SIST EN 16510-2-2:2023
(Main)Residential solid fuel burning appliances - Part 2-2: Inset appliances including open fires
Residential solid fuel burning appliances - Part 2-2: Inset appliances including open fires
This Part 2-2 of EN 16510 is applicable to hand fed solid fuel fired inset appliances, with or without functional modification, that operate without firedoors or operate with fire doors either as closed only or as closed or open, and also includes open fires fired by solid fuel. The surround of these appliances are integrated with the building with the exception of free-standing appliances and those inset appliances which are installed into a fireplace recess or enclosure. These appliances provide heat into the space where they are installed. Additionally, where fitted with a boiler, they also provide domestic hot water and/or central heating.
These appliances may burn either solid mineral fuels, peat briquettes, natural or manufactured wood logs or be multi-fuel in accordance with the appliance manufacturer’s instructions.
This Part 2-2 of EN 16510 also covers ‘Kachelofen’ and ‘Putzofen’ inset appliances, having nominal heat outputs up to 15 kW.prEN 16510-1
This Part 2-2 of EN 16510 is not applicable to appliances with fan assisted combustion air or appliances that are mechanically fed.
Open fireplace components such as a bottomgrate with associated firefront which the manufacturer supplies for installation into an existing heat resistant, insulated firebox are not covered by this Part 2-2 of EN 16510.
This Part 2-2 of EN 16510 is to be used in conjunction with EN 16510-1 of which it is an integral part.
Häusliche Heizgeräte für feste Brennstoffe - Teil 2-2: Kamineinsätze einschließlich offene Kamine
Dieses Dokument ist anzuwenden für Heizeinsätze einschließlich offener Kamine für feste Brennstoffe (handbeschickte, mit festen Brennstoffen befeuerte Einbaugeräte mit oder ohne Funktionsänderung, die ohne Feuertüren oder mit Feuertüren entweder nur geschlossen bzw. geschlossen oder offen betrieben werden, das schließt auch offene, mit festen Brennstoffen befeuerte Feuerstätten ein).
Der Verwendungszweck der Geräte ist Raumheizung in Wohngebäuden. Sie können mit wasserführenden Bauteilen (als feste Bestandteile des Gerätes mit zu erhitzendem Wasser) zur Warmwasserbereitung der Zentralheizung ausgestattet sein.
Die Verkleidung dieser Feuerstätten ist mit dem Gebäude verbunden, mit Ausnahme von freistehenden Geräten und solchen, die in eine Feuerstätten-Nische oder eine Verkleidung eingestellt sind.
Die Geräte können wie angegeben einen oder mehrere der folgenden festen Brennstoffe verfeuern:
— Scheitholz;
— Holzbriketts;
— Holzpellets;
— Braunkohlenbriketts;
— feste mineralische Brennstoffe;
— Torfbriketts.
Dieses Dokument ist auch anzuwenden für Kachelofen- und Putzofen-Heizeinsätze mit einer Nennwärmeleistung bis 15 kW.
Dieses Dokument ist nicht anzuwenden für Geräte mit gebläseunterstützter Verbrennungsluft oder für Geräte, die mechanisch beschickt werden.
Offene Kaminkomponenten wie z. B. ein Bodenrost mit zugehöriger Frontplatte zum Einbau in einen vorhandenen brandsicheren, wärmegedämmten Feuerraum werden von diesem Dokument nicht erfasst.
Dieses Dokument legt das Verfahren für die Bewertung und Überprüfung der Leistungsbeständigkeit (AVCP) der Eigenschaften von für Heizeinsätze einschließlich offener Kamine für feste Brennstoffe fest.
Equipement de chauffage domestique - Partie 2-2 : Foyers ouverts et insert
Le présent document s’applique aux foyers ouverts et inserts à combustible solide (inserts à combustibles solides à alimentation manuelle, avec ou sans modification fonctionnelle, qui fonctionnent sans porte foyère ou avec des portes foyères soit uniquement fermées, soit fermées ou ouvertes, ainsi qu’aux foyers ouverts à combustible solide).
L’usage prévu des appareils est le chauffage des locaux dans les bâtiments résidentiels. Ils peuvent être équipés d’un bouilleur (faisant partie intégrante de l’appareil et contenant de l’eau à chauffer) pour fournir de l’eau chaude aux systèmes de chauffage central.
L’habillage de ces appareils est intégré dans le bâtiment, à l’exception des appareils indépendants et des inserts qui sont installés dans une niche ou une enceinte.
Ces appareils peuvent utiliser un ou plusieurs des types de combustibles solides suivants, comme spécifié :
- bûches de bois ;
- bois compressé non traité ;
- granulés de bois ;
- briquettes de lignite ;
- combustibles minéraux solides ;
- briquettes de tourbe.
Le présent document s’applique également aux inserts pour poêles de masse en faïence ou en maçonnerie dont la puissance utile nominale est inférieure ou égale à 15 kW.
Le présent document ne s’applique pas aux appareils équipés d’un ventilateur pour l’alimentation en air de combustion ou aux appareils à alimentation mécanique.
Les éléments de cheminée ouverte, tels que grille et devanture de foyer associée qui sont destinées
à une installation dans un foyer existant, thermiquement isolé et constitué de matériaux réfractaires, ne sont pas concernés par le présent document.
Le présent document spécifie des modes opératoires pour l’évaluation et la vérification de la constance des performances (EVCP) des caractéristiques des foyers ouverts et des inserts à combustible solide.
