPS equipment in a domestic establishment or in an establishment connected directly to domestic power
supplies.
– 14 – 62040-2  CEI:1999
– ASI de classe B
ASI convenant à un usage dans tous les locaux y compris ceux à usage d'habitation et

les locaux directement connectés à un réseau d'alimentation basse tension public qui

alimente des bâtiments à usage d'habitation. (Toutes les ASI connectées par des prises

de courant nationales (CEI 60083), sauf celles marquées et vendues uniquement pour

des applications industrielles).

Les ASI de classe B doivent satisfaire aux limites correspondant à la classe B dans la

présente norme.
b) ASI distribuées d'une façon contrôlée

Lorsque la distribution ou la vente est limitée aux seuls clients et utilisateurs possédant une

compétence technique élevée, le matériel correspondant est désigné comme «équipement
distribué d'une façon contrôlée», ce qui implique des limites de perturbations émises plus
élevées du fait que, pour des raisons économiques, les deux parties, le fabricant et le
client, doivent s'assurer du respect des prescriptions essentielles de protection CEM pour
l'installation spécifique résultant de leur accord, cela en choisissant des limites de
perturbations émises ou en effectuant des mesures in situ en tenant compte de la totalité
des différents matériels et des frontières entre eux.
Le texte suivant doit être inclus dans le manuel d'utilisation:
AVERTISSEMENT Il s'agit d'un produit pour distribution restreinte à des installateurs ou
utilisateurs avertis. Des restrictions à l'installation ou des mesures additionnelles
peuvent être nécessaires pour éviter les perturbations.
Cette catégorie est limitée aux ASI dont le courant assigné de sortie est supérieur à 25 A et
destinées à être installées dans des locaux à usage commercial ou industriel avec leur
propre transformateur d'alimentation électrique et espacées au minimum de 30 m par
rapport à tous les autres locaux et/ou consommateurs.
2.3 Conditions générales de mesure
Les mesures doivent être effectuées avec le mode de fonctionnement qui produit la
perturbation maximale correspondant à des applications normales dans la bande de
fréquences essayée. Les modes de fonctionnement des ASI, à savoir le fonctionnement normal
et le fonctionnement en autonomie, sur l'énergie emmagasinée, doivent être essayés.
Il est recommandé d'essayer de rendre la perturbation maximale en faisant varier la
configuration de l'échantillon essayé.
Lorsque les ASI comportent des bornes d'alimentation additionnelles (accès) pour la connexion
de sources d'alimentation séparées pour les circuits de by-pass statique et/ou pour les circuits
de by-pass lors de la maintenance, ces bornes (accès) doivent être, lorsque cela est possible,
connectées temporairement à l'alimentation correspondant à la connexion d'entrée c.a.
normale. Les essais de perturbations conduites en 2.4 doivent comprendre la mesure de ces

circuits additionnels.
Si l'ASI fait partie d'un système, ou peut être connectée à des accessoires auxiliaires, alors
l'ASI doit être essayée en étant connectée à la configuration minimale d'accessoires auxiliaires
pour faire apparaître une impédance équivalente aux connexions ou aux bornes.
Les sorties c.a. de l'ASI doivent être chargées avec une charge linéaire capable de soumettre
l'ASI en cours d'essai à n'importe quelle condition de charge à l'intérieur des caractéristiques
de sortie assignées.
Il doit être pris note précisément dans le rapport d'essai de la configuration et du mode de
fonctionnement au cours de la mesure. Se référer à l'annexe A pour les montages d'essais et
in situ, se reporter à A.8.3.
les critères de mesure. Pour les essais

62040-2 © IEC:1999 – 15 –
– Class B-UPS
UPS suitable for use in all establishments, including domestic, and those establishments

directly connected to a low voltage public network which supplies buildings used for

domestic purposes. (All UPS connected by national plugs and sockets (IEC 60083),

except those clearly marked and marketed only for industrial applications).

Class B-UPS shall meet class B-UPS limits of this standard.

b) UPS for restricted sales distribution

Where the sales distribution is restricted to only customers and users with a high technical

competence, it is described as "restricted sales distribution", and implements higher

emission limits, because for economic reasons the manufacturer and the user who are in

partnership and agreement are required to ensure the EMC protecting requirement for the
specific installation by choice of emission limits, or by on-site measurements, together with
all different pieces of equipment and boundary conditions.
The following wording shall be included in the instructions for use:
WARNING This is a product for restricted sales distribution to informed partners.
Installation restrictions or additional measures may be needed to prevent disturbances.
This category is limited to UPS whose rated output current is greater than 25 A intended to
be installed in commercial or industrial buildings with their own electricity supply transformer
and a minimum 30 m boundary with all other establishments and/or consumers.
2.3 General measurement conditions
The measurements shall be made in the operating mode producing the largest emission in the
frequency band being investigated consistent with normal applications. UPS operating modes:
normal mode, stored energy mode, shall be investigated.
An attempt should be made to maximize the emission by varying the test set-up configuration
of the test sample.
For UPS with additional mains terminals (ports) for the connection of separate supplies for
static bypass and/or maintenance bypass circuits, these terminals (ports) shall, wherever
possible, be temporarily connected to the normal a.c. input port supply. Conducted emission
tests in 2.4 shall include measurement of these additional circuits.
If the UPS is part of a system, or can be connected to auxiliary accessories, then the UPS shall
be tested while connected to the minimum configuration of auxiliary accessories necessary to
exercise the ports, or be terminated in an equivalent impedance.
UPS a.c. outputs shall be loaded with linear load capable of operating the unit under test for
any load condition within its output rating.

The configuration and mode of operation during measurement shall be precisely noted in the
test report. Refer to annex A for test set-up and measurement criteria. For in-situ testing,
se
...