Grelne naprave na trdna goriva za stanovanjske stavbe - 2-2. del: Kaminski vložki, vključno odprti kamini na trdna goriva
Ta del 2-2 standarda EN 16510 se uporablja za vgrajene grelne naprave z ročnim dodajanjem trdnega goriva, s funkcionalnimi spremembami ali brez njih, ki delujejo bodisi samo z zaprtimi protipožarnimi vrati bodisi z zaprtimi ali odprtimi vrati, in vključuje tudi odprte kamine na trdna goriva. Okolica teh naprav je del stavbe, z izjemo prostostoječih naprav in tistih vgradnih naprav, ki so nameščene v vdolbino ali ohišje kamina. Te naprave zagotavljajo toploto v prostor, kjer so nameščene. Če so opremljene s kotlom, zagotavljajo tudi sanitarno vodo in/ali centralno ogrevanje.
V teh napravah je mogoče kuriti trdna mineralna goriva, šotne brikete, naravna ali predelana lesena polena ali več vrst goriv v skladu z navodili proizvajalca naprave.
Ta del 2-2 standarda EN 16510 zajema tudi vgradne naprave »Kachelofen« in »Putzofen«, ki imajo nazivno toplotno moč do 15 kW.prEN 16510-1
Ta del 2-2 standarda EN 16510 se ne uporablja za naprave z ventilatorjem za zgorevalni zrak ali naprave z mehanskim dodajanjem.
Sestavni deli odprtega kamina, kot je spodnja rešetka s pripadajočim ognjiščem, ki jih proizvajalec dobavi za vgradnjo v obstoječe toplotno odporno, izolirano kurišče, niso zajeti v tem delu 2-2 standarda EN 16510.
Ta del 2-2 standarda EN 16510 je sestavni del standarda EN 16510-1 in ga je treba uporabljati v povezavi z njim.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 16510-2-2:2023
01-marec-2023
Nadomešča:
SIST EN 13229:2003
SIST EN 13229:2003/A1:2004
SIST EN 13229:2003/A2:2005
SIST EN 13229:2003/A2:2005/AC:2006
SIST EN 13229:2003/A2:2005/AC:2008
SIST EN 13229:2003/AC:2004
SIST EN 13229:2003/AC:2006
Grelne naprave na trdna goriva za stanovanjske stavbe - 2-2. del: Kaminski vložki,
vključno odprti kamini na trdna goriva
Residential solid fuel burning appliances - Part 2-2: Inset appliances including open fires
Häusliche Heizgeräte für feste Brennstoffe - Teil 2-2: Kamineinsätze einschließlich
offene Kamine
Equipement de chauffage domestique - Partie 2-2 : Foyers ouverts et insert
Ta slovenski standard je istoveten z: EN 16510-2-2:2022
ICS:
97.100.30 Grelniki na trdo gorivo Solid fuel heaters
SIST EN 16510-2-2:2023 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 16510-2-2:2023
---------------------- Page: 2 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2
EUROPEAN STANDARD
NORME EUROPÉENNE
December 2022
EUROPÄISCHE NORM
ICS 97.100.30 Supersedes EN 13229:2001
English Version
Residential solid fuel burning appliances - Part 2-2: Inset
appliances including open fires
Appareils de chauffage domestiques à combustible Häusliche Feuerstätten für feste Brennstoffe - Teil 2-2:
solide - Partie 2-2 : Foyers ouverts et inserts Kamineinsätze einschließlich offene Kamine
This European Standard was approved by CEN on 23 October 2022.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 16510-2-2:2022 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
Contents Page
European foreword . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 Characteristics . 7
4.1 Protection of combustible materials . 7
4.2 Carbon monoxide emission (CO) . 8
) emissions . 9
4.3 Nitrogen oxides (NO
x
4.4 Emission of organic gaseous compounds (OGC) . 9
4.5 Particulate matter (PM) emissions . 10
4.6 Safety and accessibility in use . 10
4.6.1 General . 10
4.6.2 Flue gas outlet temperature at nominal heat output . 10
4.6.3 Flue gas outlet temperature at part load heat output. 10
4.6.4 Minimum flue draught at nominal heat output . 11
4.6.5 Minimum flue draught at part load heat output . 11
4.6.6 Flue gas mass flow at nominal heat output . 11
4.6.7 Flue gas mass flow at part load heat output . 11
4.6.8 Fire safety of installation to the chimney . 11
4.7 Energy economy and heat retention . 11
4.7.1 Space heat output at nominal heat output . 11
4.7.2 Water heat output, if existing at nominal heat output. 12
4.7.3 Efficiency at nominal heat output . 12
4.7.4 Space heat output at part load heat output . 12
4.7.5 Water heat output, if existing at part load heat output . 12
4.7.6 Efficiency at part load heat output . 12
4.7.7 Seasonal space heating efficiency at appliance’s nominal heat output . 13
4.7.8 Energy efficiency . 13
4.7.9 Electric power consumption at nominal heat output, if existing . 13
4.7.10 Electric power consumption at part load heat output, if existing . 14
4.7.11 Standby mode power consumption, if existing . 14
4.8 Environmental sustainability . 14
5 Descriptive features . 15
5.1 Data for potential use with room ventilation systems: type of appliance (in relation
to its tightness to the room) . 15
5.2 Data for the building's statics: appliance's mass . 15
5.3 Materials and construction elements . 16
5.3.1 General . 16
5.3.2 General stresses . 16
5.3.3 Integral boiler or heat exchanger . 16
5.4 Risk of burning fuel falling out . 16
5.5 Temperature rise in the fuel storage . 16
5.6 Temperature rise of the operating components . 16
5.7 Spillage of flue gases into the room . 17
5.7.1 Possible spillage of CO, if relevant for the fuel type. 17
5.7.2 Safety test for spillage of combustion gas and discharge of embers . 17
2
---------------------- Page: 4 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
5.7.3 Open operation . 17
5.8 Cleanability . 17
5.8.1 Heating surfaces . 17
5.8.2 Flueways . 17
5.8.3 Ashpan . 17
5.8.4 Bottomgrate . 17
5.8.5 Damper . 18
5.8.6 Fan-cut-out-device . 18
5.9 Strength and leak tightness of boiler shells . 18
6 Assessment and verification of constancy of performance - AVCP . 18
6.1 General . 18
6.2 Assessment of performance . 18
6.2.1 General . 18
6.2.2 Test samples, testing and compliance criteria . 19
6.3 Verification of constancy of performance . 20
6.3.1 Factory production control (FPC) . 20
Annex A (normative) Test methods . 25
A.1 Test environment . 25
A.2 Test assembly . 25
A.3 Measurement equipment. 25
A.4 Test procedures . 25
A.5 Test results . 32
A.6 Calculation methods . 32
A.7 Test report . 32
Annex BA (informative) Example for the possibility to extrapolate the steady-state
condition from a curve of temperature measurements of at least 8 h . 35
Annex ZA (informative) Relationship of this European Standard with Regulation (EU) No.
305/2011 . 37
ZA.1 Scope and relevant characteristics . 37
ZA.2 System of Assessment and Verification of Constancy of Performance (AVCP) . 40
ZA.3 Assignment of AVCP tasks . 40
Bibliography . 42
3
---------------------- Page: 5 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
European foreword
This document (EN 16510-2-2:2022) has been prepared by Technical Committee CEN/TC 295
“Residential solid fuel burning appliances”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by June 2023, and conflicting national standards shall be
withdrawn at the latest by November 2025.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 13229:2001 as amended and corrected. In relation to EN 13229:2001 as
amended and corrected the following changes have been made:
— measurement methods for NO , hydrocarbon and particulate matter emissions for solid fuel burning
x
appliances;
— specifications for classification of solid fuel burning appliances and system boundaries for room
sealed appliances;
— requirements for the safety of solid fuel burning appliances with water-bearing components added;
— Annex ZA updated according to requirements of M/577;
— energy efficiency and energy class labelling and seasonal space heating efficiency added;
— requirements for environmental sustainability added.
This document has been prepared under a standardization request given to CEN by the European
Commission and the European Free Trade Association.
For relationship with (EU) Regulation 305/2011, see informative Annex ZA, which is an integral part of
this document.
The structure of EN 16510, Residential solid fuel burning appliances, is as follows:
— Part 1: General requirements and test methods;
— Part 2-1: Roomheaters;
— Part 2-2: Inset appliances including open fires;
— Part 2-3: Cookers;
— Part 2-4: Independent boilers — Nominal heat output up to 50 kW;
— Part 2-5: Slow heat release appliances;
— Part 2-6: Mechanically by wood pellets fed roomheaters, inset appliances and cookers.
Other sections of Part 2 will be added to cover residential solid fuel burning appliances not included in
parts 2-1 to 2-6.
4
---------------------- Page: 6 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
Subclauses and Figures which are additional to those in EN 16510-1:2022 are numbered starting with
201. Annexes which are additional to those in EN 16510-1:2022 are numbered starting with BA.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
5
---------------------- Page: 7 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
1 Scope
This document is applicable to inset appliances including open fires for solid fuel (hand fed solid fuel fired
inset appliances, with or without functional modification, that operate without fire doors or operate with
fire doors either as closed only or as closed or open, and also includes open fires fired by solid fuel).
The intended use of the appliances is space heating in residential buildings. They can be fitted with a
boiler (integral part of the appliance containing water to be heated up) for the supply of hot water for
central heating systems.
The surround of these appliances is integrated with the building with the exception of free-standing
appliances and those inset appliances which are installed into a fireplace recess or enclosure.
These appliances can burn one or more types of the following solid fuels as specified:
— wood logs;
— compressed untreated wood;
— wood pellets;
— lignite briquettes;
— solid mineral fuels;
— peat briquettes.
This document is also applicable to Kachelofen/Putzofen inset appliances, having nominal heat outputs
up to 15 kW.
This document is not applicable to appliances with fan assisted combustion air or appliances that are
mechanically fed.
Open fireplace components such as a bottomgrate with associated fire front which are intended for
installation into an existing heat resistant, insulated firebox are not covered by this document.
This document specifies procedures for assessment and verification of constancy of performance (AVCP)
of characteristics of solid fuel burning inset appliances including open fires.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document.
EN 15804:2012+A2:2019, Sustainability of construction works — Environmental product declarations —
Core rules for the product category of construction products
EN 16510-1:2022 Residential solid fuel burning appliances — Part 1: General requirements and test
methods
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 16510-1:2022 apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
• ISO Online browsing platform: available at https://www.iso.org/obp
• IEC Electropedia: available at https://www.electropedia.org/
6
---------------------- Page: 8 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
Add the following new clauses:
3.201
Kachelofen/Putzofen heat generator
component of an inset in which the fuel is burned
3.202
Kachelofen/Putzofen heat generator flue gas outlet
part of the Kachelofen/Putzofen heat generator for connecting the flue gas pipe
Note 1 to entry: See EN 16510-1:2022, Figure A.16.
3.203
Kachelofen/Putzofen inset
appliance consisting of a heat generator connected to a heat-exchanger forming the flueway and
surrounded by an enclosure
Note 1 to entry: The Kachelofen/Putzofen inset appliance may be fitted with a thermostat to automatically
control the room temperature.
4 Characteristics
4.1 Protection of combustible materials
The performance of the appliance in relation to protection of combustible materials shall be determined
in accordance with EN 16510-1:2022, 5.6.
When tested in accordance with EN 16510-1:2022, 5.6, the protection measure(s) as specified according
to table 1 shall be given as minimum distance to combustible materials and if appropriate as material
type and thickness of protective insulation material.
The protection measures as specified shall be given in [mm] as an integer according to EN 16510-1:2022,
Table 22, no. 33, 34, 35, 36, 37, 38, 39 and 41 (d , d , d , d , d , d , d , s).
R S C P F L B
Table 1 — Protection of combustible materials
Protection measure Declared clearance distance to Protective
combustible material or thickness insulation material
of protective insulation material if any
[mm]
Minimum distance to -
combustible materials -
bottom (d )
B
Minimum distance to -
combustible materials –
floor in front (d )
F
Minimum distance to -
combustible materials –
ceiling (d )
C
7
---------------------- Page: 9 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
Protection measure Declared clearance distance to Protective
combustible material or thickness insulation material
of protective insulation material if any
[mm]
Minimum distance to -
combustible materials – rear
(d )
R
Minimum distance to -
combustible materials – side
(d )
S
Minimum distance to -
combustible materials – side
radiation area (d )
L
Minimum distance to -
adjacent combustible
materials (e.g. furniture)
(d )
P
Protective insulation
material (s)
4.2 Carbon monoxide emission (CO)
The performance of the appliance in relation to carbon monoxide emission at nominal heat output and at
part load heat output (if part load is specified) shall be determined in accordance with EN 16510-1:2022,
6.3.1 and 6.3.2.
The CO value if specified at nominal heat output and at part load heat output (if part load is specified) is
3
to be given in [mg/m ] as an integer according to EN 16510-1:2022, Table 22, no. 17 (CO (13 % O )).
nom 2
When tested in accordance with EN 16510-1:2022, 6.3.2 the CO emission at nominal heat output shall not
exceed the threshold levels as given in Table 2.
Table 2 — Threshold levels for CO emission
Appliance type Threshold level at 13 % O
2
3
open fronted solid fuel local space heaters
2000 mg/m
closed fronted solid fuel local space heaters using
3
solid fuel other than compressed wood in the form
1500 mg/m
of pellets including cookers
closed fronted solid fuel local space heaters using
3
compressed wood in form of pellets including
300 mg/m
cookers
8
---------------------- Page: 10 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
4.3 Nitrogen oxides (NO ) emissions
x
The performance of the appliance in relation to nitrogen oxides emissions at nominal heat output and at
part load heat output (if part load is specified) shall be determined in accordance with EN 16510-1:2022,
6.3.1 and 6.3.3.
The NO value if specified at nominal heat output and at part load heat output (if part load is specified) is
x
3
to be given in [mg/m ] as an integer according to EN 16510-1:2022, Table 22, no. 20 (NO (13 % O )).
xnom 2
When tested in accordance with EN 16510-1:2022, 6.3.3 the NO emissions at nominal heat output shall
x
not exceed the threshold levels as given in Table 3.
Table 3 — Threshold levels for NO emission (expressed as NO )
x 2
Appliance type Threshold level at 13 % O
2
open fronted solid fuel local space heaters, closed
3
fronted solid fuel local space heaters and cookers
200 mg/m
using biomass
open fronted solid fuel local space heaters, closed
3
fronted solid fuel local space heaters and cookers 300 mg/m
using fossil solid fuel
4.4 Emission of organic gaseous compounds (OGC)
The performance of the appliance in relation to organic gaseous compounds emission at nominal heat
output and at part load heat output (if part load is specified) shall be determined in accordance with
EN 16510-1:2022, 6.3.1 and 6.3.4.
The OGC value if specified at nominal heat output and at part load heat output (if part load is specified)
3
is to be given in [mg/m ] as an integer according to EN 16510-1:2022, Table 22, no. 23 (OGC
nom
(13 % O )).
2
When tested in accordance with EN 16510-1:2022, 6.3.4 the OGC emission at nominal heat output shall
not exceed the threshold levels as given in Table 4.
Table 4 — Threshold levels for OGC emission (expressed as C)
Appliance type Threshold level at 13 % O
2
3
open fronted solid fuel local space heaters
120 mg C/m
closed fronted solid fuel local space heaters using
3
solid fuel other than compressed wood in the form
120 mg C/m
of pellets including cookers
closed fronted solid fuel local space heaters using
3
compressed wood in form of pellets including
60 mg C/m
cookers
9
---------------------- Page: 11 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
4.5 Particulate matter (PM) emissions
The performance of the appliance in relation to particulate matter emissions at nominal heat output and
at part load heat output (if part load is specified) shall be determined in accordance with
EN 16510-1:2022,6.3.1 and 6.3.5.
The particulate matter value if specified at nominal heat output and at part load heat output (if part load
3
is specified) is to be given in [mg/m ] as an integer according to EN 16510-1:2022, Table 22, no. 26
(PM (13 % O )).
nom 2
When tested in accordance with EN 16510-1:2022, 6.3.5 the particulate matter (PM) emissions at
nominal heat output shall not exceed the threshold levels as given in Table 5.
Table 5 — Threshold levels for PM emission
Appliance type Threshold level at 13 % O
2
3
open fronted solid fuel local space heaters
50 mg/m
closed fronted solid fuel local space heaters using
3
solid fuel other than compressed wood in the form
40 mg/m
of pellets and cookers
closed fronted solid fuel local space heaters using
3
20 mg/m
compressed wood in form of pellets
4.6 Safety and accessibility in use
4.6.1 General
The data for the installation to a chimney are to be evaluated at nominal heat output. Specific data are to
be evaluated at safety test heat output. Additional data are to be evaluated at part load heat output, if part
load is specified.
4.6.2 Flue gas outlet temperature at nominal heat output
The performance of the appliance in relation to flue gas outlet temperature at nominal heat output shall
be determined in accordance with EN 16510-1:2022, 6.2.1.
The value of the flue gas outlet temperature for the installation of the appliance to a chimney if specified
is to be given in [°C] as an integer according to EN 16510-1:2022, Table 22, no. 47 (T ).
snom
4.6.3 Flue gas outlet temperature at part load heat output
The performance of the appliance in relation to flue gas outlet temperature at part load heat output (if
part load is specified) shall be determined in accordance with EN 16510-1:2022, 6.2.1.
The value of the flue gas outlet temperature at part load heat output (if part load is specified) for the
installation of the appliance to a chimney if specified is to be given in [°C] as an integer according to
EN 16510-1:2022, Table 22, no. 48 (T ).
spart
10
---------------------- Page: 12 ----------------------
SIST EN 16510-2-2:2023
EN 16510-2-2:2022 (E)
4.6.4 Minimum flue draught at nominal heat output
The performance of the appliance in relation to the minimum flue draught at nominal heat output shall
be determined in accordance with EN 16510-1:2022, 6.5.
The value of the minimum flue draught if specified at nominal heat output for the installation of the
appliance to a chimney is to be given in [Pa] as an integer according to EN 16510-1:2022, Table 22, no.
29 (p ).
nom
4.6.5 Minimum flue draught at part load heat output
The performance of the appliance in relation to the minimum flue draught at part load heat output (if part
load is specified) shall be determined in accordance with EN 16510-1:2022, 6.5.
The minimum value of the flue draught if specified at part load heat output (if part load is specified) for
the installation of the appliance to a chimney is to be given in [Pa] as an integer according to
EN 16510-1:2022, Table 22, no. 30 (p ).
part
4.6.6 Flue gas mass flow at nominal heat output
The performance of the appliance in relation to the flue gas mass flow at nominal heat output shall be
determined in accordance with EN 16510-1:2022, 6.12.
The flue gas mass flow value if specifi
...
SLOVENSKI STANDARD
oSIST prEN 16510-2-2:2021
01-april-2021
Stanovanjske grelne naprave na trdna goriva - 2-2. del: Kaminski vložki, vključno
odprti kamini na trdna goriva
Residential solid fuel burning appliances - Part 2-2: Inset appliances including open fires
Häusliche Heizgeräte für feste Brennstoffe - Teil 2-2: Kamineinsätze einschließlich offene
Kamine
Equipement de chauffage domestique - Partie 2-2 : Foyers ouverts et insert
Ta slovenski standard je istoveten z: prEN 16510-2-2
ICS:
97.100.30 Grelniki na trdo gorivo Solid fuel heaters
oSIST prEN 16510-2-2:2021 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
oSIST prEN 16510-2-2:2021
---------------------- Page: 2 ----------------------
oSIST prEN 16510-2-2:2021
DRAFT
EUROPEAN STANDARD
prEN 16510-2-2
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2021
ICS 97.100.30
English Version
Residential solid fuel burning appliances - Part 2-2: Inset
appliances including open fires
Equipement de chauffage domestique - Partie 2-2 : Häusliche Heizgeräte für feste Brennstoffe - Teil 2-2:
Foyers ouverts et insert Kamineinsätze einschließlich offene Kamine
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 295.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16510-2-2:2021 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 Descriptive features . 6
5 Appliance Performance requirements in relation to safety . 6
6 Appliances Performance requirements in relation to the appliance operation . 6
7 Appliance instructions . 8
8 Sustainable us of natural resources . 8
9 Assessment and verification of constancy of performance - AVCP . 8
10 Marking and technical datasheet . 8
Annex A (normative) Test methods . 9
A.1 Test environment . 9
A.2 Test assembly . 9
A.3 Measurement equipment . 9
A.4 Test procedures . 9
A.5 Test results . 14
A.6 Calculation methods . 15
A.7 Test report . 15
Annex B (normative) Test fuels and recommended fuels . 18
Annex C (informative) Arrangement for measuring the leakage rate . 19
Annex D (normative) Measuring procedure for nitrogen oxides (NO ) . 20
x
Annex E (normative) Measuring procedure for organic gaseous compounds (OGC) . 21
Annex F (normative) Measuring procedure for particulate matter (PM) . 22
Annex G (informative) Guideline for the characteristics to be taken into account in order to
decide on families of appliances . 23
Annex H (informative) Deviation of measuring results as a basis for market surveillance
measurements . 24
Annex I (informative) Standing Air Loss . 25
Annex J (informative) A-deviations . 26
Annex K (normative) Energy Label . 27
Annex BA (informative) Example for the possibility to extrapolate the steady-state
condition from a curve of temperature measurements of at least 8 h . 28
2
---------------------- Page: 4 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
Annex ZA (informative) Relationship of this European Standard with Regulation (EU) No.
305/2011 . 30
ZA.1 Scope and relevant characteristics . 30
ZA.2 System of Assessment and Verification of Constancy of Performance (AVCP) . 33
ZA.3 Assignment of AVCP tasks . 33
Bibliography . 35
3
---------------------- Page: 5 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
European foreword
This document (prEN 16510-2-2:2021) has been prepared by Technical Committee CEN/TC 295
“Residential solid fuel burning appliances”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document together with EN 16510-1:2021 will supersede EN 13229:2001 as amended and
corrected.
This document has been prepared under a standardization request given to CEN/CENELEC by the
European Commission and the European Free Trade Association.
For relationship with (EU) Regulation 305/2011, see informative Annex ZA, which is an integral part of
this document.
The structure of EN 16510, Residential solid fuel burning appliances, is as follows:
— Part 1: General requirements and test methods;
— Part 2-1: Roomheaters;
— Part 2-2: Inset appliances including open fires;
— Part 2-3: Cookers;
— Part 2-4: Independent boilers – Nominal heat output up to 50 kW;
— Part 2-5: Slow heat release appliances;
— Part 2-6: Mechanically by wood pellets fed roomheaters, inset appliances and cookers.
Other sections of Part 2 will be added to cover residential solid fuel burning appliances not included in
parts 2-1 to 2-6.
This Part 2-2 supplements or modifies the corresponding clauses in prEN 16510-1:2021, so as to convert
that publication into the European Standard: Residential solid fuel burning appliances – Requirements and
test methods for roomheaters.
This document is expected to be used in conjunction with prEN 16510-1:2021. This document refers to
Clauses of prEN 16510-1:2021 or adapts Clauses by stating “with the following modification”, “with the
following addition”, “is replaced by the following” or “shall not be applicable” in the corresponding Clause.
This document adds Clauses or Subclauses to the structure of prEN 16510-1:2021 which are particular
to this document.
Subclauses and Figures which are additional to those in prEN 16510-1:2021 are numbered starting with
201. Annexes which are additional to those in prEN 16510-1:2021 are numbered starting with BA.
4
---------------------- Page: 6 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
1 Scope
This document is applicable to hand fed solid fuel fired inset appliances, with or without functional
modification, that operate without firedoors or operate with fire doors either as closed only or as closed
or open, and also includes open fires fired by solid fuel. The surround of these appliances are integrated
with the building with the exception of free-standing appliances and those inset appliances which are
installed into a fireplace recess or enclosure. These appliances provide heat into the space where they
are installed. Additionally, where fitted with a boiler, they also provide domestic hot water and/or central
heating.
These appliances can burn one or more types of the following solid fuels in accordance with the appliance
manufacturer’s instructions:
— wood logs;
— compressed untreated wood;
— wood pellets;
— lignite briquettes;
— solid mineral fuels;
— peat briquettes.
This document also covers ‘Kachelofen’ and ‘Putzofen’ inset appliances, having nominal heat outputs up
to 15 kW.
This document is not applicable to appliances with fan assisted combustion air or appliances that are
mechanically fed.
Open fireplace components such as a bottomgrate with associated firefront which the manufacturer
supplies for installation into an existing heat resistant, insulated firebox are not covered by this
document.
This document is used in conjunction with prEN 16510-1:2021 of which it is an integral part.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
prEN 16510-1:2021, Residential solid fuel burning appliances - Part 1: General requirements and test
methods
3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 16510-1:2021 apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at http://www.electropedia.org/
5
---------------------- Page: 7 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
4 Descriptive features
prEN 16510-1:2021,Clause 4, shall be applicable with the following modifications.
4.4.5 Flueways
prEN 16510-1:2021, 4.4.5, shall be applicable with the following modification.
Addition after 1st paragraph:
For Kachelofen or Putzöfen inset appliances the flueways shall be tight and shall have tight cleaning
openings, which allow a proper cleaning. Metal flueways shall be made of steel as given in
prEN 16510-1:2021, Table 3, with a minimum thickness of 2 mm or cast iron as given in
prEN 16510-1:2021, Table 4, with a thickness of 4 mm or of austenitic stainless steel with a thickness of
1 mm. Fireclay bricks, plates or components of flueways shall withstand all mechanical, chemical and
thermal stresses under normal operation conditions.
4.4.7 Ashpan and ash removal
prEN 16510-1:2021, 4.4.7, shall be applicable with the following modification.
Addition after 1st paragraph:
Kachelöfen or Putzöfen inset appliances designed to burn coal as well as wood shall be equipped with an
3
ashpan having a minimum volume capacity of 0,8 dm per kW of nominal heat output. For Kachelöfen'
or Putzöfen' insets which are specifically designed to burn wood logs and wood briquettes, and if they
3
are equipped with an ashpan, the minimum volume capacity of this ashpan shall be 0,5 dm per kW of
nominal heat output.
4.4.8 Bottomgrate
prEN 16510-1:2021, 4.4.8, shall be applicable with the following modification.
Addition after 1st paragraph:
Grate devices fitted to Kachelöfen or Putzöfen inset appliances shall be easy to de-ash without undue
effort.
5 Appliance Performance requirements in relation to safety
prEN 16510-1:2021, Clause 5, shall be applicable.
6 Appliances Performance requirements in relation to the appliance operation
prEN 16510-1:2021, Clause 6, shall be applicable with the following modification.
6.4.1 General
prEN 16510-1:2021, 6.4.1, shall be applicable with the following modification.
Addition after 1st paragraph:
For Kachelofen and Putzofen inset appliances the manufacturer's declared efficiency value shall be equal
to or exceed 75 %.
For open fires without boiler the manufacturer's declared efficiency value shall be equal to or exceed
30 %.
For open fires with boiler the manufacturer's declared efficiency value shall be equal to or exceed 50 %.
6
---------------------- Page: 8 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
For all other inset appliances that operate with firedoors closed the manufacturer's declared efficiency
value shall be equal to or exceed 65 %.
6.7 Refuelling intervals
prEN 16510-1:2021, 6.7, shall be applicable with the following modification.
Replacement of Table 12:
Table 12 — Minimum refuelling intervals
Appliance type Test fuel type Minimum refuelling interval
(as detailed in Table B.1)
Appliance without Appliance with firedoors
firedoors closed
At nominal heat output
Continuous Wood logs, lignite briquettes or no requirements 1,5 h
burning peat briquettes
appliance
All other test fuels 1,5 h 4 h
Intermittent Wood logs, lignite briquettes or no requirements 40 min
burning peat briquettes
appliance
All other test fuels no requirements 1 h
+10
Kachelöfen or Wood logs, lignite briquettes or not applicable
min
90
)
( −20
Putzöfen inset peat briquettes
appliance
All other test fuels not applicable 4 h
At slow combustion
Continuous Wood logs, lignite briquettes or no requirements 3 h
burning peat briquettes
appliance
All other test fuels 10 h 12 h
Intermittent Wood logs, lignite briquettes or no requirements no requirements
burning peat briquettes
appliance
All other test fuels 10 h 10 h
Kachelöfen or Wood logs, lignite briquettes or not applicable burning rate to achieve
Putzöfen inset peat briquettes (50 ± 10) % of nominal
appliance heat output
All other test fuels not applicable burning rate to achieve at
least 12 h
Addition of the following new subclauses:
6.201 Accumulation heat output for Kachelofen or Putzofen inset appliances
The accumulation heat output shall be in accordance with the heat released when burning the test fuel
load in kg given by the manufacturer when tested in accordance with A.4.201.
6.202 Cut-off device for appliances without doors
If a cut-off device is fitted to an appliance without doors, it shall be able to separate the flueway of the
appliance to the chimney. The cut-off device shall not hinder control or cleaning of the connecting parts,
and the device shall maintain the position in which it is set.
7
---------------------- Page: 9 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
The marking of the position of the operating handle shall enable identification of the position of the cut-
off device. The cut-off device shall only be installed into the flue gas collector, flue spigot or flue gas
connector. The cut-off device shall only be used when the appliance is out to prevent heat loss from the
room via the chimney and to prevent the fall of soot into the room when the chimney is swept.
6.203 Temperature at air grilles for Kachelöfen or Putzöfen inset appliances
For the test in compliance with A.4.7 and A.4.201 the temperature recorded at the central flow at a
distance of 15 cm from outside of the air grilles shall not be greater than 85 °C when referenced to an
ambient temperature of 25 °C.
7 Appliance instructions
prEN 16510-1:2021, Clause 7, shall be applicable.
8 Sustainable us of natural resources
prEN 16510-1:2021, Clause 8, shall be applicable.
9 Assessment and verification of constancy of performance - AVCP
prEN 16510-1:2021, Clause 9, shall be applicable.
10 Marking and technical datasheet
prEN 16510-1:2021, Clause 10, shall be applicable.
8
---------------------- Page: 10 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
Annex A
(normative)
Test methods
A.1 Test environment
prEN 16510-1:2021, A.1, shall be applicable.
A.2 Test assembly
prEN 16510-1:2021, A.2, shall be applicable.
A.3 Measurement equipment
prEN 16510-1:2021, A.3, shall be applicable.
A.4 Test procedures
prEN 16510-1:2021, A.4, shall be applicable with the following modifications.
A.4.7 Performance test at nominal heat output
prEN 16510-1:2021, A.4.7, shall be applicable with the following modifications.
A.4.7.1 General
prEN 16510-1:2021, A.4.7.1, shall be applicable with the following modifications.
st
Addition before 1 paragraph:
In the case of Kachelöfen or Putzöfen inset appliances the performance test at nominal heat output shall
consist of three parts:
— an ignition and a dry heating, if the appliance is made of ceramic materials;
— pre-test(s) period(s);
— a test period.
The dry heating period shall be of sufficient duration to ensure that the water content of ceramic
materials does not affect the results of the weighing during the test period.
NOTE A dry heating period of 10 h or more is typical.
9
---------------------- Page: 11 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
Replacement of Table A.2:
Table A.2 — Minimum duration and minimum number of cycles
Appliance Fuel cycles (1 batch)
Minimum Minimum
duration number
At nominal heat output
Continuous burning Wood 1,5 h 3
Continuous burning Lignite briquettes and peat briquettes 1,5 h 2
Continuous burning All other solid mineral fuel 4 h 2
Intermittent burning Wood 40 min 3
Intermittent burning Lignite briquettes and peat briquettes 40 min 2
Intermittent burning All other solid mineral fuel 1 h 2
At part load heat output
Continuous burning Wood - 3
Continuous burning Lignite briquettes and peat briquettes - 2
Continuous burning All other solid mineral fuel - 2
Intermittent burning Wood - 3
Intermittent burning Lignite briquettes and peat briquettes - 2
Intermittent burning All other solid mineral fuel - 2
At slow combustion
Continuous burning Wood, lignite briquettes, peat briquettes 3 h 1
Continuous burning All other solid mineral fuel 12 h 1
Intermittent burning Wood, lignite briquettes, peat briquettes No requirement
Intermittent burning All other solid mineral fuel 10 h 1
A.4.7.3 Test period
prEN 16510-1:2021, A.4.7.3, shall be applicable with the following modification.
th
Addition before 5 paragraph:
In the case of Kachelöfen or Putzöfen inset appliances also measure and record the temperature of the
test surround and at the air grilles either continuously or at regular intervals of not more than 1 min to
ensure that the maximum temperatures achieved are recorded.
A.4.8 Part load heat output test
prEN 16510-1:2021, A.4.8, shall be applicable.
A.4.9 Slow combustion and recovery test
prEN 16510-1:2021, A.4.9, shall be applicable with the following modifications.
10
---------------------- Page: 12 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
A.4.9.1 General
prEN 16510-1:2021, A.4.9.1, shall be applicable with the following modification.
th
Addition before 6 paragraph:
The duration of the test period or the burning rate requirements in the case of Kachelofen or Putzöfen
inset appliances shall be as specified in Table 9 and Table A.2.
A.4.9.2 Pre-test period
prEN 16510-1:2021, A.4.9.2, shall be applicable with the following modification.
th
Addition before 4 paragraph:
In the case of Kachelöfen or Putzöfen inset appliances reduce the heat output by reducing the setting of
the primary air control in stages until the burning rate is either (50 ± 10) % of the measured burning rate
at nominal heat output for test wood logs and peat briquettes or approximately 33 % of the measured
burning rate at nominal heat output for other test fuels.
A.4.9.3 Test period
prEN 16510-1:2021, A.4.9.3 shall be applicable with the following modifications.
rd
Addition before 3 paragraph:
In the case of Kachelöfen or Putzöfen inset appliances measure and record the temperature of the test
surround either continuously or at regular intervals of not more than 1 min to ensure that the maximum
temperatures achieved are recorded.
th
Addition before the new 7 paragraph:
For Kachelöfen or Putzöfen inset appliances using solid mineral test fuel, end the test when the mass of
the basic firebed is the same as the basic limbed left at the end of the pre-test period.
th
Addition before the new 8 paragraph:
For Kachelöfen or Putzöfen inset appliances using wood logs and peat briquettes end the test when at
least a sufficient firebed to allow recovery is available.
A.4.9.4 Recovery test period
prEN 16510-1:2021, A.4.9.4, shall be applicable with the following modification.
Addition after the last paragraph:
For Kachelöfen or Putzöfen inset appliances the following test procedure has to be followed.
At the end of the slow combustion test period, reset the appliance controls in accordance with the
manufacturer's operating instructions to give the nominal heat output. Adjust the applied draught so that
the static pressure in the measurement section is set to (15 ± 2) Pa. De-ash the firebed in accordance with
A.4.3, and add a refuel charge, if necessary, as follows:
— when using solid mineral test fuels, the refuel charge shall be at least 33 % of the nominal heat output
test charge;
— when using wood logs or peat briquettes, the refuel charge shall be as indicated by the
manufacturer's instructions.
Record whether the fire recovers in accordance with 6.6 and record the time taken.
11
---------------------- Page: 13 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
A.4.10 Safety tests
prEN 16510-1:2021, A.4.10, shall be applicable with the following modifications.
A.4.10.3.1.3 Test period
prEN 16510-1:2021, A.4.10.3.1.3, shall be applicable with the following modification.
Replacement of the last paragraph:
Refuel the appliance with a further test load and repeat the test. If the peak temperatures during the
previous period are exceeded in the subsequent period, continue further refuelling for at least up to 8 h.
Record the maximum temperatures achieved for each combustion period.
Use the maximum temperatures achieved as a curve in order to extrapolate from this curve the maximum
temperature under steady-state conditions. For the extrapolation see Annex BA.
Of course this extrapolation has to be carried out for all sides of the trihedron at the hottest points.
A.4.10.3.2.2 Ignition and test period
prEN 16510-1:2021, A.4.10.3.2.2, shall be applicable with the following modification.
Replacement of the last paragraph:
In the case of Kachelöfen or Putzöfen inset appliances measure and record the following parameters:
— the temperatures on the test surround and at air grilles;
— the temperature in the fuel storage container, either continuously or at regular intervals of no more
than 1 min.
Refuel the appliance with a further test load and repeat the test. If the peak temperatures during the
previous period, are exceeded in the subsequent period, continue further refuelling for at least up to 8 h.
Record the maximum temperatures achieved for each combustion period.
Use the maximum temperatures achieved as a curve in order to extrapolate from this curve the maximum
temperature under steady-state conditions. For the extrapolation see Annex BA.
This extrapolation shall be carried out for all sides of the trihedron at the hottest points.
A.4.10.4.2 Ignition and pre-test period
prEN 16510-1:2021, A.4.10.4.2, shall be applicable with the following modification.
th
Addition before 4 paragraph:
In the case of Kachelöfen or Putztöfen inset appliances the pre-test shall be carried out at a burning rate
of (50 ± 10) % for wood logs and peat briquettes or 33 % for other test fuels of the consumption at
nominal heat output. The pre-test period shall be continued for a period of not less than 2 h at this burning
rate until the reading on the platform scale shows that the mass of basic firebed is achieved. Record the
reading of the platform scale.
Addition of the following new subclauses:
A.4.10.201 Temperature safety test for woodburning and multifuel appliances without doors
A.4.10.201.1 General
This test shall be performed when the appliance is designed to burn wood.
12
---------------------- Page: 14 ----------------------
oSIST prEN 16510-2-2:2021
prEN 16510-2-2:2021 (E)
This test shall consist of an ignition and a test period.
All controls except those used only for start-up purposes, shall be set in the position allowing the highest
heat output to be achieved.
The test fuel shall be fir timber with a moisture content of (15 ± 3) %; the nominal cross sectional sizes
of the timber shall be (4 × 6) cm or (5 × 5) cm. The length of the timber shall be at least two thirds of the
width of the firebox or two thirds of the depth of the firebox. If a grate is installed in the appliance, the
length and width of the profiles shall exceed the length and width of the grate so that the grate is entirely
covered with test fuel. These section timber pieces shall be put crosswise in a lattice formation so that
the space between the timber pieces is not less than 1 cm.
The grids shall be put into the firebox and stacked to a level of up to two thirds of the fire-box opening. If
burning fuel falls from the appliance during the test then the refuel load shall be reduced to give a level
of fuel sufficient to ensure this does not occur.
The appliance shall be refuelled and operated for successive test periods until the maximum
temperatures of trihedron and fuel storage container reach a steady-state.
A.4.10.201.2 Ignition and test period
Load the appliance with sufficient test fuel to ensure ignition of the fuel in accordance with the
manufacurer’s instructions. When the fuel is well alight, load the appliance with the test fuel load.
Start the flue gas extraction system and adjust the applied draught so that the static pressure in the
+2
measurement section is within Pa of the flue draught values specified in 6.1.
( )
0
Observe the static pressure at approximately 15 min intervals throughout the entire test and adjust the
applied flue draught, if necessary.
When half of the mass of the initial charge is left, a further charge of test fuel shall be introduced up to
two thirds of the firebox opening.
Measure and record:
— the temperatures on the test hearth and the walls of the trihedron;
— the temperature in the
...